TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

Similar documents
TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

TEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies

January 16 th, 2014 New York City

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Application Engineering

TEST REPORT #68. Chiao M. Lee Paul Laurentius. Hussmann Corporation St. Charles Rock Road Bridgeton, MO United States of America

Figure 1: Schematic of internal heat exchanger vapor-injection cycle

Pressure Enthalpy Charts

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Technical Information

2016 Annual Conference

Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Low GWP Refrigerants for Air Conditioning Applications

R32 Compressor for Air conditioning and Refrigeration applications in China

Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

GWP Alternative Refrigerants

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

R-404A Alternative with Low Compressor Discharge Temperature

The Refrigeration Cycle

REFRIGERANT CHANGEOVER

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

The Refrigeration Cycle

TEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

R4H4. Product Specifications

Technical Information

Refrigerant Glide and Effect on Performances Declaration

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

R4H4. Product Specifications

TEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Copeland Scroll Condensing Units for the Food Service Market

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

AE Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

AE R13 August 2018 Economized Vapor Injection (EVI) for ZF*KVE and ZF*K5E Compressors TABLE OF CONTENTS

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Refrigerants and lubricants

Technical Bulletin (TB-0037)

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Performance Measurement of R32 Vapor Injection Heat Pump System

Modeling and Testing of an R-23/R-134a Mixed Refrigerant System for Low Temperature Refrigeration

Report No CRT-414

WCH5**4. Product Specifications

Air Cooled Packaged Systems AIRAH Back to Basics

Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units

N4H4. Product Specifications

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Understanding Applications for Alternative Refrigerants

Technical Information

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers

System Modeling of Gas Engine Driven Heat Pump

Effects of Refrigerant-Lubricant Combinations on the Energy Efficiency of a Convertible Split-System Residential Air-Conditioner

A WET-VAPOUR INJECTION AND VARIABLE SPEED SCROLL COMPRESSOR AIR TO WATER HEAT PUMP MODEL AND ITS FIELD TEST VALIDATION

R-407A R-448A R-449A

Scroll Compressor for Mobile HVAC/R Application

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Comparative Performance of HFO Blends in a Condenser

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS

THE FIVE W s SYSTEMES LMP MECHANICAL SUB-COOLING. I.G.A. GIRARD, TERREBONNE, Qc. INCREASED SYSTEM EFFICIENCY & LOWER ENERGY COSTS

DOE and EPA Impacts to Commercial Refrigeration

Exhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total.

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Copeland Scroll ( HP) ZB*KA and ZF*KA for Refrigeration

Evaluation of HCFC Alternative Refrigerants

Transcritical CO2 Bottle Cooler Development

Understanding Applications for Alternative Refrigerants

Oxyvap Evaporative Cooling Applications

Technical Development Program

INDEXING AND CLASSIFICATION SYSTEM

MAC N-407 Air-Cooled Chiller

Commercial High-Efficiency Condensing Units

Single Screw Ammonia Heat Pumps. Harness Your Heat... Don t Reject It

NH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT

Refrigerant Cycle. Performance Data 1) Electric. Acoustic Pressure Level. Compressor. Connections, Dimensions

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Scroll Chillers Transition from HCFC-22 to HFCs

Transcription:

Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #34 Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor Rajan Rajendran Autumn Nicholson Emerson Climate Technologies, Inc. 1675 West Campbell Rd. Sidney, OH 45373-0669 April 14, 2014 This report has been made available to the public as part of the author company s participation in the AHRI s Low-GWP AREP.

List of Tested Refrigerants Compositions (Mass%) DR-7 R-32/R-1234yf (36/64)

Contents Introduction... 3 Details of Test Setup... 4 Description of Test Refrigerant-Lubricant and Charge... 4 Description of Compressor... 4 Table 1. Compressor Calorimeter Test Points... 4 Description and Size of Test Loop... 5 Figure 1. Simplified System Diagram of Test Setup... 5 Table 2. Test Loop Component Accuracy... 6 Results... 7 Table 3. DuPont DR-7 Test Results (20F Superheat)- Dew Point... 8 Performance Curves and Coefficients... 9 Figure 2. DR-7 10-Coefficient Polynomial Equations for Cooling Capacity and Power (20F Superheat, 0F Subcool)... 9 Figure 3a and 3b. ZF18K4E-TFD R-404A Low Temperature and Medium Temperature Operating Map-With Liquid Injection (65 F Return Gas, 0F Subcool)... 9 Figure 4. R-404A Cooling Capacity vs. Evaporating Temperature (Dew Point)...10 Figure 5. DR-7 Cooling Capacity vs. Evaporating Temperature (Dew Point)...11 Figure 6. R-404A Input Power vs. Evaporating Temperature (Dew Point)...12 Figure 7. DR-7 Input Power vs. Evaporating Temperature (Dew Point)...13 Figure 8. R-404A Cooling COP vs. Evaporating Temperature (Dew Point)...14 Figure 9. DR-7 Cooling COP vs. Evaporating Temperature (Dew Point)...15 Comparative Analysis...16 Figure 10. DR-7/R-404A Cooling COP vs. Evaporating Temperature (Dew Point)...17 Figure 11. DR-7/R-404A Cooling Capacity vs. Evaporating Temperature (Dew Point)...18 Summary...19 2

Introduction This Report covers the calorimeter testing results of DuPont DR-7 performed by Emerson Climate Technologies, Inc. (Emerson) for the AHRI Low-GWP AREP study. The testing was done in Emerson s A2L Research calorimeter lab test facility located in Sidney, Ohio. The refrigerant was tested with a R-404A Copeland Scroll compressor ZF18K4E-TFD for refrigeration applications. This report is based on a drop-in test. No optimization, oil or hardware changes were made to account for the alternative refrigerant. All compressor tests are performed at a refrigerant s dew point temperature for suction and discharge pressure conditions, per AHRI Standard 540 requirements. This does not have an impact on comparing compressor performance between two or more refrigerants that do not exhibit temperature glide. However, when refrigerants exhibit temperature glide, it is important to note that actual systems operate closer to the mid-point condition. When comparing compressor performance of one refrigerant with glide to another refrigerant without glide, or comparing two refrigerants with significantly different glides, comparison at pressures corresponding to the mid-point of the temperature glide rather than the dew point will yield results that are more representative of actual operation in a system. 3

Details of Test Setup Description of Test Refrigerant-Lubricant and Charge Refrigerant/Refrigerant Blend tested: DuPont DR-7 o Initial Refrigerant Charge: 3.3 lbs (1.5 kg) Lubricant: o 32-3MAF POE Oil o Viscosity grade: 32 cst o Any modifications to base lubricant? No Description of Compressor Copeland R-404A Scroll No compressor modifications Emerson Climate Technologies, Inc. Copeland Brand Model No. ZF18K4E-TFD, Serial No. 12A5735AD Motor Nameplate Rating: 460V-3Ø-60Hz, 2 hp, 8.9A RLA (MCC/1.4), 3500 RPM (nominal) Displacement: 5.983 in 3 /rev Air Flow Required (Y/N?): Yes Quantity: 1,360 ft 3 /min (38.5 m 3 /min) Velocity and Temperature of Air: 95 F Ambient Orientation of Air Flow In Relation to the compressor: Perpendicular to the vertical axis of the compressor Compressor Test Points (see Test Points in Table 1) Table 1. Compressor Calorimeter Test Points Refrigerant Vapor Saturated Saturated Suction Ambient Air Suction Temperature Discharge Discharge Discharge Volts-Phase- Temperature Temperature Pressure Entering Pressure Temperature Temperature 1 Frequency (Dew Point) Compressor (Dew Point) Speed F C psia Bar F C F C psia Bar F C F C V-Ø-Hz RPM 95 35.0 16.5 1.1-40 -40.0-20.0-28.9 150.7 10.3 70 21.1 202 94.4 460-3-60 3,561 95 35.0 16.5 1.1-40 -40.0-20.0-28.9 203.9 13.9 90 32.2 235 112.8 460-3-60 3,556 95 35.0 16.5 1.1-40 -40.0-20.0-28.9 263.3 17.9 108 42.2 274 134.4 460-3-60 3,542 95 35.0 24.1 1.6-25 -31.7-5.0-20.6 252.6 17.2 105 40.6 232 111.1 460-3-60 3,542 95 35.0 27.1 1.8-20 -28.9 0.0-17.8 150.7 10.3 70 21.1 171 77.2 460-3-60 3,556 95 35.0 27.1 1.8-20 -28.9 0.0-17.8 203.9 13.9 90 32.2 197 91.7 460-3-60 3,547 95 35.0 27.1 1.8-20 -28.9 0.0-17.8 344.5 23.4 128 53.3 276 135.6 460-3-60 3,515 95 35.0 42.3 2.9 0-17.8 20.0-6.7 175.8 12.0 80 26.7 161 71.7 460-3-60 3,535 95 35.0 42.3 2.9 0-17.8 20.0-6.7 235.5 16.0 100 37.8 188 86.7 460-3-60 3,535 95 35.0 42.3 2.9 0-17.8 20.0-6.7 309.9 21.1 120 48.9 221 105.0 460-3-60 3,535 95 35.0 42.3 2.9 0-17.8 20.0-6.7 377.3 25.7 135 57.2 254 123.3 460-3-60 3,489 95 35.0 63.3 4.3 20-6.7 40.0 4.4 175.8 12.0 80 26.7 146 63.3 460-3-60 3,535 95 35.0 63.3 4.3 20-6.7 40.0 4.4 235.5 16.0 100 37.8 169 76.1 460-3-60 3,518 95 35.0 63.3 4.3 20-6.7 40.0 4.4 309.9 21.1 120 48.9 196 91.1 460-3-60 3,499 95 35.0 63.3 4.3 20-6.7 40.0 4.4 309.9 21.1 120 48.9 193 89.4 460-3-60 3,485 95 35.0 63.3 4.3 20-6.7 40.0 4.4 402.3 27.4 140 60.0 231 110.6 460-3-60 3,469 95 35.0 99.9 6.8 45 7.2 65.0 18.3 235.5 16.0 100 37.8 159 70.6 460-3-60 95 35.0 99.9 6.8 45 7.2 65.0 18.3 309.9 21.1 120 48.9 180 82.2 460-3-60 95 35.0 99.9 6.8 45 7.2 65.0 18.3 402.3 27.4 140 60.0 207 97.2 460-3-60 1 Measured on Discharge Line 6" from Compressor Discharge Port. 4

Description and Size of Test Loop Test Loop Components: See Figure 1. Instrumentation/Accuracy: See Table 2. Figure 1. Simplified System Diagram of Test Setup 5

Table 2. Test Loop Component Accuracy Device Instrumentation Accuracy Full Scale/Span 3051S1TA3A2E11A2AT1 Suction Pressure Transducer +/- 0.025 % span 300 psia Discharge Pressure Transducer +/- 0.025 % span 800 psia EVI Pressure Transducer +/- 0.025 % span 400 psia G4AD3 Suction Pressure Signal Conditioning Module +/_ 0.08% full scale 300 psia Discharge Pressure Signal Conditioning Module +/_ 0.08% full scale 800 psia EVI Pressure Signal Conditioning Module +/_ 0.08% full scale 400 psia 3144PD1A1NA Suction Temperature Transducer ± 0.45⁰F ±0.02% of span 200 ᴼF Discharge Temperature Transducer ± 0.45⁰F ±0.02% of span 400 ᴼF Compressor Ambient Temperature Transducer ± 0.45⁰F ±0.02% of span 200 ᴼF G4AD3 Suction Temperature Signal Conditioning Module +/_ 0.08% full scale 200 ᴼF Discharge Temperature Signal Conditioning Module +/_ 0.08% full scale 400 ᴼF Compressor Ambient Temperature Signal Conditioning Module +/_ 0.08% full scale 200 ᴼF G4AD18 EVI Temperature Signal Conditioning Module ± 1.62 F 435 ᴼF DSP-1Y25A125 Watts +/- 0.1% reading +/- 0.01% full scale 155.885kW Volts +/- 0.1% full scale 720 V Amps +/- 0.1% full scale 125 A CMF025 W/MVD Transmitter Compressor Mass Flow ±0.35% of rate CMF010 W/MVD Transmitter Oil Circulation Mass Flow ±0.1% of rate 6

Results Table 3 shows the test results from drop-in compressor testing with DR-7. The R-404A baseline data is from published nominal rating data (capacity and EER within ±5% of test data). Capacity calculations for DR-7 are done via measured mass flow multiplied by enthalpy change using the refrigerant properties supplied by the chemical manufacturer. All compressor performance is based on dew temperature/pressure and was tested per AHRI Standard 540-2004. The comparison is only provided for 20F compressor superheat, as running at higher superheat / return gas conditions resulted in discharge line temperatures greater than Copeland application guidelines permit without additional discharge temperature protection (i.e. liquid injection). 7

1 Measured on Discharge Line 6" from Compressor Discharge Port. COP Base 2 Evaporating Temperature, F ( C) Dew Point Evaporator Glide, F (C) Condensing Temperature, F ( C) Dew Point Table 3. DuPont DR-7 Test Results (20F Superheat)- Dew Point Condenser Glide, F (C) Discharge Temperature 1 F ( C) Applicable Superheating, F (C) Applicable Subcooling, F (C) Cooling Compressor Capacity, Btu/hr (W) Refrigerant Mass Flow Rate, lbm/hr (kg/hr) Amperes, A (A) Input Power, W Cooling EER, Btu/W-hr Cooling COP, W/W -40 (-40) 10.8 (6) 70 (21.1) 10.7 (5.9) 202 (94.4) 20 (11) 0 (0) 13008 (3812) 177 (80) 5.1 2,422 5.37 1.57 1.07-40 (-40) 10.8 (6) 90 (32.2) 10.3 (5.7) 235 (112.8) 20 (11) 0 (0) 11364 (3331) 173 (79) 5.4 2,811 4.04 1.18 1.11-40 (-40) 10.8 (6) 108 (42.2) 9.7 (5.4) 274 (134.4) 20 (11) 0 (0) 9813 (2876) 168 (76) 5.9 3,299 2.97 0.87 1.12-25 (-32) 10.8 (6) 105 (40.6) 9.8 (5.5) 232 (111.1) 20 (11) 0 (0) 15920 (4666) 257 (117) 6.3 3,706 4.30 1.26 1.12-20 (-29) 10.9 (6) 70 (21.1) 10.7 (5.9) 171 (77.2) 20 (11) 0 (0) 22715 (6657) 297 (135) 5.5 2,931 7.75 2.27 1.03-20 (-29) 10.9 (6) 90 (32.2) 10.3 (5.7) 197 (91.7) 20 (11) 0 (0) 20490 (6005) 298 (135) 6.0 3,418 5.99 1.76 1.10-20 (-29) 10.9 (6) 128 (53.3) 8.8 (4.9) 276 (135.6) 20 (11) 0 (0) 14339 (4203) 274 (124) 7.5 4,812 2.98 0.87 1.12 0 (-18) 11 (6.1) 80 (26.7) 10.5 (5.8) 161 (71.7) 20 (11) 0 (0) 35368 (10366) 468 (213) 6.3 3,671 9.63 2.82 1.02 0 (-18) 11 (6.1) 100 (37.8) 10 (5.5) 188 (86.7) 20 (11) 0 (0) 31239 (9156) 462 (210) 7.0 4,354 7.17 2.10 1.05 0 (-18) 11 (6.1) 120 (48.9) 9.2 (5.1) 221 (105) 20 (11) 0 (0) 26724 (7832) 453 (206) 7.9 5,173 5.17 1.51 1.11 0 (-18) 11 (6.1) 135 (57.2) 8.3 (4.6) 254 (123.3) 20 (11) 0 (0) 22400 (6565) 431 (196) 8.8 5,958 3.76 1.10 1.13 20 (-7) 11 (6.1) 80 (26.7) 10.5 (5.8) 146 (63.3) 20 (11) 0 (0) 56549 (16574) 722 (328) 6.9 4,245 13.32 3.90 1.00 20 (-7) 11 (6.1) 100 (37.8) 10 (5.5) 169 (76.1) 20 (11) 0 (0) 49678 (14560) 706 (321) 7.6 4,921 10.10 2.96 1.04 20 (-7) 11 (6.1) 120 (48.9) 9.2 (5.1) 196 (91.1) 20 (11) 0 (0) 43900 (12866) 711 (323) 8.8 5,903 7.44 2.18 1.10 20 (-7) 11 (6.1) 120 (48.9) 9.2 (5.1) 193 (89.4) 20 (11) 0 (0) 44844 (13143) 726 (330) 8.7 5,884 7.62 2.23 1.13 20 (-7) 11 (6.1) 140 (60) 7.9 (4.4) 231 (110.6) 20 (11) 0 (0) 35047 (10272) 672 (305) 10.2 7,088 4.94 1.45 1.16 45 (7) 10.9 (6.1) 100 (37.8) 10 (5.5) 159 (70.6) 20 (11) 0 (0) 84331 (24716) 1146 (521) 8.9 6,020 14.01 4.11 0.99 45 (7) 10.9 (6.1) 120 (48.9) 9.2 (5.1) 180 (82.2) 20 (11) 0 (0) 73192 (21451) 1127 (512) 9.9 6,883 10.63 3.12 1.05 45 (7) 10.9 (6.1) 140 (60) 7.9 (4.4) 207 (97.2) 20 (11) 0 (0) 61277 (17959) 1107 (503) 11.5 8,147 7.52 2.20 1.12 2 Base Refrigerant is R-404A Cooling COP alt / 8

Performance Curves and Coefficients The following plots show baseline R-404A and LGWP alternative DR-7 capacity, input power and COP using the 10-Coefficient polynomial equation for each refrigerant (see Figure 2 for DR- 7 Coefficients). These coefficients should only be applied within the acceptable compressor operating envelope to avoid excessive extrapolation error in the results. Testing was only run between -25 F and 30 F evaporating temperatures in order to maintain acceptable discharge temperatures without requiring liquid injection. The R-404A operating envelope(s) for the test compressor is shown in Figure 3. The x and y axes show dew point temperatures. COOLING CAPACITY (Btu/hr): C0 C1 C2 C3 C4 C5 C6 C7 C8 C9 98402.6796 1548.7471-1689.9115 13.6636-10.7914 15.5175 0.0333-0.0625 0.0296-0.0530 POWER (W): P0 P1 P2 P3 P4 P5 P6 P7 P8 P9 2449.2661 35.1913 5.7478 0.3938-0.2884 0.0692 0.0024-0.0034 0.0023 0.0006 Figure 2. DR-7 10-Coefficient Polynomial Equations for Cooling Capacity and Power (20F Superheat, 0F Subcool) a. Low Temperature Liquid Injected Map b. Medium Temperature Liquid Injected Map Figure 3a and 3b. ZF18K4E-TFD R-404A Low Temperature and Medium Temperature Operating Map-With Liquid Injection (65 F Return Gas, 0F Subcool) 9

Figure 4. R-404A Cooling Capacity vs. Evaporating Temperature (Dew Point) 10

Figure 5. DR-7 Cooling Capacity vs. Evaporating Temperature (Dew Point) 11

Figure 6. R-404A Input Power vs. Evaporating Temperature (Dew Point) 12

Figure 7. DR-7 Input Power vs. Evaporating Temperature (Dew Point) 13

Figure 8. R-404A Cooling COP vs. Evaporating Temperature (Dew Point) 14

Figure 9. DR-7 Cooling COP vs. Evaporating Temperature (Dew Point) 15

Comparative Analysis Figures 10 through 11 show the ratio of DR-7 to R-404A cooling COP and cooling capacity, respectively, versus evaporating temperature. At extreme operating conditions, testing uncertainties could lead to higher than normal variability in reported results. 16

Figure 10. DR-7/R-404A Cooling COP vs. Evaporating Temperature (Dew Point) 17

Figure 11. DR-7/R-404A Cooling Capacity vs. Evaporating Temperature (Dew Point) 18

Summary The compressor calorimeter testing of DuPont DR-7 was carried out at dew point conditions and compared to R-404A. DR-7 has moderate refrigerant glide of about 11F (6C). The compressor capacity versus R-404A is within 90 to 110% of rated performance across the operating map of the tested compressor (refer back to Figures 3a and 3b). The capacity was less than R-404A capacity at condensing temperatures less than 110 F (43.3 C). The compressor COP of DR-7 is between about 100 and 115% of R-404A across the reduced compressor operating envelope (less liquid injection). 19