LO-LINE RC & LO-LINE RC HEATER/COOLER FAN CONVECTOR MODELS: 6-4, 9-6, 14-10,

Similar documents
HI-LINE RC & HI-LINE RC Heater/Cooler Models: 7-4, 10-6, 15-10, Installation, Operating, Maintenance and After Sales Manual.

SLIM-LINE RC. Installation, Operating, Maintenance and After Sales Manual. Please leave this manual with the end user. Part Number: Issue 3

SLIM-LINE RC FAN CONVECTOR.

HI-LINE SUPER RC FAN CONVECTOR MODELS: 25-18,

WHISPA III 5000 WM & 9000 WM. heatingthroughinnovation. Installation, Operating, Maintenance and After Sales Manual. Part Number: Issue 1

HI-LINE LV FAN CONVECTOR MODEL: 7-4.

WHISPA III 5000, 7000 & Installation, Operating, Maintenance and After Sales Manual. Tested to UL & CSA Standards. Part Number: Issue 1

ivector HEATER/COOLER 2 AND 4-PIPE MODELS.

KICKSPACE 500, 600, V & 800

MYSON. ivector. A NEW GENERATION OF INTELLIGENT FAN CONVECTORS. heatingthroughinnovation. NOW INCLUDING. the ivector 4-pipe

OWNER S MANUAL. Evaporative Cooler. (English) (EXH, EZH) ILL239-D ILL1140-A FAN SPEED REMOTE CONTROL ECONOMY

VD 3401 Chauffage central Installation, Operating, Maintenance and After Sales Manual

3 In 1 AIR CONDITIONER with REMOTE CONTROL MODEL NO: CA9000 PART No: OPERATION & MAINTENANCE INSTRUCTIONS

REMOTE CONTROL FAN SPEED ECONOMY BATTERY LOW. owner s manual

OWNER S MANUAL. Evaporative Cooler. (English) (EA, EXH, EZH) ILL239-D ILL1140-A FAN SPEED REMOTE CONTROL ECONOMY

Chiltrix 5.1 Thin DC - Inverter Water Fan Coil Unit Floor, Wall or Ceiling Universal Mount Manual

Imperial Electric Fires

OWNER S MANUAL. High-Wall Fan Coil Unit CONTENTS

Pedestal Range. Installation and user manual. Kiosk. Trafalgar. Tube. Issue 001 September 2017 ENGLISH UK IRL SmithsEP.co.uk

OWNER S MANUAL HIGH WALL INVERTER. (English) (MSHVD1S SERIES)

OWNER S MANUAL HIGH WALL INVERTER. (English) (BSHVD1S SERIES)

Installation, Start-Up, and Operating Instructions

Sealed Electric Wall & Floor Mounted Towel Warmers. heatingthroughinnovation. Installation, Operating, Maintenance and After Sales Manual.

ACCESSORIES INCLUDED

π H-6369, H-6370 DEHUMIDIFIER GENERAL INFORMATION uline.com WATER IN THE BUCKET RECOMMENDED HUMIDITY LEVELS WARM AIR EXHAUST IS NORMAL

Product Instructions. Hydronic Mixing Block Version Wiring Terminal Block Pressure/Temperature Sensor Delivery Fitting (3) Display Screen

INSTALLATION INSTRUCTIONS

Crown Boiler Company

Model No. GB-PAC-08E4. 8,000 BTU Portable Air Conditioner Operating Instructions

CLIM9000CE PORTABLE AIR CONDITIONER USER MANUAL

USER INSTRUCTION MANUAL. Autofill Water Boiler

Certified to CSA STD. C22.2 No.117

Service Manual & Installation Manual

PLEASE LEAVE THIS INSTRUCTION WITH THE USER ECOMFORT PLUS 25 HE. User instructions

User Manual / Care Instructions

HMT-D30-A HMT-D45E-A HMT-D70E-A. Model Numbers: HMT-D30-A HMT-D45E-A HMT-D70E-A. Portable Dehumidifier Operating Instructions V.

Prism Thermostatic Recessed Shower with Integral 2 Outlet Diverter

PLEASE LEAVE THIS INSTRUCTION WITH THE USER. Ecomfort 30 HE. User instructions

SmartRad Planning Manual

Portable Dehumidifier

INSTALLATION AND OPERATION INSTRUCTIONS FOR WALL-MOUNT AND BUILT-IN UNITS

Installation and User Guide Please leave this guide with the end user (for future reference)

INSTALLATION MANUAL. RD SERIES Digital Electric Water Heater Wall-hung Unvented

AC-12200E Portable Air Conditioner

Contents. Commissioning 6 Operation 6 Routine Preventative Maintenance 6 Fault Finding 7 Spares Parts 8 Technical Support 9

What to expect from your water softener

OWN ER'SGUIDE READ AND SAVE THESE INSTRUCTIONS

Dimplex Air Conditioner DAC 12000R

SHOWER HANDBOOK IMPORTANT

HMT-D30-A HMT-D45E-A HMT-D70E-A. Model Numbers: HMT-D30-A HMT-D45E-A HMT-D70E-A. Portable Dehumidifier Operating Instructions V.

No fan function in heat mode. Fan ON continuously. Indicates incorrect room temperature

Air Conditioner PORTABLE. Instruction Manual. Your Guarantee. Portable Air Conditioner / Heater. For models WA-1010E, WA-1010H, WA-1010M

The Professional s Choice

Model 1174 Electric Heater User instructions for LED effect 2kw Inset Heater

INSTALLATION INSTRUCTIONS

OVA-EASY ADVANCE. HATCHER User Instructions

Powermax HE 85, 115 & 150 Litre Condensing Boilers with Integrated Hot Water Storage

CentaurStat 7 User Operating Instructions Central Heating Programmable Room ThermoStat

Portable Air Conditioner 6,000 BTU 8,000 BTU 10,000 BTU

INSTALLATION AND OPERATION INSTRUCTIONS FOR BI-DEEP UNITS

OWNER S GUIDE SEQUENTIAL THERMOSTATIC SHOWER VALVE. 150mm Inlet Pipe Centres. Shower Control. Handles and. may differ depending.

Installation, operating and servicing instructions

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

5) Do not start or stop the unit by inserting or pulling out the power plug.

Models WM1-06E-01 WM1-08E-01 WM1-10E-01 WM1-12E-01 WM1-12E2-01. Electronic Window Air Conditioner Operating Instructions V ,400 BTU 8,500 BTU

ignored. Denotes content that may result in bodily injury and physical damage when ignored.

Bose 141 series II bookshelf speakers

Artisan Thermostatic Bath Filler

LOW SURFACE TEMPERATURE RADIATORS

Wall Hung Boiler Room Thermostat OR30 OT Thermostat

Model Numbers: HCT-D30-A (TDA30) HCT-D45E-A (TDA45E) HCT-D70E-A (TDA70E) Portable Dehumidifier Operating Instructions V

INSTRUCTION MANUAL (English version) Water still

Enzo Concealed Shower Mixing Valve

INSTALLATION & USER INSTRUCTIONS

ELECTRIC POSITION for electric heat, then confirm with Fan Test below.

Portable Air Conditioner

Electric Riva Flame-Effect Cassette Fire

TECHNICAL MANUAL CX(E) SPLIT SYSTEMS. Tel: Fax:

INSTALLATION & USER INSTRUCTIONS

Imperial Electric Fires

Portable Dehumidifier with Internal Pump

WatchDog NXT60. Installation and Operations Manual. Seaira Global, LLC NC Highway 50 Surf City, NC (910)

SS-THVD2-1/2 THERMOSTATIC VALVE WITH 2 WAY DIVERTER SS-THVD3-1/2 THERMOSTATIC VALVE WITH 3 WAY DIVERTER

CentaurPlus ZW and HRT4-ZW

INSTALLATION & TECHNICAL MANUAL

DUAL VOLTAGE REFRIGERATORS 220/240 VOLTS AC AND 12/24 VOLTS DC INSTALLATION AND OWNER S MANUAL

SINGLE DISHDRAWER TM DISHWASHER

Distinction. D4000 & D4000/EURO Water Still. Assembly and Operating Instructions. 1 Issue 2

General Care and Safety Guide

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

IMPORTANT SAFETY INSTRUCTIONS

BURWELL BIDET TOILET SEAT INSTALLATION

INSTALLATION INSTRUCTIONS

OVA-EASY ADVANCE. HATCHER User Instructions

5231 Series. Low Lead High Flow Thermostatic Mixing Valves. Installation, commissioning and service instructions ASSE 1017 NA10341

Indicates incorrect room temperature. No second stage or AUX heating. Emergency heat does not turn on

TBR 40 1 GD Blood Refrigerator Instruction Manual. for BLOOD STORAGE REFRIGERATORS MODEL TBR 40 1 GD. (40 x 500ml Blood Bag Capacity)

Vortex 15/21 Utility and Outdoor Module Vortex Combi 21 and Outdoor Vortex Combi 21

OPERATION MANUAL CMW30. Unit Serial Number Range: 0311XXXXCW3 to Present (From March 2011 to Present)

- Data Brochure Steam Control 279

Transcription:

LO-LINE RC & LO-LINE RC HEATER/COOLER FAN CONVECTOR MODELS: 6-4, 9-6, 14-10, 19-15. INSTALLATION, OPERATING, MAINTENANCE & AFTER SALES MANUAL Product Serial Number: Please leave this manual with the end user. Part Number: 1371053 heatingthroughinnovation. Tested to UL & CSA Standards

Contents 1.0 General Information 03 2.0 Heating System Design 03 3.0 Unit Selection/Sizing 03 4.0 Location 03 5.0 Preparation 04 6.0 Fixing 04 7.0 Water Connections 05 8.0 Electrical Connection 06 9.0 Commissioning Procedure 07 10.0 Technical Data 08 11.0 Operating Instructions 09 12.0 Troubleshooting 10 13.0 Maintenance 11

LO-LINE RC & LO-LINE RC Heater/Cooler 03 1.0 General Information l This MYSON LO-LINE fan convector is designed for wall mounted installation with a minimum installation height of 6 inches to the underside of the unit. l The LO-LINE should only be used on closed circulation, two pipe, pump assisted central heating systems (LO-LINE), on heating and cooling systems (LO-LINE Heater/Cooler), or as a stand alone zone. l The LO-LINE Heater and Heater/Cooler can be used on low water temperature systems. l The minimum side clearance is 4 inches. l In rooms with ceiling heights above 10ft a ceiling fan or other means of heating stratification should be considered. l Before proceeding with the installation, the heating system design must be considered and the unit correctly sized to meet the heat loss requirements of the room at normal fan speed. l This unit is supplied with an infra red remote control system and has 3 operating modes: Automatic the desired room temperature is programmed in to the unit and the fan speed is automatically adjusted until the desired room temperature is achieved. Fan only allows user selection of any of the 3 available fan speeds irrespective of room temperature or water temperature in the coil. Fan only with water temperature control allows the user to select any of the available fan speeds, which will operate only if the water temperature in the coil is above 90 F. This enables control of the unit via an externally mounted room thermostat if desired. 1.0 2.0 3.0 4.0 2.0 Heating System Design This fan convector can be fitted on a series loop with mono-flo or venturi Tees, on a two pipe system, or on a stand alone zone. For optimum fan convector heating performance the system must be capable of providing sufficient hot water through the heat exchanger. This means that: 1. Care must be taken in sizing both the pump and the piping. 2. The minimum pipe size from boiler to fan convector must be 1/ 2 inch copper tube. 3. Where the unit is fitted on to a system with other emitters a separate circuit for the fan convector should be considered to provide adequate water flow. 4. The system water must be above 90 F for heating mode. 5. Optimum performance of this unit will require effective balancing of the whole system. 6. This unit must not be used to replace a radiator in an existing system unless an adequate flow of water through the unit can be guaranteed. 7. The loop must be pumped. LO-LINE fan convectors are not suitable for gravity circulation systems. 3.0 Unit Selection/Sizing Heat output performance is given in the Technical Data section of this manual. Outputs are shown for the three fan speeds, however, it is important to size the unit to match the calculated heat loss requirements of the room with the unit operating on the normal fan speed. The higher fan speeds are used in automatic mode when the room temperature is significantly lower than the preset temperature. When establishing the temperature difference, i.e. entering water to room temperature, allowance should be made for temperature drop in the system. It is the water temperature at the unit that dictates the output. 4.0 Location l This LO-LINE unit may be fitted to any convenient wall at a height from floor level that suits the application, providing an unimpeded flow of warm air into the area to be heated. l The minimum distance from the underside of the unit to floor level is 6 inches. l Prior to installation the wall should be checked to make sure it is straight and flat, to avoid twisting the unit. l For cooling applications, the need for disposal of condensate may influence the position of the unit.

04 LO-LINE RC & LO-LINE RC Heater/Cooler 5.0 Preparation Before proceeding with the installation, unpack the carton contents and check against the checklist below: 1. LO-LINE or LO-LINE Heater/Cooler unit. 2. Instruction manual. 3. Fixing kit (rubber mounts and cable gland). 4. Remote control handset. 6.0 Fixing l Using the fixing dimensions (see fig. 1), mark the fixing hole positions on the wall. l Plastic or metal anchors suitable for No.8 wood screws should be used for mounting the convector to the wall. l Remove the backing from the self-adhesive washers and place on screws with adhesive side towards the point. l Tighten the screws into the wall leaving about 3 / 8 projecting. l Press adhesive washers to the wall. inch 2 7 / 16 B 2 1 / 4 2 inches min each side Dimensions (inches) Unit A B C 19-15 44 13 / 16 40 1 / 16 38 3 / 8 14-10 33 5 / 8 29 7 / 8 26 13 / 16 15 3 /16 9 3 /4 9-6 25 3 / 8 20 11 / 16 18 15 / 16 C 6-4 20 5 / 8 15 15 / 16 14 1 / 8 2 3 /16 4 1 / 4 A 6 inches Fig. 1 Remove the outer casing as follows: l Remove the 2 screws from the underside of the unit (see fig. 2). l Lift off the outer case. l Fit chassis on to mounting screws and tighten. Fig. 2 Case fixing screw positions Cover Fixing Screws

LO-LINE RC & LO-LINE RC Heater/Cooler 05 7.0 Water Connections l Connect unit to system flow and return pipes. It is recommended that two 1 / 2 inch isolating valves are fitted. This will enable isolation of the unit for maintenance activities. Note: To ensure effective venting of the heat exchanger the supply pipe should be connected to the bottom connection of the heat exchanger. Note: For LO-LINE installations pipe-work must not be routed directly underneath the unit as this will adversely affect the operation of the integral room thermostat. If this cannot be avoided, the pipe-work must be boxed to prevent heat rise. LO-LINE Heater/Cooler installations with chilled water will require provision for condensate disposal in accordance with any local regulations. A drain tray is fitted for condensate collection within the unit. This should be connected to a 15mm drain pipe. Note: External pipe-work carrying chilled water must be insulated. Use a suitable sealant as necessary to ensure that condensate does not spill or leak. Once connection to the system supply and return pipes is made, any exposed internal 1/ 2 inch pipework and isolating valves must be insulated. l Ensure system is flushed in accordance with recognised best practice and a suitable inhibitor is added to the system as necessary. l Open valves fully, check pipe connections for leaks and vent the heat exchanger - see Commissioning Procedure. 2 27 / 32 5.0 5 1 / 8 2 11 / 16 7 1 / 2 7.0 6.0 2 3 / 8 3 29 / 32 Fig. 3 3 29 / 32 2 3 / 8

06 LO-LINE RC & LO-LINE RC Heater/Cooler 8.0 Electrical Connection WARNING: This appliance must be grounded. The electrical installation must comply with state or local codes. l This unit is supplied with a factory fitted 3 core cord, 6ft in length with moulded plug. LNG O O Motor Brown Blue White Yellow O O Power Board Air Sensor Water Sensor Control Board Fig. 4 Wiring diagram

LO-LINE RC & LO-LINE RC Heater/Cooler 07 9.0 Commissioning Procedure l Fill and vent the system. l Open both valves fully and vent air from the heat exchanger by unscrewing the air bleed valve situated above the valves in the angled top of the chassis. l Check for leaks at pipe connections. l Refit the outer case and secure using the 2 fixing screws. l Check the operation of the unit by following the operating instructions. l When installation and commissioning are complete, hand over instruction manual to end-user. Heat Pump and Low Water Temperature Systems In heating mode, the control system brings the fan on when the water in the coil reaches 90 F. For low water temperature systems, e.g. heat pump systems, it is possible to switch off the boost speed option in automatic mode so that the unit runs in medium or normal fan speeds depending on demand. This means low outlet air temperatures from the unit are avoided when the room temperature is low in relation to the set temperature. This facility can be switched on or off by following the instruction below: l Isolate electrical supply. l Remove outer cover. l Change switch 1 position according to requirements (see fig. 4). l Refit outer cover. l Switch on electrical supply. Fan Pulse Fan pulse mode causes room air to be drawn over the air temperature sensor periodically to maintain room temperatures more effectively. In certain circumstances, for example when units are over-sized in relation to the heat loss of the room, it may be necessary to turn off this function. Use dipswitch 3 according to requirements. Displayed Temperature Calibration Depending on the location of the unit there may be a difference between the temperature at the unit and the temperature in the middle of the room being heated. The displayed temperature calibration function enables calibration in heating mode of the displayed temperature to the actual room temperature using the following procedure: l Run the fan convector until room conditions stabilise. l Press the On/Off key and + key for 5 seconds (the display will flash, alternating between ro and the calibration temperature. l Calibrate the displayed room temperature by using the + and - keys with the fan running. l Press the On/Off key to finish. 9.0 8.0 Fig. 5 Dipswitches Switch Switch Down Switch Up 1 Auto Fan Speed Selection 2 Speed 3 Speed 2 Heating / Cooling Heating Heating & Cooling 3 Fan Pulse Off On 4 Temperature Display F C

08 LO-LINE RC & LO-LINE RC Heater/Cooler 10.0 Technical Data Heating Performance Data Model 19-15 14-10 9-6 6-4 Fan Setting Medium Medium Medium Medium Test Pressure: 290psi Max working pressure: 145psi Water connections: 1 /2 inch sweat Electrical Supply: 110V 60Hz Cooling Performance Data (figures @ 50% RH) Model Noise Levels Fan Setting 3 3 3 3 Flowrate (GPM) Heat Output (Btu/h) Entering Water Temperature ( F), entering air temperature 65 F 110 120 130 140 150 160 170 180 190 200 7997 9691 11372 13042 14702 16354 17999 19637 21269 22895 7224 8753 10270 11777 13275 14766 16250 17728 19200 20667 6374 7722 9060 10389 11710 13024 14333 15636 16933 18227 6137 7435 8723 10002 11274 12539 13798 15052 16301 17546 5247 6356 7457 8550 9636 10717 11793 12864 13931 14994 4316 5227 6132 7030 7922 8810 9694 10574 11450 12324 4081 4942 5797 6645 7489 8328 9163 9994 10822 11647 3274 3964 4649 5329 6005 6678 7347 8013 8676 9337 2525 3058 3586 4111 4633 5151 5668 6182 6694 7204 2668 3231 3790 4344 4895 5443 5988 6531 7072 7611 1954 2366 2775 3181 3584 3985 4385 4782 5178 5572 1724 2087 2447 2804 3159 3512 3863 4213 4561 4908 Note: Performance figures for heating and cooling based on a flow rate of 3 GPM. For a flow rate of 1 GPM multiply by 0.87. 25 35 45 Tot. Sens. Tot. Sens. Tot. Sens. 5128 4366 8203 5929 11650 6425 19-15 Medium 3 4896 4024 7832 5412 11124 6077 4482 3693 7169 4816 10181 5407 4108 3519 6570 4823 9330 5315 14-10 Medium 3 3451 2937 5522 3986 7843 4317 2934 2523 4691 3469 6660 3851 2376 1943 3799 2757 5394 3564 9-6 Medium 3 2007 1696 3208 2288 4555 2439 1669 1414 2669 1916 3790 2059 1659 1328 2653 1884 3769 2435 6-4 Medium 3 1308 1121 2093 1535 2973 1691 1074 927 1718 1277 2440 1427 Cooling performance tested in accordance with BS 4856 Part 2. Flow rate 340 ltr/h. Relative humidity 50%. Model Flowrate (GPM) Sound Pressures at 2.5m (dba) Medium 19-15 27.2 31.8 38.6 14-10 23.1 28.5 40.1 9-6 21.6 29.6 38 6-4 23.7 31.7 40.7 Noise levels tested in accordance with EN 23741. Approximate Hydraulic Resistance through Fan Convectors Weight, Water Content and Motor Power Model GPM 3 1 Motor Power (W) Test Pressure: 20bar (2 MPa) Water connections: 15mm 6-4 6.7 0.6 Cooling Performance (Btu/h) Air-Mean Water Temperature Difference ( F) ft wg 9-6 14-10 6.4 9.4 0.8 1.0 Water Content (pints) Unpacked Weight (lbs) 19-15 80 1.6 34.6 14-10 62 1.2 28 9-6 35 0.7 20 6-4 35 0.6 17 19-15 13.1 1.4 Maximum working pressure: 10bar (1MPa) Electrical supply: 230V - 50Hz

LO-LINE RC & LO-LINE RC Heater/Cooler 09 11.0 Operating Instructions Description This LO-LINE unit is fitted with a control system that provides either automatic or manual control of the unit. In automatic mode the desired temperature set point is selected and the unit will adjust the fan speed according to the difference between the actual room temperature and the set point. When the room temperature reaches the set point the fan will switch off and thereafter will continue to cycle on and off to maintain the room temperature. The temperature set point range is 59-95 F. In manual mode the automatic temperature control is over ridden and any of the three fan speeds can be operated inrespective of the water temperature in the unit. This means that air circulation can be provided in summer for example, or that heating performance can be controlled manually. In manual mode, with water temperature control, any of the 3 fan speeds can be selected and the fan will operate when the water temperature in the coil is greater than 90 F. This means that heating performance can be controlled manually, and the unit could be controlled via an external room thermostat. The unit can be controlled using the infra red remote control handset supplied with the unit (see fig. 6) and also using the control panel on the unit (see fig. 7). If necessary, however, the control panel can be locked electronically to prevent tampering once the controls have been set (see over). Fig. 6 Fig. 7 The remote control hand set takes 2 AAA batteries (not supplied). Controls Display Heating Power button Switches unit on & off +/- button Adjust temperature set point from 59-95 F Scrolls into F1, F2, F3, A1, A2 or A3 manual mode. Heating will only be provided when the central heating boiler is on, the pump is running and the system water temperature is greater than 90 F. Ensure the boiler is on, and set timer, boiler controls and room thermostats as necessary. 10.0 11.0

10 LO-LINE RC & LO-LINE RC Heater/Cooler 11.0 Operating Instructions (continued...) Operation Power off Display No Display Manual Manual mode can be used for air circulation without heat or for manual control of the heating function. Switch on supply to unit (unit off) for 30 seconds Use + to scroll beyond 95 F Or use - to scroll below 59 F Selected fan speed displayed Switch on unit Supply on / unit off Set point flashes for approx 5 secs, then Ambient temperature displayed Continuous fan only Fan & water temperture Heating Mode only (water inlet >90 F) Scrolling back out of manual using the + or button will revert the unit back to last temperature set point. Use +/- to adjust set point Set point flashes for approx 5 secs, then Ambient temperature Cooling Mode l Close the heating system and isolate any other heat emitters. l Open the cooling water system. l Ensure cooling is on, and set cooling unit timer and controls as necessary. Cooling operation works in exactly the same way as heating. Follow the procedure above to set the unit controls. The ambient temperature is always displayed unless the water temperature falls below 110 F*, or if the set point is being adjusted. Water temp <110 F Shows both power & unit on *110 F in normal heating system, 90 F for heat pumps and above 68 F in cooling. 12.0 Troubleshooting Once installed this fan convector becomes part of a complete heating system that will generally include a boiler, pump, other emitters such as radiators and fan convectors, and a number of heating controls, dependent on system complexity. An apparent problem with this unit may be the result of system controls being incorrectly set and can be solved easily without calling out your installer or MYSON. Before calling your installer or MYSON, please carry out the checks listed opposite. Locking Unit Controls The control panel on the main unit can be locked electronically to prevent interference once the controls have been set. After setting the unit to the desired temperature setting and with the unit in running mode, press the On/Off button on the main unit for about 6 seconds until the two middle horizontal bars appear on the display. The horizontal bars will disappear after about 6 seconds and the unit is in key lock mode. If any of the unit controls are pressed the horizontal bars will reappear to show the key lock mode is activated, however, during this mode the handset controls remain functional. To unlock the system press the On/Off button for about 6 seconds until the horizontal bars disappear.

LO-LINE RC & LO-LINE RC Heater/Cooler 11 12.0 Troubleshooting (continued...) Problem Heating Mode - No Fan Possible Causes Unit switched off Temperature set point reached Unit not switched on at breaker panel Breaker tripped at panel Unit isolating valves shut Water temperature reaching fan convector below 110 F (Heater model only) Remedy Turn on Increase temperature set point Switch on breaker Check all wiring and reset breaker Open valves Check boiler - Programmer ON Boiler ON and set to high with central heating pump running Note: Operation of fan convector can be checked by switching to manual fan setting Heating Mode (Heater model only) poor heating performance and/or unit cycles on water sensor Low water temperature to unit Poor water flow Turn up boiler thermostat Vent air from heating system If the fan convector is still faulty after checking the above, call your installer or MYSON. Common Installation Faults For optimum performance, this unit must be correctly sized to match the heat loss requirements of the space it is required to Problem Poor heating performance (Heater model only) Heating Mode (Heater model only) poor heating performance and/or unit cycles on water sensor heat, and the heating system must be correctly designed to provide adequate flow of hot water to the unit (refer to section 2). If the recommendations in section 2 are not followed, problems may arise as detailed below. Possible Causes Unit incorrectly sized for heat loss of room Boiler thermostat set too low Lack of flow to fan convector - Pump set on low setting Isolating valves not fully open System incorrectly balanced with unit starved of hot water flow Pipe sizing to unit too small 11.0 13.0 Maintenance Before undertaking any maintenance activity isolate the electrical supply. Maintenance should be restricted to occasional removal of dust and lint around the unit. The outer surface may be wiped over with warm water and mild detergent taking care to avoid water entering the grille areas. 12.0 13.0

RETTIG USA, INC. (MYSON) 45 Krupp Drive, Williston, VT 05495 T: 800-698-9690, F: 802-654-7500, info@myson.com, www.mysoncomfort.com heatingthroughinnovation.