SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11

Similar documents
Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Condensing Unit Installation and Operating Instructions

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Air Conditioning Operation and Troubleshooting Matt Dunham

Condensing Unit Installation and Operating Instructions

442 Chapter 16. Figure 16-5 Gas leak detection

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

HSXA15 HSXB15. IMPORTANT Operating pressures of this R410A unit are higher than pressures in R22 units. Always use service equipment rated for R410A.

REFRIGERANT RECOVERY Log Book

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

Installation Instructions

SERVICE MANUAL FOR MODEL RM-49

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

Room Air Conditioner Service and Parts Manual

SERVICE MANUAL FOR MODEL RM-26

SERVICE MANUAL FOR MODEL RM-10

Harold Ag & Mobile Products

Refrigerant Recovery Unit, Model RRU134

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC.

HOSHIZAKI MODULAR CRESCENT CUBER MODEL KM-280MAH KM-280MWH SERVICE MANUAL

A/C-HEATER SYSTEM - MANUAL

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

Contour TM Screw Compressors

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

TSA WARNING. Service Literature TSA SERIES UNITS. 6, 7.5, 10, 12.5, 15 & 20 ton

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL

XC13. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R410A.

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

Installation Instructions

R410a Installation and fault finding training

APPLICATION & SERVICE GUIDE

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

Trouble Shooting Guide FAA, 3-phase (D3631)

ICE CREAM TOPPING CABINETS REFRIGERATOR or FREEZER Installation, Operation and Maintenance Instructions

Condensing Unit and Refrigeration System Installation & Operations Manual R448A/R449A

Installation, Operation, and Maintenance Information

HP13 WARNING WARNING. Service Literature HP13 SERIES UNITS

GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

Full Range Systems. Mokon Troubleshooting Guide Model 311. Process/Water Loop. Problem Possible Cause Corrective Measure. Process pump will not start

Residential Piping and Long Line Guideline

NUMBER: ISSUED: JULY 13, /336 73/23 STACKABLE CRESCENT CUBER KM-1300SWH-E SERVICE MANUAL FOR QUALIFIED SERVICE PERSON HOSHIZAKI

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SCU16LT Series Split System Air Conditioner WARNING

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Hoshizaki America, Inc.

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

The Essentials Of Working With R-410A

KML F SERIES KML H SERIES

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

Trouble Shooting Guide RAA, 1-phase (D3627)

INSTALLATION INSTRUCTIONS

Hoshizaki America, Inc.

Installation Instructions

Trouble Shooting Guide PAA, 1-phase (D3731)

HPXA15 HPXB15 WARNING

INSTALLATION INSTRUCTIONS

MASS. MARITIME ACADEMY

REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

INSTRUCTIONS! DO NOT DISCARD!

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999

CAUTION. Check Equipment and Job Site. Clearance Requirements. Unpack Unit

INSTALLATION INSTRUCTIONS

XC16. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R410A.

EBAC MODEL BD-150 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Installation Instructions

Corp L9 Revised HS27 SERIES UNITS SPECIFICATIONS. Model No. HS HS HS HS27-042

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

Installation 50% Service 20% Components 20% Applied Knowledge 10%

INSTALLATION AND OPERATING INSTRUCTIONS

1 Specifications. 2 Operation. PHOENIX 300 Operation & Service Instructions. 2.1 Transporting the Phoenix. 2.2 Location

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

SERVICE MANUAL FOR QUALIFIED SERVICE PERSON HOSHIZAKI 89/336 73/23 SELF-CONTAINED CRESCENT CUBER KM-150BAF-E KM-150BWF-E

RPI Industries, Inc.

KM-900MAF KM-900MWF KM-900MRF KM-900MRF3

EBAC MODEL CD60 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

HOSHIZAKI CUBELET ICE DISPENSER MODEL DCM-240BAF SERVICE MANUAL

power Describe the purpose of lockout/tag-out devices Demonstrate use of lockout/tagout

HSXA16 WARNING. WARNING R 410A refrigerant can be harmful if it is inhaled. R 410A refrigerant must be used and recovered responsibly.

R100 Oil-Less Refrigerant Recovery Unit

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

Refrigerant changeover guidelines

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SHP16LT Series Split System Heat Pump

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS W12A2-A W12A1-K

Room Air Conditioner CP06 & CP08. Chill 115 Volts. Service & Parts Manual THE EXPERTS IN ROOM AIR CONDITIONING _02

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

LENNDX INSTALLATION INSTRUCTIONS. IIlIIIIIIIIIIIIIIIIIIIIIIIHI A, WARNING A, WARNING WARNING RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE

NO. 15FD-742 ISSUED: AUG. 10, 2007 REVISED: SEP. 30, 2013 HOSHIZAKI SELF-CONTAINED CRESCENT CUBER KM-30A KM-35A KM-50A KM-75A MODEL SERVICE MANUAL

Transcription:

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual No.: 2100-479 Supersedes: NEW File: Volume I, Tab 1 Date: 03-08-07 Page 1 of 11

CONTENTS General Recovery Equipment Rated for R-410A...3 Leak Detectors...3 Gauge Manifold...3 Attaching Gauge Manifold...3 Attaching Manifold Hose to Schrader Valve...4 Leak Test...4 Evacuation... 4 & 5 Charging...5 Preliminary Charging Steps...5 Charging the System by Weight...5 Troubleshooting the Mechanical System Air Conditioning & Heat Pump - Cooling...9 Low Suction Low Head Pressure...9 High Suction Low Head Pressure...9 Low Suction High Head Pressure...9 High Suction High Head Pressure...9 Heat Pump - Heating...9 Low Suction Low Head Pressure...9 High Suction Low Head Pressure...9 Low Suction High Head Pressure...9 High Suction High Head Pressure...9 Figures Figure 1: Typical AC System Cooling Cycle...6 Figure 2: Typical HP System Cooling Cycle...7 Figure 3: Heating Cycle...8 Charts Troubleshooting Chart for Air Conditioners...10 Troubleshooting Chart for Air-to-Air Heat Pumps...11 Page 2 of 11

GENERAL WARNING The oils used with R-410A refrigerant are hydroscopic and absorb water from the atmosphere readily. Do not leave systems open to the atmosphere for more than 5 minutes. If the system has been open for more than 5 minutes, change the filter dryer immediately before evacuation. Then recharge the system to the factory specified charge. Recovery equipment rated for R-410A refrigerant R-410A has an ozone depletion potential of zero, but must be reclaimed due to its global warming potential. The gauge manifold set is specially designed to withstand the higher pressure associated with R-410A. Manifold sets are required to range up to 800 psig on the high side and 250 psig on the low side with a 250 psig low side retard. All hoses must have a service rating of 800 psig. (This information will be indicated on the hoses.) Vacuum Pump and micron gauge must be used when evacuating a system to 500 microns. Leak Detectors An electronic leak detector capable of detecting HFC refrigerant can be used with R-410A refrigerant. GAUGE MANIFOLD WARNING Gauge manifold must be suitable for use with R-410A refrigerant and POE oils. A necessary instrument in checking and serving air conditioning and heat pump equipment is the gauge manifold. Its purpose is to determine the operating refrigerant pressures in order for the serviceman to analyze the condition of the system. The valving on the manifold is so arranged that when the valves are closed (front-seated) the center port on the manifold is closed to the gauges and gauge ports. With the valves in the closed position, the gauge ports are still open to the gauges, permitting the gauges to register system pressures. Opening either valve opens the center port to that side of the manifold and system. ATTACHING GAUGE MANIFOLD For leak testing, purging, checking charge, charging liquid or evacuating, connect high pressure side of gauge manifold to Schrader valve on liquid or discharge line. Connect suction side of gauge manifold to Schrader valve on suction line. On heat pumps the suction line is between compressor and reversing valve. Page 3 of 11

ATTACHING MANIFOLD HOSE TO SCHRADER VALVE 1. Remove cap from valve. Leak Test WARNING As a safety measure, it is wise to detach refrigerant hoses at the lowest pressure readings on the system. To do this: A. Put high pressure hose B on first. (Unit should not be running.) B. Put low pressure hose A on second. (Unit should be running.) 2. Make sure gauge manifold valves are closed. 3. If hose does not have an unseating pin, a number 395 Superior or equivalent unseating coupler must be used. 4. Make sure coupler is lined up straight with Schrader valve. Screw coupler on to valve. 5. Open gauge manifold valve slightly and purge air from hose with refrigerant. 6. Read the suction pressure on compound gauge and heat pressure on pressure gauge. 7. To remove, push end of hose tight against end of Schrader valve and hold in place while quickly unscrewing coupler nut from Schrader valve. 8. Remove coupler from Schrader valve. Replace caps on valve. 1. Remove gauge port cap from suction and liquid service valve ports and attach manifold gauge hoses. Connect an upright R-410A drum to center port of gauge manifold. Open refrigerant drum valve and manifold high pressure gauge valve to pressurize system to a positive pressure with refrigerant vapor. Pressurize the complete system with dry nitrogen, or CO2 until the pressure reaches 200 psig. Do not exceed 250 psig. 2. Close manifold high pressure gauge valve. Check all soldered joints, including those on the evaporator coil with an Electronic Leak Detector suitable for use with HFC refrigerants or R-410A. If a leak is found which requires soldering, pressure in the system must be bled off since it is impossible to solder with unit pressurized. Be sure all leaks are located and marked before bleeding pressure from system. 3. Close drum valve and disconnect from center port. Release nitrogen or CO2 into the atmosphere through suction line of gauge manifold. 4. Correct any leaks and recheck. When leaks, if any, have been repaired, system is ready to be evacuated and charged. Relieve all pressure from the system down to 0 psig. 5. Change the filter dryer. When leaks, if any, have been repaired, system is ready to be evacuated and charged. Relieve all pressure from the system down to 0 psig. EVACUATION Evacuation An evacuation to 500 microns is usually sufficient to remove moisture from a system using R-22 and mineral oil lubricant. A 500 micron evacuation, however, will not separate moisture from Polyol Ester oil (POE) in R-410A systems. In addition to a 500 micron evacuation, the liquid line filter dryer (R-410A compatible) must be replaced any time the system is open. When removing a filter dryer from a system, do not use a torch; use a tubing cutter to avoid releasing moisture back into the system. Older R-22 leak detectors, as well as halide torch leak detectors, will not detect leaks in R-410A systems. Never use air and R-410A to leak check, as the mixture may become flammable at pressures above 1 atmosphere. A system can be safely leak-checked by using nitrogen or a trace gas of R-410A and nitrogen. Remember: Always use a pressure regulator with nitrogen and a safety valve down stream - set at no more than 150 psig. 1. Evacuate system to less than 500 microns, using a good vacuum pump and an accurate high vacuum gauge. Operate the pump below 500 microns for 60 minutes and then close valve to the vacuum pump. Allow the system to stand for 30 additional minutes to be sure a 500 micron vacuum or less is maintained. WARNING At no time use the compressor to evacuate the system or any part of it. 2. Disconnect charging line at vacuum pump and connect to refrigerant supply. Crack the cylinder valve and purge charging line at center on manifold. Then close cylinder valve. 3. The system is now ready for the correct operating charge of Refrigerant R-410A. Page 4 of 11

R-410A System Charging Even though R-410A has a very small fractionation potential, it cannot be ignored completely when charging. To avoid fractionation, charging of an air conditioner or heat pump system incorporating R-410A shall be done with liquid to maintain optimum system performance. To insure that the proper blend composition is charged into the system, it is important that liquid only be removed from the charging cylinder. Some cylinders supplied by manufacturers have dip tubes, which allow liquid refrigerant to be removed from the cylinder when it is in the upright position. Cylinders without dip tubes have to be tipped upside down in order for liquid to be removed. The Service Technician must differentiate between which type of charging cylinder they are using to avoid removing vapor refrigerant instead of liquid refrigerant to avoid fractionation and for safety concerns. Connect the gauge manifold to the high and low side. Allow liquid to enter the high side only. The high side will hold 80-100% of the total charge. When liquid stops flowing, close high side port. The remainder of the charge will be added to the low side. Keep in mind two issues: first, never start the compressor with less than 55 psig of suction pressure. Secondly, make sure the liquid is throttled, thus vaporized into the low side of the system to avoid compressor damage. A throttling valve can be used to insure that liquid is converted to vapor prior to entering the system. Proper manipulation (restricting) of the manifold gauge set can also act as a throttling device to insure liquid is not entering the compressor. CHARGING THE SYSTEM BY WEIGHT 1. Connect manifold as instructed. 2. Place refrigerant drum upright on scale and determine exact weight of the refrigerant and cylinder. 3. With manifold suction valve closed and manifold discharge valve open, open refrigerant cylinder liquid valve and allow pressure in system to balance with pressure of cylinder or 80% of charge is in the unit - whichever comes first. 4. When there is approximately an 80% charge, front seat (close) the discharge manifold valve and let the system stabilize for about five minutes. 5. Start compressor by setting thermostat. 6. Finish charging with liquid by cracking the suction valve. Open the manifold low pressure valve to allow refrigerant to flow into the system. Throttle the manifold valve to keep pressure about 100 psig for R-410A. 7. When the correct weight of refrigerant has been added to the unit, close refrigerant cylinder valve and allow unit to run for 30 minutes. Refer to Start-Up Procedure and Check List for further start-up details. 8. Front seat gauge manifold valves, disconnect charging and gauge hoses and replace all valve caps. CHARGING 1. Single Package Units Refer to the unit serial plate for the full operating charge. PRELIMINARY CHARGING STEPS If the system has been open to the atmosphere, the filter dryer should be replaced and then evacuated. Then proceed as follows: 1. Attach a drum of proper, clean refrigerant to the center port of the charging manifold with one of the charging hoses. 2. Attach a second charging hose to the suction gauge (low pressure) side of the gauge manifold. 3. Remove the cap from the suction line valve. 4. Loosely attach the suction gauge hose to the line valve. Open the valve on the refrigerant drum and the suction valve on the charging manifold slightly to purge the air from the manifold and hoses before tightening the fitting. 5. Attach the third hose to the high pressure side of the manifold and the liquid line valve. Repeat steps 3 and 4 above. Page 5 of 11

FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS-369 Page 6 of 11

FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS-368 Page 7 of 11

WARNING To speed refrigerant flow, it may be necessary to place refrigerant drum in a pan of warm water (not greater than 130ºF). Remember to either consider the total weight of the pan of water or remove the drum for weighing frequently to keep track of the charging process. FIGURE 3 HEATING CYCLE MIS-289 Page 8 of 11

Troubleshooting the Mechanical System AIR CONDITIONING AND HEAT PUMP COOLING LOW SUCTION LOW HEAD 1. Restricted airflow over indoor coil. 2. Defective indoor fan motor. 3. Low indoor temperature 4. Iced indoor coil. 5. Restricted liquid line, dryer, metering device, etc. 6. Low charge. 7. Low ambient entering air temperature. (Low entering water temperature to water coil. ) HIGH SUCTION LOW HEAD 1. Defective or broken valves. 2. IPRV valve open. 3. Defective reversing valve. LOW SUCTION HIGH HEAD 1. Partial restriction and then overcharged. HIGH SUCTION HIGH HEAD 1. High entering outdoor air temperature. (High entering water temperature. ) 2. Low airflow outdoor coil. (Low water flow. ) 3. Overcharged. 4. Air in system. 5. Restricted outdoor coil. (Restricted water coil. ) 6. High indoor air temperature. Water source heat pump. HEAT PUMP HEATING LOW SUCTION LOW HEAD 1. Restricted airflow through outdoor coil. (Restricted water flow through water coil. ) 2. Defective outdoor motor. (Defective water pump. ) 3. Low outdoor air temperature. (Low water temperature. ) 4. Frozen outdoor coil. (Frozen water coil. ) 5. Restricted liquid line, dryer, metering device, etc. 6. Low charge. 7. Low indoor air temperature. HIGH SUCTION LOW HEAD 1. Defective or broken valves. 2. IPR valve open. 3. Defective reversing valve. LOW SUCTION HIGH HEAD 1. Partial restriction and then overcharged. HIGH SUCTION HIGH HEAD 1. High entering outdoor air temperature. (High entering water temperature. ) 2. Low indoor airflow. 3. Overcharged. 4. Air in system. 5. Restricted air coil. 6. High indoor air temperature. Water source heat pump. Page 9 of 11

TROUBLESHOOTING CHART FOR AIR CONDITIONERS P ower Supply H igh Pressure Side of Syste m Low Sid e Genera l Meter of to Line Contactor Side Load to Side Motor of Contactor Terminal Control Circuit Motor s Compresso r System Operatio n Condenser Ai r Evaporator Ai r Power Failure Blown Fuses or Tripped Circuit Breakers Faulty Wiring Loose Terminals Low Voltage Single 1PH Failure of 3PH Unbalanced Power Supply 3PH Voltage Too High Open Disconnect Switch Faulty Wiring Loose Terminal Low Voltage Defective Contacts in Contactor Compressor Overload Potential Relay Fails to Open Potential Relay Fails to Close Run Capacitor Start Capacitor Faulty Wiring Loose Terminals Control Transformer Low Voltage Thermostat Contactor Coil Pressure Control Condenser Fan Relay Evaporator Fan Relay Compressor Motor Condenser Motor Evaporator Motor Compressor Off on Internal Overload Hold Down Bolts Defective Compressor Bearings Seized Compressor Defective Compressor Valves Compressor Oil Level Open or Short Motor Windings Refrigerant Charge Low Overcharge of Refrigerant High Head Pressure High Suction Pressure Low Suction Pressure Temperatures Non-Condensables (Air, etc.) Excessive Load in Space Liquid Valve Partially Closed Condenser Fins Dirty or Plugged Condenser Fan Belt Slipping Condenser Air Short Circuiting Low Condenser Air Volume Condenser Air Temperature Low Plugged or Restricted Metering Device Evaporator Fins Dirty or Plugged Evaporator Belt Slipping Low Evaporator Air Volume Dirty Filters Ductwork Small or Restricted Restrictions Thermostat Setting Thermostat Location Stratified Air in Space Incorrect Refrigerant Piping System Too Small Generally the cause. Always make these checks first. Occasionally the cause. Make these checks only if first checks fail to locate trouble. Rarely the cause. Make this check only if previous checks fail to locate trouble. Compressor and condenser fan motor w ill not start Compressor will not start but condenser fan ill run w Condenser fan motor w ill not start Compressor "hums" but w ill not start C ompressor cycles on overload Compressor on low pressure Compressor cooling short runs cycles continuously no Compressor runs continuously cooling C ompressor noisy Compressor loses oil H ead pressure too high H ead pressure too low Liquid line frosting Suction pressure too high Suction pressure or too sweating low E vaporator frosting Suction line frosting or sweating Evaporator blower will n ot start Condenser not pulled in Liquid refrigerant compressor cap tube system fan motor runs flooding contactor back to Space temperature t oo high Page 10 of 11

TROUBLESHOOTING CHART FOR AIR TO AIR HEAT PUMPS P ower Supply O utdoor Sectio n Indoor Sectio n Line Voltage Control Circui t Compresso r Refrigerant Syste m Defrost Control Rev. Valve Check Valve Outdoor Motor and Fan Coil Indoor Motor Blower and Coil Check Aux. Heat Power Failure Blown Fuse or Tripped Breaker Faulty Wiring Loose Terminals Low Voltage Single 1PH Failure of 3PH Unbalanced 3PH Defective Contacts in Contactor Compressor Overload Potential Relay Run Capacitor Start Capacitor Faulty Wiring Loose Terminals Control Transformer Low Voltage Thermostat Contactor Coil Pressure Control or Impedance Relay Indoor Fan Relay Discharge Line Hitting Inside of Shell Bearings Defective Seized Valve Defective Motor Windings Defective Refrigerant Charge Low Refrigerant Overcharge High Head Pressure Low Head Pressure High Suction Pressure Low Suction Pressure Non-Condensables Unequalized Pressures Sensing Bulb Loose-Poorly Located Cycle Too Long (Clock timer) Defective Control, Timer or Relay Leaking Defective Valve or Coil Sticking Closed Leaking or Defective Plugged or Restricted Meter Device (Htg) Fins Dirty or Plugged Motor Winding Defective Recirculation or Air Air Volume Low (Cooling) Low Temperature Coil Air (Cooling) Plugged or Restricted Metering Device (Clg) Fins Dirty or Plugged Motor Winding Defective Air Volume Low Air Filters Dirty Undersized or Restricted Ductwork Sticking Closed Leaking or Defective Auxiliary Heat Upstream of Coil Denotes common cause. Denotes occasional cause. Compressor and O.D. fan motor d o not operate Compressor will not run O.D. fan motor runs Compressor "hums" but w ill not start C ompressor cycles on overload Compressor off on high p ressure control C ompressor noisy Head pressure too high H ead pressure too low Suction pressure t oo high Suction pressure too low I.D. blower will not start I.D. coil frosting or icing- H igh compressor amps Compressor runs c ontinuously no cooling Liquid refrigerant flooding back to compressor Compressor runs c ontinuously no heating D efrost cycle initiates no ice on coil Reversing valve does n ot shift Ice build up on lower part of O.D. coil Liquid refrigerant flooding back to compressor Auxiliary heat on I.D. b lower off E xcessive operating costs Excessive ice on O.D. coil Heating Cycle Cooling Cycle Heating or Cooling Cycles Page 11 of 11