Ventilation and Humidity Control in Army Barracks Using DOAS for Better Indoor Air Quality and Energy Conservation

Similar documents
HVAC: The Next. Variable-air-volume systems. Outside-the-box thinking suggests the integration of dedicated

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

7. MECHANICAL SYSTEM DESIGN

Executive Summary. OA/person (cfm/p) Private and open offices, Classrooms, Building as designed

Direct Digital Temperature, Humidity, and Condensate Control for a Dedicated Outdoor Air-Ceiling Radiant Cooling Panel System

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Modular Active. Chilled. Beams

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

HVAC 101. H V A C S y s t e m s

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Economical, Flexible, Advanced Performance. Ventilation and Dehumidification for Healthy IAQ

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

Raised Access Floor - (AE Breadth Area)

Designing Energy Efficient Outdoor Air Systems

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

DADANCO Technical Paper

Achieving Dry Outside Air in an Energy-Efficient Manner

Benefits Offered by Passive Dehumidification Wheel Speed Control

DEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks

4. OVERVIEW OF MECHANICAL SYSTEM

High Efficiency Dehumidification System (HEDS)

Two essential attributes of mechanical systems intended to

Industrial Workshop Gettysburg, PA February 26, 2004

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

EarthWise System Seminar

NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

Dehumidifying with Dedicated Outdoor Air

To Keep Docs Cool, Dry and Happy

DES CHAMPS PRODUCTS. Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling

H O B O K E N R E S I D E N T I A L

Existing Mechanical System Operation

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2

HVAC EQUIPMENT. Exceptional Single Zone Heating and Cooling Solutions. Product Application Guide

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

HVAC DISTRIBUTION and DELIVERY SYSTEMS

The ultimate fresh air solution.

DOAS UNITS. ReznorHVAC.com MAKEUP AND VENTILATION AIR 100% OUTSIDE AIR

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

Ventilation in Humid Climates: Data from Field Experiments

Munters Heat Exchangers

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Chilled Ceilings / Beams Working Principles & Applications

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

Do All DOAS Configurations Provide the Same Benefits?

THE ULTIMATE ROOFTOP SOLUTION

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Agenda and Objectives

Chilled Beams. Getting a Warmer Reception

National Institutes of Health Building 37 Modernization Bethesda, Maryland MECHANICAL DEPTH EXISTING MECHANICAL SYSTEM

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

Comfort and health-indoor air quality

Dehumidification: Energy Efficiency Comparisons

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

CHAPTER 4. HVAC DELIVERY SYSTEMS

PRODUCT SERIES. VPR Series VPRX Series VPRE Series VPRP Series VPRC Series

RoofPak Applied Rooftop Systems

Heat pump and energy recovery systems

Bill McCullough. Director ERV Products. Dallas, TX

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

High-Performance VAV Systems

Technical Assignment 3

Redesign of Bennett Hall HVAC System

A REASONABLE ALTERNATIVE TO CHILLED BEAMS Dan Int-Hout Chief Engineer

4-Pipe VAV vs. Active Chilled Beams for Labs

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

The School District of Philadelphia Administration Headquarters

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

Mechanical Ventilation : How much is enough? Can there be Too Much? Subrato Chandra Resnet Meeting 2/20/07

FORM EG2 (502) FlexSys Configured Packaged Rooftop Air Conditioning Units

VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control

Energy Recovery with Cooling and Heating

4.0 Mechanical Redesign

Chilled Ceiling Condensation Control Experience In A Movable Sash Building

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012)

ENGINEERING. Edition No. 13 October 2002

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

Challenges and Methods of Estimating a Conceptual HVAC Design

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Custom Air Handler Solutions Custom Units to Meet Your Unique Design Needs

Appendices. Included in this section are

SECTION I: EXISITNG SYSTEM AND PROPOSED SYSTEMS

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

MultiFamily Ventilation Updates: ASHRAE 62.2, Best Practices and Practical Applications RESNET Conference Atlanta, GA

Heat Pumps M2 SERIES. Modular Self-Contained Unit Water-Source Heat Pumps (3-70 tons) Features:

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Air Change, Ventilation, and Dehumidification for Multi-family Buildings

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

RT-OA TM Rooftop Outdoor-Air (DOAS)

Transcription:

Ventilation and Humidity Control in Army Barracks Using DOAS for Better Indoor Air Quality and Energy Conservation Author:John Vavrin, PE Presenter: Dale Herron US Army Corps of Engineers Engineer Research and Development Center

What a difference!! Then Now

Introduction U.S. Military barracks range from the wooden World War II-era buildings to the college-dorm-type dwellings of today and are located in all climatic zones U.S. Army has been steadily building and renovating barracks under different long-term programs. The Barracks Upgrade Program (BUP), Training Barracks Improvement Program (TBIP), Barracks Improvement Program (BIP), and Flagship Programs are focused on improvement of conditions in permanent-party barracks and include: mold and mildew removal; repairing or replacing damaged heating or air conditioning systems; fixing water leaks; and ensuring all toilets, showers and plumbing are in working condition; painting of buildings and repair of doors and windows. These 4 programs address needs of 26 CONUS Army installations + installations in Europe and Korea with a total cost of ~$484M.

Scope of Measures Building Envelope Roofing Wall Insulation Air Leakage Reduction Window Shading Basement Water Leakage Reduction Separate Ventilation and Temperature Control (A/C) System Outdoor Air Dehumidification Demand-Side Management Lighting Occupancy Control Systems

General Problems with Humidity in Barracks, Major Concern in SE United States

Moisture Control Ft. Polk, LA Strategies for dealing with moisture in buildings include: Keeping water out, Avoiding (or managing) plumbing leaks, Avoiding condensation inside the building or within the building envelope, Controlling the entry of humid outside air, Controlling indoor sources of humidity (i.e. moisture coming from insufficiently ventilated showers), Providing adequate mechanical ventilation/dehumidification. Ft. Stewart, GA

Dedicated Outside Air System Use DOAS to pressurize apartments, provide humidity control and make-up air for mechanical exhausts (separate room temperature control system): Dehumidification Only dehumidifies and tempers summer outside air uses one air-air heat exchanger is not an air-to-air energy recovery device Dehumidification with Energy Recovery dehumidifies and tempers summer outside air tempers winter O/A uses two air-air heat exchangers performs energy recovery using building exhaust air

DOAS Systems OA DOAS Unit W/ Energy Recovery Cool/Dry Supply High Induction Diffuser Parallel Sensible Cooling/Heating System Building With Sensible and Latent cooling decoupled

Reasons Engineers Are Choosing Dedicated OA Systems Ventilation Air Distribution In All Air VAV Systems. Engineers cannot be sure where the ventilation air, in all air systems, is distributed once brought into the building and mixed with return air at the air-handling unit. Excess OA Flow And Conditioning Required For All Air VAV Systems. VAV Box Minimum Settings Must Be Surprisingly High. Inability Of Most All Air VAV Systems, As Currently Designed, To Decouple The Space Sensible And Latent Loads.

Problems of All-Air VAV Multiple spaces equation (ASHRAE Std. 62) Does not guarantee that individual space will always receive the intended OA quantity Conditioning and transporting air Consumes large quantities of energy Part load humidity problem Space humidity is passively controlled

DOAS Systems 20-70% less OA than VAV DOAS Unit W/ Energy Recovery Parallel Sensible Cooling System Cool/Dry Supply High Induction Diffuser Building With Sensible and Latent cooling decoupled

Why decouple sensible and latent space loads with DOAS? Tight humidity control minimizes the potential for IAQ problems and related sick-building illnesses, and improves thermal comfort and productivity. *Which are caused largely by biological contaminants breeding in damp ducts, ceiling tiles, insulation, behind vapor barriers and carpet.

Potential Health & Productivity Related Economic Benefits of DOAS The significance of DOAS is illustrated by estimates that US companies lose as much as $48 Billion annually to cover medical expenses and $160 Billion annually in lost productivity as a result of sick-building illnesses. Source: ASHRAE Literature

VAV problems solved with DOAS plus Radiant or Chilled Beam Poor air distribution. Poor humidity control. Poor acoustical properties. Poor use of plenum and mechanical shaft space. Serious control problems, particularly with tracking return fan systems. Poor energy transport medium, air. Poor resistance to the threat of biological and chemical terrorism, and Poor and unpredictable ventilation performance.

Additional Benefits of DOAS Beside solving problems that have gone unsolved for over 30 years with conventional VAV systems, note the following benefits: Greater than 50% reduction in mechanical system operating cost compared to VAV. Equal or lower first cost. Simpler controls. Generates up to 80% of points needed for basic LEED certification.

Conclusions Significant energy saving potential over 40% Small SA quantity Fan energy reduction Total energy recovery Equipment size reduction Increased pumping energy Offset by reduced fan & chiller energy consumption

Sample DOAS pitfalls? Wrong supply air temperature Wrong controls for the enthalpy wheel Wrong controls for the heating coil Wrong controls for the cooling coil Wrong location for the heating coil

Questions or Comments?? Contact Information Mr. John Vavrin PE http://www.cecer.army.mil US Army Corps of Engineers Engineer Research and Development Center ERDC CERL (Energy Branch) john.vavrin@erdc.usace.army.mil (217) 373-5856

BACKUP SLIDES DOAS System Psychometrics and Case Studies

EW 5 4 RA OA 1 2 3 PH CC 40 50 Space Other regions? Next slide wet dry 60 Wet Bulb (F) 70 3 4,5 2 80 80% 1 90 60% 40% 20%.028 196.024 168.020 140.016 112.012 84.008 56 Humidity ratio (grains/lb) HUMIDITY RATIO (Lbv/Lba).004 28 40 50 60 70 80 90 100 120 DRY BULB TEMPERATURE (F)

EW control for various OA conditions 90 196.028 wet dry 40 40 EW off 50 EW to modulate or duty cycle to hold SAT SP when OA < SAT SP 50 EW on when OA h > RA h 60 60 Wet Bulb (F) 70 EW off 80 80% 40% 20% 70 80 90 100 120 DRY BULB TEMPERATURE (F) 60% 168.024 140.020.016.012.008 28.004 HUMIDITY RATIO (Lbv/Lba) 112 84 56 Humidity ratio (grains/lb)

Example of an incorrect EW control logic EW on 50 EW off 60 Wet Bulb (F) 70 80 EW on 80% 90 60% Cleaning cycle when off! Frost protection when cold outside! 40% 20%.028.024.020.016.012.008 196 168 140 HUMIDITY RATIO (Lbv/Lba) 112 84 56 Humidity ratio (grains/lb) 40.004 28 40 50 60 70 80 90 100 120 DRY BULB TEMPERATURE (F)

> 3 ton cooling lost with wheel off Reheat adds 2.8 tons of cooling load, plus the heating energy wasted in the 1,710 cfm OA sys. Neutral temperature a huge energy waste! EW off, huge control error when it could significantly reduce the CC load if operating. CC load ~ 10 ton CC Control based upon maintaining a SA DPT, what happens if the OA is hot and dry?

EW Duty cycle defined RAT, 72F OAT=40F SAT=OAT when EW off (40F) SAT=OAT+(RAT-OAT)*EWeff (65.6F) EWeff, 0.8 By adjusting the EW ON time (54.7% or 8.2 min) in 1 period (15 min) can get an avg. temperature equal to the desired SAT (54F). Duty cycle changes to 100% ON at 40F OAT to avoid tripping freeze stats. NOTE: HC must be off since when EW off, DAT < DATSP and the CC must be off when the EW on!

EW operation when OA below 54F SA Temperature, F 70 68 66 64 62 60 58 56 No duty cycle SAT OPP duty cycle SAT Revised duty cycle SAT VFD EW SAT 54 52 50 Heating Coil begins modulation at -18F to maintain 54F SAT -20-16 -12-8 -4 0 4 8 12 16 20 24 28 32 36 40 44 48 52 56 OA Temperature, F

Findings from Case Study @ Ft. Stewart Chilled water temperature rise in the distribution system between the CEP to barracks by 8 F 50 F CWS can t dehumidify properly CWS should be 45 F or less Many rooftop MUA units not operational Portable space dehumidifiers require daily emptying and add to room cooling load Condensation drips and negative room pressure lead to mold growth At least $1 Million annually for mold cleanup Potential man-hours lost due to building related illness (BRI)

Example of Dehumidification Project for Barracks Scope, Costs and Savings for Ft. Stewart Scope 31 modular barracks 2460 rooms 1,160,000 ft 2 conditioned space Costs Estimate Total Cost Installed - $2.8 Million Savings (Energy and Ancillary) $715K Payback 3.9 Years

Flow Schematic: Typical Unit

Dehumidification with Energy Recovery 83/72F 55/55F 95/76F 68/68F 50/75F 52/73F

Other Findings: Supply Air Ducts in Barracks and Mold in Barracks Rooms Mold Mold Supply Air Grill Not Changed (Clean Only) During Renovation 1. Mold and Mildew 2. Rust Clean thoroughly with bleach-type cleaner and paint or replace all grills Closet: Pre-renovation 1. Dehumidify Air 2. Ensure supply air units operating 3. Blower door tests to ensure room tightness 4. Install insulation on exposed cold piping 5. Clear condensate drain panels 6. Replace wall partitions

Pilot "Proof Of Concept" DOAS/CRCP (Ceiling Radiant Cooling Panel) System Penn State University Space Conditions 3200 ft 2 studio (43 X 74 ) 14 ceiling height with 8 rows of pendent illumination at the 9-ft plane 40 students Office equipments (desk lamps, personal computers)

Chiller Energy Reduction Chiller Size 29% reduction VAV system: 14 ton DOAS/CRCP pilot system: 10 ton 25% reduction Annual Chiller Energy Consumption VAV system: 10.6 MWh/y (3.7 seasonal COP) DOAS/CRCP pilot system: 7.9 MWh/y (4.5 seasonal COP)

Fan and Pumping Energy Fan Energy Reduction Design SA quantity: DOAS 1200 scfm VAV 3220 scfm 37% of VAV Annual Fan energy: DOAS 2.33 MWh/y VAV 7.97 MWh/y 71% Reduced Pumping Energy But, DOAS/CRCP system consumes nearly twice as much pumping energy Counterbalanced by the greatly reduced fan and chiller energy

Total Energy Consumption 42% Reduced! 19 MWh 11 MWh Fan Pump Chiller DOAS/CRCP VAV