Technologies Fire Prevention Systems. Oxeo Prevent Oxygen Reduction System Active Fire Prevention using natural Nitrogen

Similar documents
Branch Solution Wood based panel plants. Fire protection solutions for wood based panel plants

Oxeo extinguishing systems

Technologies Gas extinguishing systems. MX 200 Fire Extinguishing Systems Fighting Fire using HFC-227ea

Special solution KS marine. Kitchen protection system KS marine Fire prevention for galleys

Technologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230

GAS EXTINGUISHING SYSTEMS INERT GAS. Argotec with argon or nitrogen

Carbon Dioxide Extinguishing Systems Fighting fire with CO2

Technologies Hazard management system. Inveron Hazard management system

Inveron Hazard management system

Water mist fire suppression systems. Minifog ProCon Low-pressure water mist system

GAS EXTINGUISHING SYSTEM INERT GAS. Argotec with carbon dioxide. Safe for certain.

PRICELESS PROTECTION INERGEN Clean Agent Fire Suppression Systems

Fire Prevention Systems

Water mist fire suppression systems. Minifog EconAqua Water mist sprinkler systems

IQ8Quad. The right sensor for every environment. The detection principles of the IQ8Quad detector. Fire detection technology

How can you minimize consequential damages in case of a fire?

...extinguish it with a water spray.

Fire protection for a hazardous materials. warehouse. OxyReduct FirExting TITANUS. Reference solution

Vaults 5/03/2015. Introduction. Vault Types. Stand alone building Free standing structure VAULTS

GAS EXTINGUISHING SYSTEMS INERT GAS. Argon Extinguishing Systems. Fire Protection Systems

LEARNING SPECIAL HAZARD DETECTION TYPES

Fire protection solutions for ships and offshore facilities

PRICELESS PROTECTION INERGEN Clean Agent Fire Suppression Systems

Aspirating Smoke Detection (ASD) Systems Fire Detection

Safe, Effective, Environment-friendly

Press Presse Press Presse

Fire protection in information technology facilitie. CFPA-E Guideline No 14:2007 F

Fire protection solutions for ships and offshore facilities BRANCH SOLUTION

CO 2 EXTINGUISHING SYSTEMS

InstrumentationTools.com

Solutions. Fire risk under control in welding fume extraction systems

Fire Detection systems. UniVario industrial fire detectors for every job

UniVario Industrial Fire Detectors Versatile in Application

FIRE PROTECTION IN SUB-ZERO TEMPERATURES. DELIVERY CAPACITY ON ICE. DELIVERY CAPACITY WITH GUARANTEED PROTECTION.

Chapter 9: The basics of air preparation

What extinguishes fires without pressure peaks?

APPLICATION BULLETIN COMBUSTION TURBINE FACILITIES. Overview

Fire protection in high-bay warehouses:

EXTINGUISHES FIRES QUICKLY AND EFFECTIVELY. FirExting Gas extinguishing systems with non-liquefied and natural inert gases. Nitrogen Argon IG-541

Reflex fire detection and extinguishing system filled with ABC dry powder. Installation, operation and maintenance instructions

MB05. RESPOND TO EMERGENCIES BASIC KNOWLEDGE OF EMERGENCY PROCEDURES, INCLUDING EMERGENCY SHUTDOWN

Technical Specifications and User Guide for the GDCO Detector

XC10 combined fire detection and extinguishing control

Chapter 12 HOT WORK OPERATIONS. Purpose:

Before proceeding with the selection process, let s briefly look at the various explosion protection options:

Fire Protection for Catering Kitchens KS 2000 Compact Extinguishing System. Safe for certain.

Issue 70 June 2017 THE GLOBAL VOICE FOR PASSIVE AND ACTIVE FIRE PROTECTION

Fire Protection for Catering Kitchens KS 2000 Compact Extinguishing System. Safe for certain.

KD Innovative extinguishing with Novec TM 1230 by 3M TM

Introduction Carbon monoxide (CO) is a colorless, odorless and tasteless gas which is toxic and can quickly become a mortal danger. Amongst others, ca

XC10 combined fire detection and extinguishing control

Fire suppression systems for server rooms and data centres

Membrane Dryer. Air inflow rate KMM Series to m 3 /min

Inert Gas Fire Extinguishing System

Desigo Fire Safety intelligent detectors for complete safety

Fire and Extinguishing Tests on Computer Equipment

TR-1 single separator for MQL and dry processes. Explosive dusts from dry processes or MQL extracted directly at the machine and separated safely

AUTOMATIC FIREFIGHTING SYSTEMS IN HOSPITALS

FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK

Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS)

Releasing Systems. Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd.

Mitigating Risk of Battery Testing in Environmental Chambers. Mark Chrusciel & Wayne Diener Cincinnati Sub-Zero

SMOKE CONTROL - NEW DIRECTIONS

Institute for Plasma Research Welcomes you all on

Carbon Monoxide (CO) Gas Detector March 15 GCO 300

ST. JOHN HEALTH SYSTEM PHYSICIAN SAFETY MANUAL

NEW ENGINEERING GUIDELINE (VDI 2263 PART 7) ON DUST FIRES AND EXPLOSIONS PROTECTION IN SPRAY DRYING AND INTEGRATED EQUIPMENT

Fire Suppression Systems

HeatExchangerSpares.com Ltd HRS Heat Exchangers Ltd HRS Hevac Ltd HRS Hevac Engineering Ltd HRS International Ltd HRS Investments Ltd

Chapter 7 Fire Protection

FIRE SUPPRESSION SYSTEM

AUTOMATIC FIREFIGHTING SYSTEMS IN PAINT BOOTHS

Title: Fire Protection Effective Date: 7/1/2013 Control Number: THG_0039 Revision Number: 1 Date: 10/23/2015 Annual Review Completed: 5/13/2015

WHITE PAPER: IBS & IBSB ADVANCED

Membrane Dryers KMM Series

CerberusTM. PRO intelligent protection. A comprehensive fire protection system. Answers for infrastructure.

Technical Information

FoamFatale INTRODUCTION OF A NOVEL HIGH END TECHNOLOGY FOR LARGE ATMOSPHERIC STORAGE TANK FIRES. TFEX 1 Ltd.

Minifog EconAqua Water mist sprinkler systems

INTRODUCTION TO DUSTS AND THEIR EXPLOSIVE PROPERTIES

FINO Kältetrockner. Original FINO

RENNER SCREW COMPRESSORS WATER-INJECTED 100% OIL-FREE COMPRESSED AIR Made in Germany

Self Expanding Foam Fire Suppression System SPECIFICATION SHEET Rev

Hazardous Goods Warehouse. VOSSCHEMIE GmbH. Preventive Fire Protection. Case study

"FIRE PREVENTION IN HEALTHCARE FACILITIES"

Workplace FIRE SAFETY

I wish I could protect my business with the most suitable Water Mist solution to fit my needs.

Y. ORMIERES. Fire risk analysis method for nuclear installations

TAMUCC Fire Safety Training

To understand FIRE and how to EXTINGUISH it, we first need to know: What is FIRE?

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

Meeting NFPA standards for

Minifog PressProtect Fire protection solutions for industrial presses BRANCH SOLUTION

ISO/TS TECHNICAL SPECIFICATION. Fire detection and alarm systems Part 9: Test fires for fire detectors

The Complete Guide to Gas Sample Drying for Your Analyzer or Process

Savard Labor & Marine Staffing, Inc. Fire Prevention Program Rev3/14

Why is this important?

Significance of the Construction Products Regulation, including for data centers WHITEPAPER

Cerberus PRO intelligent fire protection. A comprehensive portfolio of innovative and industry-leading technology.

High flying fire protection HI-FOG for aircraft hangars

Transcription:

Technologies Fire Prevention Systems Oxeo Prevent Oxygen Reduction System Active Fire Prevention using natural Nitrogen

fire prevention Active prevention instead of firefighting Active fire prevention beats fire extinguishing: the Oxeo Prevent fire prevention system simply prevents fires from occurring. Unlike reactive firefighting using extinguishing systems or by fire brigades, methods that aim to deal with initial fires, Oxeo Prevent actively rules out the possibility of fire in the first place by oxygen reduction. In order for a fire to occur certain conditions have to be fulfilled: If the three key factors combustible material, ignition energy and oxygen are present in the right quantities and proportions, a fire can break out at any time. Generally it is simply impossible to remove all combustible materials or eliminate all potential ignition sources. The oxygen level can, however, be targeted and specifically reduced, making an open combustion process impossible: that is active fire prevention. Reducing the oxygen level The air around us has an oxygen content of nearly 21% by volume. By targeting and reducing this level according to nature of the goods you wish to protect, it s impossible for a fire to occur. Through the controlled supply of nitrogen, the Oxeo Prevent fire prevention system maintains the volume of oxygen in the protected area at a lower level. The nitrogen suppresses the proportion of oxygen, and a fireproof atmosphere is created. Wherever the protected area is well sealed, the Oxeo Prevent fire prevention system can simply remove the risk of fire occurring. The following are generally applicable to the Oxeo Prevent system: It offers permanent protection against fire by reducing the oxygen in the air. It avoids environmental damage from the fire or its effects. It prevents fire damage from the extinguishant itself. Oxeo Prevent can be adapted to modified conditions of use and fire load.

oxygen REDUction Taking a relaxed deep breath The nitrogen required for the oxygen reduction process is produced cheaply and directly onsite by the Oxeo Prevent fire prevention system using a nitrogen generator. The monitoring and control unit of the Oxeo Prevent fire prevention system continuously regulates the proportion of oxygen in the air. Oxeo Prevent atmosphere is still breathable Areas protected by Oxeo Prevent remain accessible to your workforce and can be used almost without restriction. The inert gas nitrogen (inert = dull, passive, inactive) is completely safe at normal atmospheric pressure. As it makes up 78 % by volume of the natural atmosphere, the human body is perfectly well adapted to it. The reduction in oxygen content of the air to around 15% by volume using nitrogen under the Oxeo Prevent fire prevention system corresponds to the level of oxygen at an altitude of around 3,000 m. The fireproof Oxeo Prevent atmosphere is comparable to that found in high mountain regions. With due regard for certain safety measures, therefore, there is no danger at all in reducing the oxygen level. Ignition limits of combustible materials and physiological effects Combustibility Cellulose Paper Wood Plastics Oxygen content % by volume 21,0 Impact to personnel harmless 15,0 14,0 13,5 13,0 10,0 6,0 Oxeo Prevent operating sphere distraction fatigue, sickness, faint health hazards

design and The components The main components of the Oxeo Prevent fire prevention system are an air compressor, a compressed air conditioner, a nitrogen generator and the oxygen sensors with the monitoring and control panel. To achieve effective fire prevention through the reduction of oxygen, the individual components must interact as follows: Residual content in the room in % by volume Operational phases of the Oxeo Prevent fire prevention system 20 Nitrogen N 2 15 10 Oxygen O 5 2 0 0 5 10 15 hours Oxygen reduction 21 % 15 % Operation Stand-by The air compressor sucks in normal air and compresses the air up to 13 bar, depending on the application. In the compressed air conditioning unit, the compressed air is cleaned of dirt particles, moisture and residual oil to ensure a long life of the nitrogen generator.

functionsimply safe In the nitrogen generator (membrane or PSA technology), the compressed air is separated into its main constituents, nitrogen (78.0%) and residual gases (22.0%). While the remaining gases are released, the nitrogen replaces part of the room atmosphere in the protected area, thus reducing the proportion of oxygen to below that required for independent combustion. In most cases a reduction from 21% to 15% by volume is sufficient to prevent the occurrence of fire. Sensors continuously measure the oxygen level of the air in the protected area. The supply of nitrogen is adjusted by a solenoid valve, that is regulated by the monitoring and control unit. Once the required level of nitrogen is reached, the Oxeo Prevent fire prevention system automatically switches to stand-by operation. It then only recommences mode if the oxygen level begins to rise, e.g. through unsealed points in the building or open doors and gates. Schematic diagram of nitrogen production installation (membrane technology) Nitrogen generator Compressor and dryer Filter systems O 2, Ar Air inlet (natural atmosphere) Air N 2 Supply to room (N 2 ) Cross section of a hollow fibre membrane Outlet air residual gases (O 2, Ar, others)

DDED SYFETY by use of early fire detection Early fire detection and fire prevention are an optimal combination for guaranteed fire protection The Oxeo Prevent fire prevention system creates an oxygen-reduced atmosphere thus providing protection against the occurrence or propagation of fires. Smoldering fires, however, may occur even- at a low oxygen content, e.g. due to a thermal overload of electric components. Systems for the early detection of fires detect the smoldering fire and will automatically disconnect the power supply if necessary. Moreover, they report the smoldering fire to a superordinate point. The oxygen-reduced atmosphere does the rest and prevents further burning. Detecting a fire even before the first signs of smoke. A particular feature of the Minimax early fire detection systems is the detection of an increase in the carbon monoxide concentration. Smoldering in a reduced oxygen atmosphere constitutes an incomplete combustion process, and carbon monoxide occurs even before smoke emerges. For this reason, the detection of carbon monoxide concentrations is a fundamental addition to the other fire detection criteria applied. Detecting a fire before it starts burning HELIOS AMX5000 smoke aspirating systems are able to detect even minute glowing and smoldering fires both safely and securely. The HELIOS system has a detection sensitivity of 0.002 %/m and is thus 400 times as sensitive as a conventional optical smoke detector. The HELIOS AMX5000 can be equipped additionally with a sensor for monitoring carbon monoxide for the earliest detection of fires. One detector ± multiple criteria The HELIOS AMX5000 alarm threshold Signal level Smolderinmg fire e.g. materials containing cellulose White fuming fire, e.g. cotton Black fuming fire, e.g. cables CO-gas sensor Optical smoke sensor Ionization smoke sensor

APPLICATIONS a class on its own Wherever the protected area is well sealed, the Oxeo Prevent fire prevention system can simply remove the risk of fire occurring. The Oxeo Prevent system also offers the following specific benefits in individual application areas: Automated frozen and cold warehouses Lasting prevention even at very low temperatures. Economic fire prevention by making use of existing sealed conditions. System easily adapts to building alterations. Highly accessible as system components are outside cold area. Hazardous goods storage and automated high bay warehouses Optimal suitability for high fire loads and mixed storage. Minimal outlay on pipe and sensor installation. Problem-free integration into existing buildings. Spacious dimensioning of fire sections. No toxic reactive products from extinguishant and burnt goods. Telecommunications and Information processing Guaranteed system availability through fire prevention. Can easily be adapted to modified conditions of use. Minimal outlay on installation and maintenance in sensitive security and technical areas. Archives, Libraries, Museums, Storerooms Prevention against fire and consequential damage to irreplaceable objects of artistic and cultural value. Staff and visitors can still use the protected areas. Additional benefit: the reduction in oxygen can also help conserve valuable items.

dvantages Overview Clearly superiour The Oxeo Prevent fire prevention system offers a better solution than extinguishing systems if relatively few people use the protected area and the room itself is well sealed. Under such conditions the Oxeo Prevent system offers the best possible kind of fire protection: active fire prevention. Whereas extinguishing systems are designed to put out existing fires, the Oxeo Prevent fire prevention system actually stops them breaking out in the first place. The benefits at a glance: Prevents fire from occurring. Damage is limited to the defective component. Ensures availability of technical equipment and processes. No smoke-related damage. The Oxeo Prevent system avoids the possible side-effects of normal fire extinguishing methods: rapid temperature changes in specific points, electric short-circuits, extinguishing agent residue. Decreasing oxygen content reduces the risk of fire (Example: solids) Risk of fire Oxygen concentration in normal ambient air Oxeo Prevent operating sphere 22 21 20 19 18 17 16 15 14 13 12 11 Oxygen concentration in % by volume Minimax GmbH & Co. KG Industriestraße 10/12 D-23840 Bad Oldesloe Tel.: +49 45 31 8 03-0 Fax: +49 45 31 8 03-248 E-Mail: clean-agents@minimax.de www.minimax.de PB07Ce_05/07.14/1/03.04/HV Printed in Germany Pictures Page 7: EDEKA, Rhenus, Fotolia Page 8 NASA Subject to technical modifications