Investigation of the Potential Use of Blue Light in Forward Scattering Optical Smoke Chambers to Detect all UL217 Fires in the New Standard

Similar documents
UL268 7 th challenge with single infrared smoke detector

Polarized Light Scattering of Smoke Sources and Cooking Aerosols

Optimization of Sensitivity Characteristics of Photoelectric Smoke Detector to Various Smokes

A Method for Fire Detecting by Volume and Surface Area Concentration Based on Dual Wavelengths

Keywords: Fire detection, smoke alarm, nuisance, UL 217, polyurethane foam

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

Impact on Smoke Alarm Performance Considering New Nuisance and Fire Tests

Characterising the smoke produced from modern materials and evaluating smoke detectors

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

Smoke Alarm Research at NIST

BEYOND COOKING: SMOKE ALARM NUISANCE SOURCES EVALUATED. Joshua B. Dinaburg, P.E. Dr. Daniel T. Gottuk, P.E. SUPDET 2016 March 4, 2016

Effect of Contamination on the Sensitivity of Optical Scatter Smoke Sensors

Keywords: VEWFD; Smoke detection; Smoke production; In-situ testing.

MR300 OPTICAL SMOKE DETECTOR RANGE PRODUCT APPLICATION & DESIGN INFORMATION

by Richard W. Bukowski Center for Fire Research Program for Fire Detection and Control Systems National Bureau of Standards Washington,

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME

A Comparison of Carbon Monoxide Gas Sensing to Particle Smoke Detection in Residential Fire Scenarios

A Comparison of Aspirated Smoke Detectors

ISO/TS TECHNICAL SPECIFICATION. Fire detection and alarm systems Part 9: Test fires for fire detectors

LEARNING SPECIAL HAZARD DETECTION TYPES

Using Smoke Obscuration to Warn of Pre-Ignition Conditions of Unattended Cooking Fires

AEROSOL SPECTROMETERS

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

Smoke Alarm Research at NIST

Validation of a Smoke Detection Performance Prediction Methodology. Volume 3. Evaluation of Smoke Detector Performance

Analisi del Focus-shift su sorgenti multikw. Luca Porcelluzzi Ophir Spiricon Europe GmbH

7.1 Smoke Detector Performance

Gas Temperature Measurements with High Temporal Resolution

Understanding total measurement uncertainty in power meters and detectors

Distributed Temperature Sensing

DEVELOPMENT OF THE INFRARED INSTRUMENT FOR GAS DETECTION

CALIBRATION HOW IT WORKS

CCTV, HOW DOES IT WORK?

CALIBRATION HOW IT WORKS

An FT-NIR Primer. NR800-A-006

The Optical Time Domain Reflectometry and the Fusion Splicer Laboratory exercise

PREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR

Smoke Detector Testing

Research into multi-sensor detector capabilities and false alarm reduction

INTERNATIONAL JOURNAL OF RESEARCH GRANTHAALAYAH A knowledge Repository

PLASMA ETCHING TO HELP IDENTIFY ACOUSTIC AGGLOMERATION SOOT PATTERNS ON SMOKE DETECTOR PIEZO DISKS

Development and demonstration of a diode laser sensor for a scramjet combustor

optical detector multisensor detector heat detector mounting bases product guide

FIRE IR SENSOR Flame Detection

The performance of multi-sensors in fire and false alarm tests

OH110, OP110, HI110. Automatic Fire Detectors. Automatic Fire Detector For collective and conventional detector lines

Experimental Study on Response Sensitivity of Smoke Detectors in High Flow Velocity

Smoke Alarms: Comparing the Differences in Response Times and. Nuisance Alarms. Chris Kasperczyk. University of Cincinnati.

Notifier by Honeywell: SMART Detection. SMART Detection. The Ultimate in False Alarm Technology...Make the SMART choice

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Optec NGN-2 LED Ambient Integrating Nephelometer

IQ8Quad. The right sensor for every environment. The detection principles of the IQ8Quad detector. Fire detection technology

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

CALIBRATION HOW IT WORKS

ISO INTERNATIONAL STANDARD. Coating powders Part 13: Particle size analysis by laser diffraction

S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection

The new detector from Rafiki

Product data sheet Palas Fidas 200 S

Determination of Fire Exposure Heat Flux in Cable Fire Tests

Experimental Study on Effects of Non-spherisity of Smoke Particles on the Light Scattering Characteristics

Direct measurement of the aerosol absorption and extinction cross section for a variety of chemical and biological simulants in the LWIR

Research on Evaluation of Fire Detection Algorithms

Wildland fire phenomenology experiments:

Range Dependent Turbulence Characterization by Co-operating Coherent Doppler Lidar with Direct Detection Lidar

Band Selection & Algorithm Development for Remote Sensing of Wildland Fires

Optics & Radiometry Laboratory

Intelligent Signature Series Analog Detection

An experimental study of the impact of tunnel suppression on tunnel ventilation

MINERVA S200Plus. Fire Detection. Triple Waveband Infra-Red Flame Detection. Features: Minerva S200PLUS

In Search of Standard Reference Materials (SRMs) for ASTM E05 Fire Standards by. Norman Alvares & Harry Hasegawa

Dr. Daniel T. Gottuk Joshua B. Dinabug SUPDET 2014

Intelligent. Signature Series Multisensor Detection. An EDWARDS brand.

KEYWORDS: Smart fire detection, fire signatures, nuisance sources, non-fire signatures

Fire Detection System: An Overview

Stand-off Detection of Trace Explosives by Infrared Photothermal Imaging. Trace Contamination

Bright, Chromatic and Distinct - Perception and Detection of LED-based Airfield Lighting

Meeting NFPA standards for

Hygrometry. The art or science of humidity observation

Potential Impact of New UL Fire Test Criteria

Validation of a Smoke Detection Performance Prediction Methodology. Volume 4. Evaluation of FDS Smoke Detection Prediction Methodology

Desigo Fire Safety intelligent detectors for complete safety

FiberSystem. Fiber Optic Linear Heat Detection for Special Hazard Applications

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

ISO INTERNATIONAL STANDARD. Smoke alarms using scattered light, transmitted light or ionization

CHARACTERIZATION OF SMOKE MACHINES IN TESTING AIRCRAFT SMOKE DETECTORS TINA EMAMI. A thesis submitted to the. Graduate School New Brunswick

Abstract. Introduction

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

Meets all design requirements of U.S.EPA. Double pass optical system for accuracy and sensitivity. Modulated light beam to eliminate interference

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

ISO INTERNATIONAL STANDARD

Pyroelectric Infrared Sensor PIR

IRIS IP65 IRIS UNISCAN APPLICATION MANUAL

Towards Predicting High Sensitivity Smoke Detector Operational Performance in Building Environments

APN0064.P65 Issue 01-06/2000 COMPARISON OF OPTICAL DETECTION SYSTEMS FOR INFRARED HYDROCARBON GAS DETECTION

Combinational Smoke Detector

SupDET 2015 Characterization of Dust and Water Steam Aerosols in False Alarm Scenarios

Low-Power Detectors. Key Features. 818 Series. Power levels from pw to 2W. Wavelengths from 190 nm to 1800 nm. Proprietary detector optics

NEBOSH International Technical Certificate in Oil and Gas Operational Safety

Transcription:

Investigation of the Potential Use of Blue Light in Forward Scattering Optical Smoke Chambers to Detect all UL217 Fires in the New Standard David Richardson, Daniel O Shea, Stephen Daniels, Michael Byrne Ei Electronics, Shannon, Ireland Abstract In this study we investigate the response of blue (470 nm) light and infra-red IR (870 nm) in different types of smouldering and flaming fires to investigate their potential to detect all UL217 fires in the new standard. We show that correlation between the European EN smoke tunnel and the American UL smoke box does not exist for both blue and IR optical chambers. In the study we show that blue light responds better in flaming fires than IR light, including the new flaming polyurethane test. We also show that during the nuisance broiling hamburger test, the blue response is possibly larger than that of any of the actual flaming fires. However, though there is potential to pass the new UL217 standard, this is just an initial study and a wide range of comprehensive testing is still required. Keywords: UL217, fire detection, forward scattering, optical chamber, blue light Introduction With the recent adoption of ANSI/UL 217-2015 [1], smoke alarms must undergo a variety of new fire tests in order to pass the standard. Smouldering and flaming polyurethane, along with a nuisance test, broiling hamburgers, will prove the most challenging to pass due to the similarities of the test obscuration and ionisation profiles. Recently, the National Institute of Standards and Technology, conducted a study in which 45 commercially available smoke alarm models from 7 different manufacturers were fire tested to the new standard. This study found that no alarms currently on the market could meet the new standard [2]. Therefore, it is clear that either a major overhaul of current technology, or an introduction of new technology is required to pass the new fire tests. It has been shown that flaming polyurethane fires produce smoke

particles with an average particle diameter of less than 0.05 µm, as compared with 0.1 µm for smouldering ponderosa pine [3]. Theory suggests that smaller incident wavelengths such as blue light instead of current infra-red (IR) light, will have an increased scattering signal for smaller particle sizes [4]. Therefore, optical smoke sensors incorporating blue LEDs with smaller wavelengths may have the potential to better detect the new UL217 flaming polyurethane test fire. The use of blue LEDs to detect smoke is not a new technology and the concept of its use has been described previously [5]. There are a number of smoke detection units currently on market combining blue and IR LEDs. One such company, Nest have published a white paper in which they show that their response time is improved in flaming fires with the use of split-spectrum blue and IR LED sensor [6]. However, as shown in the white paper, eliminating false alarms during the nuisance hamburger test has remained elusive. While previous studies have discussed the response of blue LEDs, the raw data has not been included. In this study, the data from both blue and IR LEDs in a range of test fires will be presented. Using this data the potential for the use of blue LEDs to pass the UL217 standard will be discussed. Experimental A blue LED, λ = 470 nm and an IR LED, λ = 870 nm, were mounted within standard Ei Electronics optical chambers. Both sets of LEDs had the same viewing angle and luminous intensity. Initial testing and calibration was carried out in an AW Technologies 1000 series smoke tunnel, with a Topas Aerosol Generator ATM 225 and a UL smoke box. The smoke tunnel utilises paraffin aerosol, and is used to conform to the European EN standard, while the UL smoke box utilises cotton wick and is used to conform to the North American UL standards. Further testing was carried in a custom built Ei Electronics smoke test box, while official testing was carried out in an EN fire test room in ANPI, Belgium. Theory Light scattering by small sub-micron sized particles is governed by Mie scattering theory. The general solution for Mie scattering is found through the application of Maxwell s equations. However, a simplified approximation of Mie scattering is given in Eq. 1 [7]. =2 sin+ (1 cos) (Eq. 1) Where, = () Q = efficiency factor of scattering a = diameter of the particle n = refractive index of the particle Λ = wavelength of incident light

Taking the refractive index of smoke particles as 1.5 [8], the theoretical scattering Q factor for blue and IR light is shown in Fig. 1. This theory indicates that for particles below 0.1 µm blue light will scatter 3 times more efficiently than IR light, while for particles close to 1 µm both blue and IR light should scatter a similar amount. Utilizing this knowledge, we will investigate if the ratio of blue to IR light scattering can be used to determine the fire type to potentially pass the new UL217 standard. Fig. 1. Theoretical scattering strength of blue light (λ = 470 nm) and IR light (λ = 870 nm) according to the van de Hulst approximation for Mie Scattering [7] taking the refractive index of smoke to be 1.5. Results Initial calibration of the blue and IR optical chambers was carried out in the European EN standard smoke tunnel. This tunnel utilizes atomised aerosol paraffin oil which has an approximate particle diameter of less than 1 µm [9]. The gain factors both blue and red optical chambers were calibrated to give the same output during a test ramp within the EN smoke tunnel as shown in Fig. 2. This is the same test that is carried out during testing for the European EN Standards. Although the blue and IR optical units are calibrated together in the EN smoke tunnel, the results of the UL smoke box with smouldering wick are remarkably different. As shown in Fig. 3 the blue LED response is approximately 5 times larger than the IR LED response. The average particle diameter of smouldering cotton wick is 0.09 µm [3]. Due to the small size of these smoke particles theory states that blue light will scatter more than red light. However, an increase by a factor of 5 is more than expected. There is no simple explanation for this, but factors such as the smoke particle shape, particle colour or clumping of smoke particles is not taken into account in the theory and can affect the scattering intensity.

Fig. 2. Comparison of the signal strength response of blue LED (λ = 470 nm) and IR LED (λ = 870 nm) to aerosol paraffin in the EN smoke tunnell. Fig. 3. Comparison of the signal strength response of blue LED (λ = 470 nm) and IR LED (λ = 870 nm) to smouldering cotton wick in the UL smoke box. These initial results are promising as blue light is scattered more in small particles than IR light. However, it is clear that calibration of the blue and red optical chambers is not comparable between the UL and EN smoke tests. As testing is carried out in actual fires with real smoke, the units were both calibrated to the same sensitivity in the UL 217 box for all further tests in this study. Theoretically flaming fires produce smaller smoke particles than smouldering fires. A simple check of this was carried out in the Ei smoke chamber testing both smouldering and flaming paper fires. The results of the smouldering and flaming fires are shown in Fig. 4 and 5 respectively.

For the smouldering paper the response of the IR and blue LEDs are similar and no clear distinction between their responses can be made. This is expected as the mean particle diameter for smouldering paper is approximately 0.1 µm, similar to that of smouldering cotton wick, with a particle diameter of 0.09 µm [3]. Fig. 4. Comparison of the signal strength response of blue LED (λ = 470 nm) and IR LED (λ = 870 nm) to smouldering paper in a custom built smoke chamber. However, during the flaming paper combustion the blue LED response is up to a factor of 4 times stronger than the IR LED response. The mean particle diameter for flaming paper combustion is 0.04 µm [3], just under half that of smouldering combustion. This decrease in mean particle size results in an increased scattering ratio between IR and blue light. Fig. 5. Comparison of the signal strength response of blue LED (λ = 470 nm) and IR LED (λ = 870 nm) to flaming paper in a custom built smoke chamber.

Similar results were also found for flaming wood with a blue LED response between 2 and 3 times larger than that of the IR LED. Flaming wood has a larger particle diameter than flaming paper, 0.06 µm [3], so the small decrease in the observed response may be attributed to Mie scattering theory, though other effects such as particle shape and colour may also affect the scattering ratio. These results prove that blue light has the potential to distinguish between smouldering and flaming fires. However, it is the response to flaming polyurethane that is of most interest to this study. The response of the blue and IR LEDs to flaming polyurethane in the Ei test box are shown in Fig. 6. The blue signal recorded is approximately twice as strong as the IR signal. Polyurethane foam has a particle diameter of approximately 0.05 µm, so an increased signal from the blue LED is expected. However, the ratio of blue to IR signal is not as strong as that observed for flaming paper and flaming wood. The cause is not clear, but again may be due to particle colour or refractive index which can also influence the scattering intensity. Although this internal testing shows promising results, fire tests in an accredited lab are required to confirm the initial findings. Large scale testing was carried out in ANPI, Belgium which has a fire test room built to the European EN standard. Here a range of fire tests were carried out to investigate the response of blue and IR optical chambers. Fig. 6. Comparison of the signal strength response of blue LED (λ = 470 nm) and IR LED (λ = 870 nm) to flaming polyurethane in a custom built smoke chamber.

The first test carried out was TF2, which is a smouldering wood test. The response of the IR and blue optical units were similar as shown in Fig. 7. The quickness of the blue response can be attributed to the slow air flow and the unpredictability of smoke particle density during TF2. It is highly possible that randomness in the smoke pattern reached the blue chamber before the IR chamber so the authors do not consider this initial blue response a notable finding. Overall, the blue LED has a slightly stronger overall response than the IR LED in this test by up to 50 %. Fig. 7. Comparison of the signal strength response of blue LED (λ = 470 nm) and IR LED (λ = 870 nm) during TF2, smouldering wood in the ANPI fire test room. TF4 is a flaming polyurethane test as part of the EN standard. Although similar, it is not identical to the new UL 217 flaming polyurethane test. The recorded blue and IR LED data for the EN TF4 is shown in Fig. 8. Again, the blue signal is double that of the IR signal. Although this is a promising result, it is not clear that this difference between blue and IR LED response will be enough to pass the UL217 test. The increased signal strength of blue light over IR light is observed for all flaming fires including TF1 (flaming Wood) and TF5 (flaming Heptane). During this study it was found that on many occasions it was possible to differentiate smouldering from flaming fires using the blue LED as a secondary indicator. However, to pass UL217 the units must not alarm during the nuisance test which is proving a challenge for current optical units on the market.

Fig. 8. Comparison of the signal strength response of blue LED (λ = 470 nm) and IR LED (λ = 870 nm) during TF4, flaming polyurethane in the ANPI fire test room. Provisional results for the nuisance broiling hamburger test from internal testing are shown in Fig.9. The response of the blue LED is between 5 and 6 times that of the IR LED. This ratio is larger than that seen previously for any of the flaming fire tests. Therefore, theoretically it may be possible to distinguish between the UL fire tests and the nuisance hamburger tests. However, in a life-saving application, dependence on an increased signal to distinguish a nuisance source is a potentially dangerous situation. While these preliminary results show potential, the authors advise caution and that a comprehensive range of fires must be tested to ensure customer safety. Fig. 9. Comparison of the signal strength response of blue LED (λ = 470 nm) and IR LED (λ = 870 nm) for broiling hamburger test.

Conclusions Although this study is still in its infancy, the results show that there is potential for a combination of blue and IR forward scattering optical chambers to be used to pass the new UL217 test. We have shown that blue light has a larger response to flaming fires than smouldering fires. Therefore, it should be possible to detect all fire tests including flaming polyurethane. The nuisance hamburger test will remain difficult to distinguish. Initial testing has shown that the blue LED response is larger for the nuisance test. Therefore, it may be possible to distinguish the nuisance test from one of the actual fire tests. However, this is a potentially dangerous situation in a real world setting as it could lead to a delayed alarm response in the presence of an actual fire. At the time of publication testing has not been conducted in the UL test lab and this must be completed to confirm the initial findings of this study. Another issue that must be considered is the accuracy of unit calibration and repeatability of smoke chamber. We have found issues with consistent readings in the UL smoke box with variances of up to 30 %. This may prove an issue when attempting to remain within the upper and lower smoke limits of the broiling hamburger and flaming polyurethane tests. References [1] ANSI/UL 217-2015: Standard for Safety Smoke Alarms, Underwriters Laboratories Inc., Northbrook, IL, 2015. [2] T.G. Cleary "A Study on the Performance of Current Smoke Alarms to the New Fire and Nuisance Tests Prescribed in ANSI/UL 217-2015", NIST Technical Note 1947, December 2016. [3] T.Z. Fabian, P.D. Gandhi, "Smoke Characterization Project: Final Report ", Universal Laboratories Inc., Northbrook, IL, April, 2007. [4] A.J. Cox, A.J. DeWeerd, J. Linden "An experiment to measure Mie and Rayleigh total scattering cross sections", American Journal of Physics, 70, 6, 620, June 2002 [5] B.D. Powell, Smoke Detector, Patent No. WO 2003/100397, Issued Dec 2003 [6] Nest Split-Spectrum White Paper, Nest Labs, June 2015 [7] P. Walstra, "Approximation formulae for the light scattering coefficient of dielectric spheres". British Journal of Applied Physics 15, 1545, July 1964 [8] W.D. Conner, J.R. Hodkinson, Optical properties and visual effects of smoke-stack plumes, Environmental Protection Agency, May 1972 [9] TOPAS Atomizer Aerosel Generator ATM225 Datasheet Topas GmbH, Dresden