Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture

Similar documents
Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance

York 25-Ton VAV Rooftop Unit

TC-9102 Applications

Multi-Story Building Floor Above/Floor Below Pressurization and Exhaust Logic

Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43

DX-9100/9120 Local Sonalert Logic

Reciprocating Chiller

Verasys System Operation Overview Technical Bulletin

Metasys System Extended Architecture Smoke Control System

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

DX-9100 Applications from Engineering Services

Fire Operator Workstation (Fire OWS) User s Guide

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

UNIFIED FACILITIES GUIDE SPECIFICATIONS

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

1.0 Digital Controller

Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

Laptop / PC Programming Manual

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

1.0 Digital Controller

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

Version 1.03 January-2002 USER S MANUAL

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

Digital Precise Air Control - DPAC

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

Feature Summary. I. System

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Halton SAFE / 7.14 user guide and installation instructions

Table of Contents. W2W Open

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

P2000 and Metasys System Integration

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

Solution Guide. UUKL Smoke Control System. 1/6. UL 864, 9th Edition, UUKL Smoke Control Listing. Overview

TEC Networked Multi-Stage Economizer Thermostat

TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072

Autoclave Operations Manual

DACC - NMDA BUILDINGS

P2000 and Metasys System Integration

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies

I/O ZONE 560/583 USERS GUIDE

AirTrak. Digital Control System. User Manual. Touchscreen Systems

ASHRAE Guideline 36 Advanced HVAC Control Sequences

i-vu CCN 4.0 Owner s Guide

Table of Contents. i-vu CCN Standard 4.2

AdaptAire. Digital Control System. User Manual

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

American University Design Standards

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

Introduction. What is the W2W Open controller?

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

Smoke Control Manual

HVAC Controls Upgrades: Requirement Details ( )

Document # R01

U ser's Guide PC6010

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone:

HVAC Controls Upgrades: Requirement Details ( )

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies

Metasys Integrator TITUS Application

RPM1600 Series Room Pressure Monitors

MicroTech Self-Contained Air Conditioning System

Simplex Panel Interface Guide

CSP-204 CSP-208 CSP-104 CSP-108

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS

Ion Gateway Cellular Gateway and Wireless Sensors

Security System. User Guide for the LED Command Center

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

Siemens Thermostats. RDY2000BN Thermostat

Rotem One Touch. User Manual PRELIMINARY DOCUMENT. Ag/MIS/UmGB /18 Rev 1.0 P/N:

Natural Ventilation Controller with 24vDC drive NVC-1204

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

TEC Networked Single-Stage Thermostat

Your Home. Jacco & Assoc.

BACnet Points List for Single Compressor Water to Water PROSSWWE-01

Instruction, Operation, and Maintenance: Controls Software Versions: R37+

MicroTech Rooftop/RMC

SEQUENCE OF OPERATIONS

PF1000 CONTROLLER. for the. Heateflex Corporation 405 E. Santa Clara St. Arcadia, CA TEL: (626) ; FAX: (626)

SECTION SEQUENCE OF OPERATIONS FOR BUILDING CONTROLS

Platinum Touch/Rotem One Touch


Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

The Information Contained in this Document is Proprietary and should only be used for Service or Training of Authorized Blodgett Servicers who will

VT8000 Series Replacement Procedure to Replace VT8000 Series Room Controller and Pair with ZigBee Pro Sensors

Using the Room View Window

Transcription:

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Code No. LIT-1201737 Release 1.2 Issued January 10, 2005 Document Introduction................................................. 3 Related Documentation................................................. 3 Application Overview.................................................. 4 Automatic Smoke Control.................................................. 4 Pullstation Logic........................................................... 4 Automatic Smoke Control Priorities......................................... 5 Manual Smoke Control.................................................... 5 Auto Command Retry Logic................................................ 5 FSCS................................................................... 6 Assigning the Fire Object Category to Smoke Control Objects................... 7 Security Administration System............................................. 8 Roles and User Accounts Overview........................................... 8 UUKL Smoke Control Security Administration Details.............................. 8 Security Administration Detailed Procedures.................................... 10 Creating a New Role.......................................................... 10 Creating a New User Account................................................... 10 Configuring User Profiles....................................................... 10 Configuring Role Properties.................................................... 11 Assigning System Access Permissions............................................ 11 Design Considerations................................................ 11 DX Design Considerations................................................ 11 Smoke Control NAE Design Considerations.................................. 14 DX-9100 Multi-Story Building Smoke Control Application................... 15 Application File Location................................................. 15 GX Control Logic........................................................ 15 Point List............................................................... 16 GX Configuration Parameters.............................................. 17 Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture 1

Smoke Control NAE Application........................................ 22 Application File Location................................................. 22 Metasys System Extended Architecture Objects.............................. 22 Multi-Story Building Smoke Control........................................ 23 Floor Above/Floor Below Logic.............................................. 23 All Floors Logic............................................................... 27 Lock Alarms Logic............................................................ 30 Alarm Lockout Interlock Logic................................................... 31 FSCS Control............................................................ 35 FSCS Zone 2 IFC Zone Interlock Definition......................................... 35 FSCS Zone 2 3rd Party Zone Interlock Definition.................................... 35 FSCS Zone 2 Smoke Interlock Definition........................................... 36 FSCS Zone Switch Logic....................................................... 36 FSCS Floor 2 Supply Fan 1 Logic................................................42 Floor 2 VMA 1 Logic........................................................... 46 FSCS Floor 2 Damper 1 Logic...................................................52 FSCS Floor 2 Damper 2 Logic...................................................57 FSCS Floor 2 Zone Smoke LED Logic............................................ 62 FSCS Floor 2 Damper 3 Logic...................................................65 FSCS Floor 2 Exhaust Fan 1 Logic............................................... 70 FSCS Stairwell Fan 1 Logic..................................................... 75 FSCS Elevator Fan Logic....................................................... 81 FSCS Firefighter Control Logic.................................................. 86 Using Multiple Smoke Control NAEs or NIEs................................. 88 Requirements for Larger Sites............................................... 88 Object Limits................................................................ 88 Site Director Smoke Control NAE................................................88 FSCS Smoke Control NAE.....................................................88 Smoke Control System Connection Overview................................... 88 FSCS Alarms................................................................ 90 Monitoring the Site Director Smoke Control NAE................................ 90 Monitoring a Smoke Control NIE............................................. 93 2

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Document Introduction Smoke control applications issue commands to controlled devices that pressurize or exhaust an area of a building. This document describes smoke control for a multi-story building with floor above/floor below pressurization in the Metasys system extended architecture. The smoke control strategy is achieved with the DX-9100 (DX) application and the smoke control Network Automation Engine (NAE) application described in this document, with manual override of the smoke control logic provided by the Fire Fighter s Smoke Control Station (FSCS). Note: These application notes only present an example of one smoke control strategy. Since every building is unique, the details of applying the strategy vary. These application notes can help you develop an appropriate application for your project. Related Documentation Table 1 lists related smoke control documentation. Table 1: Related Documentation For Information On Refer To LIT No./Part No. General smoke control information Logic programming for the DX-9100 controller Single story enclosed shopping mall smoke control Warehouse smoke control Weekly testing of dedicated stairwell pressurization fans Weekly testing of dedicated smoke control dampers Metasys System Extended Architecture Smoke Control System Technical Bulletin GX-9100 Software Configuration Tool Technical Bulletin Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Warehouse Smoke Control with FSCS Override - Metasys System Extended Architecture Weekly Testing of Dedicated Stairwell Pressurization Fans - Metasys System Extended Architecture Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture LIT-1201684 LIT-6364060 LIT-1201736 LIT-1201738 LIT-1201739 LIT-1201743 Specific wiring requirements Metasys System Extended Architecture LIT-1201753 Smoke Control Wiring Technical Bulletin UL 864 UUKL requirements MSEA UL 864 UUKL Compliance Checklist LIT-1201754 3

Application Overview This application provides smoke control for a multi-story building. The application logic provides automatic smoke control, floor above/floor below pressurization and exhaust, stairwell and elevator pressurization, and fire fighter manual override. The DX controllers provide field connections, and the DX application provides basic HVAC and automatic smoke control for the multi-story building. The smoke control NAE provides a connection to the FSCS, and the smoke control NAE application provides automatic smoke control and fire fighter manual override for the smoke control system. Automatic Smoke Control Automatic Smoke Control provides the logic for UUKL first incident rule by locking out subsequent alarms from automatic smoke control. Floor Above/ Floor Below logic depressurizes the floor that goes into smoke alarm. The floor above the alarm, floor below the alarm, stairwell and elevator shaft are pressurized. Pressurize and Depressurize commands in automatic smoke control are commanded at a Priority 3. Priority 3 commands are released when the smoke alarm is reset. If a floor, stairwell, or elevator shaft is under smoke control, the FSCS controls the Light-Emitting Diodes (LEDs) next to each FSCS switch to indicate the current status of the fans, dampers, and zone. Status LEDs for a fan show the fan status as On, Off, or in Trouble. Status LEDs for a damper show the damper status as Open, Closed or in Trouble. Status LEDs for a zone (store or mall area) show the zone status as Pressurize mode, Depressurize mode, or Purge mode. The Auto LED for each fan, damper, and zone switch remains on while the point is in automatic smoke control. The logic to check the status of fans and dampers for trouble is initiated when a floor, stairwell, or elevator shaft goes into smoke control. If a fan does not reach its set point within 60 seconds, its Trouble LED on the FSCS is turned on. If a damper does not reach its set point within 75 seconds, its Trouble LED on the FSCS is turned on. After a commanded point goes into Trouble, the Automatic Command Retry logic repeats the command that failed every 60 seconds until the command is successful. Pullstation Logic Pullstations are not allowed to initiate automatic smoke control for individual floors. However, they are allowed to initiate smoke control pressurization for stairwells and elevators. 4

Automatic Smoke Control Priorities All automatic smoke control commands are commanded at a Priority 3. Fire fighter manual overrides, issued from the FSCS panel, to pressurize or depressurize zones, are commanded at a Priority 2. Fire fighter manual overrides, done from the FSCS panel, to control individual fans and dampers, are done at a Priority 1. Manual Smoke Control Manual Smoke Control logic is initiated when a fire fighter turns the FSCS Panel Enable key from the Auto position to the Fire Fighter Control position and initiates a manual override of a fan, damper, or zone point from the Auto setting on the FSCS panel. This turns off the Panel Enable switch Auto LED, and turns on the Panel Enable switch Fire Fighter Control LED. There are two levels of manual smoke control. A fire fighter can put a floor in manual smoke control by turning the zone knob to Pressurize, Depressurize, or Purge. The zone smoke control commands are commanded at Priority 2. Priority 2 commands are released when the fire fighter turns the zone knob back to Auto or turns the Panel Enable key back to Auto. A fire fighter can put a point in manual smoke control by flipping a fan toggle switch to On or Off, or a damper or Variable Air Volume (VAV) toggle switch to Open or Close. Individual points are commanded at Priority 1. Priority 1 commands are released when the fire fighter flips the toggle switch to Auto or turns the Panel Enable key back to Auto. Any point that is under manual smoke control activates the trouble checking logic. If a fan does not reach its set point within 60 seconds, its Trouble LED turns on. If a damper does not reach its set point within 75 seconds, its Trouble LED turns on. After a commanded point goes into Trouble, the Automatic Command Retry logic repeats the command that failed every 60 seconds until the command is successful. Auto Command Retry Logic The Auto Command Retry logic is used for fans, dampers, and VMAs. It does a comparison check between the commanded state and the actual device state, to verify that the command was successful. In the event a command to a fan, damper, or VMA fails, possibly because the MCO for the commanded device is on a remote smoke control NAE panel. The additional time required to communicate with the remote smoke control NAE might exceed the command response limit. Therefore, the command is resent every 60 seconds until the command is successful. The Auto Command Retry logic is used when either a device MCO does not match command, a fan, damper, or VMA status does not match its commanded value, or a fan, damper, or VMA trouble input is active. 5

FSCS The FSCS panel example (Figure 1) shows the manually controlled devices for Floor 6 only, the elevator supply fan, and stairwell supply fan. The devices for Floor 6 are three dampers, a supply fan, an exhaust fan, and a VAV. The LEDs next to each dial or toggle switch (Table 2) designate the status of each device or zone. The Smoke LED indicates a smoke alarm for the zone (floor).the FSCS in this application has six floors and additional controls not shown here. Figure 1: FSCS Panel Floor 6 Example The LEDs on the FSCS panel (Figure 1) can be set to the following values. Table 2: FSCS LED Blink Condition FSCS LED Value LED Blink Condition 0 LED is off 1 LED is on continuously 2 LED slow blink 3 LED fast blink and Sonalert turns on The FSCS panel is responsible for all Sonalert logic. A Trouble LED is lit when a fan or damper fails to achieve its commanded state, an automatic smoke detector triggers an alarm, or an AI or DI fuse on the DX fails. The LED value is set to 3 or 4, as described in Table 2, and the Sonalert sounds. Pressing the Silence button on the FSCS panel silences the Sonalert and changes the Trouble LED to a slow blink. The Trouble LED remains on slow blink until it is commanded off. The panel starts a timer and resounds the Sonalert within 24 hours if the Trouble LED is not turned off. The Sonalert sounds if the FSCS Panel Enable key is turned from the Firefighter Control position to the Auto position and all zone knobs and point toggle switches are not set to Auto. The FSCS still goes into Auto mode, but the Sonalert reminds the firefighter to set the manual smoke control switches to the Auto position. 6

The General Trouble LED turns on to a fast blink if the panel loses N2 communications. Assigning the Fire Object Category to Smoke Control Objects You must assign every object used specifically for smoke control as a Fire object. This limits the control of smoke control devices and points to authorized Fire operators.! WARNING: Risk of serious injury or death if a smoke control object is not assigned as a Fire object! In the event of a fire or smoke control event, devices or points used for smoke control that are not assigned as Fire objects allow those devices and points to be controlled by non-fire authorized operators. It is imperative that every smoke control device or point be assigned as a Fire object. Use the pull down menu to assign the Fire object category (Figure 2). Figure 2: Assigning the Fire Object to Smoke Control Objects 7

Security Administration System The Security Administration system authenticates and authorizes users of Metasys system extended architecture applications. The Security Administrator is a browser-based interface that manages all accounts. Use the Security Administrator System to authenticate and authorize users on the Metasys system extended architecture. The Security Administrator creates User Accounts and Roles, and assigns access permissions to each user of the Metasys system extended architecture. Roles and User Accounts Overview Security is based on User Accounts and Roles. Roles are groups of users with a specific function within the Metasys system. To access the system, an individual provides a user account and the correct password. Use letters, numbers, or symbols to create user account passwords. Use the Login button from the logon prompt to send the user s credentials. A unique Session generates when the user s credentials match the logon requirements. UUKL Smoke Control Security Administration Details UUKL smoke control requires that only operators designated as fire operators be able to control the smoke control system. This required the creation of four new roles: 1. Administrator - This is the highest level of control and allows site control of all HVAC and Fire features. 8

2. Fire Administrator - This role is a fire manager level setting. It allows for full system control, including system modification or configuration. Figure 3: Fire Administrator Access Permissions 3. Fire User - This role is for most fire field technicians and allows system control and alarm acknowledgement, but not system modification or configuration. Figure 4: Fire User Access Permissions 9

4. Fire Limited - This is the lowest of the permissions and only allows the operator to view fire/smoke control devices and alarms. Security Administration Detailed Procedures Creating a New Role To create a new role: 1. From the Security Administration menu bar, select Insert > New Role. The New Role dialog box appears. 2. Fill in the information. 3. Click OK. The New Role appears in the tree. Creating a New User Account To create a new user account: 1. From the Security Administration menu bar, select Insert > New User. The User Properties tab appears. 2. Fill in the information. 3. Click OK. The New User appears in the tree. Configuring User Profiles To configure a user profile: 1. Select the user whom you wish to configure. 2. From the menu bar, select Edit > Properties. The User Properties tab appears. 3. Modify the desired user information. 4. Click OK. Figure 5: Fire Limited Access Permissions 10

Configuring Role Properties To configure role properties: 1. Select the user whom you wish to configure. 2. From the menu bar, select Edit > Properties. The User Properties tab appears. 3. Select the Roles tab, then select an Available Role. 4. Click Add. The selected role appears in the Assigned Role list box. 5. Click OK. Assigning System Access Permissions To assign system access permissions: 1. Select the user whom you wish to assign system access permissions. 2. From the main menu, select Edit > System Access Permissions. The System Access Permission dialog box appears. 3. Select an available privilege. 4. Click Add, then click OK to assign the user s System Access Permissions. Design Considerations This DX9100 and Smoke Control NAE application, as it exists in the Metasys System Extended Architecture Smoke Control Library, complies with the UL 864 UUKL Smoke Listing. However, you are responsible for ensuring that the application complies with state and local regulations, and is approved by the Authority Having Jurisdiction (AHJ). You are also responsible for configuring all of the smoke control components, as well as the programming of those components, in order to comply with the UL 864 UUKL Smoke Listing as documented herein. DX Design Considerations A DX will need to provide the following BACnet Binary Value object (BV) points: Zone Pressurize Command Set to true to turn on supply fans Zone Depressurize Command Set to true to turn on exhaust fans BV Auto point Normally set to true. Point is false when a fire fighter turns a fan On or Off, or sets a damper to Open or Close. BV command point for each fan BV feedback point for each fan BV command point for each damper BV open feedback point for each damper BV close feedback point for each damper 11

BV point for an Analog Input (AI) Fuse BV point for a Binary Input (BI) Fuse Use the following priorities for commands to DX points: Priority 3 commands from automatic smoke control Priority 2 commands from manual smoke control for zone pressurize, depressurize, and purge. Priority 1 commands from manual smoke control for individual points. For information on the definition and the initial configuration of the Programmable Logic Controllers (PLCs), use the GX-9100 Software Configuration Tool (GX Tool) to examine this program. This application can be expanded for a building with more than six stories. For further details, please contact Field Support Services in Milwaukee. You must define tag names for all points. You must define the hardware location for each object You must name each object with a descriptive name that is unique in the system. An alarm occurs if the command does not equal the condition for any pressurization or exhaust output. Each Binary Output (BO) for pressurization and exhaust outputs must be configured to have its own feedback (proof sensor) input. The FSCS indicates when command does not equal condition. For UL compliance: If DX Digital Inputs (DIs) are used for smoke control, then DI8 must be jumpered and mapped to the smoke control NAE as a normal state of On. If DI8 is off, a critical alarm must be issued at the FSCS to indicate a binary input fuse failure that must be fixed immediately, because the DI is no longer accurate. If DX Analog Outputs (AOs) are used for smoke control, then Analog Output 14 (AO14, voltage) must be wired to Analog Input 8 (AI8, voltage) and the AI must be mapped to the smoke control NAE with a low alarm limit of 20%. If the AI goes below 20%, it indicates the AO has failed because of a blown fuse, which drops the AO to 0V and the AI to 0% (low alarm). The DX is downloaded so that the AO is normally at 5V because its source point is an Analog Constant (ACO) with a default of 50. 12

Response time for individual smoke control components to achieve their desired state of operational mode, exclusive of control system response, should not exceed the following time periods: 60 seconds for fan operation at the desired state plus 90 seconds to annunciate; 75 seconds for completion of damper travel plus 90 seconds to annunciate. In the case of fan start after damper close, these times are additive. If the damper must be closed before the fan starts, the total response time could be up to 135 seconds for operation, 75 seconds for damper to close plus 60 seconds for fan to start. Time to annunciate would be added to this time. (Control system response is the time from automatic detection of a smoke condition to the issuing of an appropriate command to the equipment.) For specific wiring requirements, refer to the Metasys Smoke Control Wiring Technical Bulletin (LIT-1201753). 13

Smoke Control NAE Design Considerations The smoke control NAE reports critical alarms based on the alarm condition, and the alarm can only be cleared by resetting from the Intelligent Fire Controller (IFC) panel or the Firefighter s Smoke Control Station (FSCS). A Programming In Progress BV point is required. You must set this point to true any time you are making changes to the Smoke Control system. This turns on the Programming In Progress LED on the FSCS to let a fire fighter know that changes are currently being made, and the system may not be fully functional. The point must be turned off when changes are complete. A master reset interlock is required. The interlock is true after you press reset on the Intelligent Fire Controller (IFC) panel. Each floor requires a Latched Alarm BV object. The lock alarm logic sets this point to true for the first alarm detected. Each floor requires an Alarm Lockout Interlock. The interlock is true if any latched alarms for other floors is true or the master reset interlock is true. Do not include a floors latched alarm in its own Alarm Lockout Interlock. Response time for individual smoke control components to achieve their desired state of operational mode, exclusive of control system response, should not exceed the following time periods: 60 seconds for fan operation at the desired state plus 90 seconds to annunciate; 75 seconds for completion of damper travel plus 90 seconds to annunciate. In the case of fan start after damper close, these times are additive. If the damper must be closed before the fan starts, the total response time could be up to 135 seconds for operation, 75 seconds for damper to close plus 60 seconds for fan to start. Time to annunciate would be added to this time. (Control system response is the time from automatic detection of a smoke condition to the issuing of an appropriate command to the equipment.) For specific wiring requirements, refer to the Metasys Smoke Control Wiring Technical Bulletin (LIT-1201753). 14

DX-9100 Multi-Story Building Smoke Control Application Application File Location This Metasys system extended architecture smoke control application is located on the Metasys Branch Purchase Package (BPP) CD in the Metasys System Extended Architecture Standard Smoke Control Applications directory. GX Control Logic The GX Tool was used to create the logic for this DX smoke control application. This DX smoke control application resides on each DX-9100 controller used for smoke control. Find more information and guidelines for using the GX Tool in the GX-9100 Software Configuration Tool Technical Bulletin (LIT-6364060). The main GX screen shows the multi-story floor above/floor below smoke control application as user names (Figure 6) or tag names (Figure 7) depending on the view selected. Figure 6: GX-9100 Graphical Layout (User Names) Figure 7: GX-9100 Graphical Layout (Tag Names) 15

Point List Table 3 and Table 4 show the hardware and software point requirements for the GX configuration. Table 3: Hardware I/O Requirements Input Requirements Hardware Location Name of Module Engineer Units Req? Description AI1 DA-T F Yes Discharge Air Temp AI3 STATIC-P PSI Yes Static Pressure AI8 AI-FUSE % Yes AO-AI FUSE CHECK DI8 DI-FUSE ON/OFF Yes DI FUSE CHECK Output Requirements Hardware Location Name of Module Engineer Units Req? Description AO1 CLG-VLV % Yes Cooling Valve AO2 INLT-VN OPN/CLO Yes Inlet Vane Control AO14 AO-FUSE % Yes AO FUSE MONITOR DO3 SF-SS ON/OFF Yes AHU SUPPLY FAN STA/ST DO4 EF-SS ON/OFF Yes AHU EXH FAN STA/STO DO5 ODA-DPR % Yes OUTDOOR AIR DAMPER DO6 RA-DPR % Yes RETURN AIR DAMPER DO7 EA-DPR % Yes EXHAUST AIR DAMPER TDO1 ON-DELAY SECONDS Yes TIMER ON DELAY Table 4: Software I/O Requirements (Part 1 of 2) Module Name of Module Engineer Units Req? Description ACO1 DAT-SP F Yes Discharge Air Temp Setpoint ACO2 STATP-SP PSI Yes Static Pressure Setpoint ACO8 AOFUSE-O ON/OFF Yes Manual Reset DCO1 PRESSURE OPN/CLO Yes Inlet Vane Control DOC2 EXHAUST % Yes AO FUSE MONITOR DCO4 OCC- ON/OFF Yes AHU SUPPLY FAN STA/ST NORM DCO6 OAD-AUTO ON/OFF Yes AHU EXH FAN STA/STO DCO7 OAD-OVR ON/OFF Yes Outdoor Air Damper DCO8 RAD-AUTO ACT/INA Yes Return Air Damper Auto DCO9 RAD-OVR OPEN Yes Return Air Damper Override DCO10 EAD-AUTO ACT/INA Yes Exhaust Air Damper Auto DCO11 EAD-OVR OPEN Yes Exhaust Air Damper Override DCO12 SF-AUTO ACT/INA Yes Supply Fan Auto DCO13 SF-OVR OPEN Yes Supply Fan Override DCO14 EF-AUTO ACT/INA Yes Exhaust Fan Auto DCO15 EF-OVR ON/OFF Yes Return Air Damper LRS1 SF-CTL ON/OFF Yes Supply Fan Control 16

Table 4: Software I/O Requirements (Part 2 of 2) Module Name of Engineer Req? Description Module Units LRS2 EF-CTL ON/OFF Yes Exhaust Fan Control LRS3 ODADPR-C CLOSE Yes Outdoor Air Damper Close LRS4 RADPR-C CLOSE Yes Return Air Damper Close LRS5 EADPR-C CLOSE Yes Exhaust Air Damper Close LRS6 SF-GO ON/OFF Yes Supply Fan LRS7 ALM-MODE ALM/ NORM Yes Automatic Smoke Control Return Air Damper Control GX Configuration Parameters Figure 8 through Figure 10 show the configuration parameters for the control loops, output points, and programmable logic. PID data values shown are default values and must be tuned upon commissioning. TIMER (TIMER3) - Data ----------------------- User Name : Description : TIMER #1 TYPE 4 TIMER #5 TYPE 0 Input Connection #1--> LRS5 Input Connection #5--> Reset Connection #1--> Reset Connection #5--> Time Period #1 30. Time Period #5 10. Time Units #1 0 Time Units #5 0 TIMER #2 TYPE 0 TIMER #6 TYPE 0 Input Connection #2--> Input Connection #6--> Reset Connection #2--> Reset Connection #6--> Time Period #2 10. Time Period #6 10. Time Units #2 0 Time Units #6 0 TIMER #3 TYPE 0 TIMER #7 TYPE 0 Input Connection #3--> Input Connection #7--> Reset Connection #3--> Reset Connection #7--> Time Period #3 10. Time Period #7 10. Time Units #3 0 Time Units #7 0 TIMER #4 TYPE 0 TIMER #8 TYPE 0 Input Connection #4--> Input Connection #8--> Reset Connection #4--> Reset Connection #8--> Time Period #4 10. Time Period #8 10. Time Units #4 0 Time Units #8 0 Figure 8: Timer 3 Data 17

PID (PID1) Data --------------------- User Name :CLG-CNTL Description :COOLING CONTROL Ena Shutoff: 0=N 0 Maximum WSP --> Shutoff Out Level 0.0000 Local Set Pt.(LSP) 0.0000 Ena Startup: 0=N 0 Proport. Band(PB) 30.0000 Startup Out Level 100.0000 Reset Action(TI) 0.2000 Ena Symm Mode: 0=N 0 Rate Action(TD) 0.0000 ExtForce Out Level 0.0000 Standby Bias(BSB) 0.0000 Ena PID to P: 0=N 0 Off Mode Bias(BOF) 0.0000 Remote Mode: 0=N 0 Symmetry Band(SBC) 5.0000 Ena OFF Trans: 0=N 0 Err Deadband(EDB) 0.1000 Process Variable --> AI1 Output Bias(OB) 0.0000 Remote Setpoint --> ACO1 Out High Lmt(HIL) 100.0000 Reference Variable--> Out Low Lmt(LOL) 0.0000 Proportional Band --> Dev H.H.Limit(DHH) 10.0000 OFF Mode Control --> Dev High Limit(DH) 5.0000 Standby Control --> Dev Low Limit(DL) 5.0000 Reverse Action --> Dev L.L.Limit(DLL) 10.0000 External Forcing --> Minimum WSP(MNWS) -50.0000 Output Bias --> Maximum WSP(MXWS) 999.0000 Minimum WSP --> Figure 9: PID1 Data 18

PID (PID2) Data --------------------- User Name :InltVane Description :Inlet Vane Control Ena Shutoff: 0=N 0 Maximum WSP --> Shutoff Out Level 0.0000 Local Set Pt.(LSP) 0.0000 Ena Startup: 0=N 0 Proport. Band(PB) -60.0000 Startup Out Level 100.0000 Reset Action(TI) 0.3000 Ena Symm Mode: 0=N 0 Rate Action(TD) 0.0000 ExtForce Out Level 0.0000 Standby Bias(BSB) 0.0000 Ena PID to P: 0=N 0 Off Mode Bias(BOF) 0.0000 Remote Mode: 0=N 0 Symmetry Band(SBC) 5.0000 Ena OFF Trans: 0=N 0 Err Deadband(EDB) 0.1000 Process Variable --> AI3 Output Bias(OB) 0.0000 Remote Setpoint --> ACO2 Out High Lmt(HIL) 100.0000 Reference Variable--> Out Low Lmt(LOL) 0.0000 Proportional Band --> Dev H.H.Limit(DHH) 10.0000 OFF Mode Control --> Dev High Limit(DH) 5.0000 Standby Control --> Dev Low Limit(DL) 5.0000 Reverse Action --> Dev L.L.Limit(DLL) 10.0000 External Forcing --> Minimum WSP(MNWS) -50.0000 Output Bias --> Maximum WSP(MXWS) 999.0000 Minimum WSP --> Figure 10: PID2 Data An alarm is generated: if the command to the fan is On and the feedback does not come On within 60 seconds if the command to the fan is Off and the feedback does not go Off within 60 seconds whenever there is a mismatch between the command and the feedback 19

Figure 11: Logic Module Ladder Diagram - PLC1 The PLC1 logic module ladder diagram (Figure 11) logic states: If in Pressurize mode (floor above or below is in alarm) or normal Occupied mode, and the FSCS Supply fan switch is in Auto mode (SF-AUTO) or Override mode (SF-OVR), then start the AHU supply fan. If in Unoccupied mode, then stop/shutdown the AHU supply fan. If AHU supply fan is commanded on, and the FSCS Outdoor Air Damper switch is in Auto mode (OAD-AUTO) or Override mode (OAD-OVR), then start/open the Outdoor Air Damper. If in Pressurize mode (floor above or below in alarm) or Exhaust mode (this floor in alarm), then start a pseudo point called alm-mode. 20

Figure 12: Logic Module Ladder Diagram - PLC2 The PLC2 logic module ladder diagram (Figure 12) logic states: If in normal occupied mode and not in alm-mode (not Pressurize or Exhaust), and the FSCS Return Air Damper switch is set to Auto (RAD-AUTO) or Override (RAD-OVR), then start/open Return Air Damper. If in Unoccupied mode or alm-mode, then stop/close the Return Air Damper. If in normal Occupied mode or in Exhaust mode, and the FSCS Exhaust Air Damper switch is set to Auto (EAD-AUTO) or Override (EAD-OVR), then start/open the Exhaust Air Damper. If in Unoccupied mode, then stop/close the Exhaust Air Damper. If Exhaust Air Damper is open, and the time delay has completed, and the FSCS Exhaust Fan switch is in Auto mode (EF-AUTO) or Override mode (EF-OVR), then start the Exhaust Fan. If the Exhaust Air Damper is not commanded to open, then stop the Exhaust Fan. 21

Smoke Control NAE Application Application File Location This Metasys system extended architecture smoke control application is located on the Metasys Branch Purchase Package (BPP) CD in the Metasys System Extended Architecture Standard Smoke Control Applications directory. Metasys System Extended Architecture Objects This smoke control NAE application resides on the smoke control NAE and was created with the System Configuration Tool (SCT) to define the required Control System, Interlock, and Multiple Command objects. The Logic Connector Tool (LCT) is used to create the logic within the Control System object. The LCT logic and configuration screens are organized into two sections: Multi-Story Building and FSCS. The Multi-Story Building section shows logic and configuration screens for the floor above/floor below pressurization and exhaust logic, lock alarms, latched alarms, and alarm lockout interlock settings for the stairwells, elevators, and each of the six floors. The FSCS section shows the logic and configuration screens for each of the devices the FSCS controls and/or displays status for. These devices include the Zone Switch, Damper 1, Supply Fan 1, Variable Air Volume Modulating Assembly (VMA) 1, Zone Smoke LED, Damper 2, Damper 3, and Exhaust Fan 1 for each of the six floors. In addition, the logic and configuration screens for the stairwell fans, elevator fans, and Fire Fighter Control is provided. 22

Multi-Story Building Smoke Control Floor Above/Floor Below Logic The Floor Above/Floor Below main logic (Figure 13) controls the automatic smoke control. It consists of the inputs, two system blocks, and outputs. The inputs (Figure 14) are one interlock for each floor and a master reset interlock. The Lock Alarms block (Figure 15) locks in the first incident. The All Floors Logic block determines which floors to pressurize and depressurize. Outputs (Figure 16) are binary points within a DX. Each floor has a pressurize and depressurize point. Figure 13: Floor Above/Floor Below Main Logic 23

The inputs and the Lock Alarms block is shown in Figure 14. Each floor has one smoke alarm interlock. The Lock Alarms block locks in the first incident. The Master Reset Interlock releases the locked alarms. There is an output alarm for each floor. Only the first floor in alarm is set to true. All other floors are set to false. Figure 14: IFC Alarm Input Points, FSCS Reset Point, and Lock Alarms Block 24

The Lock Alarms block and All Floors Logic block (Figure 15) show the outputs from the Lock Alarms block feeding into the All Floors Logic block, and the resulting outputs. Figure 15: Lock Alarms and All Floors Logic Blocks 25

The outputs from the All Floors Logic block (Figure 16) connect to zone pressurize and depressurize points in the DX. Stairwells and Elevator shafts also have pressurize points in a DX.. Figure 16: All Floors Outputs to DX Controllers 26

All Floors Logic The following screens show the expanded All Floors Logic block that includes a system block for each of the six floors (Figure 17), and a stairwell block and elevator block (Figure 18). Each floor logic has an input for that floors smoke alarm, one for the floor above and one for the floor below. Outputs tell the DX to pressurize or depressurize. Figure 17: All Floors - Floors 1, 2, 3, 4, 5 and 6 Logic 27

The Stairwell Logic block and Elevator Logic block (Figure 18) both have an input for each floor, and one pressurize output. Figure 18: All Floors - Stairwell and Elevator Logic The expanded Stairwell Logic block (Figure 19) pressurizes the stairwell if any floor is in smoke alarm or a pull station is active. Figure 19: All Floors - Stairwell Pressurization Logic 28

The expanded Elevator Logic block (Figure 20) pressurizes the elevator shaft if any floor is in smoke alarm or a pull station is active. Figure 20: All Floors - Elevator Pressurization Logic 29

Lock Alarms Logic The Lock Alarms All Floors system block (Figure 21) has a lock control system block for each floor. Inputs are that floor s alarms, an Alarm Lockout Interlock that is true if there is an alarm on any other floor, and a Master Reset Interlock. Outputs feed into the All Floors logic and to the Latched Alarm point. The latched alarm point is input into the Alarm Lockout Interlock for all other floors. Figure 21: Lock Alarms - All Floors 30

The expanded Floor Lock logic (Figure 22) shows the logic for a single floor. The first latch latches the alarm for that floor until it is reset. The second latch latches the first incident. Figure 22: Lock Alarms - Single Floor Lockout Logic Alarm Lockout Interlock Logic The Master Reset Interlock Definition (Figure 23) releases the locked alarms when commanded by the IFC fire panel Reset button. Figure 23: Master Reset Interlock Interlock Definition The Master Reset Interlock Action Table (Figure 24) sets the Manual Latched Alarm Reset to inactive 60 seconds after the IFC fire panel Reset button is pressed. Figure 24: Master Reset Interlock Action Table 31

The Alarm Lockout Interlocks for each floor (Figure 25-Figure 30) are displayed below. The Interlock definition includes the Master Reset and the Latch Alarms from all other floors. Do not include the current floor s Latch Alarm. The Floor 1 Alarm Lockout Interlock Definition (Figure 25) locks out all floors except for Floor 1, when Floor 1 is in smoke alarm. Figure 25: Floor 1 Alarm Lockout Interlock Definition The Floor 2 Alarm Lockout Interlock Definition (Figure 26) locks out all floors except for Floor 2, when Floor 2 is in smoke alarm. Figure 26: Alarm Lockout Interlock Definition 32

The Floor 3 Alarm Lockout Interlock Definition (Figure 27) locks out all floors except for Floor 3, when Floor 3 is in smoke alarm. Figure 27: Floor 3 Alarm Lockout Interlock Definition The Floor 4 Alarm Lockout Interlock Definition (Figure 28) locks out all floors except for Floor 4, when Floor 4 is in smoke alarm. Figure 28: Floor 4 Alarm Lockout Interlock Definition 33

The Floor 5 Alarm Lockout Interlock Definition (Figure 29) locks out all floors except for Floor 5, when Floor 5 is in smoke alarm. Figure 29: Floor 5 Alarm Lockout Interlock Definition The Floor 6 Alarm Lockout Interlock Definition (Figure 30) locks out all floors except for Floor 6, when Floor 6 is in smoke alarm. Figure 30: Floor 6 Alarm Lockout Interlock Definition The Pull Station Interlock Definition (Figure 31) sets the zone to be in active alarm. Its only control is to turn on the stairwell and elevator fans. Figure 31: Pull Station Interlock Definition 34

FSCS Control The FSCS Control section contains logic and configuration screens for each of the six floors, the stairwell, the elevator, and Fire Fighter Control. The logic for each floor is the same, with the only difference being the floor name. Floor 2 is used as an example here. FSCS Zone 2 IFC Zone Interlock Definition The FSCS Zone 2 IFC Zone Interlock Definition (Figure 32) includes the Floor 2 IFC Zones for that floor. Figure 32: Zone 2 IFC Zone Interlock Definition Table 5: IFC Point State Table BACnet Point State State 1 - Normal State 2 - Active Alarm State 3 - Fault State 4 - Disable NAE Point State State 1 - Normal State 2 - Active Alarm State 3 - Fault State 4 - Unreliable FSCS Zone 2 3rd Party Zone Interlock Definition The FSCS Zone 2 3rd Party Zone Interlock Definition (Figure 33) includes a point for an optional, third-party, normally open (N.O.) contact input connection. Figure 33: Zone 2 3rd Party Zone Interlock Definition 35

FSCS Zone 2 Smoke Interlock Definition The FSCS Zone 2 Smoke Interlock Definition (Figure 34) includes the Zone 2 IFC Zone Interlock and the Zone 2 third-party zone interlock. Figure 34: Zone 2 Smoke Interlock Definition FSCS Zone Switch Logic The FSCS Zone Switch main logic (Figure 35) inputs from the FSCS are Zone Pressurize, Zone Depressurize, Zone Purge, and Firefighter Control switch. Inputs from the DX are Zone Pressurize and Zone Depressurize. Outputs are the Pressurize, Auto, Depressurize, and Purge LEDs on the FSCS panel and the Zone MCO. Figure 35: Zone Control Switch Main Logic The expanded Zone Control system block logic (Figure 36) controls the FSCS Zone LEDs for the zone, depending on the Fire Fighter Control Key setting. The Purge LED is lit if the pressurize and depressurize points in the DX are true. The Pressurize LED is lit if the DX pressurize point is true and the depressurize point is false. The Depressurize LED is lit if the DX depressurize point is false and the pressurize point is true. 36

The Auto LED is lit only if the Zone Switch on the FSCS panel is not set to Pressurize, Depressurize, or Purge. The Pressurize, Depressurize, and Purge settings on the FSCS panel are not functional unless the Fire Fighter Control Key has been turned on. If the Fire Fighter Control Key is off, the FSCS Request is set to 0. Figure 36: Expanded Zone 2 Control Switch Logic 37

The Zone 2 MCO Action Table is shown in Figure 37. Figure 37: Zone 2 Switch MCO Action 38

The FSCS Zone Switch setting determines the state value (Table 6), which in turn determines the smoke control action. Table 6: FSCS Zone Switch State Value FSCS Zone Switch Position State Value Smoke Control Action Pressurize 1 Zone s Supply Fan On Auto 0 Auto Depressurize 2 Zone s Exhaust Fan On Purge 3 Zone s Supply Fan On Zone s Exhaust Fan On 39

The Zone 2 Pressurize MCO Action Table is shown in Figure 38. Figure 38: Zone 2 Pressurize MCO Action Table 40

The Zone 2 Depressurize MCO Action Table is shown in Figure 39. Figure 39: Zone 2 Depressurize MCO Action Table 41

FSCS Floor 2 Supply Fan 1 Logic FSCS Floor 2 Supply Fan 1 (Figure 40) inputs from the DX are the Fan Commanded State, Fan Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points. Figure 40: Supply Fan 1 Main Logic 42

The FSCS and Fan Trouble Control blocks are shown in Figure 41. Figure 41: Supply Fan 1 FSCS and Fan Trouble Control Main Logic The expanded FSCS Fan block logic is shown in Figure 42. Figure 42: Supply Fan 1 FSCS Logic 43

The expanded Fan Trouble Control block logic is shown in Figure 43. Figure 43: Supply Fan 1 Fan Trouble Control Logic The Supply Fan 1 Interlock Definition (Figure 44) sets the values that, when reached, trigger a trouble alarm. The definition includes status and reliability points for the DX AO and BI fuses, supply fan reliability and DX offline status. Figure 44: Supply Fan 2-1 Trouble Interlock Definition 44

The Supply Fan 1 MCO Action is shown in Figure 45. The Supply Fan Auto point is a binary point in the DX to indicate that the fan is under automatic smoke control. When a fire fighter turns the fan on or off, the Supply Fan Auto point is turned off. The Supply Fan Command is a point in the DX to control the fan. Figure 45: Supply Fan 1 MCO Action The FSCS Supply Fan toggle switch setting (Table 7) determines the state value, which in turn determines the smoke control action. Table 7: FSCS Supply Fan 1 Switch State Value FSCS Supply Fan 1 Toggle Switch Position State Value Smoke Control Action On 1 Supply Fan 1 On Auto 0 Auto Off 2 Supply Fan 1 Off 45

Floor 2 VMA 1 Logic The VMA main logic (Figure 46) consists of a VMA system control block. Inputs from the DX are the Fan Commanded State, Fan Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points. Figure 46: VMA Main Logic 46

The expanded VMA block consists of two system blocks, the FSCS block and the VMA Trouble Control block (Figure 47). The FSCS block controls the LEDs on the FSCS panel and commands the DX. The VMA Trouble Control block sets the Trouble LED on the FSCS. Figure 47: VMA1 FSCS and VMA 1 Trouble Control Main Logic 47

The expanded FSCS block (Figure 48) controls the Open, Close, and Auto LEDs of the FSCS. The Open LED is lit only if the FSCS is in Fire Fighter Control and the VMA Interlock is true. The Close LED is lit only if the FSCS is in Fire Fighter Control and the VMA Interlock is false. The Auto LED is lit only if the toggle switch is not in the Open or Close setting. If the Fire Fighter Control Key is Off, FSCS Request is set to 0. If the Fire Fighter Control Key is On, FSCS Request is set to the following values depending on the position of the toggle switch. Figure 48: VMA 1 Expanded FSCS Logic 48

The expanded VMA Trouble Control block (Figure 49) controls the FSCS Trouble LED. The Trouble LED is lit if the VMA is in smoke control and the VMA Interlock has not reached its desired set point within 75 seconds or one of the DX fuses has blown. A VMA is in smoke control if either the DX is in pressurize or depressurize mode, or, the Fire Fighter Control Key is on and the FSCS toggle switch is set to Open or Close. Figure 49: VMA 1 Expanded Trouble Control Logic The VMA 1 Close Interlock Definition (Figure 50) sends the VAV close command as a group, in the event there is more than one VAV. If any VAV in the group fails to close its damper, the FSCS VAV Trouble LED turns on. Figure 50: VMA1 Close Interlock Definition 49

The VMA 1 Open Interlock Definition (Figure 51) sends the VAV open command as a group, in the event there is more than one VAV. If any VAV in the group fails to open its damper, the FSCS VAV Trouble LED turns on. Figure 51: VMA 1 Open Interlock Definition The VMA 2-1 Trouble Interlock Definition (Figure 52) sets the values that, when reached, trigger a trouble alarm. The definition includes DX offline status and reliability points for the Network Integration Engine (NIE) Monitor and the VMA Open and Close commands. Figure 52: Trouble Interlock Definition 50

The VMA 1 MCO Action is shown in Figure 53. The VAV Auto point is a binary point in the DX to indicate that the VAV is under automatic smoke control. When a fire fighter sets the VMA to open or close, the VAV Auto point is turned off. The VAV Command is a point in the DX to control the VAV. Figure 53: VMA 1 MCO Action The FSCS VAV toggle switch setting (Table 8) determines the state value, which in turn determines the smoke control action. Table 8: FSCS VMA 1 Switch State Value FSCS VAV Toggle Switch Position State Value Smoke Control Action Open 1 Open VAV Damper Auto 0 Auto Close 2 Close VAV Damper 51

FSCS Floor 2 Damper 1 Logic Floor 2 Damper 1 (Figure 54) main logic inputs from the DX are the Damper Commanded State, Damper Open Present Value, Damper Close Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the Open and Close toggle switch and the Fire Fighter Control Key. Outputs are the Open, Auto, Close, and Trouble LEDs on the FSCS and an MCO that commands the DX points. Figure 54: Damper 1 Main Logic 52

The expanded Damper 1 block (Figure 55) consists of two control systems, the FSCS block, and the Damper Trouble Control block. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Trouble LED on the FSCS.. Figure 55: Damper 1 FSCS and Damper Trouble Control Main Logic 53

The expanded Damper 1 FSCS block is shown in Figure 56. The Open LED is lit only if the FSCS is in Fire Fighter Control and the damper is open. The Close LED is lit only if the FSCS is in Fire Fighter Control and the damper is closed. The Auto LED is lit only if the toggle switch is not in the Open or Close setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch: Open 1 Auto 0 Close 2 Figure 56: Damper 1 Expanded FSCS Logic 54

The expanded Damper 1 Trouble Control block is shown in Figure 57. The Trouble LED is lit if the damper is in smoke control and the damper has not reached its desired setpoint within 75 seconds or one of the DX fuses has blown. A damper is in smoke control if either the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to Open or Close.. Figure 57: Damper 1 Expanded Trouble Control Logic The Damper 2-1 Trouble Interlock Definition (Figure 58) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the NIE Monitor, the exhaust air damper close and open commands, and the DX offline status. Figure 58: Damper 2-1 Trouble Interlock Definition 55

The Damper 2-1 MCO Action Table is shown in Figure 59. The Damper Auto point is a binary point in the DX to indicate that the exhaust air damper is under automatic smoke control. When a fire fighter sets the exhaust air damper to open or close, the exhaust air damper Auto point is turned off. The Damper Command is a point in the DX to control the exhaust air damper. Figure 59: Damper 1 MCO Action The FSCS Damper 1 toggle switch setting (Table 9) determines the state value, which in turn determines the smoke control action. Table 9: FSCS Damper 1 Switch State Value FSCS Damper 1 Toggle Switch Position State Value Smoke Control Action Open 1 Open Damper 1 Auto 0 Auto Close 2 Close Damper 1 56

FSCS Floor 2 Damper 2 Logic FSCS Floor 2 Damper 2 main logic is shown in Figure 60. Inputs from the DX are the Damper Commanded State, Damper Open Present Value, Damper Close Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the Open and Close toggle switch and the Fire Fighter Control Key. Outputs are the Open, Auto, Close, and Trouble LEDs on the FSCS and an MCO that commands the DX points. Figure 60: Damper 2 Main Logic 57

The expanded Damper block (Figure 61) consists of two control blocks: the FSCS block, and the Damper Trouble Control block. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Trouble LED.. Figure 61: Damper 2 FSCS and Damper Trouble Control Main Logic 58

The FSCS block expanded logic is shown in Figure 62. The Open LED is lit only if the FSCS is in Fire Fighter Control and the damper is open. The Close LED is lit only if the FSCS is in Fire Fighter Control and the damper is closed. The Auto LED is lit only if the toggle switch is not in the Open or Close setting.. Figure 62: Damper 2 FSCS Logic 59

The expanded Damper 2 Trouble logic is shown in Figure 63. The Trouble LED is lit if the damper is in smoke control and the damper has not reached its desired setpoint within 75 seconds or one of the DX fuses has blown. A damper is in smoke control if the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to Open or Close. Figure 63: Damper 2 Trouble Control Logic The Damper 2-2 Trouble Interlock Definition (Figure 64) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the return air damper close and open commands, and the DX offline status. Figure 64: Damper 2-2 Trouble Interlock Definition 60

The Damper 2-2 MCO Action Table is shown in Figure 65. The Damper Auto point is a binary point in the DX to indicate that the return air damper is under automatic smoke control. When a fire fighter sets the return air damper to open or close, the return air damper Auto point is turned off. The Damper Command is a point in the DX to control the return air damper. Figure 65: Damper 2 MCO Action The FSCS Damper 2 toggle switch setting (Table 10) determines the state value, which in turn determines the smoke control action. Table 10: FSCS Damper 2 Switch State Value FSCS Damper 2 Toggle Switch Position State Value Smoke Control Action Open 1 Open Damper 2 Auto 0 Auto Close 2 Close Damper 2 61

FSCS Floor 2 Zone Smoke LED Logic The Floor 2 Zone Smoke LED main logic (Figure 66) controls the Zone 2 Smoke LED on the FSCS. Figure 66: Zone Smoke LED Main Logic The Zone Smoke expanded logic (Figure 67) has the following logic: If the zone is in smoke control, turn the Smoke LED on. If the panel status is Off Normal, flash the Smoke LED. Figure 67: Zone Smoke Logic 62

The Zone Smoke LED IFC Zone Trouble Interlock Definition (Figure 68) includes points for status and reliability each zone in the list, reliability of the smoke interlock and the status of the IFC Zone Detector Trouble point. Any zone that goes offline or has a status of unreliable will light that zone s trouble LED. Figure 68: Zone Smoke LED IFC Zone Trouble Interlock Definition 63

The Zone Smoke LED IFC Zone Detector Trouble Interlock Definition (Figure 69) includes points for reliability each smoke detector in the list. A smoke detector status that goes to unreliable will light that zone s smoke LED. Figure 69: Zone Smoke LED IFC Zone Detector Trouble Interlock Definition The Zone Smoke LED 3rd Party Zone Trouble Interlock Definition (Figure 70) includes a point for reliability of the 3rd party zone interlock and offline status and reliability of the 3rd party zone. Any zone that goes offline or has a status of unreliable will light that zone s trouble LED. Figure 70: Zone Smoke LED 3rd Party Zone Trouble Interlock Definition 64

FSCS Floor 2 Damper 3 Logic The Floor 2 Damper 3 main logic is shown in Figure 71. Inputs from the DX are the Damper Commanded State, Damper Open Present Value, Damper Close Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the Open and Close toggle switch and the Fire Fighter Control Key. Outputs are the Open, Auto, Close, and Trouble LEDs on the FSCS, and an MCO that commands the DX points. Figure 71: Floor 2 Damper 3 Main Logic 65

The Floor 2 Damper 3 expanded logic (Figure 72) consists of two control blocks. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Trouble LED. Figure 72: Floor 2 Damper 3 FSCS and Damper Trouble Control Main Logic 66

The Damper 3 FSCS block logic shown in Figure 73. The Open LED is lit only if the FSCS is in Fire Fighter Control and the damper is open. The Close LED is lit only if the FSCS is in Fire Fighter Control and the damper is closed. The Auto LED is lit only if the toggle switch is not in the Open or Close setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch: Open 1 Auto 0 Close 2 Figure 73: Damper 3 FSCS Block Expanded Logic 67

The expanded Damper Trouble Control block is shown in Figure 74. The damper Trouble LED is lit if the damper is in smoke control and the damper has not reached its desired setpoint within 75 seconds or one of the DX fuses has blown. A damper is in smoke control if the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to Open or Close. Figure 74: Damper 3 Damper Trouble Control Logic The Damper 2-3 Trouble Interlock Definition (Figure 75) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the NIE Monitor, the outside air damper close and open commands, and the DX offline status. Figure 75: Damper 2-3 Trouble Interlock Definition 68

The Damper 3 MCO Action Table is shown in Figure 76. The Damper Auto point is a binary point in the DX to indicate that the outside air damper is under automatic smoke control. When a fire fighter sets the outside air damper to open or close, the outside air damper Auto point is turned off. The Damper Command is a point in the DX to control the outside air damper Figure 76: Damper 3 MCO Action The FSCS Damper 3 toggle switch setting (Table 11) determines the state value, which in turn determines the smoke control action. Table 11: FSCS Damper 3 Switch State Value FSCS Damper 3 Toggle State Value Switch Position Smoke Control Action Open 1 Open Damper 3 Auto 0 Auto Close 2 Close Damper 3 69

FSCS Floor 2 Exhaust Fan 1 Logic The Floor 2 Exhaust Fan 1 main logic is shown in Figure 77. Inputs from the DX are the Fan Commanded State, Fan Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points. Figure 77: Exhaust Fan 1 Main Logic 70

The Exhaust Fan 1 expanded main logic (Figure 78) consists of two control blocks. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Trouble LED. Figure 78: Exhaust Fan 1 FSCS and Fan Trouble Control Logic 71

The FSCS block logic is shown in Figure 79. The On LED is lit only if the FSCS is in Fire Fighter Control and the fan is on. The Off LED is lit only if the FSCS is in Fire Fighter Control and the fan is off. The Auto LED is lit only if the toggle switch is not in the On or Off setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch: On 1 Auto 0 Off 2 Figure 79: Exhaust Fan 1 FSCS Block Logic 72

The Fan Trouble Control block logic is shown in Figure 80. The Trouble LED is lit if the fan is in smoke control and the fan has not reached its desired setpoint within 60 seconds or one of the DX fuses has blown. A fan is in smoke control if, the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to On or Off. Figure 80: Exhaust FAN 1 Fan Trouble Control Block Logic The Exhaust Fan 2-1 Trouble Interlock Definition (Figure 81) includes the DX DI Fuse and AO Fuse.. Figure 81: Exhaust Fan 2-1 Trouble interlock Definition 73

The Exhaust Fan 2-1 MCO Action is shown in Figure 82. The Exhaust Fan Auto point is a binary point in the DX to indicate that the Fan is under automatic smoke control. When a fire fighter turns the fan on or off, the Exhaust Fan Auto point is turned off. The Exhaust Fan Command is a point in the DX to control the fan.. Figure 82: Exhaust Fan 2-1 MCO Action The FSCS Exhaust Fan 1 toggle switch setting (Table 12) determines the state value, which in turn determines the smoke control action. Table 12: FSCS Exhaust Fan 1 Switch State Value FSCS Exhaust Fan 1 State Value Smoke Control Action Toggle Switch Position On 1 Exhaust Fan 1 On Auto 0 Auto Off 2 Exhaust Fan 1 Off 74

FSCS Stairwell Fan 1 Logic The FSCS Stairwell Fan 1 main logic (Figure 83) inputs on the DX are the Fan Commanded State, Fan Present Value, and Stairwell Pressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points.. Figure 83: FSCS Stairwell Fan 1 Main Logic 75

The FSCS Stairwell Fan 1 expanded logic (Figure 84) consists of two system blocks. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Fan Trouble LED.. Figure 84: Stairwell 1 FSCS and Fan Trouble Control Main Logic 76

The FSCS Stairwell 1 FSCS block logic is shown in Figure 85. The On LED is lit only if the FSCS is in Fire Fighter Control and the fan is on. The Off LED is lit only if the FSCS is in Fire Fighter Control and the fan is off. The Auto LED is lit only if the toggle switch is not in the On or Off setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch: On 1 Auto 0 Off 2 Figure 85: Stairwell 1 FSCS Logic 77

The Fan Trouble Control module logic is shown in Figure 86. The Trouble LED is lit if the fan is in smoke control and the fan has not reached its desired setpoint within 60 seconds or one of the DX fuses has blown. A fan is in smoke control if the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to On or Off.. Figure 86: Stairwell 1 Fan Trouble Control Logic The Stairwell Fan 1 Trouble Interlock Definition (Figure 87) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the stairwell supply fan, the DX offline status, and the stairwell fan failure. The stairwell fan failure alarm is triggered if the stairwell fan fails a weekly test. Figure 87: Stairwell Fan 1 Trouble Interlock Definition 78

The Stairwell Fan 1 MCO Action Table is shown in Figure 88. The Stairwell Fan Auto point is a binary point in the DX to indicate that the fan is under automatic smoke control. This MCO controls the stairwell fan during manual smoke control. When a fire fighter turns the FSCS Stairwell Fan switch on or off, the stairwell fan responds accordingly and the Stairwell Fan Auto point is turned off. Figure 88: Stairwell Fan 1 MCO Action 79

The Stairwell Auto Pressure MCO Action Table (Figure 89) controls the stairwell fan when it is not in manual smoke control. The MCO turns the stairwell fan on if an automatic smoke control device detects smoke, a pullstation is pulled, or an FSCS floor zone switch is turned on. When a fire fighter turns the FSCS Stairwell Fan on or off, the Stairwell Fan Auto point is turned off. Figure 89: Stairwell Auto Pressure MCO Action Table The FSCS Stairwell Fan 1 switch setting (Table 13) determines the state value, which in turn determines the smoke control action. Table 13: FSCS Stairwell Fan 1 Switch State Value FSCS Stairwell Fan 1 Toggle Switch Position State Value Smoke Control Action On 1 Stairwell Fan 1 On Auto 0 Auto Off 2 Stairwell Fan 1 Off 80

FSCS Elevator Fan Logic The FSCS Elevator Fan 1 main logic (Figure 90) inputs from the DX are the Fan Commanded State, Fan Present Value, and Stairwell Pressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points.. Figure 90: FSCS Elevator Fan 1 Main Logic 81

The expanded elevator fan logic (Figure 91) consists of two control blocks: the FSCS block (Figure 92) and the Fan Trouble Control block (Figure 93). Figure 91: FSCS Elevator Fan 1 FSCS and Fan Trouble Control Main Logic 82

The FSCS logic (Figure 92) controls the elevator LEDs on the FSCS panel and commands the DX. The elevator On LED is lit only if the FSCS is in Fire Fighter Control and the elevator fan is on. The elevator Off LED is lit only if the FSCS is in Fire Fighter Control and the elevator fan is off. The elevator Auto LED is lit only if the toggle switch is not in the On or Off setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch: On 1 Auto 0 Off 2 Figure 92: FSCS Elevator Fan 1 FSCS Logic 83

The Fan Trouble Control logic (Figure 93) sets the elevator fan Trouble LED on the FSCS. The Trouble LED is lit if the fan is in smoke control and the fan has not reached its desired setpoint within 60 seconds or one of the DX fuses has blown. A fan is in smoke control if the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to On or Off. Figure 93: FSCS Elevator Fan 1 Fan Trouble Control Logic The Elevator Fan 1 Trouble Interlock Definition (Figure 94) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the elevator supply fan, the DX offline status, and the elevator fan failure alarm. The elevator supply fan failure alarm is triggered if the elevator supply fan fails a weekly test. Figure 94: FSCS Elevator Fan 1 Trouble Interlock Definition 84

The Elevator Fan 1 MCO Action is shown in Figure 95. The Elevator Fan Auto point is a binary point in the DX to indicate that the fan is under automatic smoke control. When a fire fighter turns the fan on or off, the Elevator Fan Auto point is turned off. The Elevator Fan Command is a point in the DX to control the fan. The FSCS Elevator Fan 1 toggle switch setting (Table 14) determines the state value, which in turn determines the smoke control action. Table 14: FSCS Elevator Fan 1 Switch State Value FSCS Elevator Fan 1 Switch Position Figure 95: FSCS Elevator Fan 1 MCO Action State Value Smoke Control Action On 1 Elevator Fan 1 On Auto 0 Auto Off 2 Elevator Fan 1 Off 85

The FSCS Elevator Fan 1 Auto Pressure MCO Action Table (Figure 96) determines the state value, which in turn determines the smoke control action. Figure 96: FSCS Elevator Auto Pressure MCO Action Table FSCS Firefighter Control Logic The FSCS Fighter Control main logic (Figure 97) turns the Fire Fighter Control Auto LED on if the Fire Fighter Control Key is off. It turns the Fire Fighter Control LED on if the Fire Fighter Control Key is on. If the Programming in Progress point is on, the logic turns on the Programming Active LED. This point must be turned on any time changes are being made to the LCT application. Figure 97: Fire Fighter Control LED Main Logic 86

The expanded Fire Fighter Control logic is shown in (Figure 98). Figure 98: Fire Fighter Control Logic

Using Multiple Smoke Control NAEs or NIEs Requirements for Larger Sites There are larger sites where, due to a large number of objects, several smoke control NAEs or NIEs may be required. If this is the case, then one smoke control NAE must be designated as the FSCS smoke control NAE and must connected directly to the FSCS. A Site Director smoke control NAE is used to monitor all smoke control NAEs and smoke control NIEs. Object Limits Each device and its programmed points use objects. There is a suggested object limit of, for performance purposes, 5,000 objects per smoke control NAE/NIE. When approaching the object limit it is sometimes necessary to add additional smoke control NAEs or NIEs. Site Director Smoke Control NAE The Site Director smoke control NAE provides the ability to monitor and control all devices connected to the smoke control system. FSCS Smoke Control NAE The FSCS smoke control NAE connects directly to the FSCS and monitors the Site Director smoke control NAE. Smoke Control System Connection Overview The example multi-story smoke control system (Figure 99) shows the IFC panels, the FSCS panel, the Site Director smoke control NAE, the smoke control FSCS NAE, a smoke control NIE, and various N1 and N2 devices, communicating over Ethernet and fiberoptic connections. 88

Figure 99: Example Multi-Story Smoke Control System

FSCS Alarms Table 15 shows the resulting FSCS alarms when any of the devices in the example multi-story smoke control system (Figure 99) go offline. Table 15: Example System Offline Device Alarms Offline Device FSCS Alarm FSCS Smoke Control NAE Offline Site Director Smoke Control NAE Offline Smoke Control NIE Offline NCM 350 Floor 1 Offline NCM 350 Floor 2 Offline Floor 1 DX9100 Offline Floor 2 VMA Offline Monitoring the Site Director Smoke Control NAE General Trouble LED + Sonalert Floors 1,2,3 All Point Trouble LEDs + Sonalert Floors 1,2 All Point Trouble LEDs + Sonalert Floor 1 All Point Trouble LEDs + Sonalert Floor 2 All Point Trouble LEDs + Sonalert Floor 1 Damper and Fan Trouble LEDs + Sonalert Floor 2 VMA Trouble LED + Sonalert The Site Director smoke control NAE must be monitored by the FSCS smoke control NAE in the event it goes offline. The NAE Site Director Monitor Interlock (Figure 100) is used to monitor the Site Director. If the Site Director smoke control NAE goes offline the FSCS Smoke control NAE detects the offline alarm and sends trouble alarms to the FSCS for any floors, devices, or points being controlled by the Site Director smoke control NAE.. Figure 100: Site Director Offline Monitor Point Interlock Definition To monitor the Site Director smoke control NAE: 1. Add a Site Director Monitor point (Figure 101) to the tree in the FSCS folder of the FSCS smoke control NAE 2. Create a folder inside the FSCS folder of the FSCS smoke control NAE for each floor the Site Director smoke control NAE monitors. 3. Inside each newly created floor folder, create a folder for Damper 1, Damper 2, Damper 3, Exhaust Fan 1, Supply Fan 1, VMA 1, and Zone Smoke LED. 90

4. Add a Trouble LED Control interlock point for each device in the device s respective folder (Figure 102). Include the Action Table for each device (Figure 103). Figure 101: NAE Connections 91

Figure 102: Trouble LED Control Interlock Definition Figure 103: Damper 3-2 Trouble LED Control Action Table 92

Monitoring a Smoke Control NIE Each smoke control NIE must be monitored by the Site Director in the event it goes offline. If a smoke control NIE goes offline the Site Director smoke control NAE detects the offline alarm and sends trouble alarms to the FSCS smoke control NAE for any floors, devices, or points being controlled by the smoke control NIE. To monitor a smoke control NIE: 1. Add an NIE monitor point (Figure 105) to the tree in the FSCS folder of the Site Director smoke control NAE (Figure 104). Figure 104: NIE Monitor and Trouble Interlocks 93

Figure 105: NIE Monitor Trouble Interlock 2. Add the NIE Monitor point to the Trouble Interlock for the fans, dampers and VMA of every floor the NIE controls (Figure 106). Figure 106: NIE Monitor Trouble Interlock Controls Group 507 E. Michigan Street Milwaukee, WI 53202 Metasys is a registered trademark of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. 2005Johnson Controls, Inc. 94 Published in U.S.A. www.johnsoncontrols.com