Use of Earth to Air Heat Exchangers for Cooling M. Santamouris University of Athens, Greece

Similar documents
PERFORMANCE OF EARTH TUBE HEAT EXCHANGER COOLING OF AIR A REVIEW

1. COOL ROOFS. What is a Cool Roof

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

The Corbioli House is a single-family house situated

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Indoor Climate Control Effect of AAC Panel Heat Capacity Experimental rooms and simulations with three structural materials

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

Kills bills. How Vaillant technologies reduce home heating bills

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Smart Green Roofs: Cooling with variable insulation

Why Vaillant? Home Heating Guide. Because they can reduce our heating bills and our carbon footprint

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

HSPF Calculation of a System Allowing Switching Between a Single-Stage to a Two-Stage Compression System

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER

Stochastic Model of Appliances Energy Consumption 3.1 A SMART, ENERGY-SAVING TENANTS SOLUTION

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Reducing the Carbon Footprint of Existing Domestic Heating: A Non-Disruptive Approach

K.F. Fong *, C.K. Lee, T.T. Chow

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE

Appendix C House models for Dymola to be used in connection with the OPSYS test rig and annual simulations of the performance of heat pumps

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

A full list of energy conservation opportunities (ECO) for air-conditioned buildings

Effect of domestic storage and cooking conditions on the risk distribution in ready to cook meat products

for family composition, time allocation of people, ownership and specification of home appliances. This paper first presents the simulation procedure

Numerical study of heat pipe application in heat recovery systems

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Requirements for the Collection, Transportation, Storage and Treatment of Cooling and Freezing Appliances containing Hydrocarbons (HC)

Figure 1: Low energy dwellings testsite

Victoria & Albert Museum, London Medieval & Renaissance Galleries: A Passive Approach to Humidity Control

Adelaide Homes Design Guide 4 - Winter warming

SOLAR HOT WATER AND HEAT PUMP BOOSTER ENERGY CALCULATION METHODOLOGY

Regenerator Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

*Bioenergy GmbH Gewerbepark Haag 3, 3250 Wieselburg Land, Austria

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

Evaluation of HCFC Alternative Refrigerants

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

EFFECTS OF VARIABLES ON NATURAL CONVECTIVE HEAT TRANSFER THROUGH V-CORRUGATED VERTICAL PLATES

Sprinklers Modeling for Tunnel Road Fire Fighting

This document is a preview generated by EVS

VRV The total solution. Integrated Climate Control

Eurocode 9 Design of aluminium structures

ENERGY EFFICIENCY BRIEF REPORT

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Energy Efficiency Standards

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

FLIGHT UNLOADING IN ROTARY SUGAR DRYERS. P.F. BRITTON, P.A. SCHNEIDER and M.E. SHEEHAN. James Cook University

nzeb office building

EFFECTS OF COMBINING SMART SHADING AND VENTILATION ON THERMAL COMFORT

[Eswaran, 3(3): March, 2014] ISSN: Impact Factor: 1.852

LIGHTING APPLICATIONS - TUNNEL LIGHTING IRISH STANDARD I.S. CR 14380: Price Code. Údarás um Chaighdeáin Náisiúnta na héireann

AIR TO WATER HEAT PUMPS. Hot water and comfortable ambient temperature all year round

European Sprinkler Campaigns. Edinburgh, 20 January 2010 Alan Brinson

Residential ventilation concepts based on the idea of displacement airflow distribution

Temperature Rises as Products Compete in the Heat. Market. Contact: Tim Page Press Release No: 20. Release date: Immediate Date: 11/11/09

Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Available online Journal of Scientific and Engineering Research, 2018, 5(11): Research Article

Foreword. A completely revised report for quicker and easier access to key information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Department of Architecture Federal University of Technology, Akure ARC 810: Applied Climatology Course Outline ( Session)

General HVAC Recommendations

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

EFFECT OF BOLT CONNECTION OF SQUARE-SHAPED GEOCELL MODEL ON PULLOUT TEST RESULTS

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

Solar Air-Conditioning and Refrigeration - Introduction

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Reduced Order WECC Modeling for Frequency Response and Energy Storage Integration

EFFECT OF DIVERSE STREAM PATTERNS ON THE PERFORMANCE OF SOLAR AIR HEATER

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Potential and Simulation of Open-Cycle Solar-Assisted Climatisation-Plants in Single-Family-Houses

Shortcut Model for Predicting Refrigeration Cycle Performance

PERFORMANCE MONITORING OF A HIGH-TEMPERATURE AIR-TO-WATER HEAT PUMP WITH INJECTION CYCLE INSTALLED IN A LOW-INSULATED SINGLE-FAMILY HOUSE IN BELGIUM

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

Annual environmental performance evaluation of light and heat in daylight harvesting systems using Radiance and NewHASP

Managing the Heating Demand in Institutional Buildings with an Innovative Thermal Storage System

Seminar on Standardisation in Research and Innovation Practical tools for the dissemination and implementation of research results

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

Connect North and South Korean Separated Families Higher Comfort Lower Energy

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

English Version. Daylight of buildings

August 15, 2013 Page 1 of 19

DESIGN, FABRICATION & PERFORMANCE ANALYSIS OF SOLAR AIR HEATER

Optimization of Hybrid Noncondensable Gas Removal System for a Flash Steam Geothermal Power Plant

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos

Windows Influence on Room Daylighting in Residential Buildings

Transcription:

V entilation I nformation P aper n 11 January 2006 INIVE EEIG Operating Agent and Management Boulevard Poincaré 79 B-1060 Brussels Belgium inive@bbri.be - www.inive.org International Energy Agency Energy Conservation in Buildings and Community Systems Programme Air Infiltration and Ventilation Centre Use of Earth to Air Heat Exchangers for Cooling M. Santamouris University of Athens, Greece 1 Introduction The present Ventilation Information Paper aims to present the basic knowledge on the use of earth to air heat exchangers. The increased need for air conditioning has made alternative passive and hybrid cooling techniques very attractive. The technique is based on the use of the ground as a heat sink during the summer and winter period. In fact, the soil at a certain depth is at a much lower temperature than the ambient one, during summer and much higher during winter. Thus, the excess heat from a building may be dissipated to the ground through horizontally positioned buried pipes, reducing thus the indoor temperature in summer. In winter the pipes are used for preheating of the ventilation air, reducing thus the heating load of buildings. The principles of operation as well as the way to apply earth to air heat exchangers are described. Performance data from various examples are presented as well. Finally, information on various methodologies to calculate the performance of the systems is given. Detailed information on earth to air heat exchangers can be found in Santamouris and Assimakopoulos (1996). 2 The Increased Needs for Cooling Air conditioning has become popular during recent years because of the increased living standards in the developed world and the use of non-climatically responsive architectural standards. [Ref. 1] According to the International Institute of Refrigeration (IIR) (IIR, 2002), actually there are more than 240 million air conditioning units and 110 million heat pumps installed worldwide. The same study shows that the refrigeration and air conditioning sectors consume about 15% of all electricity consumed worldwide (IIR, 2002). The annual sales of air conditioning equipment approach a level of $60 billion/year (IIR, 2002). This is almost equivalent to 10% of the automobile industry sales on a worldwide basis. The penetration of air conditioning is increasing continuously. According to the Japan Air Conditioning and Refrigeration News (JARN) and Japan Refrigeration and Air Conditioning Industry Association (JRAIA) in 1998 the total annual number of sales was close to 35 million units; by 2000 it had increased to 42 million units and to 45 million units by 2002, with a predicted level of 53 million units in 2006 (JARN and JRAIA, 2002). 1

The use of air conditioning is the cause of different problems. Apart from the serious increase of the absolute energy consumption of buildings, other important impacts include: The increase of the peak electricity load; Environmental problems associated with the ozone depletion and global warming; Indoor air quality problems. High peak electricity loads oblige utilities to build additional power plants in order to satisfy the demand, but as these plants are used for short periods, the average cost of electricity increases considerably. One of the major scientific and technical requirements of our days is to address successful solutions to reduce energy and environmental effects of air conditioning. Passive cooling techniques when applied to buildings have been proven to be very effective and contribute greatly in decreasing the cooling load of buildings, provide excellent thermal comfort and indoor air quality, together with low energy consumption. 3 The Use of the Ground as a Heat Sink The ground temperature presents on average much lower temperatures than the ambient air during the summer period and higher during the winter period. The exact value of the ground temperature is a function of the depth, z, the thermal characteristics of the soil and in particular of its thermal diffusivity, (a), and of the variation of the surface temperature, The ground temperature at any depth can be predicted using the equation given below. Ground cooling is based on the dissipation of the excess heat from a building to the ground. During the summer period, the ground presents a much lower temperature than the ambient air. The dissipation of the excess heat may be achieved by the use of earth to air heat exchangers. More information on the potential of the heat dissipation to the ground can be found in (Mihalakakou et al, 1994). An earth to air heat exchanger is a horizontal pipe buried at a certain depth. Air is circulated inside the pipe (in most cases by mechanical means) and because of the lower ground temperature its temperature is reduced, (figure 1).The cool air is then sucked inside the building to decrease indoor temperature. 0.5 0.5 πα 2 π z 365α Tzt, = Tm Asexp z cos t t0 365 365 2 π Where : T m is the average annual temperature of the soil surface (K) A s is the amplitude of the surface temperature variation (K) z is the depth (m) α is the thermal diffusivity of the ground (m²/h) t is the time elapsed from the beginning of the calendar year (days) t 0 is a phase constant (hours since the beginning of the year of the lowest average ground surface temperature). More information on the ground temperature can be found in Mihalakakou et al, (1992, 1997). Air Infiltration and Ventilation Centre 2 WWW.AIVC.ORG

Figure 1: Principle of earth to air heat exchangers There are two main configurations for the earth to air heat exchangers. The system may be an open or a closed loop circuit. In an open loop circuit the ambient air is circulated inside the pipes and then is transferred into the building (Figure 1) while in closed loop circuit configurations, both inlet and outlet are located inside the building (Figure 2). The specific performance of the earth to air heat exchangers and in particular the achieved air temperature decrease is a function of the inlet air temperature, of the ground temperature at the depth of the exchanger, of the thermal characteristics of the exchangers and of the soil, and finally of the air velocity and the pipe dimensions. 4 Description of Earth to Air Heat Exchangers An earth to air heat exchanger is a plastic, concrete, ceramic or metallic pipe buried at a certain depth in the ground (Figures 3-4). Given the very high thermal inertia of the ground, the conductivity of the pipe is of minor importance. In order to improve the thermal contact between the pipe and the ground, 5 cm of sand are typically placed below and above the pipe (Figure 5). Figure 3: Placement of a pipe into the ground [Ref. 1] Figure 2: A close loop earth to air heat exchanger [Ref. 1] Figure 4: Placement of a pipe into the ground Information on the cooling potential of earth to air heat exchangers can be found in (Mihalakakou et al, 1994b). Also information on the impact of ground cover on the efficiency of earth to air heat exchangers can be found in (Mihalakakou et al, 1994c, 1996) Figure 5: Placement of a pipe into the ground using sand to improve thermal contact between the pipe and the soil V. I. P. n 11 3 January 2006

Every exchanger has an inlet and an outlet part where air enters and exit. The pipes may be connected between them in order to have a common inlet and a common exit (Figure 6) or may be independent. The air is circulated through the pipes using either a common or individual fans. The selection of the fan has to be done in order to achieve the best appropriate air speed inside the tubes. Although earth to air heat exchangers are in principle rather simple low-cost systems, condensation problems may appear, that may be the source of important indoor air quality problems. This may be resolved, for example, by having the pipes installed with a small tilt of e.g. 1% slope for drainage. A small hole at the lower part of the exchanger may help to avoid collection of water inside the tube. Design of a drainage system is also possible. Filtering of the air might be useful or necessary. In some cases the air is circulated inside the building through an air handling unit and thus air is filtered. The main parameters to be defined before the installation of an earth to air heat exchanger system are: The depth the exchanger has to be placed; The length and the diameter of the pipes; The air speed inside the pipes; The control system to be applied. The pipes have to be separated between them at about 2m distance to allow heat dissipation; In some of the cases, periodic cleaning of the tubes is important. This may be achieved by installing the tubes with a drop in height from start to end of 1:60 to allow jet washing. Earth to air heat exchangers may be used to supply cool air directly to the building, or may be connected to an existing air conditioning system. In the later case, the exchangers may be used. As it concerns the control of the system, a very simple strategy has to be applied. In a first step it has to be assured that the temperature at the exit of the pipes is at least 3-4 C lower than the indoor temperature (summer). Second it has to assured that the energy spent for the circulation of the air is much lower than the cooling power offered by the system. To achieve the above, the inlet and exit temperatures of the air as well as the indoor temperatures have to be measured. A very simple controller can be used to satisfy the above conditions. Optimisation of the design requires a complete thermal simulation of the system. In the following some methodologies to design earth to air heat exchangers are presented. Based on the existing experience some preliminary guidelines may be offered. These guidelines may be applied at any climate. In particular it has to be considered, that: The length of the exchanger should be at least longer than 20 m; The diameter of the exchanger should range between 0.2 to 0.3 m; The depth of the exchanger should range between 2 m to 3 m; The air velocity through the buried pipe should range between 6 and 10 m/s. Lower air speeds may be used as well, but the heat exchange coefficient inside the pipes will be lower, and thus the efficiency of the system will be reduced; Figure 6: Buried pipes with a common inlet and exit [Ref. 1] Air Infiltration and Ventilation Centre 4 WWW.AIVC.ORG

5 Examples and Performance Data Performance data from applications of earth to air heat exchangers to buildings are available from many projects. Information about the projects is given below. In most of the projects it is evident that the exit temperature from the tubes is quite low and can highly contribute to satisfy the cooling needs of buildings. 5.1 University building Figure 7 shows the minimum and maximum ambient temperature as well as the exit temperature from an earth to air heat exchanger at the University of Ioannina, Greece, (Stournas Triantis et al, 1986). The length of the pipes was almost 30 m and the pipes were buried at about 3 m depth. Monitoring has taken place during the summer period and figure 7 shows data for 31 consecutive days in July. As shown, the achieved maximum temperature drop at the exit of the pipes was close to 10 C compared to the maximum ambient temperature. The building employs energy saving techniques such as the earth to air heat exchangers, shadow and windshield cladding and VRV (Variable Refrigerant Volume) type heat pumps, combined with simple ceiling fans for air conditioning in the office. The earth to air heat exchanger consists of two tubes of 0.315 m diameter buried at 2 m depth around the building. The length of each one is 50 m. They are designed to provide 4500 m³/h of air (air velocity equal to 8 m/s). The building is being monitored since November 2004 to assess the effectiveness of the energy saving techniques. Temperature 31 Days of July 50 Max Indoor Figure 8: Outdoor view of the Aggelidis paper warehouse building 40 30 20 10 Max Ambient Exit Tubes Min Ambient 0 Days Figure 7: Performance of earth to air heat exchangers at the University of Ioannina 5.2 Paper warehouse The Aggelidis building is a paper warehouse placed on a site of 10.900 m², 21km out of the center of Athens and on the Athens Thessaloniki highway. It has three levels: the basement where the parking and central mechanical equipment are placed, the ground floor for the main storage room and lifting platforms, and the first floor for special products storeroom, platform and offices (see Figures 8, 9). Figure 9: Point where the air from the earth tube is introduced in the building The daily mean maximum inlet and outlet temperatures from one of the earth to air heat exchangers are given in Figure 10. As shown the mean temperature drop at the exit of the temperature is close to 5 C. The use of the earth to air heat exchangers has permitted to keep indoor temperature inside the comfort levels without the use of air conditioning. Figure 11 shows the distribution of indoor V. I. P. n 11 5 January 2006

1 4 7 temperature in the warehouse during the summer period. 33,00 28,00 23,00 18,00 13,00 Temperature 10 13 Aggelidis Building Performance of Buried Pipes 16 19 22 Inlet temperature 25 28 31 34 37 40 43 46 Exit temperature 49 52 55 Days Figure 10: Inlet and outlet temperatures in one of the heat exchangers during the summer period (%) 100.0 80.0 60.0 40.0 20.0 0.0 Measured temperatures in the warehouse 100.0 96.3 95.1 85.1 72.9 45.2 58 61 64 30.1 67 70 17.1 73 76 79 3.4 >18 >19 >20 >21 >22 >23 >24 >25 >26 T (degree C) Figure 11: Distribution of indoor temperatures in the warehouse during the summer period 5.3 COOLHOUSE project The COOLHOUSE project of the European Commission aimed to test the viability of alternatives to air conditioning using passive and low energy construction, cooling and ventilating techniques in Mediterranean and coastal climates and to demonstrate that such strategies can be practical and provide comfortable internal conditions for the occupants (Burton, 2004). The project involved three demonstration sites in Portugal, France and Italy. 82 The main energy components were External wall insulation; Solar shading; Internal thermal mass, including adobe internal walls; Ground cooling using standard PVCu drainage pipework. The main characteristics of the earth to air heat exchangers used (Figure 2) are: Pipe diameter 160mm; Two ground tubes of 25m length each; Fan assistance; Separation between pipes of 2m to allow heat dissipation; 90º bends formed from two 45º pipe sections to reduce the air resistance; Periodic cleaning by installing the tubes with a fall from start to end of 1: 60 to allow jet washing. Monitoring of the project has shown that the ground cooling system was very effective at removing the peaks and troughs of the external air temperature. The maximum +DT (i.e. heat removed from the incoming air) was 11 C, while the maximum -DT (i.e. heat added to cold external air) was 8 C. The temperature of the air from the ground pipes varied from 26 C in August to 15 C in winter. Calculations show a 95% reduction in energy and CO 2 emissions, compared with the corresponding emissions in case conventional air conditioning was used. In parallel, additional ventilation pre-heat gains are also available in winter mode. A significant benefit of ground cooling is the reduction in internal relative humidity (RH). It may be about 25% to 30% of RH recorded something particularly important in Portugal. 5.3.1 Large new residential community in Portugal The Alma Verde project in Portugal involves: 35.3 hectare new residential community; Numerous public and private amenities located in the unspoiled western Algarve 8km west of Lagos, Portugal, some 25km east of the tip of Europe 6 detached houses used to demonstrate the COOLHOUSE principles 5.3.2 Nursing home in France L Aubier de Cybele in Southern France, is an 80 beds care home for elderly people. It is considered as a first green nursing home in the south of France that uses bioclimatic and passive cooling design. It involves a number of energy efficiency and bioclimatic measures, like: insulation, solar shading, daylighting, thermal mass, natural ventilation, planting, solar water heating, passive solar gain and ground cooling. Air Infiltration and Ventilation Centre 6 WWW.AIVC.ORG

The ground cooling system serves the dining room area of 380 m², and it consists of a grid of 11 pipes each of 200 mm diameter buried 2 m below ground (Figure 6). The project is monitored in the frame of the Coolhouse project and it is found that while the initial cooling power was14 kw at 2 m³/s air flow-rate and 9.5 kw at 1m³/s air flow-rate, in July and August, the cooling power values have been reduced to about 5 kw after one to three days of uninterrupted use. 5.3.3 Aler Pavia The Aler Pavia project (Italy) is in an area of existing social housing and is related to the refurbishment of 220 dwellings. It involves a new community centre, the CircoLab, a multi-functional facility with corporate, conference, recreational, cultural and community functions. It is designed as a concrete box, cut by two internal glazed patios and completely greened by creepers. The project uses a ground cooling system, involving PVC pipes, with a diameter of 400 mm, 40 m long, buried 4 m below ground level (Figure 3). The outdoor air is taken from a shaded area at the opposite side of the courtyard. An air to air heat air heat exchanger is placed between the ground pipe and the ventilation system. Monitoring has shown that ground cooling is very effective at removing the peaks and troughs of the external air temperature. The average temperature difference of the air entering the building below external air temperature was 2.9 C 6 Calculation Methods Calculation of the thermal performance of earth to air heat exchanger is a complex problem. Calculation tools can be classified in simplified and detailed ones. Simplified tools are mainly designed to calculate the exit air temperature from the pipes. Detailed tools are simulation methodologies that solve simultaneously the heat transfer equations for the air, the tube and the ground. A full presentation as well a comparison of most of the simplified methods is given by (Tzaferis et al, 1992). A simple validated parametric model to calculate the outlet temperature from buried pipes is proposed by (Mihalakakou et al, 1995b). Various detailed simulation models to calculate the heat transfer phenomena associated with earth to air heat exchangers have been developed. A validated model coupled to the TRNSYS program is described in (Mihalakakou et al, 1994d). The coupled heat transfer phenomena between buildings and earth to air heat exchangers are of high importance. Information on the ground temperature below buildings can be found in (Mihalakakou et al, 1995). In parallel, a method to estimate the specific performance of buildings coupled with earth to air heat exchangers is given in Santamouris et al, (1995, 1997). V. I. P. n 11 7 January 2006

7 References 10. Mihalakakou, M. Santamouris, D. 1. Burton S.: Final Report of the Coolhouse Project. European Commission, Directorate General for Energy and Transport, 2003. 2. Japan Air Conditioning and Refrigeration News (JARN), Japan Refrigeration and Air Conditioning Industry Association (JRAIA). 2002. Air Conditioning Market. Tokyo, Japan 3. International Institute of Refrigeration. 2002. Industry as a partner for sustainable development refrigeration,. Report Published by, Paris, France 4. Mihalakakou, M. Santamouris and D. Asimakopoulos :Modelling the earth temperature using multiyear measurements. J. Energy and Buildings, 19, 1-9, 1992. 5. Mihalakakou, M. Santamouris and D. Asimakopoulos : On the Use of Ground for Heat Dissipation J. of Energy, 19, 1, p.p. 17-25, 1994. 6. Mihalakakou, M. Santamouris and D. Asimakopoulos :On the Cooling Potential of Earth to air heat Exchangers, J. Energy Conversion and Management, 35, 5,395-402, 1994b. 7. G. Mihalakakou, M. Santamouris and D. Asimakopoulos and N. Papanikolaou : The impact of the ground cover on the efficiency of Earth to air heat Exchangers. J. Applied Energy, 48, p.p. 19-32, 1994c. 8. Mihalakakou, M. Santamouris and D.N. Asimakopoulos : Modelling the thermal performance of the earth to air heat exchangers.solar Energy, 53,3, 1994d 9..Mihalakakou, M. Santamouris, D. Asimakopoulos and A. Argiriou : On the ground temperature below buildings. Solar Energy, 55, 5, 355-362, 1995 Asimakopoulos and I. Tselepidaki : Parametric Prediction of the Buried Pipes Cooling Potential for Passive Cooling Applications. Solar Energy, 55, 3, p.p. 163-173, 1995b 11. Mihalakakou, J.O. Lewis and M. Santamouris :The Influence of Different Ground Covers on the Heating Potential of Earth to Air Heat Exchangers. Journal of Renewable Energies, 7,1, p.p. 33-46, 1996 12. Mihalakakou, M. Santamouris J.O.Lewis and D.N. Asimakopoulos : On the application of the energy balance equation to predict the ground temperature profiles. Solar Energy, 60,3/4,p.p, 181-190, 1997 13. Santamouris, G. Mihalakakou, A. Argiriou and D.N. Asimakopoulos : On the Performance of Buildings coupled with earth to air heat exchangers. Solar Energy, 54, 6, 375-380, 1995 14. Santamouris M, and D.N. Assimakopoulos, (Eds) : Passive Cooling of Buildings. James and James Science Publishers, London, 1996. 15. Santamouris G. Mihalakakou and D.N. Asimakopoulos : On the coupling of thermostatically controlled buildings with ground and night ventilation passive dissipation techniques. Solar Energy, 60,3/4,.p.p. 191-197, 1997 16. Stournas-Triantis, M. Santamouris και T. Metsis : Passive Solar Restoration of the new School of Philosophy building in the University of Ioannina, Greece. Proc. Conference "International Climatic Architecture Congress", Belgium, 1986. 17. Tzaferis, D. Liparakis, M. Santamouris and A. Argiriou : Analysis of the accuracy and sensitivity of eight models to predict the performance of earth to air heat exchangers. J. Energy and Buildings, 18, 35-43, 1992 The Air Infiltration and Ventilation Centre was inaugurated through the International Energy Agency and is funded by the following seven countries: Belgium, Czech Republic, France, Greece, the Netherlands, Norway and United States of America. The Air Infiltration and Ventilation Centre provides technical support in air infiltration and ventilation research and application. The aim is to promote the understanding of the complex behaviour of the air flow in buildings and to advance the effective application of associated energy saving measures in the design of new buildings and the improvement of the existing building stock. Air Infiltration and Ventilation Centre 8 WWW.AIVC.ORG