DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE

Similar documents
SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE

Pre-Pack INTEGRATED PRE-ACTION SYSTEM

WATER POWERED OSCILLATING MONITOR

FOAM MAKER MODEL - FMA & FMA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA INSTALLATION, TESTING AND MAINTENANCE APPLICATION SPECIFICATION

SPRINKLER ALARM TECHNICAL DATA SPRINKLER ALARM MODEL - GA

FOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA FEATURES APPLICATION

FOAM CHAMBER MODEL - FCA & FCA-S TECHNICAL DATA FEATURES APPLICATION. Carbon Steel Construction FCA-65, FCA-80 & FCA-100. Stainless Steel Construction

Nitin Ventures FZE. (A Division of Nitin Fire Protection Industries Ltd.)

FOAM CHAMBER MODEL - FCA & FCA-S TECHNICAL DATA FEATURES APPLICATION. Carbon Steel Construction FCA-65, FCA-80 & FCA-100. Stainless Steel Construction

DELUGE VALVE MODEL: SD-DVH2 TECHNICAL DATA TRIM DESCRIPTION DESCRIPTION VALVE OPERATION. 82 ASTM A 216 WBC.

mechanical. OPERATION Rapidrop Global

TECHNICAL DATA. 319a. January 27, 2012

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

TECHNICAL DATA OBSOLETE

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

Deluge & Preac tion Systems

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

Model CV-1FR Riser Check Valves 2 to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data. Page 1 of 6 OCTOBER 2010 TFP950

BERMAD Fire Protection

TotalPac X Single interlock SUREFIRE system

TOTALPAC2 Integrated Fire Protection System

TotalPac X Firecycle III Preaction Double interlock system

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

Model: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Instructions for Installation, Operation, Care and Maintenance

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock

TotalPac 3 Firecyle III Deluge Remote controlled system

Technical Data. Installation

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

Worldwide Contacts.

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

TECHNICAL DATA. Factory Mutual Approval is pending for the system as a whole.

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

INSTRUCTION MANUAL HS-229G

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

N2 BLAST Datasheet Preaction double interlock, Electric/Pneumatic c/w N 2 Blast Nitrogen generating system Self contained unit

M Series Fan Filter Units

Design Criteria. Installation

INSTALLATION, OPERATION AND MAINTENANCE

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Self-contained system

Sprinkler Identification Number TY ECLH HSW, 8.0K, 3/4"NPT

Model CHEC 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers General Description

TotalPac 3 Single interlock Firecyle III Preaction Self-contained system

Rev. None AUGUST 2012 MDM SERIES MODULAR MEMBRANE AIR DRYERS OPERATOR MANUAL MDM1 MDM4 MDM9 MDM13 MDM24 MDM49 MDM66 MDM106 MDM138

The Series LFII (TY3596) Residential

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Series TY-B & TY-FRB, 10 mm Orifice, ISO 7/1-R3/8 Upright, Pendent, and Recessed Pendent Sprinklers Standard and Quick Response General Description

TotalPac 3 Wet pipe system c/w retard chamber

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE

TITAN FLOW CONTROL, INC.

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT

BROCHURE COMMERCIAL FIRE SPRINKLER CONNECTIONS. Product Submittal A PART OF

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

N2 BLAST Datasheet SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Self contained unit

DBF 4XL Dryer Booster Fans

Model/Sprinkler Identification Numbers

GRUNDFOS INSTRUCTIONS CMBE. Installation and operating instructions. Drinking Water System Component NSF / ANSI 61 NSF / ANSI 372

Model DDX Deluge Valve

AQUAMIST Mist Control Center (MCC) Pump Skid Unit. General Description. Technical Data. Page 1 of 8 JANUARY 2016 TFP2270. Worldwide Contacts

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard)

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

CSD-1 CRN Electra Steam, Inc. Instruction Manual for JR06 Steam Generator, JG- and JJ- Models

N2 BLAST Datasheet Preaction double interlock, Electric/Pneulectric c/w N 2 Blast Nitrogen generating system Self contained unit

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

Series RFII 5.6 K-factor. Flush II Concealed Pendent Sprinklers

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

OPERATION & INSTALLATION MANUAL

Deluge System. Pneumatic Release. Deluge System. Pneumatic Release

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

CONSTRUCTION REQUIREMENTS

SOLARHOT. SuperVox. Description / Applications System Overview. Installation/ Owner s Manual

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

ELECTRIC FIREPLACE HEATER WITH SINGLE GLASS DOOR

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

SYSTEM CONTROL KIT Model: CK-41P

TECHNICAL DATA. model c-2

SECTION FIRE-SUPPRESSION STANDPIPES

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

INSTALLATION 125 PSI (8.6 BAR) MAXIMUM OPERATING PRESSURE

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General Description

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM

TECHNICAL DATA OBSOLETE

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

TotalPac 3 Deluge, Electric release Self-contained system

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description

Sound Cover [ , , , ]

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

Transcription:

DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE HD FIRE PROTECT TECHNICAL DATA SIZE DELUGE VALVE CHECK VALVE SPRINKLER ALARM RELEASE PANEL 50, 80, 100, 150 & 200 NB Model H3, UL Listed Model-CH UL Listed (Optional) UL Listed (Optional) WATER FLOW UL Listed SWITCH SOLENOID VALVE 24V DC, UL Listed AUTOMATIC AIR Oil-less Risermount SUPERVISOR Compressor (Optional) AIR PRESSURE PMD-1 (Optional) MAINTENANCE DEVICE MANUAL SYSTEM UL Listed, Butterfly Valve - SHUTOFF VALVE Standard supply. (Gate Valve - Optional) MAXIMUM WORKING 17.5 Kg./sq.cm. (250 PSI) PRESSURE SYSTEM END Grooved (Standard supply) CONNECTION Flanged (Optional supply) APPROVAL UL Listed DESCRIPTION The Double Interlock Preaction System with Electric/ Pneumatic Release is generally used to protect water sensitive areas such as computer rooms, storage areas, refrigerated areas etc., to avoid water damage due to inadvertent flooding of the sprinkler system piping. In normal condition, preaction system does not contain water in the sprinkler piping. The sprinkler piping contains air pressure for the purpose of supervising its leak tightness. This is most commonly used system. This system utilizes a Deluge Valve H3 and Riser Check Valve Model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check so that the system can be automatically pressurized with a nominal supervisory air or nitrogen pressure of 10 psi (0,69 bar). A supervisory low pressure alarm switch can be set at nominally 6 psi (0,42 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open. The releasing trim for Deluge Valve utilizes a Solenoid Valve and a Dry Pilot Actuator in a series configuration. The system air pressure holds the Dry Pilot Actuator closed, whereas the Solenoid Valve remains closed until it is electrically energized by a Deluge Valve Releasing Panel (automatic control unit). The Releasing Panel is operated either by a fire detection device or manual electric pull station. In order for the Double Interlock Pre-Action System to automatically actuate, two independent events must occur. The Deluge Valve Releasing Panel must operate and open the Solenoid Valve upon automatic operation of the electric fire detection initiating circuit and the sprinkler system piping must lose air pressure due to operation of one or more sprinklers. The Double Interlock Pre-Action System will automatically actuate only when both the Dry Pilot Actuator and the Solenoid Valve are open at the same time. Unintended opening of just the Dry Pilot Actuator or the Solenoid Valve will only cause an alarm and not actuate the system or flood the sprinkler system piping. Deluge Valve H3 is diaphragm valve as described in Technical Data Sheet HD 235. INSTALLATION & COMMISSIONING The preaction system valves, panel, indicators must be installed in a readily visible and accessible location. The system valves and accessory shall not be installed in an area having temperature less than 4 o C (40 o F). Heat tracing to system valve and accessory is not permissible. The system must be installed and operated carefully by a trained person, having good knowledge of equipment. All system piping must be flushed thoroughly before commissioning. After initial successful tests, an authorized person must be trained to perform inspection, testing and maintenance of the system. JANUARY, 2018 PAGE 1 OF 6

RECOMMENDED SEQUENCE OF INSTALLATIONS 1. Install the Deluge Valve on Riser in vertical position. 2. Install the Riser Check Valve above Deluge Valve as shown in installation drawing. 3. On completion of system piping, install all the trims as per the trim drawing. Care must be taken to ensure that Check Valves, Strainers, Valves etc. are installed with the flow arrows in the proper direction. 4. Connect all drain piping as shown in the drawing. 5. All unused opening on valve or trim parts must be plugged. 6. Connect air supply line. 7. Connect all electrical to control panel as per wiring drawing. 8. Make sure that all the nut bolts, fittings are screwed properly. 9. Follow the valve resetting and test procedure. 10. The pipe fittings and nipple must be cleaned. Use thread sealent on male threads only. 11. For common drain piping a check valve to be provided interconnecting main dran and the funnel. 12. The drain tubing to be drip funnel must be installed with smooth bends that will restrict flow. 13. The drain piping must be free-flow and care must be taken to direct the drain in proper area to avoid damage due to release of system. 14. A supervisory air (Nitrogen) supply is to be installed as given in the data sheet. An air dryer, if specified, needs tobe installed as per authority having jurisdiction. 15. The electric connection through conduit is to be made as per authority having jurisdiction. RESETTING PROCEDURE a. Close the upstream side stop valve of the Deluge Valve. b. Open drain valves and allow water to drain (if water flow was establish) & close drain valve when water flow has ceased. c. Check all release devices are closed. Inspect the release devices if system was subject to fire condition. d. Open the priming line so that the diaphragm chamber reads the system water pressure. Open the manual release station partly to vent the air & then close it. e. Open the upstream side of stop valve to read the Deluge Valve Inlet water supply pressure. The Deluge Valve is set. f. Open the air supply line and check the pressure is maintained up to 0.7 Kg./Sq.Cm. (10 PSI) and Control Panel is kept on. h. Check all the trim parts for possible leak. INSPECTION AND MAINTENANCE Inspection and testing is to be carried out only by an authorized and trained personnel. DO NOT TURN OFF the water supply or close any valve to make repair(s) or test the valve, without placing a roving fire patrol in the area covered by the system. Also inform the local security personal and central alarm station, so that there is no false alarm signal. It is recommended to carry out physical inspection of the system at least twice a week. The inspection should verify that no damage has taken place to any components and check for following normal condition of the system. The owner is responsbile for maintaining the pre-action system. NORMAL CONDITION a. All main valves are open and sealed with tamper proof seal. b. All drain valves are in closed condition. c. No leak or drip is detected from drip valve. d. All water gauge of deluge valve, should show the required pressure. e. No leak in any trim or other piping. f. Release panel is on and no abnormal indication are seen. g. All testing procedure to be verified. CAUTION Procedure outlined below will result in operation of associated alarm. Concerned authorities to be informed about the tests before conducting the tests. QUATERLY TEST WATER FLOW ALARM TEST Open the sprinkler alarm gong test valve, the water will flow through sprinkler alarm and/or water flow switch. On satisafctory observation close the alarm test valve. JANUARY, 2018 PAGE 2 OF 6

SOLENOID VALVE TEST a. Close the system water supply valve provided at inlet of deluge valve. Open the main drain valve. b. Close the diaphragm chamber supply control valve and system air supply control valve. c. Energize the solenoid valve through release panel as per instruction of panel manufacturers. Water flow must start through solenoid valve and deluge valve diaphragm chamber pressure must drop down and water will get discharged through Solenoid Valve continuously. d. De-energize to close the solenoid valve and follow resetting procedure. CAUTION The system must be inspected, tested and maintained as instructed above, in addition to the requirement of NFPA or as per requirement of authority having jurisdiction. The owner is responsible for the inspection, testing and maintenance of the system and devices. AIR SUPPERVISORY LOW PRESSURE ALARM Release air pressure gradually through valve provided on check valve. When air pressure drops to 0.42 ± 0.07 Kg./Sq.Cm. (6 PSI ± 1), the supervisory low pressure alarm must be observed. Close the valve & observe that air pressure has been established to 0.7 ± 0.14 Kg. / Sq. Cm. (10 ± 2 PSI), the supervisory air pressure alarm must come to normal condition. If required reset the release panel. ANNUAL OPERATION TEST Testing valve operation without causing water upply to the deluge valve. a. Close the main system valve controlling water supply to the deluge valve. b. Open the main drain valve provided on deluge inlet side and allow water to drain. When water flow from drain valve has stopped crack open the main system valve and close the main drain valve partly allowing the water pressure at inlet of deluge valve to raise up to 1.4 Kg. / Sq. Cm.(20 PSI) and no more pressure is rising. c. Actuate the solenoid valve from control panel as per instruction of control panel manufacturer. deluge valve must open and water flow must be noticed through drip valve and through solenoid valve. Close the main supply control valve immediately and allow water to drain from drain valve. d. When water flow has stopped, reset the deluge valve as per resetting procedure. CAUTION The steps b & c must be performed very quickly to prevent water flow to riser. NOTE: For abnormal condition of deluge valve refer the data sheet No. HD235. JANUARY, 2018 PAGE 3 OF 6

HD FIRE PROTECT DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE SCHEMATIC DIAGRAM 18 13 11 10 17 9 5 3 11 15 8 12 13 4 7 2 19 6 1 FRONT VIEW 11 9 17 18 5 13 8 3 12 10 14 19 2 5 1 15 JANUARY, 2018 REAR VIEW PAGE 4 OF 6

DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE PART LIST PREACTION TRIM SIZE QUANTITY PER PREACTION TRIM ITEM NO CODE NO DESCRIPTION SIZE/ MAKE 200 NB 150 NB 100 NB 80 NB 50 NB 1 BFV WAFER TYPE GEAR OPRT. 2, HD MAKE WITH TAMPER SWITCH * (MODEL NO.HDMW300) 1 1 1 1 1 2 6458 DELUGE VALVE FLANGE END 2, HD MAKE (MODEL NO.DV-H3) - - - - 1 2 6455 DELUGE VALVE FLANGE END 3, HD MAKE (MODEL NO.DV-H3) - - - 1-2 6454 DELUGE VALVE FLANGE END 4, HD MAKE (MODEL NO.DV-H3) - - 1 - - 2 6453 DELUGE VALVE FLANGE END 6, HD MAKE (MODEL NO.DV-H3) - 1 - - - 2 6457 DELUGE VALVE FLANGE END 8, HD MAKE (MODEL NO.DV-H3) 1 - - - - 3 1563 DRY PILOT ACTUATOR 1/2 HD MAKE (MODEL NO. H1) 1 1 1 1 1 4 1951 EMERGENCY RELEASE STATION 1/2 HD MAKE (MODEL NO.ERS-1) 1 1 1 1 1 5 9392 ANGLE VALVE 1-1/4 - - - 1 1 5 9394 ANGLE VALVE 2 1 1 1 - - 6 9423 PRIMING VALVE 1/2 1 1 1 1 1 7 - RESTRICTED CHECK VALVE 1/2 1 1 1 1 1 8 1825 ANTI RESET VALVE (ARV-1) 1/2 1 1 1 1 1 9 3569 CHECK VALVE - FLANGE TO GROOVE 2, HD MAKE (MODEL NO. CH) - - - - 1 9 114345 CHECK VALVE - FLANGE TO GROOVE 3, HD MAKE (MODEL NO. CH) - - - 1-9 114346 CHECK VALVE - FLANGE TO GROOVE 4, HD MAKE (MODEL NO. CH) - - 1 - - 9 114343 CHECK VALVE - FLANGE TO GROOVE 6, HD MAKE (MODEL NO. CH) - 1 - - - 9 114347 CHECK VALVE - FLANGE TO GROOVE 8, HD MAKE (MODEL NO. CH) 1 - - - - 10 74 PRESSURE MAINTENANCE DEVICE* 1/2 (PMD-1) 1 1 1 1 1 11 114071 PRESSURE GAUGE 0-300 PSI, UL LISTED 1 1 1 1 1 12 14 SPRINKLER ALARM (GONG BELL)* HD MAKE (TYPE-A) 1 1 1 1 1 13 - PRESSURE SWITCH POTTER MAKE, UL LISTED 1 1 1 1 1 14 - SOLENOID VALVE PARKER MAKE, UL LISTED 1 1 1 1 1 15 DV RELEASING PANEL * POTTER MAKE, UL LISTED 1 1 1 1 1 TRIM FITTINGS 1 1 1 1 1 17 AUTOMATIC SPRINKLER ** 1 1 1 1 1 18 HEAT DETECTOR/ SMOKE DETECTOR ** 1 1 1 1 1 19 SPLASH PROOF FUNNEL 1 1 1 1 1 * OPTIONAL SUPPLLY ** NOT SUPPLLIED BY HD FIRE NOTES: DELUGE VALVE END CONNECTION (OPTIONAL - G X G/ F X F) CHECK VALVE END CONNECTION (OPTIONAL - G X G/ F X G / F X F) BUTTERFLY VALVE END CONNECTION (OPTIONAL - G X G/ WAFER TYPE / LUG TYPE) PRESSURE GAUGE (OPTIONAL - HDP-1 / HDP-2) OPTIONAL TRIM SUPPLY - LOOSE / SEMI ASSEMBLED) SHAPE OF FITTINGS / VALVES MAY CHANGE. SYSTEM PIPING, SPRINKLER, DETECTOR NOT SUPPLIED BY HD FIRE PRIMING LINE BY OTHERS F = FLANGE END G = GROOVE END JANUARY, 2018 PAGE 5 OF 6

ORDERING INFORMATION X XX X X X Size Actuation Device Air Maintenance Device Control Panel Compressor 1 50 2 65 3 80 4 100 5 150 6 200 DP Double Interlock Electric/Pneumatic Release Pre-action System N None 1 PMD-1 2 Nitrogen Air Maintenance Device N A None Included N None 1 1/6 HP 2 1/3 HP 3 1/2 HP 4 3/4 HP 5 1 HP 6 1-1/2 HP LIMITED WARRANTY HD FIRE PROTECT hereby referred to as HD FIRE warrants to the original purchaser of the fire protection products manufactured by HD FIRE and to any other person to whom such equipment is transferred, that such products will be free from defect in material and workmanship under normal use and care, for two (2) years from the date of shipment by HD FIRE. Products or Components supplied or used by HD FIRE, but manufactured by others, are warranted only to the extent of the manufacturer s warranty. No warranty is given for product or components which have been subject to misuse, improper installation, corrosion, unauthorized repair, alteration or un-maintained. HD FIRE shall not be responsible for system design errors or improper installation or inaccurate or incomplete information supplied by buyer or buyer s representatives. HD FIRE will repair or replace defective material free of charge, which is returned to our factory, transportation charge prepaid, provided after our inspection the material is found to have been defective at the time of initial shipment from our works. HD FIRE shall not be liable for any incidental or consequential loss, damage or expense arising directly or indirectly from the use of the product including damages for injury to person, damages to property and penalties resulting from any products and components manufactured by HD FIRE. HD FIRE shall not be liable for any damages or labour charges or expense in making repair or adjustment to the product. HD FIRE shall not be liable for any damages or charges sustained in the adaptation or use of its engineering data & services. In no event shall HD Fire s product liability exceed an amount equal to the sale price. The foregoing warranty is exclusive and in lieu of all other warranties and representation whether expressed, implied, oral or written, including but not limited to, any implied warranties or merchantability or fitness for a particular purpose. All such other warranties and representations are hereby cancelled. NOTICE : The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also with the provision of government codes or ordinances wherever applicable. The information provided by us is to the best of our knowledge and belief, and consist of general guidelines only. Site handling and installation control is not in our scope. Hence we give no guarantee for result and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information, recommendation or damages due to our product. Product development is a continuous programme of HD FIRE PROTECT and hence the right to modify any specification without prior notice is reserved with the company. HD FIRE PROTECT Protecting What Matters Most to You D-6/2, ROAD NO. 34, WAGLE INDUSTRIAL ESTATE, THANE 400 604, INDIA. TEL: + (91) 22 2158 2600 FAX: +(91) 22 2158 2602 EMAIL: info@hdfire.com WEB: www.hdfire.com JANUARY, 2018 PAGE 6 OF 6