IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

Similar documents
IMO Resolution MSC 61(67): Annex 1: Part 2

Review Fire Test Report

NF X : Parts 1, 2, 3, 4 & 5

BS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.

BS EN ISO : 2010

BS EN ISO : 2010

BS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products

BS EN ISO : 2010

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited

IEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions

BS EN : 2001 & IEC :2000

BS 476: Part 6: 1989+A1:2009

BS EN : Measurements Of Smoke Density Of Electric Cables. WF Report Number. Date: 17 th November Test Sponsor:

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

BS 476: Part 6: 1989+A1:2009

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

warring tonfire I I Il il il I 3 :I ~ :I :I :I =- ~ :a ::I fl ," global safety =.I =-a IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1

BS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions.

EN : A Report To: Poliuretanos S.A. Document Reference: (Issue 2), (Issue 2) & (Issue 4) Date: 13 th February 2015

Method of test defined in IEC for determining the circuit integrity performance of a cable under fire conditions.

Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves.

BS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No.

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

Test Report: ICL/H18/9039 Rev 1

ASTM F25 SEMINAR Fire Testing for SOLAS and Navy Vessels New Test Procedures and Materials Approval Process

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Smoke Seals in Accordance with BS 476: Part 31, Section 31.

CERTIFICATE OF APPROVAL No ME 5085

Fire Test Reports for Interpon D Powder Coatings

The Fire Resistance Performance Of Timber Or Mineral Composite Based Insulated Doorsets When Fitted With D & E Architectural Hardware Spring Hinges

Test report. NanoPhos coating system EPR and EEN. Name of client: NanoPhos SA. Date: Pages: 5 Encl.: 1 Ref: BP / KTO

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy

25 th November Title:

Test Report: ICL/CR15/11/087

Title: WF Assessment Report No B. Prepared for: CHEMOLLI S.A.S. di Eros Chemolli & C. Via Fitta, Arco (TN), Italy

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

CERTIFICATE OF APPROVAL No CF 5236 EMVER PAINTS INDUSTRIES LLC

Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

INTERNATIONAL STANDARD

FRANCE M & F RANKING ACCORDING TO NF F

BCTC CARPET TECHNICAL CENTRE

TFI Report Reaction to fire test

Global Requirements for the Fire Protection of Ships. Dr Janet Murrell Warrington Certification Ltd

ISO 5657 INTERNATIONAL STANDARD. Reaction to fire tests Ignitability of building products using a radiant heat source

ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415

C-01 FIRE DECKS AND BULKHEADS

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

The Train Now Arriving At... Harmonised Fire Safety For European Rolling Stock

IMO COMPREHENSIVE REVIEW OF THE FIRE TEST PROCEDURES CODE

Test Report Reg.no 12.

Analysis Report

Classification of Fire Performance of Wall and Ceiling Lining Materials

Star Princess Safety Centre. Annex A

Schedule of Accreditation issued by United Kingdom Accreditation Service High Street, Feltham, Middlesex, TW13 4UN, UK

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.


ISO INTERNATIONAL STANDARD. Reaction to fire tests for floorings Part 1: Determination of the burning behaviour using a radiant heat source

7.1 Smoke Detector Performance

Test Report No: ICL/H17/7967

IMO FP 53 Report. Lloyd s Register report on the 53 rd session of IMO Fire Protection Sub-Committee. 16 th March, 2009

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

Cone Calorimeter. (ISO 5660 ASTM E 1354) The most comprehensive bench scale fire test THE BENCHMARK IN FIRE TESTING

26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

SOUTH AFRICAN NATIONAL STANDARD

TFI Report Classification

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

Report VNLF Test Report

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

AGT 1 Confined Space. Authorised Gas Tester 1. Scienco Limited. Authorised Gas Tester 1 1

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

ISO/TR TECHNICAL REPORT. Reaction-to-fire tests Full-scale room tests for surface products Part 2: Technical background and guidance

ASTM E662 TESTING FOR COLE MOTORSPORTS/CM RACING PRODUCTS ON WINDSHIELD TEAROFFS ON ¼ GLASS VTEC # TESTED: MARCH 27, 2009

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

CLEARING MISCONCEPTIONS ABOUT LOW-SMOKE, HALOGEN-FREE CABLES

Glass fibre rovings - Non-metallic materials

ASTM E 662 Rate of Smoke Generation of OXIFREE TM198"

NBS Smoke Density Chamber

Annex to the Accreditation Certificate D PL according to DIN EN ISO/IEC 17025:2005

Quality. Water. Water Quality. Testing. Testing. Toxic Gas Detection. Toxic Gas. Detection. Air Quality. Monitoring. Monitoring. Monitoring.

Sieger Apex. Flexibility that meets your requirements

Glenside Environmental Services Ltd

ISO INTERNATIONAL STANDARD

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

SBI. Single Burning Item - EN THE BENCHMARK IN FIRE TESTING

REACTION TO FIRE LABORATORY

BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS

ISO INTERNATIONAL STANDARD

Characterising the smoke produced from modern materials and evaluating smoke detectors

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

INTERNATIONAL STANDARD

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

26 June 2001 GUIDELINES ON ALTERNATIVE DESIGN AND ARRANGEMENTS FOR FIRE SAFETY

Transcription:

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2 Smoke & Toxicity Test WF Report Number: 166040 Date: 13 th August 2007 Test Sponsor: Fiba Tech Industries Ltd. 0249

Page 2 of 13 Bodycote warringtonfire Test Report No. 166040 International Maritime Organisation Resolution MSC 61 (67) 1996; The International Code For Application Of Fire Test Procedures; Annex 1, Part 2 - Smoke & Toxicity Test Sponsored By Fiba Tech Industries Ltd. Willmotts Business Park Waterlip Nr Cranmore BA4 4RN

Page 3 of 13 CONTENTS PAGE NO. TEST DETAILS... 4 DESCRIPTION OF TEST SPECIMENS... 5 TEST RESULTS... 6 Table 1... 8 SPECIMEN BEHAVIOUR... 9 SIGNATORIES... 11 Table 2... 12 Table 3... 12 Table 4... 13

Page 4 of 13 Test Details Introduction This test method, adopted by the International Maritime Organisation, is used for measuring fire characteristics of bulkhead, ceiling and deck finish materials as a basis for characterising their production of smoke and toxic products and thus their suitability for use in maritime construction. The tests were performed in accordance with the procedure specified in IMO Resolution MSC, 61(67) Annex 1, Part 2 as amended by MSC/Circ.916 dated 4 th June 1999 and revised by MSC/Circ.1008 dated 8 th June 2001, and it is advised that this report is read in conjunction with that document. Scope of test The IMO Resolution MSC, 61(67) Annex 1, Part 2 (Ref.1) specifies that smoke generation tests should be conducted in accordance with ISO 5659 Part 2 (Ref.2). The Resolution also details a classification system based on the maximum specific optical density of smoke occurring during the test, averaged over three replicate tests, carried out in each of three test conditions. In addition, the Resolution specifies limits for 7 toxic gases which must not be exceeded in any of the three test conditions. Fire test study group/egolf Instruction to test Conditioning of specimens Exposed face Substrate Provision of test specimens Certain aspects of some fire test specifications are open to different interpretations. The Fire Test Study Group and EGOLF have identified a number of such areas and have agreed Resolutions which define common agreement of interpretations between fire test laboratories which are members of the Groups. Where such Resolutions are applicable to this test they have been followed. The test was conducted on the 2 nd August 2007 at the request of Fiba Tech Industries Ltd., the sponsor of the test. The specimens were received on the 20 th July 2007. Prior to the tests, the specimens were conditioned to constant mass at a temperature of 23 ± 2 o C and a relative humidity of 50 ± 10%. The smooth face of the specimens was exposed to the radiant heat of the furnace when the specimens were mounted in the test position. The specimens were tested without a substrate present. The specimens were supplied by the sponsor of the test. Bodycote warringtonfire was not involved in any selection or sampling procedure.

Page 5 of 13 Description of Test Specimens The description of the specimens given below has been prepared from information provided by the sponsor of the test. All values quoted are nominal, unless tolerances are given. General description UV curing, flame retardant grade, glass reinforced plastic sheet. Product reference Fibaroll M1 1.0mm grey Name of manufacturer Fiba Tech Industries Ltd. Colour reference Grey Overall thickness 1.0mm stated by the sponsor of the test 1.3mm measured by a member of the Reaction to Fire department at Bodycote warringtonfire Overall weight per unit area 2.2kg/m² stated by the sponsor of the test 2.08kg/m² measured by a member of the Reaction to Fire department at Bodycote warringtonfire Generic type Trade name / product reference Resin Name of manufacturer Trade name of flame retardant Generic type of flame retardant Amount of flame retardant Trade name / product reference Glass Type reinforcement Configuration of glass reinforcement Name of manufacturer Resin to glass ratio (by weight) 4:1 Percentage glass reinforcement (by weight) 20% Curing process UV cured Brief description of manufacturing process UV cured sheet moulding compound (SMC) sheet Note 1 = The sponsor of the test has provided this information, but at the specific request of the sponsor, these details have been omitted from the report and are held on the confidential file relating to this investigation.

Page 6 of 13 Test Results Test procedure A 75mm x 75mm specimen was mounted horizontally inside a smoke chamber of the design specified in ISO 5659 Part 2, 25mm below a cone shaped, radiant electric heater capable of producing a uniform irradiance of 50kW/m 2 on the specimen surface. A premixed propane/air pilot flame of length 30mm may be applied 10mm above the specimen surface. Three replicate specimens are tested in each of 3 test conditions: 1. Irradiance of 25kW/m 2 in the presence of pilot flame. 2. Irradiance of 25kW/m 2 in the absence of pilot flame. 3. Irradiance of 50kW/m 2 in the absence of pilot flame. The attenuation of a light beam passing through the evolved smoke is measured and the results are reported in terms of the maximum Specific Optical Density attained during the test, given by the equation: Ds = (V/(A*L)*log 10 (100/T) Where: V = total volume of the chamber (m 3 ) A = exposed area of the specimen (m 2 ) L = optical length (m) of smoke measurement T = % light transmitted. Test duration is a minimum of 10 minutes. This period is extended by a further 10 minutes if the maximum Specific Optical Density has not been reached. The sampling of the fire effluent created in the chamber during the test for the analysis of the concentration of the 7 different gases for which criteria are given is conducted using a variety of methods. In all cases, the sample is taken from the geometric centre of the chamber and sample lines with the exception of those for the Carbon Monoxide and Oxides of Nitrogen are kept as short as possible between the top of the smoke chamber and the sampling media. For the analysis of oxides of nitrogen and carbon monoxide, continuous measurements are made throughout the duration of the test. For the other gases, single point analysis is conducted. The gases are absorbed into aqueous media and analysed remotely. Two types of media are used; 0.1M sodium hydroxide solution and 0.3% Hydrogen Peroxide solution. The gases are sampled over the three minute period of maximum smoke density by bubbling the gases through the media using a fritted funnel Dreschel bottle arrangement. Analysis of the gases is conducted using the methods given in ISO TR 9122-3.

Page 7 of 13 Carbon monoxide (CO) is determined continuously using a pre-calibrated nondispersive infra-red analyser with a range of 0 to 0.5% CO. The values reported are those averaged over a 3 minute period of maximum smoke obscuration. Oxides of Nitrogen (NO x ) are determined continuously using a chemiluminesence analyser with a range of 0 to 500ppm. Again, the values reported are those averaged over a 3 minute period of maximum smoke obscuration. Hydrogen Cyanide (HCN) is determined from gases absorbed into a solution of sodium hydroxide and analysed using Ion chromatography via an ion exchange column and eluent as specified in ISO TR 9122-3. Hydrogen Fluoride (HF), Hydrogen Chloride (HCl) and Hydrogen Bromide (HBr) are absorbed into a solution of 0.3% hydrogen peroxide and are also analysed by ion chromatography. Sulphur Dioxide (SO 2 ) is analysed by absorbing into an aqueous solution and using ion chromatography to determine concentrations. Summary of results Specimens of UV curing, flame retardant grade, glass reinforced plastic sheet (product reference Fibaroll M1 1.0mm grey ) have been tested for smoke generation and toxicity in accordance with IMO Resolution MSC 61 (67), Annex 1, Part 2 as amended by MSC/Circ.916 dated 4 th June 1999 and revised by MSC/Circ.1008 dated 8 th June 2001. The specimens as tested achieved the criteria for smoke generation and toxicity for bulkhead, wall and ceiling as specified in the Resolution.

Page 8 of 13 Table 1 Summary of Results. GAS Limit (ppm) Condition 1 Reading (ppm) Condition 2 Condition 3 Carbon Monoxide CO 1450 204 758 340 Hydrochloric Acid HCl 600 ND ND ND Hydrogen Bromide HBr 600 ND ND ND Hydrogen Fluoride HF 600 ND ND ND Hydrogen Cyanide HCN 140 ND ND ND Nitrous Fumes NOx 350 1 1 ND Sulphur Dioxide SO2 120 ND ND ND Averaged Specific Optical Density 200 90 148 131 Where ND indicates non-detected. The test results relate only to the behaviour of the specimens of the product under the particular conditions of the test, they are not intended to be the sole criterion for assessing the potential fire hazard of the product in use. The tests results relate only to the specimens of the product in the form in which they are tested. Small differences in the composition or thickness of the product may significantly affect the performance during the test and may therefore invalidate the test results. Care should be taken to ensure that any product which is supplied or used is fully represented by the specimens which were tested. The quantity of each specific toxic gas species generated is dependant upon the fire model used and the burning behaviour of the specimen during each individual fire test. The quantitative determination of combustion products therefore relates only to the specimens tested under the conditions stated and when combustion occurs as described in this test report. The test results relating to smoke production are contained in Table 2. The toxicity data generated during the tests are contained in Table 3. Time to maximum Specific Optical Density and mass loss during the test are contained in Table 4.

Page 9 of 13 Specimen Behaviour Condition 1 In the case of each specimen, light coloured smoke was produced from the early stages of the test. In the case of specimen number one, ignition of the specimen occurred after approximately two minutes fifteen seconds test duration and the flaming ceased at approximately four minutes twenty-three seconds test duration. In the case of specimen number two, ignition of the specimen occurred after approximately one minute thirty-three seconds test duration and the flaming ceased at approximately four minutes five seconds test duration. In the case of specimen number three, ignition of the specimen occurred after approximately two minutes twenty-four seconds test duration and the flaming ceased at approximately four minutes three seconds test duration. Condition 2 In the case of each specimen, light coloured smoke was produced from the early stages of the test. Condition 3 In the case of each specimen, light coloured smoke was produced from the early stages of the test which progressed to dark coloured smoke upon ignition. In the case of specimen number one, ignition of the specimen occurred after approximately one minute three seconds test duration and the flaming ceased at approximately two minutes seventeen seconds test duration. In the case of specimen number two, ignition of the specimen occurred after approximately one minute eleven seconds test duration and the flaming ceased at approximately two minutes forty-eight seconds test duration. In the case of specimen number three, ignition of the specimen occurred after approximately one minute eleven seconds test duration and the flaming ceased at approximately two minutes forty-one seconds test duration.

Page 10 of 13 References 1. International Maritime Organisation Resolution MSC 61(67) 1996; The International Code for Application of Fire Test Procedures, Annex 1, Part 2: Smoke and Toxicity Test. 2. ISO 5659 Plastics - Smoke Generation - Part 2 1994: Determination of Optical Density by a Single Chamber Test. 3. ISO/TR 9122 Toxicity Testing of Fire Effluents - Part 3: Methods for the Analysis of Gases and Vapours in Fire Effluents. Validity The specification and interpretation of fire test methods are the subject of ongoing development and refinement. Changes in associated legislation may also occur. For these reasons it is recommended that the relevance of test reports over five years old should be considered by the user. The laboratory that issued the report will be able to offer, on behalf of the legal owner, a review of the procedures adopted for a particular test to ensure that they are consistent with current practices, and if required may endorse the test report. This report may only be reproduced in full. Extracts or abridgements shall not be published without permission of Bodycote warringtonfire.

Page 11 of 13 Signatories Tested By D Hird * Approved B Dean * Senior Analytical Chemist Authorised C Dean * Operations Manager * For and on behalf of Bodycote warringtonfire Report Issued: 13 th August 2007 This version of the report has been produced from a.pdf format electronic file that has been provided by Bodycote warringtonfire to the sponsor of the report and must only be reproduced in full. Extracts or abridgements of reports must not be published without permission of Bodycote warringtonfire. The original signed paper version of this report, which includes signatures in blue ink, is the sole authentic version. Only original paper versions of this report bear authentic signatures of the responsible Bodycote warringtonfire staff.

Page 12 of 13 Table 2 Maximum Specific Optical Density Condition 25kW/m 2 In The Presence Of A Pilot Flame 25kW/m 2 In The Absence Of A Pilot Flame 50kW/m 2 In The Absence Of A Pilot Flame Ds 95 148 127 (max) Specimen D 1 (Clear 10 7 16 beam) Ds 77 148 134 (max) Specimen D 2 (Clear 8 7 16 beam) Ds 98 148 133 (max) Specimen D 3 (Clear 11 7 15 beam) Averaged Ds (max) 90 148 131 Limit 200 200 200 Table 3 GAS Limit Reading (ppm) (ppm) Condition 1 Condition 2 Condition 3 Carbon Monoxide CO 1450 204 758 340 Hydrochloric Acid HCl 600 ND ND ND Hydrogen Bromide HBr 600 ND ND ND Hydrogen Fluoride HF 600 ND ND ND Hydrogen Cyanide HCN 140 ND ND ND Nitrous Fumes NOx 350 1 1 ND Sulphur Dioxide SO2 120 ND ND ND Where ND indicates non-detected.

Page 13 of 13 Table 4 Condition Specimen Number Time To Ds (Max) (s) Mass Loss (g) 1 330 4.4 2 300 3.9 3 360 4.2 1 600 4.2 2 600 4.3 25kW/m 2 in the presence of a pilot flame 25kW/m 2 in the absence of a pilot flame 50kW/m 2 in the absence of a pilot flame 3 600 4.2 1 120 5.2 2 240 5.1 3 210 5.1

Bodycote warringtonfire Testing Holmesfield Road Warrington Cheshire WA1 2DS United Kingdom Tel: +44 (0) 1925 655 116 Fax: +44 (0) 1925 655 419 Email: Info@warringtonfire.net Website: www.warringtonfire.net