June Copyright Climatec

Similar documents
SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

A. Detail drawing M1 Standard Chilled Water Schematic 1.03 DESCRIPTION OF THE PULLMAN CAMPUS CENTRAL CHILLED WATER LOOP SYSTEM:

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Method to test HVAC equipment at part load conditions

opti-visor ultra-efficient chiller plant automation Typical specification

F-1100 Series Single Turbine Meters Suitable for pipe sizes 1 ¼ and larger.

HVAC Water chiller selection and optimisation of operation

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost

November 11, City of Sparks 215 S. 21 st St. Sparks, NV

Packaged Instantaneous Domestic Hot Water Generator Energy Source: Boiler Water

Chiller Plant Design. Application Guide AG McQuay International. Elevation Difference. Column Height When Pump Is Off

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

Water-cooled chillers with High Speed Centrifugal Compressors

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION

BOILER APPLICATION GUIDE for:

EZ Plate Instantaneous

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

CONTROLLED CHILLED BEAM PUMP MODULE

ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY

PACKAGED AIR COOLED Product Data Catalog

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall.

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

Integrated Automation Instrumentation & Terminal Devices

CONTROLLED CHILLED BEAM PUMP MODULE

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled

GP SERIES Packaged Chillers

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating

TOTAL SYSTEM EFFICIENCY: CONTROL STRATEGIES & SYSTEM DISTRIBUTION. David Grassl PE Mechanical Engineer Principal

By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL

Daikin Blueprint: Delivering Hot Water with a Chiller

University of Delaware

District Heat Montpelier. Customer Training

PURCHASING SECTION th Street, Surrey, B.C. V3S 3C7 Tel: Fax: ADDENDUM NO.

CHILLED WATER SYSTEM 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods

P-K MACH 'n' ROLL DOMESTIC HOT WATER AND COMFORT HEAT SYSTEM

Summary Comparison of Simulation Program Features

Improving Cold Chain Competitiveness with Danfoss Energy Efficiency Solutions.

Chapter-8 Capacity Control of Refrigeration Systems

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

Water Piping and Pumps

Open Protocol Data Communications

September 19, 20, 2009 Fort Lee, VA

DISTRIBUTION SYSTEMS. Water Piping and Pumps

Fans and Pumps I. Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong

Water-Cooled Dual Compressor Screw Chiller

PRESSURE INDEPENDENT CONTROL VALVE TECHNOLOGY. 3/16/2012 Fred Ferrara 1

Technical Development Program

Heat Pumps COMFORT NEED IT. When You

LL Series Chillers and Outdoor Mechanical Rooms. Engineering Catalog

Smardt Oil-Free Chillers

RTHE Series R Helical Rotary Liquid Chiller Tons 60Hz

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

TRACE 700. Slide 1. Hello, my name is Nick Cavitt and I m a marketing engineer in the C.D.S. group at TRANE.

Energy Recovery with Cooling and Heating Model ERCH

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days

Energy / Temp / Flow Monitoring with Ultrasonic Flow Meters

Life Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint. Daryl Showalter ChillerApplications Manager McQuay International

MEDICAL CHILLER SYSTEMS

MicroTech Series-200 Flooded Screw Chiller

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

American University Design Standards

Modular Chiller Systems. Application Guide

APPLICATION GUIDE BEAMS

HVAC Controls Upgrades: Requirement Details ( )

CVGF. Water Cooled Centrifugal Chillers

TRIDENT GS SERIES Central Chiller

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X

EVAPORATIVE COOLING AND HUMIDIFICATION. High-Pressure System Wetted Media System

Magnetic Bearing Technology: Achievements in Higher Efficiency

96% AFUE Efficiency CONDENSING RESIDENTIAL GAS BOILERS CONTROL WITH ADVANCED USER FEATURES MODELS FROM 80,000 TO 285,000 BTU/HR

CONTENTS. B. System Design and Performance Requirements

MicroTech Series 200 Centrifugal Chiller

Chiller Plant Efficiency

NET ENERGY WATER LOOPS A clear path to net zero energy buildings

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

UW Purchase Specification Section Steam Condensate or Hot Water Meter Page 1 of 9

Technical Criteria for District Energy Ready Buildings Master Requirement ENG 108 Building Department: ,

This guide will discuss the scope of work, and technical requirements of connecting to the Energy Transfer Station(s) (herein referred to as ETS).

Sequence of operation

SEQUENCE OF OPERATIONS

Ohio Energy. Workshop HH. Strategies & Technologies to Improve the Boiler Room Efficiency. Wednesday, February 21, p.m. to 3:15 p.m.

Cold Weather Operation Of Cooling Towers

Trailblazer air cooled scroll chillers

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Smardt vs. McQuay Comparison of Standard Options and Other Benefits < 400 tons

SmartVFD HVAC and BYPASS

96% COMMERCIAL INDUSTRIAL HEATER. Condensing Gas Water Heating System. Thermal Efficiency

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

Medium Mass Boilers. Maxim Power VT

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

Cutting Edge Compressor Technology

Transcription:

June 2013 Copyright Climatec

GUIDLINES FOR CENTRAL PLANT OPTIMIZATION The following document provides guidelines which if followed will maximize the energy savings potential for a central plant available through optimization. The attached drawing used is a typical primary variable flow chilled water plant which includes the minimum points required. There are many variations of this design based on size, budgets, and plant requirements but the guidelines will still be applicable. 1 OSA Temperature / Humidity A good quality temperature / humidity must be supplied with at least 3% humidity accuracy. It should be located in a location representative of the building and cooling tower air intakes. It must be located out of direct sunlight at all times throughout the day and out of area that can be heated up due to indirect sunlight, heat, or humidity generating equipment such as a cooling tower or other mechanical equipment. 2 Cooling Tower Selection Select cooling towers with the largest surface area as space and budget will allow. Ensure that low flow nozzles / doers are supplied to allow the best flow turndown possible. These are almost always a special order on cooling tower equipment so early communication with the contractor ordering the cooling tower is necessary. 3 Cooling Tower Isolation / Bypass Valves In a simple 2 chiller 2 tower plant, automatic CT Isolation valves are not required if the cooling towers are selected where the minimum flow for each tower is half the minimum flow of one chiller. If isolation valves are used on open circuit cooling towers make sure the isolation valves are on both the inlet and outlet of the cooling towers. A bypass valve is not typically needed in moderate climates due to the variable speed condenser water pumps. If one is used because of extremely cold conditions it must be installed below the cooling tower sump level.

4 Cooling Tower Outlet Temp Individual CT outlet temperature sensors are not required for optimization but are recommended for additional monitoring points and they will allow for fault detection. 5 VFD s Variable Speed Drives for all equipment must be have open protocol communication; preferably BACnet. Most drives provide the necessary points required for optimization through the interface however some may not have atrue kw reading which is required for optimization. Power reading in percent units or deriving power from Amps is not acceptable. 6 Condenser Water Temperatures Condenser supply and return water sensors are required in the common piping between multiple chillers and cooling towers. 7 Chiller Flow If the chillers do not have reliable condenser and evaporator flow readings available from the chiller interface, differential pressure (DP) sensors must be added to determine CHW flow as an analog measurement in gallons per minute (GPM). The following guidelines need to be followed: a. The chiller DP to flow curves need to be obtained from the chiller manufacturers along with the minimum and maximum flow requirements of the condenser and evaporator. Note: A formula as opposed to a graph is preferred for accuracy. The DP sensors should beof the wet-to-wet diaphragm type as opposed to the type with separatehigh and low side transducers with ±0.25% accuracy; recommend Setra Model 230. c. d. The DP sensor range should be selected as low as possible so that the maximum design flow (DP) is approximately in the 75% of the range and the minimum flow (DP) is not below 10% of the range of the instrument. The DP sensors should be installed with a 3-valve manifold for serviceability. Ensure the pressure taps in the pipe are on the chiller side of the isolation valves.

8 measurements Chillers should be selected with the lowest NPLV (non-standard part load value) based on the load characteristics the plant will be serving. The chiller must have a network interface which gives all the critical chiller information including water temperatures and refrigerant pressures and temperatures. Onmany chillers, the kw power is an option or not available. If the chiller does not come with a true kw reading then an external power meter will need to be supplied for each chiller. Note: Percent power or calculation from amps is not acceptable. 9 Bypass Valve A modulating bypass valve is required for primary variable pumping systems located on the building side of the chilled water pumps. The bypass valve must be modulating and properly sized for the minimum flow of one chiller. A decoupler is required for primary secondary systems located between the primary and secondary chilled water pump loops. 10 Flow/Energy Meter An Onicon magnetic insertion meter with matchedtemperatures sensors and a BTU (Energy) Totalizer with BACnet interface or similar is highly recommended. An accurate energy reading is critical for the optimization process. The following guidelines must be adhered to: a. The flow and temperature sensors must be mounted on the building side of the bypass valve or, in the case of a primary-secondary system after the secondary chilled water pumps. It is critical that there are enough straight runs of pipe before and afterthe flow meter to allow for accurate flow readings. This is the number one cause for inaccurate energy readings in the plant. c. It is imperative that that the location be coordinated with the mechanical engineer and contractor. Do not trust the drawings alone. Being involved with the shop drawing layout process and onsite location of the flow meter and temperature sensors is a must.

11 Plant DP A differential pressure (DP) sensor in the plant is required at a minimum. Optionally, DP sensors can be located near the end of runs or at remote buildings for informational inputs but they are not required if all the chilled water valve positions at the loads are known. If there are areas where valve positions are not known, DP sensors need be located in a representative location near those loads and a minimum DP established for each DP location. 12 Building loads All building loads must be known and understood for proper optimization of the chiller and chilled water pumps. The status of the loads must be available through an Open Protocol network (BACnet preferred). Loadinformation that is highly recommended in order of preference are: a. CHW valve positions. The power (kw) for any variable speed loads that are influenced by CHW temperature. c.` The dehumidification control signal of any humidity sensitive areas.