SECTION SPRINKLER SYSTEMS

Similar documents
B. Section Identification for Fire Suppression Piping and Equipment.

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

Port of St Helens SIA Aircraft Hanger Scappoose, OR

SPRINKLERS TABLE OF CONTENTS

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

SECTION DRY-PIPE SPRINKLER SYSTEMS

FIRE SUPPRESSION SPRINKLER SYSTEM

Gas Station & C Store SECTION CWM Job No

B. Related Sections: The following Sections contain requirements that relate to this Section.

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

Mercury Plastics New Building February TABLE OF CONTENTS

SECTION SPRINKLER SYSTEMS

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

SECTION WET-PIPE SPRINKLER SYSTEMS

B. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

North Hanover Township School District North Hanover Township, New Jersey

TABLE OF CONTENTS

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

DIVISION 21: FIRE SUPPRESSION

A. This Section includes the following fire-suppression piping inside the building:

WET-PIPE SPRINKLER SYSTEMS

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

DIVISION 21: FIRE SUPPRESSION

SECTION FIRE SUPPRESSION SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

New Rigby Elementary School February TABLE OF CONTENTS

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION

SECTION FIRE-SUPPRESSION STANDPIPES

Lucy s Pizza 100% CD Specification 06/22/2018

SECTION WET-PIPE SPRINKLER SYSTEMS

Kenworth Sales Co. - North Las Vegas, Nevada November TABLE OF CONTENTS

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

SECTION WET FIRE SPRINKLER SYSTEMS

SECTION FIRE-SUPPRESSION PIPING

PART 1 - GENERAL SECTION FIRE PROTECTION BASIC MATERIALS AND METHODS

A. Standard-Pressure Piping System Component: Listed for 175-psig minimum working pressure.

WET AUTOMATIC FIRE SPRINKLER SYSTEMS

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION PREACTION SPRINKLER SYSTEMS

Environmental Health & Safety

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

ADDENDUM NO. 3 March 19, 2018

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

SECTION WET-PIPE FIRE SUPPRESSION SPRINKLERS

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

2. Welding Materials and Procedures shall conform to the ASME Code.

Design and Construction Standards SECTION FIRE SUPPRESSION

SECTION FIRE PROTECTION

PHYSICAL FACILITIES. 1 General. 2 Related Requirements. 5 Quality Assurance. 3 Wiring. 4 Submittals

SECTION FIRE-SUPPRESSION SYSTEMS

DIVISION 21: FIRE SUPPRESSION WATER BASED FIRE SUPRESSION SYSTEMS

A. This section includes design and performance information for fire protection and suppression systems.

2016 CDM Smith All Rights Reserved July 2016 SECTION FIRE PROTECTION - SPRINKLER AND STANDPIPE SYSTEMS

SECTION DRY-PIPE FIRE-SUPPRESSION SPRINKLERS

DIVISION 21 - FIRE SUPPRESSION

SECTION FIRE SUPRESSION

B. Standard-Pressure Standpipe Piping: Fire-suppression standpipe piping designed to operate at working pressure 175 psig (1200 kpa) maximum.

Sprinkler Permit Applications

Specialties Quality, Durability, Reliability. FIrE ProTECTIon

CITY OF PASADENA FIRE DEPARTMENT

Page 1 of 7. Replaces Form No. F_ Rev 16.3 (Added 16X22 and 18X20 coverage areas)

DIVISION 21 - FIRE SUPPRESSION

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

New Construction Fire Inspection Process

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

SECTION FIRE PROTECTION

CONSTRUCTION REQUIREMENTS

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems

Standard Spray concealed horizontal sidewall sprinkler VK481

Model F3-80 Dry K8.0 (115 metric) Standard-Response, Standard Spray Sprinklers

Fire Protection Systems

Sprinkler System Installer Level 2

TECHNICAL DATA. Refer to Approval Chart 1 and Design Criteria for culus Listing requirements that must be followed.

Copyright 2016 AIA MasterSpec Full Length 09/16 PRODUCT MASTERSPEC LICENSED BY AVITRU, LLC TO VICTAULIC COMPANY.

TECHNICAL SPECIFICATIONS SECTION DRY PIPE SPRINKLER SYSTEM PLAISTOW PUBLIC LIBRARY 85 MAIN STREET PLAISTOW, NEW HAMPSHIRE 100%CD.

Transcription:

SECTION 15325 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Wet-pipe sprinkler systems. B. Preaction sprinkler systems. C. System design, installation, and certification. D. Fire department connections. E. Roof hose cabinets. F. Monitors. 1.2 RELATED SECTIONS A. Division 2 - Trenching. B. Section 15190 - Mechanical Identification. C. Section 15245 - Vibration Isolation. D. Division 16 - Equipment Wiring Systems: Electrical characteristics and wiring connections. E. Division 16 Fire Alarm System: Heat or smoke detectors to activate the pre action systems. 1.3 REFERENCES A. NFPA 13 - Installation of Sprinkler Systems. B. NFPA 70 - National Electrical Code. C. UL - Fire Resistance Directory. D. UL 199 - Automatic Sprinklers. E. Warnock Hersey - Certification Listings. 1.4 SYSTEM DESCRIPTION A. Systems to provide coverage for entire building. B. Provide systems to NFPA 13. Hazard levels are indicated on the drawings. SPRINKLER SYSTEMS 15325-1

C. Conduct water flow test and hydraulically design systems. D. Interface systems with building fire and smoke alarm system. E. Provide fire department connections where indicated. F. Provide, where indicated on the drawings, Wet-Pipe Sprinkler Systems: Automatic sprinklers are attached to piping containing water and that is connected to water supply. Water discharges immediately from sprinklers when they are opened. Sprinklers open when heat melts fusible link or destroys frangible device. G. Provide, where indicated on the drawings, Preaction Sprinkler Systems: Automatic sprinklers are attached to piping containing air. Actuation of fire-detection system in same area as sprinklers opens deluge valve, permitting water to flow into piping and to discharge from sprinklers that have opened. H. Provide roof hoses, cabinets, fire department connections or monitors if required by the local fire department or any authorities having jurisdiction. 1.5 PERFORMANCE REQUIREMENTS A. Standard Piping System Component Working Pressure: Listed for at least 175 psig. B. Fire-suppression sprinkler system design shall be approved by authorities having jurisdiction 1. Margin of Safety for Available Water Flow and Pressure: 10 percent, including losses through water-service piping, valves, and backflow preventers. 2. Minimum Density for Automatic-Sprinkler Piping Design: See drawings for hazard classifications and densities. C. Seismic Performance: Fire-suppression piping shall be capable of withstanding the effects of earthquake motions determined according to NFPA 13 and ASCE 7, "Minimum Design Loads for Buildings and Other Structures": Section 9, "Earthquake Loads. 1.6 SUBMITTALS FOR REVIEW A. Product Data: For the following: 1. Piping materials, including sprinkler specialty fittings. 2. Pipe hangers and supports including seismic restraints. 3. Valves, including listed fire-protection valves, unlisted general-duty valves, and specialty valves and trim. 4. Air compressors, including electrical data. 5. Sprinklers, escutcheons, and guards. Include sprinkler flow characteristics, mounting, finish, and other pertinent data. SPRINKLER SYSTEMS 15325-2

6. Hose connections, including size, type, and finish. 7. Roof hose cabinets. 8. Monitors. 9. Fire department connections, including type; number, size, and arrangement of inlets; caps and chains; size and direction of outlet; escutcheon and marking; and finish. 10. Alarm devices, including electrical data. B. Shop Drawings: Diagram power, signal, and control wiring. C. Fire-hydrant flow test report. D. Approved Sprinkler Piping Drawings: Working plans, prepared according to NFPA 13, that have been approved by authorities having jurisdiction, including hydraulic calculations, if applicable. E. Field Test Reports and Certificates: Indicate and interpret test results for compliance with performance requirements and as described in NFPA 13. Include "Contractor's Material and Test Certificate for Aboveground Piping" and "Contractor's Material and Test Certificate for Underground Piping." F. Welding certificates. G. Field quality-control test reports. H. Operation and Maintenance Data: For sprinkler specialties to include in emergency, operation, and maintenance manuals. I. Submit shop drawings, product data, hydraulic calculations to engineer of record for review prior to submittal for code compliance. 1.7 SUBMITTALS AT PROJECT CLOSEOUT A. Project Record Documents: Record actual locations of sprinklers and deviations of piping from drawings. Indicate drain and test locations. B. Manufacturer's Certificate: Certify that system has been tested and meets or exceeds specified requirements and code requirements. C. Operation and Maintenance Data: Include components of system, servicing requirements, record drawings, inspection data, replacement part numbers and availability, and location and numbers of service depot. D. Warranty: Submit manufacturer warranty and ensure forms have been completed in Owner's name and registered with manufacturer. 1.8 QUALITY ASSURANCE A. Perform Work in accordance with NFPA 13 SPRINKLER SYSTEMS 15325-3

B. Manufacturer Qualifications: Company specializing in manufacturing the Products specified in this section with minimum three years experience. C. Installer Qualifications: Company specializing in performing the work of this section with minimum three years documented experience approved by manufacturer. D. Design and install system under direct supervision of a licensed sprinkler contractor and installer. 1.9 DELIVERY, STORAGE, AND PROTECTION A. Store products in shipping containers and maintain in place until installation. Provide temporary inlet and outlet caps. Maintain caps in place until installation. Store piping off the ground or floor. Piping installed with dirt and/or rust will be cleaned and painted! 1.10 EXTRA MATERIALS A. Provide extra sprinklers under provisions of NFPA 13. B. Provide suitable wrenches for each sprinkler type. C. Provide metal storage cabinet located adjacent to alarm valve. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Gem. B. Star C. Viking. D. Reliable. 2.2 SPRINKLERS A. Suspended Ceiling: 1. Type: Semi-recessed pendant type with matching clamp on escutcheon plate. 2. Finish: Chrome plated or white enamel. 3. Escutcheon Plate Finish: To match head 4. Fusible Link: Fusible solder link type temperature rated for specific area hazard. B. Exposed Area Type: 1. Type: Standard upright type with guard in mechanical rooms and gymnasiums. 2. Finish: Brass. 3. Fusible Link: Fusible solder link type temperature rated for specific area hazard. C. Sidewall Type: 1. Type: Semi-recessed horizontal sidewall type with matching clamp on escutcheon plate and guard. 2. Finish: Chrome plated. SPRINKLER SYSTEMS 15325-4

3. Escutcheon Plate Finish: Chrome plated. 4. Fusible Link: Fusible solder link type temperature rated for specific area hazard. D. Dry Sprinklers: 1. Type: Semi-recessed pendant type with matching push on escutcheon plate. 2. Finish: Chrome plated. 3. Escutcheon Plate Finish: Chrome plated. 4. Fusible Link: Fusible solder link type temperature rated for specific area hazard. E. Guards: Finish to match sprinkler finish. 2.3 PIPING SPECIALTIES A. Wet Pipe Sprinkler Alarm Valve: Check type valve with divided seat ring, rubber faced clapper to automatically actuate water motor alarm and electric alarm, with pressure retard chamber and variable pressure trim; with test and drain valve. B. Dry Pipe Sprinkler Alarm Valve: Check type valve with divided seat ring, rubber faced clapper to automatically actuate water motor alarm and electric alarm, with accelerator; with test and drain valve. C. Electric Alarm: Electrically operated red enameled gong with pressure alarm switch. D. Water Flow Switch: Vane type switch for mounting horizontal or vertical, with two contacts; rated 10 amp at 125 volt AC and 2.5 amp at 24 volt DC. E. Fire Department Connections: 1. Type: Free standing type with ductile iron pedestal red enamel finish. 2. Outlets: Two way with thread size to suit fire department hardware; threaded dust cap and chain of matching material and finish. 3. Label: "Sprinkler - Fire Department Connection". 2.4 AIR COMPRESSOR A. Compressor: Single unit, electric motor driven, motor, motor starter, safety valves, check valves, air maintenance device incorporating electric pressure switch and unloader valve. B. Electrical Characteristics: 1. 3/4 hp. 2. 120 volts, single phase, 60 Hz. PART 3 - EXECUTION 3.1 INSTALLATION A. Install in accordance with NFPA 13. B. Install equipment in accordance with manufacturers instructions. SPRINKLER SYSTEMS 15325-5

C. Install buried shut-off valves in valve box. Provide post indicator. FLEX FILMS, U.S.A, LLC D. Provide approved double check valve assembly at sprinkler system water source connection. E. Locate fire department connection with sufficient clearance from walls, obstructions, or adjacent siamese connectors to allow full swing of fire department wrench handle. F. Locate outside alarm gong on building wall as indicated. G. Place pipe runs to minimize obstruction to other work. H. Place piping in concealed spaces above finished ceilings. I. Center sprinklers in two directions in ceiling tile and provide piping offsets as required. J. Apply masking tape or paper cover to ensure concealed sprinklers, cover plates, and sprinkler escutcheons do not receive field paint finish. Remove after painting. Replace painted sprinklers. K. Install air compressor on vibration isolators. L. Flush entire piping system of foreign matter. M. Install guards on sprinklers where exposed. N. Hydrostatically test entire system. 3.2 INTERFACE WITH OTHER PRODUCTS A. Ensure required devices are installed and connected as required to fire alarm system. END OF SECTION SPRINKLER SYSTEMS 15325-6