INSTRUCTIONS FOR THE LCR10 TEN INCH CIRCULAR CHART RECORDER

Similar documents
Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

AutomationDirect PM24. Microprocessor - Based Process/Temperature Limit Controller. Operator s Manual. Technical Support.

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS

108A OTP1800. Grid Support. General Description

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

Series Temperature Controller Instruction Sheet

DIGITAL METERS Large Display Temperature Meters Instruction Manual

INSTALLATION INSTRUCTIONS

E340 BOILER CONTROL INSTALLATION MANUAL

Analog Room Pressure Monitor RPC Series

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS

Interchangeable thermistor (THE types) Output Contact E5CS-R1KJX-F E5CS-R1PX-F E5CS-R1GX-F Voltage E5CS-Q1KJX-F E5CS-Q1PX-F E5CS-Q1GX-F

DICKSON KT6 DICKSON. Temperature Chart Recorder. Specifications. Product. Display Symbols. Information & Operating. Contents:

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

Temperature Controllers

WSK300 Multifunction Wall Control

Operator: Save these instructions for future use!

Digi-Sense TC9000 Advanced PID and On/Off Temperature Controller with Thermocouple Input

I/A Series 716C 1/16 DIN Temperature Controller

Carbon Monoxide Transmitter

Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3

UDC100 Universal Digital Controller Specifications

Combustible Gas Sample-Draw Detector Operator s Manual

Carbon Dioxide Sample-Draw Detector Operator s Manual

DE20 INSTRUCTION MANUAL

UDC 700 Universal Digital Controllers and Indicator Specifications

TECHNICAL INFORMATION Touchtronic Clothes Dryers

User's Manual: Series 260A Model 260A Process Current Loop-Powered Alarm

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

Duct and Rough Service Carbon Monoxide Sensor

Operator: Save these instructions for future use!

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25T EN0l-6091 February 2009

Oakton TEMP 9500 Advanced Multiparameter Controller

Table of Contents. T538 Instruction Manual Rev # 6 June R6T538 June rtf E L Switchgear and Control Inc

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

DESCRIPTIVE AND INSTALLATION INSTRUCTION MANUAL FOR MODEL G1000 AND H1000 SERIES ANNUNCIATORS

SERVICE MANUAL VC3ED FULL SIZE ELECTRIC CONVECTION OVEN - NOTICE -

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT

Table of Contents SECTION PAGE

Greentrol Automation, Inc.

S304 and S305 Dust Emission Monitors. User Manual. Distributor

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

02/11/2015

IF79 CAUTION CONTENTS YOUR THERMOSTAT REPLACES 1 PREPARATIONS. Installation Instructions for. Heating & Air Conditioning

LC2200 Level Controller Installation and Maintenance Instructions

MAINTENANCE & TROUBLESHOOTING GUIDE LEAK ALARM CHANNEL DRY OIL WATER AUX ALARM HIGH LOW CRITICAL WATER TANK LEVEL ALARM MODEL LDE-740 ADVANCE PAPER

Operator: Save these instructions for future use!

Mark 25 Ultrapure Water Conductivity Analyzer

SAFETY INFORMATION AND WARNINGS

MODEL AC-SCC-5 INSTALLATION, OPERATION & MAINTENANCE MANUAL

RTD TEMPERATURE SENSING SYSTEM

Beacon 800 Gas Monitor Operator s Manual

SERVICE MANUAL FOR 6795B,C,D SERIES PACKAGED AIR CONDITIONERS

Beacon 410A Gas Monitor Operator s Manual

Operator: Save these instructions for future use!

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

CP CP

Operator: Save these instructions for future use!

DESCRIPTIVE AND INSTALLATION INSTRUCTION MANUAL FOR MODEL AH1000, BH1000, AND EH1000 SERIES ANNUNCIATORS

MODEL: O ELECTROCHEMICAL O2 DETECTOR (Used with ST1400 O2 Sensor) Part Number: MAN Rev. 0

INSTRUCTION MANUAL Portable Refrigerator Units MODEL 15-LITER Including the Standard Battery Backup System (BBS)

RATIO:GUARD Model E-1S EC Monitor

INTRODUCTION / TABLE OF CONTENTS

Dual Input Toroidal Analyzer

RK-OXY Oxygen Sample-Draw Detector Operator s Manual Part Number: RK Revision: P1 Released: 7/18/02

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

Dual Input ph/orp Analyzer

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

RKA-LEL Sample Draw Combustible Gas Detector

Operating Instructions. For. Alarm Control Module. Model SSR 500

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Carbon Monoxide Sample-Draw Detector Operator s Manual

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A

IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

MODEL 8144-RD CLOCK SELECTOR/DISTRIBUTION AMPLIFIER INSTRUCTION MANUAL. SPECTRACOM CORPORATION 95 Methodist Hill Drive, Suite 500 Rochester, NY 14623

HP 101A Series Humidity Temperature Probes INSTRUCTION MANUAL

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

VARIABLE SPEED GRINDER OWNER S MANUAL R MANUAL VERSION SERIAL #

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Series 670 Hood Monitor. Bulletin AV-670

3800 North Mill Road Vineland, NJ USA Tel: Fax: Web: Rev. A

FLT93 Installation, Operation and Troubleshooting Guide

F4 Process Controller Installation and Operation Guide

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010 Rev.

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

R1000 / R1040 / R1080

TFD-1 Installation & User s Guide

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

Transcription:

INSTRUCTIONS FOR THE LCR10 TEN INCH CIRCULAR CHART RECORDER LOVE LOVE CONTROLS a Division of Dwyer Instruments, Incorporated PO Box 338 Michigan City, IN 46361-0338 (800) 828-4588 (219) 879-8000 FAX (219) 872-9057 www.love-controls.com April, 2003 Page 1 of 20 LCR10 IOM

Contents Chapter 1 Overview 1-1 General...3 1-2 Model Identifi cation...3 Chapter 2 Installation 2-1 Unpacking...4 2-2 Mounting...4 2-3 Case Location...5 2-4 Wiring Precautions...6 2-5 Power Wiring...7 2-6 Sensor Installation Guidelines...8 2-7 Thermocouple Input Wiring...9 2-8 RTD Input Wiring...10 2-9 Linear DC Input Wiring...10 2-10 Alarm Relay Wiring...10 2-11 Changing the Chart...11 2-12 Marking Systems...11 2-13 Replacement of Pen...12 2-14 Battery Backup...13 Chapter 3 Programming 3-1 Recorder Setup...14 3-2 Alarm Settings...15 Chapter 4 Calibration...16 Chapter 5 Specifi cations...18 Chapter 6 Dimensions...19 Chapter 7 Green LED Troubleshooting Guide...20 LCR10 IOM Page 2 of 20 April, 2003

Chapter 1 Overview 1-1 General The LCR10 is a microprocessor based 10 inch circular chart recorder. Programmable alarm options combined with ease of setup provide the fl exibility required for a multitude of recording applications. The Ink style LCR10 is the fi rst recorder with self documenting confi guration during initial setup. It can operate using standard or competitive charts. The battery backup feature provides up to 48 hours of recording in the event of a power loss, providing an additional degree of protection for customer processes. A unique setup template provides the user with an on the spot manual. This setup template will also self document the current setup for quick review by an operator. These units are powered by a fi eld selectable 110/220VAC 50/60Hz. supply. A 9 Volt battery allows for operation for up to 48 hours if the main power supply fails. Standard inputs are programmable for thermocouple types J, K, T, R, B and S as well as 4-20mA or 0-5 VDC. Optional alarm relay is available and programmable for low, hi, or band in latching or non-latching operation. High accuracy, maximum fl exibility, fast response and a simple interface are the main benefi ts of the LCR10 recorder. 1-2 Model Identifi cation LCR10 - Rotation: 1 = Counterclockwise 2 = Clockwise Outputs: 0 = None 1 = 1 Relay Enclosure: 1 = Standard 2 = NEMA 4X 3 = Platen Mount April, 2003 Page 3 of 20 LCR10 IOM

Chapter 2 Installation Dangerous voltages capable of causing serious injury or death are sometimes present in this instrument. Before installation or beginning any troubleshooting procedures, the power to all equipment must be switched off and isolated. More than one power disconnect may be required. Units suspected of being faulty must be disconnected and removed to a properly equipped workshop for testing and repair. Component replacement and internal adjustments must be made by a qualifi ed maintenance personnel only. To minimize the possibility of fi re or shock hazards, do not expose this instrument to rain or excessive moisture. Do not use this instrument in areas under hazardous conditions such as excessive shock, vibration, dirt, moisture, corrosive gases or oil. The ambient temperature of the areas should not exceed the maximum rating specifi ed in Chapter 5. 2-1 Unpacking Upon receipt of the shipment remove the unit from the carton and inspect the unit for shipping damage. If any damage due to transit, report and claim with the carrier. Write down the model number, serial number, and date code for future reference when corresponding with our service center. The serial number (S/N) and date code (D/C) are labeled on the box and the platen of the unit. Make sure that all items are accounted for: 1: Battery (for battery backup) 2: Installation manual 2-2 Case Location Upon unpacking, fi nd a suitable location to mount the recorder before wiring power to the unit. Select a location that is well lighted, free form dust, dirt, or corrosive fumes. The recorder should not be located near any sources of heat or be subjected to sudden or extreme temperature changes. It should be mounted on a rigid support that is not subject to vibration. LCR10 IOM Page 4 of 20 April, 2003

2-3 Mounting Make panel cutout to dimension shown in Figure 2-1. Install both mounting clamps and insert the case into the panel cut out. Dimensions are in millimeters (inches). 355.60 (14.000) 334.95 (13.187) 90.07 (3.546) 17.45 (0.687) 355.60 (14.000) 302.41 (11.906) 320.68 (12.625) 355.60 (14.000) 90.07 (3.546) 320.68 (12.625) Figure 2-1 April, 2003 Page 5 of 20 LCR10 IOM

2-4 Wiring Precautions Before wiring, verify the label for correct model number and options. Switch off the power when checking. Care must be taken to ensure that maximum voltage rating specifi ed on the label are not exceeded. It is recommended that power of these units to be protected by fuses or circuit breakers rated at the minimum value possible. All units should be installed inside a suitably grounded metal enclosure to prevent live parts being accessible from human hands and metal tools. All wiring must conform to appropriate standards of good practice and local codes and regulations. Wiring must be suitable for maximum voltage, current, and temperature rating of the system. Take care not to over-tighten the terminal screws. Unused control terminals should not be used as jumper points as they may be internally connected, causing damage to the unit. Verify that the ratings of the output devices and the inputs as specifi ed in Chapter 5 are not exceeded. Electric power in industrial environments contains a certain amount of noise in the form of transient voltage and spikes. This electrical noise can enter and adversely affect the operation of microprocessor-based controls. For this reason we strongly recommend the use of shielded thermocouple extension wire which connects the sensor to the unit. This wire is a twisted-pair construction with foil wrap and drain wire. The drain wire is to be attached to earth ground at the sensor end only. LCR10 IOM Page 6 of 20 April, 2003

2-5 Power Wiring The unit is supplied to operate at 110/220VAC 50/60Hz. Check that the installation voltage corresponds with the power rating indicated on the product label before connecting power to the unit. The recorder uses AC power when it is operating normally. The battery backup option will allow the recorder to operate for approximately 48 hours in case of a power loss. In order to connect the recorder to the main AC power, you must fi rst gain access to the microprocessor PC board that is mounted to the back of the chart plate. Your recorder will have a hinged chart plate held in place by two (2) screws located on the right hand side of the chart plate. Remove these two screws and open the hinged chart plate. If you are not sure how to access the back of the chart plate. See Figure 2-5 (pg. 13) for screw location. T1 T2 T3 T4 AC Input Terminals L1 L2 T1 T2 T3 T4 L1 L2 110 VAC Wiring 220 VAC Wiring NOTE: Connect Earth Ground to terminal on rear of chart plate near power transformer. Figure 2-2 The AC power connections are made to terminal block location on the back side of the chart plate of the recorder. Refer to Figure 2-2 for proper connection to the main AC power. This equipment is designed for installation in an enclosure which provides adequate protection against electric shock. The enclosure must be connected to earth ground. Local requirements regarding electrical installation should be rigidly observed. Consideration should be given to prevent unauthorized or accidental access to the power terminals. April, 2003 Page 7 of 20 LCR10 IOM

2-6 Sensor Installation Guidelines Proper sensor installation can eliminate many problems in a control system. The probe should be placed so that it can detect any temperature change with minimal thermal lag. In a process that requires fairly constant heat output, the probe should be placed close to the heater. In a process where the heat demand is variable, the probe should be close to the work area. Some experiments with probe location are often required to fi nd this optimum position. Proper sensor type is also a very important factor to obtain precise measurements. The sensor must have the correct temperature range to meet the process requirements. In special processes the sensor might need to have different requirements such as leak-proof, anti-vibration, antiseptic, etc. Standard thermocouple sensor limits of error are 2 degrees C (4 degrees F) or 0.75% of sensed temperature (half that for special limits of error) plus drift caused by improper protection or an over-temperature occurrence. This error is far greater than recorder error and cannot be corrected at the sensor except by proper selection and replacement. In order to connect the probe input device to the recorder, you must fi rst gain access to the microprocessor PC board that is mounted to the back of the chart plate. CAUTION! DO NOT TOUCH the terminals of the transformer while the recorder is connected to the main AC power supply. To avoid the risk of possible electric shock, unplug or disconnect the recorder from the main power supply before attempting to open the recorder. Also, disconnect the 9 Volt battery to avoid damaging the recorder and draining the battery. The recorder has a hinged chart plate held in place by two (2) screws located on the right hand side of the chart plate. Remove these two screws and open the hinged chart plate. See Figure 2-5 (pg. 13) for screw location. LCR10 IOM Page 8 of 20 April, 2003

Note: Internal circuitry shown at right of terminations, external to the left. Optional Relay 1 Relay Connections Relay 2 1 J2 1 J2 P1 P2 J5 RTD Voltage/ Current 1 J3 1 2 3 4 1 2 3 4 1 J3 T/C J1 1 J3 1 2 3 4 1 J3 J1 Optional Relay (Connected to power input) Figure 2-3 Input/Relay wiring - PCB layout 2-7 Thermocouple Input Wiring Thermocouple input connections are shown in Figure 2-3. The correct type of thermocouple extension lead-wire or compensating cable must be used for the entire distance between the unit and the thermocouple, ensuring that the correct polarity is observed throughout. Splices in the cable should be avoided, if possible. If the length of thermocouple plus the extension wire is too long, it may affect the temperature measurement. A 400 ohms K type or a 500 ohms J type thermocouple lead resistance will produce approximately 1 degree C temperature error. April, 2003 Page 9 of 20 LCR10 IOM

2-8 RTD Input Wiring Two-wire RTD s should be used in short lead lengths, if possible, for the purpose of accuracy. A 0.4 ohm lead resistance of a two-wire RTD will produce 1 degree C temperature error. RTD connection are shown in Figure 2-4, with the compensating lead connected to terminal 4. For twowire RTD inputs, terminals 2 and 4 should be linked. The three-wire RTD offers the capability of lead resistance compensation provided that the three leads are of same gauge and equal length. 2-9 Linear DC Input Wiring DC linear voltage and linear current connections are also shown in Figure 2-5. Terminal 2 = negative. Terminal 3 = positive. 2-10 Alarm Relay Connections If your recorder has the optional relay contacts installed, then terminal blocks J1 and J2 have been provided for connection to the relay on the microprocessor PC board of the recorder. Refer to Figure 2-4 (page 9) for the location of J1 and J2 on the microprocessor PC board. CAUTION! DO NOT TOUCH the terminals of the transformer while the recorder is connected to the main AC power supply. To avoid the risk of possible electric shock, unplug or disconnect the recorder from the main power supply before attempting to access the terminals of the relay. If the recorder is installed with the battery back-up option, disconnect the 9 Volt battery to avoid damaging the recorder and draining the battery. The recorder has a hinged chart plate held in place by two (2) screws located on the right hand side of the chart plate. Remove these two screws and open the hinged chart plate. See Figure 2-5 (pg. 13) for screw location. The relay is rated for the following maximum Values: 2.0 AMPS at 25VDC, 1.0 AMP at 120VAC Warning: Damage to the recorder may result if the ratings for the relay is exceeded. LCR10 IOM Page 10 of 20 April, 2003

2-11 Changing the Chart Press and releasethe CHANGE CHART button (#3), Figure 3-1 (pg. 14). The pen will move to the left of the chart and the LED begins blinking rapidly. Unscrew (counterclockwise) the chart hub knob at the center of the chart. Remove the old chart paper and position the new one so that the correct time line coincides with the time line groove on the left side of the chart plate. Refer to Figure 2-5 (pg. 13) for the location of the time line groove. Re-attach the chart hub knob and screw securely (by hand) against the chart. Press and release the CHANGE CHART button (#3). The pen will move to the outer ring and then pause. The LED remains on. If the unit is equipped with alarm(s) or the alarm(s) are enabled, the pen will them move to the current alarm setpoint settings. For mor information on setting the alarms, see Section 3.2 (pg. 15). If the unit is not equipped with alarm(s) or the alarm(s) are disabled, the pen will move to the current input value. Check to make sure that the pen is marking on the chart paper. If it is not, then carefully adjust the pen arm to establish contact with the paper. 2-12 Chart Pens The chart pen consists of a self contained ink reservoir with a porous plastic stylus which is fastened around the outer edge of the metal pen arm. A pen cap is provided to extend the life of the ink pen during shipping or when the recorder is not in service. To remove the pen cap, gently lift the pen arm away from the chart paper. Remove the black plastic pen cap to expose the fi ber tip of the ink pen and gently place the pen back onto the chart paper. Do not let the pen arm snap back onto the chart paper. This will fl atten the fi ber tip of the pen and will no longer give you a fi ne line marking on the chart paper. Place the pen cap in a safe place for future use. If the stylus does not touch the chart, adjustment can be made by slightly bending the metal pen arm in the center towards the chart paper. Do not use more pressure than is necessary to create a fi ne line marking on the chart paper. Note: As the pen ink supply runs out, the pen color will become lighter. This indicates that the pen should be replaced. April, 2003 Page 11 of 20 LCR10 IOM

2-13 Pen Installation / Replacement Recorders that are equipped with fi ber tipped cartridge pens will have a cartridge that is color coded red. The pen cartridge is securely fastened to the metal pen arm using a special U clip tab. For ease of replacement, it is suggested that the two (2) screws that hold the pen arm be loosened and the pen cartridge and metal pen arm be removed as an assembly. Refer to Figure 2-5, pg.13, for the location of the pen arm screws. Unsnap the plastic U clip tab of the pen cartridge from the metal pen arm, remove and discard the old pen cartridge. Replace the new cartridge by opening the hinge and snapping it securely around the metal pen arm. Refer to the Figure 2-4. Pen Arm Pen Cap "U" Clip Tab Pen Cartridge Figure 2-4 Pen Installation / Replacement LCR10 IOM Page 12 of 20 April, 2003

2-14 Battery Backup Having the 9 volt DC battery back-up in place, will allow the recorder to continue to function normally for approximately 48 hours in the event of a power failure. The battery strap and battery holder are located on the front of the chart plate (refer to Figure 2-5). In order to change the battery, you must open the recorder case door. Note: Use only NEW 9 volt alkaline replacement batteries. PEN ARM SCREWS KEYPAD INDICATOR LAMP BATTERY CONNECTOR PEN ARM 9 VOLT BATTERY BATTERY HOLDER CHART 'HUB' CHAIN TIME LINE GROOVE CHART 'HUB' KNOB CHART PLATE SCREWS CHART PAPER CHART PLATE Figure 2-5 Recorder Platen Layout/Battery Installation CAUTION! DO NOT TOUCH the terminals of the transformer while the recorder is connected to the main AC power supply. To avoid the risk of possible electric shock, unplug or disconnect the recorder from the main power supply before attempting to access the terminals of the relay. If the recorder is installed with the battery back-up option, disconnect the 9 Volt battery to avoid damaging the recorder and draining the battery. April, 2003 Page 13 of 20 LCR10 IOM

Chapter 3 Programming 3-1 Recorder Setup In order to confi gure the recorder, you will need the recorder SET-UP CHART, P/N R18-270 for CCW rotation or P/N R18-272 for CW rotation. This chart contains the confi guration categories for the recorder (Probe Input, Inner Chart Values, Outer Chart Values, Scale Units, Chart Rotation Speed, Input Averaging and Relay Opotions). 1. Place the SETUP CHART on the recorder. 2. Press and release the CHANGE CHART key (3). 3. Wait until pen moves above scale and green LED stops fl ashing. 4. Press and hold the LEFT arrow key (1) until the LED goes off, then release. 5. The Pen will move to the outer ring of the chart. Wait for the LED to fl ash slowly. (.8 sec on /.8 sec off). The LED will continue to fl ash slowly during setup. 6. Loosen the Chart Knob and rotate the chart to position the RED pen in the middle of the START CIRCLE. 7. Tighten the chart knob. Press and release the CHANGE CHART key (3). The Pen will move to the PROBE INPUT column on the setup chart. 8. Using the LEFT (1) and RIGHT (2) keys, move the pen to the desired selection. 9. Press and release the CHANGE CHART key (3) to store the selection and advance to the next category. 10. Repeat selection process until all categories are programmed. You must press and release the CHANGE CHART key (3) after the last category. 11. After all categories are selected, the pen will move off scale and the LED will Stop fl ashing. (Steady on) 12. Remove the SETUP CHART and save. Install an actual recording chart. 13. Press and release CHANGE CHART key (3). 14. The LED will remain on steady, the pen will stop at the 100% ring, then move to the Alarm Setpoint Values (if enabled). The LED will turn off when the pen reaches the alarm Setpoint. Use RIGHT/LEFT arrow keys to adjust alarm value(s). The LED is on steady when the pen is recording actual values. Press and release the CHANGE CHART (#3) key to begin recording. The SET-UP CHART should be saved for future reference. Figure 3-1 Keyboard Layout LCR10 IOM Page 14 of 20 April, 2003

3-2 Alarm Settings Alarm setpoint values are selected by positioning the pen to the actual value on the recording chart. Alarm settings can be changed or viewed after a CHART CHANGE, recorder setup, or during initial power up. To set the alarm setpoint during normal recording operation, complete the following steps. Press and release the CHANGE CHART key ( 3 on Figure 3-1). Wait until the pen moves off scale AND the LED stops fl ashing quickly and goes to a steady on. Press and release the CHANGE CHART key ( 3 ) again. The pen will begin to move back onto the chart briefl y stopping at (or close to) the outermost graduation of the chart. The Green LED remains on steady during this time. Single Alarm Setting When the above operation is complete, the pen will move to the current alarm setpoint position on the chart. The green LED will go out, during this time the alarm setpoint can be adjusted using the LEFT arrow (1) or the RIGHT arrow (2) keys on the keypad. Once the alarm setpoiont is set, wait for the green LED to turn on. The pen will then move to indicate the input value and the unit will begin normal recording operation. Band Alarm Setting When programming the recorder for operation, the pen will move fi rst to alarm band 1 setpoint on the chart. The green LED will go out. The alarm band 1 setpoint can now be adjusted using the LEFT arrow (1) or the RIGHT arrow (2) keys. Once set, wait for the green LED to turn on. The active pen will then move to the second band alarm setpoint. The green LED will go out. The alarm band 2 setpoint can now be adjusted using the LEFT arrow (1) or the RIGHT arrow (2) keys. When pen alarm setpoints adjustments are complete, wait for green LED to turn on. The pen will then move to the current input value and recorder will begin normal operation. The Change Chart key is the RESET when the recorder is programmed for latching alarm operation. Please note that the relay will only reset if alarm condition has been cleared. April, 2003 Page 15 of 20 LCR10 IOM

Chapter 4 Calibration 4-1 Pen Arm Calibration Pen calibration is a two point calibration. To check and/or adjust the recording pen(s) calibration to the inner and outer graduations of the chart, Perform the following. 1. Remove power to instrument and remove the battery. 2. With all power removed, press and hold the CHANGE CHART key (3). While holding the CHANGE CHART key(3), re-apply power. Release key upon applying power, either AC or battery, which ever is convenient. 3. The pen will move off scale, The LED will fl ash rapidly. The Green LED will then go to steady on. 4. The red pen will then move to the 100% ring. Adjust pen using the LEFT (1) and RIGHT (2) keys to position pen on the 100% ring, if necessary, Then Wait. 5. The Red pen will then move to the 0% ring. Adjust the pen position using the LEFT (1) and RIGHT (2) keys, if necessary, then wait. 6. The Red pen will then move full upscale. 8. Red pen calibration is now complete. If unit has alarms enabled pens will now go to current alarm settings. See Section 3.2. Then to actual recording value. If no alarms are enabled pen will then go directly to actual recording values and begin normal operation. Each time the chart paper or fi ber tip pen cartridge is changed, you should make sure that each pen stops at the inner and outer most temperature graduations of the chart paper. Otherwise, this pen offset can cause the unit to record an incorrect value on the chart. Figure 4-1 LCR10 IOM Page 16 of 20 April, 2003

4-2 Probe Offset Adjustment (pen offset) This recorder has been accurately calibrated at the factory. Before making any adjustments, this instrument should be in service for 24 hours. Thereafter, if any adjustment is required, perform the following procedure. 1. Place a Certifi ed Test indicator alongside the recorder s sensor probe in a monitored controlled condition. 2. Once the input has leveled out, compare the position of the pen on the recorder to the reading on the test device. 3. If an adjustment is required, depress and hold either the LEFT (1) or RIGHT (2) arrow key. The pen will begin to move after approximately ten (10) seconds. Using the LEFT arrow (1) or RIGHT (2) arrow keys, position the pen on the chart to correspond to the value of the test device. Once the corrected value is obtained no further keystrokes are required. After the calibration check is complete, the recorder will return to normal recording mode within 10 seconds. April, 2003 Page 17 of 20 LCR10 IOM

Chapter 5 Specifi cations Input: Thermocouple: Type J, K, T, R, S, B. RTD: 100 Ohm Platinum DIN Curve (0.00385 ohms per ohm per degree C) Process: 0 to 5 VDC, 250 Ohms impedance. 4 to 20 ma across 250 Ohms. Cold Junction Accuracy: ±0.2 C @ 25 C ambient. Cold Junction Error: ±0.2 C @ 25 C ambient. Input Filtering: Programmable, 0, 2, 4, 8, 16, 32, 64, 128 seconds. Recording: Chart Size: 254 mm (10 inches) Recording Accuracy: ±0.5% of span (100 division span) Sensor Break: Full scale pen < 10 seconds. Chart Speed: Programmable, 4, 8, 12, 24, 48, 72, 168 hour rotation (168 hours = 7 days). Output Relay: Form C (DPDT), 1A @ 240VAC Resistive. Power: Line Voltage: 110/220 VAC ±10%, 50~60 Hz. Common Mode Rejection: >120db @ 60 Hz. Normal Mode Rejection: 85dB @ 60 Hz. Power Consumption: 15 VA maximum. Backup Battery: 9 Volt alkaline (IEC 6LR61 or equivalent). Operational and Physical: Operating Temperature: 0 to 60 C (32 to 140 F) Storage Temperature: -40 to 65 C (-40 to 150 F) Humidity: 0 to 90% RH (non-condensing) Vibration: 0.3 to 100 Hz @ 0.2g Mounting: ±20 degrees of vertical, ±10 degrees of horizontal. Dimensions: See drawing. Panel Ratings: NEMA 12X standard, NEMA 4X optional Moldings: Fire retardant Noryl w/ acrylic window. Weight: 3.2 kg (7.0 pounds) maximum. LCR10 IOM Page 18 of 20 April, 2003

Input Ranges Input Signals SENSOR TYPE RANGES Thermocouple J -130 to 760 C -202 to 1400 F Thermocouple K -130 to 1360 C -202 to 2498 F Thermocouple T -200 to 400 C -328 to 752 F Thermocouple R 0 to 1650 C 32 to 3002 F Thermocouple S 0 to 1650 C 32 to 3002 F Thermocouple B 100 to 1824 C 212 to 3315 F RTD 100 Ohm Plt. DIN -210 to 440 C -346 to 824 F DC Voltage: 0 to 5 VDC, linear. DC Current: 4-20mA, linear. 0 to 100% of the chart span. Chapter 6 Dimensions Dimensions are in millimeters (inches). 355.60 (14.000) 334.95 (13.187) 90.07 (3.546) 17.45 (0.687) 355.60 (14.000) 302.41 (11.906) 320.68 (12.625) 355.60 (14.000) 90.07 (3.546) 320.68 (12.625) April, 2003 Page 19 of 20 LCR10 IOM

7 - GREEN LED Troubleshooting Guide 7-1 LED LIGHT SEQUENCE GUIDE 1.) LED on steady and pen(s) within chart range, unit is recording normally. 2.) LED on steady and pen(s) above 100% ring indicates unit is in CHART CHANGE mode. Action: Press and release CHART CHANGE key to return to normal recording mode. 3.) LED fl ashing RAPIDLY and pen(s) within chart range indicates battery voltage is low. Action: Replace battery. 4.) LED fl ashing RAPIDLY and pen(s) at 0 or 100 % ring indicates that input sensor(s) are in a break condition. Action: Check or replace sensor, validate setup information for sensor. 5.) LED fl ashing slowly (.8 sec.. On/.8 sec. off) indicates the unit is in setup mode. Action: Complete setup procedure of recorder. 6.) LED not on indicates no power to unit. Action: Check to see if AC present on power terminals. Check and / or replace battery. LCR10 IOM Page 20 of 20 April, 2003