TXgard-Plus. Flameproof Toxic and Oxygen Gas Detector with Non-intrusive One-man Calibration. Installation, Operation and Maintenance Instructions

Similar documents
IREX Pellistor exchange IR gas detector

Gasmonitor+ Installation, Operation and Maintenance Manual

XgardIQ Duct Mounting Kit

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS WITH LOCAL DIGITAL DISPLAY

CellarSafe. Carbon Dioxide and Oxygen Safety Monitor

REMOTE TOXIC, COMBUSTIBLE, AND OXYGEN GAS SENSORS

Fixed Gas Detection Equipment

Xgard. Fixed detectors For flammable, toxic or oxygen gases

Crowcon XgardIQ. Intelligent Gas Detector and Transmitter. Installation, operating and maintenance instructions M070030/SF

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

Zareba Sensepoint Pro

Gasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.

Sieger Sensepoint. Easy to Use Factory set operation Simple to replace Minimal training required

Crowcon XgardIQ. Intelligent Gas Detector and Transmitter. Installation, operating and maintenance instructions M070030

Signalpoint. The Signalpoint range of flammable, toxic and Oxygen gas detectors offer users a low cost solution to their indoor gas monitoring needs

Crowcon Gasmaster. 1 to 4 channel gas detection control panel. Installation, Operation and Maintenance Manual

Sensepoint. Fit For Purpose Flammable, toxic and Oxygen versions available High performance, low cost Suitable for new and retro fit applications

ULTIMA XL/XT Series Gas Monitors. [ Ultimate Features Extreme Design ]

Sensepoint. Fit For Purpose Flammable, toxic and oxygen versions available High performance, low cost Suitable for new and retro fit applications

Dräger Polytron 5700 IR Detection of flammable gases and vapours

Operating Instructions

Fixed Life Single Gas Monitor

Flammable gases Detectors. Model DAX 03F DAX 03F- C DAX 03F- H. Note for installation, use and maintenance. Version 1.2

HART TOCSIN 903 SINGLE CHANNEL GAS DETECTOR USER INSTRUCTIONS. Oliver IGD Limited NEW WITH OPTIONAL. 4a Pepper Road Stockport SK7 5BW England

Fixed Range. Fixed Gas Detection Equipment. Field mounted gas detection. solutions for the protection of. plant and personnel

Sensepoint. The Sensepoint range of flammable, toxic and oxygen gas detectors offer users a low cost solution to their gas monitoring needs.

standards: standards:

Dräger Polytron 5200 CAT Detection of flammable gases and vapours

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

Zareba Metro Gas Detector

BX444-Mc Gas Detector

Touchpoint 4. The Touchpoint 4 controller provides protection of personnel and plant from flammable, toxic and Oxygen gas hazards

Dräger Polytron 5200 CAT Detection of flammable gases and vapours

Technical Manual. Sensepoint XCD Gas Detector PRE-LAUNCH

Tetra 3. Personal Multigas Monitor. User Manual

Model D12-IR. Digital Gas Transmitter...

Danfoss gas detection unit Type GD Heavy Duty

Quick Start Guide. XNX Universal Transmitter

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

VQ500 Series Combustible Gas Detector Elements

GAS PLUS ALARM SYSTEM

Dräger Polytron 8200 Stationary gas detector (CatEx)

INSTRUCTIONS. PointWatch Infrared Hydrocarbon Gas Detector PIR9400

INSTRUCTION MANUAL. E2xB05 & E2xB10 Xenon Beacons For use in Hazardous Locations

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

Technical Manual. Zareba Sensepoint Gas Detectors

TOXIC GAS AND OXYGEN DETECTOR DTX 420 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS DTX420_MAN01_EN_V1R2

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

RK-05 Combustible Gas Transmitter Operator s Manual

Touchpoint 1. The Touchpoint 1 controller provides 24 hour protection from flammable, toxic or Oxygen gas hazards.

VQ600 Series Combustible Gas Sensing Head

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon

APPLICATION DATA SHEET

Dräger Polytron 8310 Stationary gas detector (DSIR)

THE BELGIAN PIONEER IN GAS DETECTION

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors

ULTIMA X5000. MSAX5000.com

RK-05 Carbon Monoxide Transmitter Operator s Manual

MAN0604_Issue 09_ Apex

Gasman. User Manual. Personal Single Gas Monitor. M07630 Sep 2015 Issue 11

Carbon Monoxide Transmitter

IECEx Certificate. INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certification Scheme for Explosive Atmospheres

Design Manual Installation Operation Maintenance

Two-Channel Gas Controller

ESD3000 ESD200 Combustible / Toxic Gas Detector

Combustible Gas/Carbon Monoxide Sample-Draw Detector Operator s Manual

S5000 Gas Monitor. GMS5000.com

Unipoint Controller. The Unipoint, a simple DIN rail mounted controller

Dräger Polytron 5720 IR Toxic Gas Detection

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

Tetra 3. User Manual. Personal Multigas Monitor. M07654 January 2007 Issue 3

Dräger PointGard 2100 Detection of toxic gases and vapours

DESIGN MANUAL MODEL GIR900 INFRARED COMBUSTIBLE GAS SENSOR

Dräger Polytron 5720 IR Detection of carbon dioxide

TC100N. Fixed Gas Detector Operation Manual

Metro Gas Detector. The Metro addressable gas detector enables remote monitoring of flammable and toxic gas hazards

EXAMPLES OF HOW TO ORDER

GS100M Gas Detection Controller

EXAMPLES OF HOW TO ORDER

Technical Manual. Series 3000 MkII Gas Detector

TOCSIN 750 SERIES SAFE AREA GAS DETECTORS. 2-Wire Addressable Systems. 2 Core Cable Unscreened. 6 Standard 20mm Gland Entry Knockouts

RTK Instruments Limited St James Business Park, Knaresborough, North Yorkshire, England. HG5 8PJ

Model C Combustible Gas Transmitter. 6 Iron Bridge Drive Unit 1 & 2 Gatehead Business Park

VQ600 Datasheet. Pellistor Gas Sensor for Hazardous Areas (Fixed Systems) FEATURES TECHNICAL SPECIFICATION OPERATION

Technical Manual. Touchpoint 4 4 Channel Gas Detector Controller

GS100M Gas Detector. Technical Specification

PolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen

Instructions

RK Carbon Monoxide Transmitter Operator s Manual

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual

Series 3000 XPIS. 2-wire loop powered toxic and Oxygen gas detector for use in potentially explosive atmospheres

4) Intrinsic Safety Certification

Oxygen (O2) Single-Point Gas Detection System

Unipoint Controller. The Unipoint, a simple DIN rail mounted controller

Dräger PIR 3000 Detection of flammable gases and vapours

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

RK Hydrogen Sulfide Transmitter Operator s Manual

GL-CO-RFG Channel Gas Leak Alarm System

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

Transcription:

TXgard-Plus Flameproof Toxic and Oxygen Gas Detector with Non-intrusive One-man Calibration Installation, Operation and Maintenance Instructions M07194 Issue 5 March 2015

TXgard-Plus Introduction 1 Introduction 1.1 Product overview TXgard-Plus is a flameproof toxic and oxygen gas detector suitable for use in zone 1 or 2 hazardous areas. It is designed to detect toxic gases and oxygen using a range of electrochemical sensors. A local display and magnetically operated switches allow non-intrusive one-man calibration without a hot work permit. Powered by 24 V dc (nominally) TXgard- Plus provides a 4-20 ma signal (sink or source) proportional to the gas concentration and can also be fitted with optional alarm and fault relays. For a list of gases that can be detected, please contact Crowcon. 1.2 Product description TXgard-Plus comprises four parts; 96HD sensor housing, junction box, amplifier and terminal board. Diagram 1 details Txgard-Plus. The overall assembly is certified Ex d IIC T6 in Europe and Class 1, Zones 1&2 AEx d IIC T6 in the USA. The 96HD sensor housing is a modular stainless steel assembly that dismantles to allow plug in sensors to be replaced easily (see Diagram 4). The assembly screws into an M20 entry on the junction box. The junction box is manufactured from marine grade alloy and is supplied with 2 x M20 (1/2 NPT for USA) cable entries for customer use. Alternative cable entries are available from Crowcon. The amplifier plugs into the terminal board, and is held in place by two captive screws. The amplifier provides power to the sensor, local display and controls, and a 4-20 ma signal proportional to the gas concentration for connection to a control panel. To remove, turn screws anti-clockwise and use them to pull amplifier out of the enclosure. All electrical connections are made via the terminal board mounted in the base of the junction box (see Diagram 2). Optional alarm relays (AL1 & AL2) and one fault relay (FAULT) are mounted on the terminal board which may be used to drive local warning devices or connect TXgard- Plus to a control panel. 1

Introduction TXgard-Plus 1.3 Status Indication TXgard-Plus includes a local display and status LED, visible through the junction box window, see Diagram 1. The display shows the gas concentration and current mode of operation ie. NORMAL, ZERO or CAL. The LED shows the current alarm state of the detector. This is summarised in Table 1. Operational state Normal operation Normal operation (ALARM 1) Normal operation (ALARM 2) LED indication Steady green Steady red Flashing red Relay states* AL1 - Off AL2 - Off FAULT - On AL1 - On AL2 - Off FAULT - On AL1 - On AL2 - On FAULT - On Over-range Flashing red AL1 - On AL2 - On FAULT - On Zero/ calibration mode Detector fault Flashing green Steady amber Configuration dependent (see section 2) AL1 - Off AL2 - Off FAULT - Off Comment* Gas level < AL1 Current output = 4-20 ma Gas level > AL1 < AL2 Current output = 4-20 ma Gas level > AL2 Current output = 4-20 ma Gas level > full scale Display backlight flashes Current output = 24 ma Latched until reset via 'MENU' Current output = 2 ma 4 ma option) Current output = 0 ma *See section 2 for AL1 and AL2 standard settings = Relay version only Table 1: LED status indicator summary. 2

5 TXgard-Plus Introduction 1 115(4 / 2 ") UNITS 1 M20 ( /" 2 NTP) CABLE ENTRY TAMPER PROOF GRUB SCREW (1.5mm ALLEN KEY) LOCAL DISPLAY STEADY ON INDICATES ZERO/CAL MODE ACTIVATED "UP" 200 (8") 135(5 ") /16 TXgard-Plus LEL ZERO CAL INHIBIT STATUS Menu SN: M20 (½" NTP) CABLE ENTRY FLASHING INDICATES 4-20mA/RELAYS INHIBITED ALARM1&2 ADJUSTMENT POTS STATUS LED "DOWN" EXTERNAL EARTH POINT 4OFF FIXING HOLES Ø6mm (¼") 83 (3 ¼" ) 1 HEIGHT =115 (4/") 2 All dimmensions in mm unless otherwise stated Diagram 1: TXgard Plus general arrangement 3

1 2 3 4 5 SENSOR 6 Introduction TXgard-Plus REAR VIEW OF AMPLIFIER GAS RANGE ALARM SK SR OUTPUT OUTPUT OPTIONS 4mA - TEST INHIBIT + POINT N Y CONTACT REVERSING LINKS GND ISOLATE LINK USED FOR OXYGEN TXGARD FOR TOXIC LINK SET TO OTHER CONTROL EQUIPMENT ISOLATE 0V GND OTHER 40-200mV NC NO NO NC NC NO OXYGEN RL1 RL3 RL2 17 4 2 7 8 9 10 11 12 FAULT ALARM1 ALARM 0V 10-30V 4-20mA ALARM1 ALARM 2 RELAY CONTACT ALARM 2 ALARM1 FAULT ALARM SET POTS TO 96HD SENSOR INTERNAL TERMINAL LAYOUT = ALARM RELAY VERSION ONLY Diagram 2: Terminal and amplifier layouts 4

TXgard-Plus Detector configuration 2. Detector configuration 2.1 Standard configuration As standard, TXgard-Plus is factory set as follows: Current source with 0 ma = Fault 2 ma = Inhibit ie. Zero/Cal mode 4-20 ma = Normal operation 24 ma = Over-range clamp AL1 relay Alarm level 1, see Table 3 Normally de-energised, energising on alarm Contact normally open (NO), closing on alarm AL2 relay Alarm level 2, see Table 3 Normally de-energised, energising on alarm Contact normally open (NO), closing on alarm FAULT relay Normally energised, de-energised on fault Contact normally closed (NC), opening on fault Alarm/fault relays automatically reset when alarm or fault has cleared. INHIBIT Normally selected, ie. when CAL/ZERO selected current output is forced to 2mA and relays are held in normal/no alarm state. Table 2: Standard configuration for TXgard-Plus. 5

Detector configuration TXgard-Plus Table 3 details standard alarm points for the available gases and ranges. Gas Range* AL1* AL2* Hydrogen sulphide 0-25 ppm 5 ppm 10 ppm Carbon monoxide 0-250 ppm 30 ppm 200 ppm Oxygen 0-25% vv 19% vv 17% vv *Alternative ranges and alarm set points must be specified when ordering Table 3: Standard ranges and alarm set points. Location of links are shown in Diagram 2. 2.2 4-20mA options To change current source output to sink, set switch to SK position. To change Inhibit from 2 ma to 4 ma, fit link to 4 position. 2.3 Relay options To change AL1 or AL2 relay from NO to NC, fit link in the NC position. To change FAULT relay from NC to NO, fit link in the NO position. 2.4 Inhibit options To not inhibit 4-20 ma signal and relays, fit link to N and link to 4. 6

TXgard-Plus Installation 3. Installation WARNING TXgard-Plus is designed for use in Zone 1 and 2 hazardous areas and is certified Ex d IIC T6 (AEx d IIC T6 in USA). Installation must be in accordance with the recognised standards of the appropriate authority in the country concerned. For more information contact Crowcon. Prior to carrying out any work ensure local regulations and site procedures are followed. 3.1 Location There are no rules which dictate the siting and location of detectors, however, considerable guidance is available from BS EN 50073:1999 British Standard Code of Practice for the Selection, Installation, Use and Maintenance of Apparatus for the Detection and Measurement of Combustible Gases or Oxygen. In the USA refer to the National Electrical Code (NEC 1999). Similar international codes of practice may be used where applicable. In addition certain regulatory bodies publish specifications giving minimum gas detection requirements for specific applications. The detector should be mounted where the gas is most likely to be present. The following points should be noted when locating gas detectors: To detect gases which are lighter than air, detectors should be mounted at high level and Crowcon recommend the use of a collector cone (Part No. C01051). To detect heavier than air gases (eg hydrogen sulphide), detectors should be mounted at low level. When locating detectors consider the possible damage caused by natural events e.g. rain or flooding. For detectors mounted outdoors Crowcon recommend the use of a Weatherproof Cap (Part No. C01442). Consider ease of access for functional testing and servicing. Consider how the escaping gas may behave due to natural or forced air currents. Mount detectors in ventilation ducts if appropriate. 7

Installation TXgard-Plus Consider the process conditions (ie whether gas within a process is at high temperature or high pressure) Detector placement should be determined following advice of experts having specialist knowledge of gas dispersion, the plant processing equipment as well as safety and engineering issues. The agreement reached on the locations of sensors should be recorded. 3.2 Mounting The mounting detail of TXgard-Plus is given in Diagram 1. TXgard- Plus should be installed at the designated location with the detector pointing down. This ensures that dust or water will not collect on the sinter and stop gas entering the detector. 3.3 Cabling requirement Cabling to TXgard-Plus must be in accordance with the recognised standards of the appropriate authority in the country concerned and meet the electrical requirements of the detector. Crowcon recommend the use of steel wire armoured (SWA) cable and suitable explosion proof glands must be used. Alternative cabling techniques, such as steel conduit, may be acceptable provided appropriate standards are met. TXgard-Plus requires a dc supply of 12-30 V at up to 100 ma. Ensure the minimum dc supply of 12 V is observed at the detector, taking into account the voltage drop due to cable resistance. For example, a nominal dc supply at the control panel of 24 V has a guaranteed minimum supply of 20V. The maximum voltage drop allowed is therefore 8V. TXgard-Plus can demand up to 100 ma and so the maximum loop resistance allowed is 80 Ohms. A 1.0 mm2 cable will typically allow cable runs up to 2000m. Table 4 shows maximum cable distances given typical cable parameters. 8

TXgard-Plus Installation CSA Resistance (Ohms per km) Max. distance mm 2 (awg) Cable Loop m (ft) 1.0 (17) 18.1 36.2 1000 (3280) 1.5 (15) 12.1 24.2 1500 (4920) Table 4: Maximum cable distances for typical cables Acceptable cross sectional area of cable is 0.5 to 1.5 mm 2. Table 2 provides guidance only, actual cable parameters for each application should be used to calculate maximum cable distances. 3.4 Electrical connections All connections are made via the terminal board mounted in the base of the junction box (see Diagram 2). The 3 wires from the 96HD are colour coded and should be terminated in the corresponding colour coded terminal (terminals 4, 5 & 6). Terminals 1 (0 Vdc), 2 (12-30 Vdc) and 3 (4-20mA signal) are connected to the control equipment. TXgard Plus is factory set as a 4-20 ma sink device unless specified otherwise when ordering (see Section 2 to change configuration). Diagram 3 summarises the electrical connections. Note: The junction box and cable armour must be earthed at the detector or control panel to limit the effect of radio frequency interference and to maintain electrical safety. Note: The junction box for the TXgard Plus is manufactured from marine-grade alloy, and has a powder-coated finish. Care should be taken during installation to protect the painted finish, as use in saline environments could result in paint flaking off from damaged junction boxes. This in no way compromises the performance of the detector, as the marine-grade alloy junction box is approved for use in offshore environments. 9

Installation TXgard-Plus All electrical connections to the optional relays are made via the 6-way terminal block on the terminal board in the base of the junction box (see Diagram 2). The relay contacts are rated 1 A @ 30 Vdc. CONTROL EQUIPMENT SAFE AREA CONTROL EQUIPMENT SAFE AREA +V 0V +V 0V 12-30 V 4-20mA 0 V 12-30 V 4-20mA 0 V 2 3 1 2 3 1 TXGARD-PLUS SOURCE TXGARD-PLUS SINK Diagram 3: Electrical connections to TXgard-Plus 10

TXgard-Plus Operation 4. Operation WARNING Prior to carrying out any work ensure local regulations and site procedures are followed. Never attempt to open the detector or junction box when flammable gas is present. Ensure that the associated control panel is inhibited so as to prevent false alarms. 4.1 Commissioning Procedure a Open the junction box of the detector by loosening the tamper proof grub screw and removing the lid by rotating it anti-clockwise. b Remove the amplifier and check that all electrical connections have been made and are correct as per Diagram 3. c Replace the amplifier and close the junction box ensuring that all screws have been re-fitted correctly. d Apply power to the detector. The status LED will show a steady green indicating normal operation. e Leave the detector to stabilise for 1-2 hours. Zeroing the detector (ZERO Mode): f Place the end of CRO-Mag over the MENU. Green Status LED will flash. Decimal point above ZERO will illuminate. Display backlight will illuminate. Decimal point above INHIBIT may flash if the option has been internally selected. g With no flammable gas present at the detector, place the end of the CRO-Mag key over the UP or DOWN arrow pads to make the display read zero. Note: Oxygen detectors may be zeroed in fresh air. Calibrating the detector (CAL Mode): h Place the end of the CRO-Mag over the MENU pad. The decimal point above the word CAL will illuminate. Other indications remain unchanged. i Apply calibration gas to the detector at a flow rate of 0.5 litres/min. (contact Crowcon for the supply of calibration gas.) 11

Operation TXgard-Plus j Allow the gas reading to stabilise. k Place the end of the CRO-Mag over the UP or DOWN arrow pads to make the display read the correct concentration. l If the control equipment display requires adjustment consult the operating manual for the equipment. Returning to normal operation (NORMAL Mode): n Place the end of CRO-Mag over the MENU pad. All decimal points will disappear and the backlight will turn off. The green status LED will be on steadily (assuming no gas is present at the detector). o The detector is now operational. Note: Always return the detector to NORMAL mode to avoid leaving the detector in a permanently inhibited state. 4.2 Routine maintenance The operational life of the sensors depends on the application, frequency and amount of gas being seen. Under normal conditions (6 monthly calibration with periodic exposure to CAL gas) the life expectancy of the detectors are: Hydrogen sulphide 18 to 36 months Carbon monoxide 18 to 36 months Oxygen 24 months Site practices will dictate the frequency with which detectors are tested. Crowcon recommend detectors are gas tested at least every 6 months and re-calibrated as necessary following the steps given in 4.1. 12

TXgard-Plus Operation 4.3 Sensor replacement/servicing of detectors WARNING This work should be carried out by Crowcon or an approved service centre unless suitable training has been received. TXgard-Plus uses the 96HD sensor housing which allows the user to replace the sensors, gaskets and sinter if necessary. An exploded view of the 96HD sensor housing is given in Diagram 4. The following procedure may be followed when servicing a TXgard-Plus detector. a Switch off and isolate power to the detector requiring attention. b Open the detector Junction box by loosening the tamper proof grub screw and removing the lid by rotating it anti-clockwise. c Remove the amplifier. d Disconnect the 3 sensor wires from the terminal board (terminals 4, 5 & 6). e Unscrew the complete 96HD sensor housing from the junction box. Note: If a spare 96HD sensor housing complete with new sensor is available ignore steps f to k and return the old 96HD to Crowcon or an approved service centre for repair. f Open the 96HD sensor housing by removing the four Allen head screws from the Top Cap with a 3mm Allen key. g Remove the sensor from the Top Cap PCB. h Fit the replacement sensor checking the part number is correct. This part number is labelled on the main body of the detector. i Inspect the gaskets and replace if necessary. j The sinter assembly will only need to be replaced if it has become blocked by dust or oil. Such blockage causes the response time of the detector to be slow and may affect sensitivity. To remove the sinter a removal tool (Part # M01614) is required. Loctite No 243 must be used on the sinter assembly threads to maintain certification. 13

Operation TXgard-Plus 4 OFF M4X12MM ALLEN HEAD SCREWS TOP CAP & SENSOR PCB NEOPRENE GASKET 1 (Part No MO4452) PELLISTOR GASKET 2 (Part No MO4128) SLEEVE MAIN BODY SINTER SINTER ASSEMBLY (Part No SO1781) Diagram 4: 96HD assembly k Re-assemble the 96HD housing taking time to ensure that the 3 mm Allen head screws are securely fixed into position. I Fit the 96HD sensor housing to the junction box ensuring that the colour coded wires are terminated correctly. m Replace amplifier ensuring the captive screws are fastened securely. n Switch on power. 14

TXgard-Plus Operation o Close the junction box remembering to fasten the tamper proof grub screw into position. p Follow the Commissioning Procedure given in 4.1. 4.4 Changing Alarm Levels (Relay Version Only) WARNING This work should be carried out by Crowcon or an approved service centre unless suitable training has been received. Before attempting to change alarm levels ensure the detector is in fresh air and no flammable gas is present. Alarm levels are factory set as detailed in Table 3. To change either alarm level: a Switch off and isolate power to the detector requiring attention. b Open the junction box of the detector by loosening the tamper proof grub screw and removing the lid by rotating it anti-clockwise. c Remove the amplifier from the terminal board. d Ensure that the INHIBIT link is set to N. e Re-fit the amplifier to the terminal board ensuring that all screws have been secured correctly. f Apply power to the detector and allow the detector to stabilise. g Place the end of CRO-Mag over the MENU pad. The decimal point above the word ZERO will illuminate, the status LED will flash green and the display backlight will illuminate. h With clean air present at the detector, place the end of the CRO- Mag key over the UP or DOWN arrow pads to make the display read the desired alarm level. i Using a long instrument screwdriver, turn the relevant ALARM SET pot mounted on the terminal board (see Diagrams 1 & 2) to adjust the alarm level. Tripping of the ALARM 1 level relay is confirmed by the status LED turning a steady red. Tripping of the ALARM 2 level relay is confirmed by the Status LED flashing red. 15

Operation TXgard-Plus j Once the alarm level has been set, place end of CRO-Mag over the UP or DOWN arrow pads and reset the display to read zero. k Place the end of the CRO-Mag over the MENU pad to return the detector to normal operation, ie. No decimal points displayed, backlight off and the Status LED indicating steady green. l Check that the detector operates correctly by applying test gas as necessary. m Switch off and isolate power to the detector. n Reset jumpers which may have been changed in step d above. o Replace the amplifier and close the junction box, ensuring that all screws have been re-fitted correctly. p Apply power to the detector and allow to stabilise before checking correct operation. q Re-calibrate if necessary as per section 4.1. Notes: Area Classifications:- Zone 0: An area classified, as Zone 0 will have ignitable concentrations of flammable gases, vapours or liquids present continuously or for long periods of time under normal operating conditions. Zone 1: An area classified, as Zone 1 is likely to have ignitable concentrations of flammable gases, vapours or liquids present under normal operating conditions. Zone 2: An area classified, as Zone 2 is not likely to have ignitable concentrations of flammable gases, vapours or liquids present under normal operating conditions. 16

TXgard-Plus Spare parts and accessories 5. Spare parts and accessories Please refer to the Sensor Replacement Label mounted on the outside of the 96HD housing for the correct replacement part number. Description Part number Complete 96HD sensor housing with sensor Sensor only Hydrogen sulphide (96HD/HS) S01750 E01229 Carbon monoxide (96HD/CO) S01751 E01344 Oxygen (96HD/OX) S01753 E01488/A M20 to 1/2 inch NPT adaptor M20 to 3/4 inch NPT adaptor Gasket 1 Gasket 2 Sinter removal tool Collector Cone Weatherproof Cap Replacement CRO-Mag Sinter assembly Amplifier (Toxic version) Amplifier (Oxygen version) Terminal board Relay board Loctite No. 243 Calibration gas M02125 M02281 M04452 M04128 M01614 C01051 C01442 C01697 S01781 S01866 S01867 S01846 S01847 Contact Crowcon Contact Crowcon 17

Specifications TXgard-Plus 6. Specifications Dimensions 200 x 115 x 115 mm (8 x 41/2 x 41/2 ) Weight 2.2 kg (4.8 lbs) Material 96HD sensor housing: 316 Stainless steel Junction box: Marine grade alloy Temperature range -10 C to +55 C (14 F to 131 F) Humidity range 15-90% RH, non condensing Ingress protection IP65 Explosion protection Flameproof Approval codes II 2 G Ex d IIC T6 (+55 c) UL Class 1, Zones 1 & 2, AEx d IIC T6 Safety Cert No. Sira03ATEX1124 Standards EN60079-0, EN60079-1: 2007, UL2279 Zones Certified for use in Zone 1 or Zone 2 areas. (see area classifications section) Gas groups IIA, IIB, IIC Operating voltage 12-30 Vdc Operating current Relay version: 100 ma (maximum) Non-relay version: 50 ma (maximum) Detector output 4-20 ma source or sink selectable 0 ma = Fault 2 ma = Inhibit (4 ma option) 4-20 ma = Normal gas range 24 ma = Over range Relays outputs 2 x Alarm relays SPNO (SPNC option) 1 x Fault relay SPNC (SPNO option) Contact rating 1 A @ 30 Vdc 18

UK Office Crowcon Detection Instruments Ltd 172 Brook Drive, Milton Park, Abingdon Oxfordshire OX14 4SD Tel: +44 (0) 1235 557700 Fax: +44 (0) 1235 557749 Email: sales@crowcon.com Website: www.crowcon.com USA Office Crowcon Detection Instruments Ltd 1455 Jamike Ave, Suite 100 Erlanger KY 41018 Tel: +1 859 957 1039 or 1 800 527 6926 Fax: +1 859 957 1044 Email: salesusa@crowcon.com Website: www.crowcon.com Netherlands Office Crowcon Detection Instruments Ltd Vlambloem 129 3068JG, Rotterdam Netherlands Tel: + 31 10 421 1232 Fax: + 31 10 421 0542 Email: eu@crowcon.com Website: www.crowcon.com Singapore Office Crowcon Detection Instruments Ltd Block 194, Pandan Loop #06-20 Pantech Industrial Complex Singapore 128383 Tel: + 65 6745 2936 Fax: +65 6745 0467 Email: sales@crowcon.com.sg Website: www.crowcon.com China Office Crowcon Detection Instruments Ltd (Beijing) Unit 316, Area 1, Tower B, Chuangxin Building 12 Hongda North Road, Beijing Economic Technological Development Area Beijing, China 100176 Tel: +86 10 6787 0335 Fax: +86 10 6787 4879 Email: saleschina@crowcon.cn Website: www.crowcon.com