Instruction Sheet 00 Variable Speed Delta T (00-VDT)

Similar documents
Instruction Sheet. Variable Speed - Outdoor Reset (00-VR) 00 Cartridge Circulator

Instruction Sheet. Variable Speed - Solar (00-VT) 00 and Load Match Cartridge Circulators

Pre-Fab Easy Installation For Model 0011-CF-USK Installation and Operating Instructions for Existing Homes Or Buildings with Standard Piping

Instruction Sheet. Press & Hold: Item, to view settings, to test. 24 V ±10% 50/60 Hz 3 VA 120 V (ac) 5 A 1/6 hp pilot 240 VA 20 to 260 V (ac) 2 VA

Installation Guide

Instruction Sheet LTR - Low Water Cutoff for Hot Water Boilers

Instruction Sheet RMB - Radiant Mixing Block

Instruction Sheet X Pump Block (XPB)

RMB - Radiant Mixing Block

Variable Speed Outdoor Reset 00 Circulator (00-VR)

Advanced Snow Melt Control Installation Manual

Taco 00 Series Cartridge Circulators

- Data Brochure Mixing Control 361

SC-3 Controller INSTALLATION AND OPERATING INSTRUCTIONS FOR GAS-FIRED, OIL FIRED AND DUAL FUEL HOT WATER HEATING PLANTS. SC-3 Applications CONTENTS

- Data Brochure Mixing Control 360

SC-9 Controller INSTALLATION AND OPERATING INSTRUCTIONS. SC-9 Applications CONTENTS

Installation & Operation Manual

ProRadiant Basic Heating Control Installation Manual 2013

Product Instructions. Hydronic Mixing Block Version Wiring Terminal Block Pressure/Temperature Sensor Delivery Fitting (3) Display Screen

COMPASS HIGH-EFFICIENCY WET-ROTOR CIRCULATORS

Radiant Thermostat 519

Installation & Operation Manual

Installation & Operation Manual

Installation & Operation Manual

Installation & Operation Manual

OWNER S MANUAL INSTALLATION AND OPERATING INSTRUCTIONS REPAIR PARTS LIST

- Data Brochure D 260. Boiler Control /09

- Data Brochure Snow Detector & Melting Control 667

Radiant Mixing Block

Instruction Sheet. ECM High-Efficiency Circulator. SUPERSEDES: January 24, 2016 EFFECTIVE: March 29, 2016

Installation & Operation Manual

00e series VT2218 Instruction Sheet

B-40/B-41 Modulating Temperature Controller

- Data Brochure. This brochure is for Thermostats 510 and 511 (with sensor). The section on the 079 slab sensor installation is for the 511 only!

MODEL SF-10 CONTROL OPERATION AND INSTRUCTION MANUAL

HPS Controls Ltd. Series 600 LFI / CFI Series 700 HFS Zone Control Stations. Heating and Radiant Floor Zone Control Stations

Installation Guide. ZXU1 Mixing Loop Control - Single Zone. Self-Contained Interoperable Controller Model UCP-1

WWSD. Power. DHW Demand. Maximum. Supply. Minimum Boiler DHW. Zone 1 / Cooling. Pump / Vlv. System Pump. UnOccupied. of full output NRTL/C LR 58223

Installation & Operation Manual

Plumbing. ECM High-Efficiency Hot Water Recirculation System. Instant hot water for existing plumbing systems; no dedicated return line needed

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

Installation Guide. FCU4 Fan Coil Unit. Self-Contained Interoperable Controller Model UCP-1 for Software Version 3

AquaSaver DISPOSER CONTROL CENTER Installation Manual. Model AS-101K

PLL. Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

Installation & Operation Manual

- Data Brochure D 665. Snow Detector & Melting Control /12

Installation & Operation Manual

- Data Brochure Steam Control 279

Installation, Operation & Service Manual

Domestic Hot Water Recirculation Systems Application, Selection & Installation Guide

AC6 & AC8 HORIZONTAL SERIES Sealed Metallic Centrifugal Pumps Installation and Maintenance Instructions

Melting Control Stk# Melt Demand Idle Demand WWSD Minimum Maximum Water Melting. Do not apply power. 15 Mix Com. Mix. Melt/Idle Demand.

AQ475A Aquatrol Outdoor Temperature Compensator for Boilers

Astro 2 circulator models. Installation and operating instructions

- Data Brochure Universal Reset Module 422

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA The first totally integrated multiple boiler management control.

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

MODEL TA. TA-SB 117.5mm mm HOT INLET. TA mm mm mm mm

Boiler Demand Mix 1 Demand Mix 2 Demand DHW Demand Setpoint Demand

Bathroom Exhaust Fan/Fluorescent Light Combination

INSTALLATION INSTRUCTIONS WARRANTY

HPS Controls Ltd. Series 600 LFI / CFI Series 700 HFS Zone Control Stations. Heating and Radiant Floor Zone Control Stations

Note: Please provide valve serial number (stamped on cover of valve) when ordering parts. Thermometer. Hot Water Inlet. Cold Water Inlet G3600LF

DISPOSER CONTROL CENTER

BB3000 Series. Application. Features. Injection Pump Control General Instructions

The smart way to instant hot water comfort.

52 BERKSHIRE CEILING FAN

TMC Temperature Monitoring Control Temperature Range -30 to 250 F (-35 to 120 C)

Model R060 Installation - Operation Manual

MP-MBA-45T-1/60T-1 / 75T-1

- Data Brochure Mixing Control 360e

- Data Brochure Boiler Control 264

D1C HP Centrifugal Grinder Pump Installation & Service Manual with Parts List. Grinder Pump for Residential and Pressure Sewer Applications

INSTALLATION INSTRUCTIONS and OPERATING MANUAL. *Aquastat is a registered trademark of Honeywell International, Inc.

be liable for any other loss or damage, whether direct, indirect, incidental or consequential.

SOLARHOT. SuperVox. Description / Applications System Overview. Installation/ Owner s Manual

TA-300, TA-300-LF, TA-350, TA-350-LF

1900 Series In-Line Pump

SUBMERSIBLE SEWAGE PUMP. Automatic and manual models. Single phase power only 115 or 230 volt.

OWNER S Manual PRINTED IN CANADA 10/2009

INSTALLATION ADJUSTMENT SERVICE

SPA BLOWER OWNER'S MANUAL XXXX, XXXX, XXXX, XXXX, XXXX, XXXX fax

Laing Thermotech. Autocirc The Instant Hot Water Pump Models E1-BCANCT1W-06 and E1-BCANRT1W. Installation & Operating Manual

RATIO:GUARD. MODEL P-1 ph INDICATOR/CONTROLLER GETTING TECHNICAL ASSISTANCE

INFRARED RADIANT HEATERS

MG200 SERIES GRINDER PUMPS INSTALLATION AND SERVICE MANUAL. 2 HP Grinder Pump for Residential and Pressure Sewer Applications.

"S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16

- Data Brochure Snow Detector & Melting Control 665

MODEL EM-10 ELECTRIC BOILER CONTROL OPERATION AND INSTRUCTION MANUAL

Bathroom Exhaust Fan/Fluorescent Light Combination

52 BAYTOWNE CEILING FAN

INSTALLATION ADJUSTMENT SERVICE TYPE TM-15, TM-20, TM-20-LF (As furnished with models TM-554, TM-356, TM-356-W/HA)

TWIN-FLOIII HEATER INSPECT THE SHIPMENT IMMEDIATELY WHEN RECEIVED TO DETERMINE IF ANY DAMAGE HAS OCCURRED DURING SHIPMENT.

Installation & Operation Manual

E340 BOILER CONTROL INSTALLATION MANUAL

- Essay Control Functions and Benefits

DBF 4XL Dryer Booster Fans

- Data Brochure Addendum

RATIO:GUARD Model E-1S EC Monitor

SM-909/SM /2" Sweat 3/4" Sweat 3 3/8" F.L. Max. Max. Line Weight Model No. HP Inlet/Outlet Volts Amps Fluid Temp. Pressure (Lbs.

Transcription:

Instruction Sheet 00 Variable Speed Delta T (00-VDT) 102-359 SUPERSEDES: January 1, 2010 EFFECTIVE: May 1, 2010 Plant ID# 001-3927 The Variable Speed Delta T 00 Cartridge Circulator (00-VDT) is a microprocessor-based pump which automatically adjusts its performance to deliver the optimal heat transfer based on the actual operation of the system. The 00-VDT regulates the temperature to provide a fixed temperature difference (ΔT) of between 5-50 F between two field installed sensors. Variable Speed Differential Temperature Control Variable speed pumping to maintain a set differential temperature (delta T or ΔT) between two sensors allows for automatic adjustment of the pump s performance to match the load of the system or zone, eliminate velocity noise in zone valve systems and conserve energy. Since delta T is directly related to flow rate, the pump s speed continually adjusts to the required BTU per hour. In almost all applications the design of the system was based on being able to maintain a certain delta T and figured by using the universal hydronics equation of BTU/hr = GPM x 500 x ΔT. Given that, any time there is a change to the heat load (i.e. warmer day or greater heat loss from a structure) then the GPM should change to match the required BTU/hr. This is achieved when the variable speed 00-VDT Circulators automatically and continually adjust their GPM output (by varying speed) to match the required BTU/hr output of the system, no matter the changes in heat load, while always maintaining the designed delta T between a supply and return sensor. Applications Delta T Across a Series Loop System Using Zone Valves M M M Supply "00"-VDT DIP 5 = Off DIP 4 = Off DIP 3 = On DIP 2 = Off or On DIP 1 = On Return The 00-VDT Variable Speed Circulator adjusts its speed to maintain the differential temperature (based on the RANGE dial setting) between the supply sensor and the return sensor whenever a heat demand is present. This will increase overall comfort and sharply reduce boiler short-cycling. The 00-VDT will also control velocity noise issues in the system, eliminating the need for a pressure differential bypass valve. Delta T Across Multi-Zone Radiant Manifolds with Loop Actuators Outdoor M M M M Supply 00 -VDT Return B C A iseries-r Boiler DIP 5 = Off DIP 4 = Off DIP 3 = On DIP 2 = Off or On DIP 1 = On The 00-VDT Variable Speed Circulator adjusts its speed to maintain the differential temperature (based on the RANGE dial setting) between the supply sensor and the return sensor whenever a heat demand is present. The 00-VDT will also eliminate velocity noise by slowing the actual flow rate through the zone to the minimum required to deliver proper heat. If other zones on the manifold open, the 00-VDT will increase its speed to deliver the required BTU s, while at the same time maintaining the designed for delta T across the radiant system. See www.taco-hvac.com for additional applications for the 00-VDT circulators. Pump Selection The circulator should be sized, using conventional sizing practices, based on the required head and flow for the system or zone on which the circulator is being installed.

Sequence of Operation Power Up and Heat Request Whenever the 00-VDT is powered up, the green PWR LED turns on. The 00-VDT starts operating once a heat request signal is present at the Heat Request (Ht Req) terminals. The heat request terminals come factory jumpered so the pump will start as soon as it is powered up. The jumper may be removed and a heat request signal may be provided by external end switches from zone valves or Taco ZVC/SR series zone controls, applying a dry contact closure or a powered 24 V (ac) signal across the Ht Req terminals. Once a heat request signal is present, the green HEAT REQ LED turns on. Delta T Setting and Operation Once a heat request is present, the 00-VDT operates to provide a fixed ΔT between the supply sensor (S2) and the return sensor (S1). The fixed ΔT is set using the RANGE dial, where 5 F and 50 F corresponds to 1 and 10 respectively on the RANGE dial, with the temperature increasing in 5 F increments. The percent output (% OUT) LED flashes at different rates based on the speed of the pump. Dip Switch Settings 3 8 2 4 1 5 6 RANGE 7 9 10 15ºF 40ºF 10ºF 20ºF 5º ºF ºF 35ºF T 45ºF 50ºF DIP Switch 5: Output Characteristic = Off or On DIP Switch 4: Output Response = Off DIP Switch 3: Mode of Operation = On DIP Switch 2: Minimum Speed = Off or On DIP Switch 1: T Operation = On Minimum Variable Speed Output When the 00-VDT is configured for reverse acting mode (ΔT operation), a minimum variable speed ouput is incorporated during operation to insure proper flow across both sensors. In Minimum Variable Speed Output this case, the variable speed output is adjusted between the selected minimum variable DIP switch 2 = Off DIP switch 2 = On speed output percentage and full output. Depending on the amount of system resistance in your application, select the preferred minimum variable speed output from the table to Normal (default) Lower the right. The 00-VDT also provides full output for 30 seconds when the Heat Request appears, then resumes normal operation. Note: Minimum variable speed output is not available when configured for Direct Acting Mode (DIP switch 3 set to Off). Pump Start-up When the 00-VDT is powered up, the circulator operates at full speed for 30 seconds before varying its speed anywhere between minimum and full speed as required to maintain the selected differential temperature. In Direct Acting Mode (DIP switch 3 = Off) the speed of the circulator will ramp up as required to maintain the selected differential temperature. Exercising Every 72 hours of no operation, the 00-VDT is designed to exercise for 10 seconds in order to prevent precipitate build-up in the pump. The % OUT LED turns on during the exercising function. 2

Wiring and Installation WARNING: Wiring connections must be made in accordance with all applicable electrical codes. CAUTION: To prevent electrical shock, disconnect electric power to system at main fuse or circuit breaker box until installation is complete. When a service switch is installed, more than one disconnect switch may be required to deenergize this device for servicing. Powering the Control Insert the line voltage wires through the knockout of the enclosure and connect the live wire to the H terminal and the neutral wire to the N terminal on the PC Board. Ensure that no power is present during this process. Heat Request The heat request signal may be provided by the factory installed jumper or the jumper can be removed and a heat request signal may be provided by external end switches from zone valves or Taco ZVC/SR series zone controls, applying a dry contact closure or a powered 24 V (ac) signal across the Ht Req terminals. s Do not apply power to these terminals as this will damage the PC Board. The wiring terminals for the sensors may be removed for ease of installation. Do not run the wires parallel to telephone or power cables. If the sensor wires are located in an area with strong sources of electromagnetic interference (EMI), shielded cable or twisted pair should be used or the wires can be run in a grounded metal conduit. If using shielded cable, the shield wire should be connected to the Com terminal on the PC Board and not to earth ground. Installation and Placement The sensors can be strapped directly to the pipe using a cable tie. Insulation should be placed around the sensor to reduce the effect of air currents on the sensor measurement. The sensors should be placed downstream of a pump or after an elbow or similar fitting. This is especially important if large diameter pipes are used because the thermal stratifcation within the pipe can result in erroneous sensor readings. Proper sensor location requires that the fluid is thoroughly mixed within the pipe before it reaches the sensor. If the system sensor is used to measure duct (air) temperature, the sensor should be mounted in such a manner that it measures the average duct outlet temperature. Return (S1) Connect the two wires from the return sensor (S1) directly into the Com and S1 terminals on the PC Board. Supply (S2) Connect the two wires from the supply sensor (S2) directly into the Com and S2 terminals on the PC Board. S3 Supply (S2) S2 S1 Com Ht Ht Req Req Return (S1) 0.1µF 0.1µF R Y Made in Canada N H coil fuse T2.5A 250V Factory Installed Jumper or End Switch XFMR MOV Power: 120 V ±10% 900 VA 60 Hz Var. Speed: 120 V (ac) 2.4 A 1/6 hp To ground screw on PCB enclosure N H 120 V (ac) 3

Troubleshooting As in any troubleshooting procedure, it is important to isolate a problem as much as possible before proceeding. The error messages greatly simplify troubleshooting of the 00-VDT. When the 00-VDT flashes an error message, identify the fault and follow standard testing procedures to confirm the problem. If you suspect a wiring fault, return to the wiring section on this brochure and carefully check all external wiring and wiring connections. For your safety and protection from permanent damage to the microprocessor, the 00-VDT includes a 2.5 A (250 VAC) field replaceable fuse. Multi-Status LED LED LED Status OO-VDT Status PWR Solid Power On HEAT REQ Solid Heat Request % OUT Flash (Solid) Variable Speed Output HEAT REQ RED OUT HEAT REQ and RED OUT POWER, HEAT REQ and RED OUT Flash Flash Flash Flash System S1 Fault. 00-VDT does not operate. System S2 Fault. 00-VDT does not operate. Boiler S3 Fault. No sensor should be connected to S3. 00-VDT does not provide boiler protection. No sensors connected, or incompatible mode and sensor combination. Testing the s A good quality test meter capable of measuring up to 5,000 kω (1 kω = 1000Ω) is required to measure the sensor resistance. In addition to this, the actual temperature must be measured with a good quality digital thermometer. First measure the temperature using the thermometer and then measure the resistance of the sensor at the 00-VDT. The wires from the sensor must not be connected to the PC Board while this test is performed. The wiring terminals are easily removed by pulling them from the PC Board. Using the chart below, estimate the temperature measured by the sensor. The sensor and thermometer readings should be close. If the test meter reads a very high resistance, there may be a broken wire, a poor wiring connection or a defective sensor. If the resistance is very low, the wiring may be shorted, there may be moisture in the sensor or the sensor may be defective. To test for a defective sensor, measure the resistance directly at the sensor location. Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance F C Ω F C Ω F C Ω F C Ω -30-34 234,196 30-1 34,558 90 32 7,334 150 66 2,045-20 -29 165,180 40 4 26,099 100 38 5,828 160 71 1,689-10 -23 118,018 50 10 19,900 110 43 4,665 170 77 1,403 0-18 85,362 60 16 15,311 120 49 3,760 180 82 1,172 10-12 62,465 70 21 11,883 130 54 3,050 190 88 983 20-7 46,218 80 27 9,299 140 60 2,490 200 93 829 Application 1. Maximum operating pressure: 125 psi (862 kpa) on all 00 Series Circulators. 2. Maximum water temperature not to exceed nameplate rating. 3. Cast iron circulators are to be used for closed loop systems. Bronze circulators are to be used for open loop, fresh water, or potable water systems. 4. Taco Cartridge circulator pumps are for indoor use only employer uniquement a l interieur. 4

Installation 1. Mounting position Circulator must be mounted with the motor in a horizontal position. It may be mounted vertically with the motor up, provided that the system pressure is at least 20 psi (138 kpa). 2. Rotating body Body has an arrow on the front that indicates direction of flow. To rotate body, remove the four body bolts, rotate body and replace bolts. Make sure that the junction box is NOT located underneath the circulator. (The junction box must NOT be located in the 6 o clock position, as viewed from the motor end.) 3. Electrical connections Observe all applicable codes when connecting to power supply. The motor is impedance protected, and does not require overload protection. The pump cannot run backwards. WARNING: Do not use in swimming pool or spa areas; pump has not been investigated for this application. WARNING: In the event the retaining screws have been pulled out of the housing, DO NOT replace them. Use of any other screw may short out the stator windings, creating a risk of electrical shock. CAUTION: When installing electrical connections, do not apply mechanical loads to the capacitor box; otherwise, retaining screws may be pulled out of the housing, making circulator unusable. 4. Fill system with tap water The system must be filled before operating the circulator. The bearings are water lubricated and should not be allowed to operate dry. Filling the system will result in immediate lubrication of the bearings. It is always good practice to flush a new system of foreign matter before starting the circulator. 5. Circulator operation Operate the circulator for 5 minutes immediately after filling system to purge remaining air from the bearing chamber. This is especially important when installing the circulator during the off-season. CAUTION: The addition of petroleum based fluids or certain chemical additives to systems utilizing TACO equipment voids the warranty. CAUTION: Use supply wires suitable for 90 C ATTENTION: Employer des fils d alimentation adequats pour 90 C. WARNING: To avoid electrical shock, disconnect the power supply to the circulator and the main electrical unit. Replacing Cartridge Assembly 1. Disconnect the electrical supply. 2. Reduce system pressure to 0 psi and allow system to return to room temperature. Isolate the circulator by closing the service valves or draining the system. 3. Remove the body bolts and swing motor assembly away from the body. 4. Pull cartridge out of the motor housing. 5. Install replacement cartridge, making sure that the cover plate is between the cartridge flange and motor. 6. Make sure the replacement cartridge corresponds to the full circulator product number. A complete parts list is available from your local plumbing supply wholesaler. 7. Reassemble the circulator using the new gasket and bolts supplied. 8. Follow the Installation procedure to start up the circulator. 5

Replacing Integral Flow Check (IFC) Assembly (if applicable) 1. Disconnect the electrical supply. 2. Reduce system pressure to 0 psi and allow system to return to room temperature. Isolate the circulator by closing the service valves or draining the system. 3. Loosen flange bolts and remove entire circulator from the system to access the flange mounted IFC. 4. Remove IFC, using needle nose pliers. 5. Install replacement IFC by pressing valve into casing until it is firmly seated. 6. Follow the Installation procedure to start up the circulator. Replacing Circuit Board 1. Disconnect the electrical supply and all field wiring to the circuit board. 2. Unplug the 3-pin plastic connector that connects the motor to the circuit board. 3. Bend the lip of the capacitor base to ease the removal of the circuit board. Pull the circuit board up and out. 4. Reverse directions to install the new circuit board. Notes 6

Notes 7

Notes LIMITED WARRANTY STATEMENT Taco, Inc. will repair or replace without charge (at the company s option) any Taco 00 Series circulator or circulator part which is proven defective under normal use within three (3) years from the date of manufacture. In order to obtain service under this warranty, it is the responsibility of the purchaser to promptly notify the local Taco stocking distributor or Taco in writing and promptly deliver the subject product or part, delivery prepaid, to the stocking distributor. For assistance on warranty returns, the purchaser may either contact the local Taco stocking distributor or Taco. If the subject product or part contains no defect as covered in this warranty, the purchaser will be billed for parts and labor charges in effect at time of factory examination and repair. Any Taco product or part not installed or operated in conformity with Taco instructions or which has been subject to misuse, misapplication, the addition of petroleum-based fluids or certain chemical additives to the systems, or other abuse, will not be covered by this warranty. If in doubt as to whether a particular substance is suitable for use with a Taco product or part, or for any application restrictions, consult the applicable Taco instruction sheets or contact Taco at (401-942-8000). Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part. Taco reserves the right to make changes in details of design, construction, or arrangement of materials of its products without notification. TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES. ANY WARRANTY IMPLIED BY LAW INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS IS IN EFFECT ONLY FOR THE DURA- TION OF THE EXPRESS WARRANTY SET FORTH IN THE FIRST PARAGRAPH ABOVE. THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR STATUTORY, OR ANY OTHER WARRANTY OBLIGATION ON THE PART OF TACO. TACO WILL NOT BE LIABLE FOR ANY SPE- CIAL, INCIDENTAL, INDIRECT OR CONSE- QUENTIAL DAMAGES RESULTING FROM THE USE OF ITS PRODUCTS OR ANY INCIDENTAL COSTS OF REMOVING OR REPLACING DEFECTIVE PRODUCTS. This warranty gives the purchaser specific rights, and the purchaser may have other rights which vary from state to state. Some states do not allow limitations on how long an implied warranty lasts or on the exclusion of incidental or consequential damages, so these limitations or exclusions may not apply to you. COMFORT MADE EASY. TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. TACO (Canada), Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8. Telephone: (905) 564-9422. FAX: (905) 564-9436. Visit our web site at: http://www.taco-hvac.com Copyright 2010 TACO, Inc. Portions Copyright 2003 tekmar Control Systems, Ltd. tekmar Control Systems, Inc. Printed in USA 8