TRNSYS modeling of a novel ceiling panel designed to maintain space humidity in an office building

Similar documents
SIMULATING A HEAT AND MOISTURE TRANSFER PANEL (HAMP) FOR MAINTAINING SPACE HUMIDITY

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Performance Of The Dehumidification Cycle Of A 3-Fluid Liquid Desiccant Membrane Air-Conditioning System

A study of radiant cooling for a room with daytime application in tropical climate

Comfort and health-indoor air quality

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

K.F. Fong *, C.K. Lee, T.T. Chow

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

New Convection Correlations for Cooled Ceiling Panels in Room with Mixed and Stratified Airflow

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Cooling load calculations of radiant and all-air systems for commercial buildings

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

Potential and Simulation of Open-Cycle Solar-Assisted Climatisation-Plants in Single-Family-Houses

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Recent Advances in Energy, Environment and Economic Development

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Desiccant Cooling with Solar Energy

Don t Turn Active Beams Into Expensive Diffusers

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Human response to thermal environment in rooms with chilled beams

The Use Of Attic Space For Cooling and Dehumidification

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

DESIGN AND SIMULATION OF A SOLAR ASSISTED DESICCANT-BASED AIR HANDLING UNIT

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

EVALUATION OF A LIQUID DESICCANT AIR CONDITIONING SYSTEM WITH SOLAR THERMAL REGENERATION

Achieving Dry Outside Air in an Energy-Efficient Manner

Chilled Ceilings / Beams Working Principles & Applications

Investigation of an evaporative air cooler using solar energy under Algerian climate

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Experimental study of space cooling using ceiling panels equipped with capillary mats

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY

State of the Art of HVAC Technology in Europe and America

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

Performance of an Improved Household Refrigerator/Freezer

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

DEHUMIDIFICATION PERFORMANCE INVESTIGATION OF RUN-AROUND MEMBRANE ENERGY EXCHANGER SYSTEM

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Benefits Offered by Passive Dehumidification Wheel Speed Control

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment. AHRI Guideline T (I-P)

Experimental Performance of Solar Collector cum Regenerator for Coupling with a Liquid Desiccant Cooling System

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

DYNAMIC THERMAL MODELING OF A RADIANT PANELS SYSTEM AND ITS ENVIRONMENT FOR COMMISSIONING: APPLICATION TO CASE STUDY

Heat pump and energy recovery systems

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Thermal Comfort with Convective and Radiant Cooling Systems

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Performance of solar-assisted hybrid air-conditioning liquid desiccant system in Beirut

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

EXPERIMENTAL STUDY OF AIR FLOW RATE EFFECTS ON HUMIDIFICATION PARAMETERS WITH PREHEATING AND DEHUMIDIFICATION PROCESS CHANGING

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

EMBEDDED PIPE SYSTEMS. SURFACE HEATING AND COOLING Heat transfer coefficient COOLING CAPACITY. Max. heating-cooling-capacity

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff

Chilled Ceiling Condensation Control Experience In A Movable Sash Building

Performance evaluation of a liquid desiccant solar air conditioning system

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

Optimization of Moisture condensation rate of Liquid Desiccant Dehumidifier through Genetic Algorithm

Active desiccant integration with packaged rooftop HVAC equipment

INDOOR HUMAN THERMAL COMFORT OPTIMAL CONTROL WITH DESICCANT WHEEL COOLING SYSTEM

EVALUATION OF HEAT REJECTION STRATEGIES FOR LIQUID DESICCANT AIR-CONDITIONING SYSTEMS

Energetic vs. Exergetic Efficiency of Food Drying Via Forced Convection with and without Electrohydrodynamic Enhancement

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Regenerator Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations

Optimisation of cooling coil performance during operation stage for improved humidity control

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

How to ensure Thermal Comfort in buildings with CFD

Residential ventilation concepts based on the idea of displacement airflow distribution

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

LATENT COOLING LEAD. Kecha Thirakomen EEC Engineering Network

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

indirect evaporative cooling: interaction between thermal performance and room moisture balance

Transcription:

TRNSYS modeling of a novel ceiling panel designed to maintain space humidity in an office building Radia Eldeeb 1, Melanie Fauchoux 2, and Carey Simonson 3 1 M.Sc Candidate, Department of Mechanical Engineering, University of Saskatchewan, Saskatoon, Saskatchewan 2 Ph.D. Candidate, Department of Mechanical Engineering, University of Saskatchewan, Saskatoon, Saskatchewan 3 Professor, Department of Mechanical Engineering, University of Saskatchewan, Saskatoon, Saskatchewan Abstract Ceiling cooling panels have one of the highest technical energy savings and they achieve high comfort levels. However, they are unable to maintain the indoor relative humidity as they only transfer sensible heat. In order to overcome this problem, a novel heat and moisture transfer panel (HAMP) is developed and tested. In this paper, the applicability of the HAMP is tested using the TRNSYS simulation program. The impact of the HAMP on space relative humidity is investigated by modeling a 1-storey office building in two Canadian cities (Saskatoon and Toronto) as representatives of the Canadian climatic conditions. The validity of the HAMP and resulting energy savings is represented and compared against a similar building operating with a conventional all air system. The HAMP proved to be able to maintain space relative humidity levels between 22% RH and 55% RH in Saskatoon; and between 23% RH and 57% RH in Toronto. 1. Introduction Radiant ceiling panels are temperature controlled indoor surfaces placed on ceilings, floors or walls. The temperature can be maintained by circulating water, air, or electric current. The panels transfer heat to the space by convection and radiation. Convection heat transfer takes place between the panels and the room air, while radiation heat transfer takes place between the surface of the panels and the room surfaces and objects. The name radiant comes from the fact that 5% or more of the design heat transfer is taking place by thermal radiation. The minimum ventilation required for the space is still provided to meet minimum indoor air quality levels. Many papers in the literature discuss and document the theory and performance of radiant cooling regarding its comfort, efficiency, and cost effectiveness. Kulpmann (1993) studied a space with chilled ceiling panels and found that the system provided good thermal comfort. Simmonds (1997) studied the first cost and long term energy savings of ceiling radiant cooling panels compared to conventional air conditioning systems (or all air systems) and concluded as follows: The first cost is 15% less with experienced contractors. The long term savings due to using smaller chillers and reduced fan power is 2-3%. There are less moving parts showing potential reduced operational and maintenance costs. Simpler and less expensive testing and balancing at commissioning. With proper selection and installation of the ceiling panels, the only problem faced by this system is condensation. To overcome this problem, many researchers introduced the idea of http://esim.ca Page 176 of 614 May 1-4, Halifax Nova Scotia

using radiant ceiling panels integrated with other all air systems. Conroy and Mumma (21) reported the use of radiant ceiling panels to control sensible load only, while a dedicated outdoor air system (DOAS) controlled 1% of the space latent load so that the dew point temperature of the space could be controlled. Sodec (1999); Miriel et al. (22); and Vangtook and Chirarattananon (26, 27) all showed that radiant panels, combined with mechanical ventilation systems, consume less energy than all air systems. Miriel et al. (22) performed computer simulations using experimental results from two winters and one summer in Rennes in western France. The results showed a 1% reduction in energy consumption compared to a conventional all-air system. On the other hand, Sodec (1999) used a numerical simulation to compare an all air system with a radiant ceiling panels system regarding the energy costs, first costs, and the space area requirements. He concluded that the energy savings can be up to 1-2% in cooling, the first costs can be reduced by up to 2%, and the space requirements can be reduced by 4-55%. Busweiler (1993) introduced the first system that used desiccant cooling with a cooled ceiling system. It was also the first such system installed in Germany. Due to limited space in the plenum above the suspended ceilings in a hotel in Bremen, conventional air conditioning systems could not be installed. This led to the use of a cooled ceiling system with ventilation air coming in from outlets near the floor. A desiccant wheel was used to dehumidify a 1% outdoor air stream, and an evaporative cooler was used to humidify it according to the air conditions. The system ran successfully for a year and proved to save energy and reduce the peak electricity consumption. In general, according to Mumma (21) ceiling panels with their different applications are more widely used in Europe than in North America. A novel solution for the condensation problem of this system is using a liquid desiccant. A novel heat and moisture transfer panel (HAMP) is developed, tested and investigated by Fauchoux et al. (29) and Fauchoux et al. (28). Figure 1 shows a sketch of the top and side views of the HAMP as used in testing. An actual HAMP might however look different due to other design considerations. A HAMP is a panel constructed from a porous membrane that uses a salt solution as the transfer media so that it can control both temperature and relative humidity. This will allow the space relative humidity to be controlled together with its temperature. The salt solution is held by retaining walls on the top and sides. (a) (b) Porous membrane Salt solution Air flow Ceiling Solution channels Figure 1: The (a) top view, and (b) side view of the HAMP used in testing http://esim.ca Page 177 of 614 May 1-4, Halifax Nova Scotia

It is important to control moisture in buildings to achieve required comfort levels and avoid condensation problems. Controlling the indoor relative humidity is important for occupant health and productivity. ISO Standard 773 (1994) suggests that the indoor relative humidity be between 3% and 7%. Bornehag et al. (21) and Kosonen and Tan (24) reported that indoor humidity levels outside this range leads to discomfort, lower productivity. Further investigation of the HAMP use in a 1-storey office building using the building simulation program TRNSYS is presented in this paper. The study is done in two Canadian cities, Saskatoon and Toronto, representing the cold dry and humid Canadian climates, respectively. 2. Model description 2.1. TRNSYS According to a study performed by Fauchoux (26) on the different types of building simulation programs commercially available, TRNSYS was found to be the best out of 11 programs that suits the required characteristics for this research. TRNSYS is defined by Klein (2) as a FORTRAN-based transient system simulation program which is designed to solve complex thermal systems by breaking them down into less complicated components. As was shown by Beckman et al. (1994), TRNSYS is characterized by its capability of solving each thermal component independently and then coupling them to solve the main thermal system. Thermal Energy System Specialists, TESS, is one of the major developers of TRNSYS component libraries. TRNSYS 17 and the second version of TESS libraries are used in this study. 2.2. Building Based on research carried out by the Pacific Northwest national Laboratory (PNL), United States office building stock has been classified into 25 buildings categories. Each of these buildings represents a specific percentage of the US office building stock as determined by a Commercial Building Energy Consumption Survey (CBECS) carried out by the Energy Information Administration (1986) of the U.S. department of energy. The building used for this investigation is chosen from a set of 2 buildings describing the existing building stock as of 1979. The 2 buildings are described in details by Briggs et al. (1987). A 1-storey office building with a floor area of 73 m 2 and 3% windows area is selected for this study. The building description from the PNL study is based on the location of the building in El Paso, Texas. ASHRAE standard 9.1 (24) categorizes cities around the world into 8 climatic zones categories starting from the warmest cities in zone 1, and ending at the coldest cities in zone 8. El Paso in Texas is categorized by ASHRAE standard 9.1 (24) as zone 3B. However, the cities presented in this paper are Toronto and Saskatoon which are categorized as zones 6 and 7, respectively. This enforced some modifications on the insulation of the building walls, roof, floor, and fenestration to be done. Table 1 shows a detailed description of the convective heat transfer coefficients; U values. http://esim.ca Page 178 of 614 May 1-4, Halifax Nova Scotia

Table 1: Building modifications U-value (W/m 2 K) Wall Roof Floor Fenestration Original in PNL model 1.25 1.46.279 5.68 Building model.423.254.279 1.73 Maximum allowed, according to ASHRAE 9.1 (24), for zone 7.513.36.496 3.24 Maximum allowed, according to ASHRAE 9.1 (24), for zone 6.592.36.496 3.24 For this building, lighting, occupancy and equipment have maximum intensity of 14.25 W/m 2, 5 Persons/1m 2 and 11.7 W/m 2, respectively. TESS component type 571 is used to calculate the building infiltration rate as a function of the wind speed; indoor and outdoor temperatures; ambient pressure and relative humidity at each time step. The average value for infiltration is.27 ACH. The latent load of this building represents 11.1% and 9.1% of the total load of Saskatoon and Toronto, respectively. Figure 2 shows the hourly schedule of the fractional internal loads and ventilation with respect to the peak values. (a) 1. (b) 1. Fraction of Lighting in-use.75.5.25. 6 12 18 24 Time of day (h) Occupancy ratio.75.5.25. 6 12 18 24 Time of day (h) (c) 1. (d) 1. Fraction of Equipment in-use.75.5.25. 6 12 18 24 Fraction of Ventilation in-use.75.5.25. 6 12 18 24 Time of day (h) Time of day (h) Weekday Saturday Sunday Figure 2: Schedule of (a) lighting, (b) occupancy, (c) equipment, and (d) ventilation in the 1-storey building http://esim.ca Page 179 of 614 May 1-4, Halifax Nova Scotia

2.3. HVAC System TRNSYS 17 allows the user to define an active layer that act as a radiant ceiling panel with a user defined fluid specific heat and panel heat transfer coefficient. The convective heat transfer coefficient is assumed to be contributed only by natural convection. It is calculated in a separate component for every time step depending on the panel temperature and the space air temperature. Equations 1a and 1b were used to calculate the convective heat transfer coefficients for heating and cooling ceiling panels respectively (ASHRAE 28). ( ) (1a) (1b) The radiation heat transfer coefficient is also calculated in a separate component and the total heat transfer coefficient is calculated and given to the building as an input in every time step. The HAMP moisture addition or removal is added or removed as a gain to the space. This gain is calculated using a Matlab code with input information from the building space. The Matlab is integrated into the TRNSYS using Type 155 which calls the Matlab code in every time step. The final equation used to calculate the moisture added or removed is ( ) (2) Table 2 shows the three systems studied. Case A represents a conventional dedicated outdoor air system (DOAS) that removes only space and ventilation sensible loads. Case B studies the effect of using radiant ceiling panels (RCP) in the space instead of DOAS. In addition, the ventilation latent load is removed using DOAS. The area of the radiant ceiling panel used is 6% of the total ceiling area. Finally, case C studies the same system as case B with the same area of radiant ceiling panels with the addition of using the HAMP to remove the space latent load. A controlled energy wheel is used to precondition the ventilation air in cases B and C. Further heating, cooling, humidification, and dehumidification are then done as required using different control signals in these two cases to precondition the ventilation air. 2.4. Ventilation Table 2: Different cases represented Space Ventilation Sensible Latent Sensible Latent Case A DOAS None DOAS None Case B RCP None DOAS DOAS Case C RCP HAMP DOAS DOAS The building is ventilated using a constant flow of 1% outdoor fresh air. The outdoor ventilation rate is.31 m 3 /s and the ventilation schedule is shown in Figure 2 (d) to meet ASHRAE Standard 62.1 (27). The outdoor ventilation rate is determined according to the occupancy, area, and building type. http://esim.ca Page 18 of 614 May 1-4, Halifax Nova Scotia

2.5. HAMP The HAMP used in the office building uses Lithium Chloride (LiCl) as the salt solution. All solution properties used for calculations are based on LiCl properties. The area of the HAMP used is 1% of the total ceiling area. This means that the total area used by RCP and the HAMP is 7% of the total ceiling area. The main purpose of this study is to prove the applicability of the HAMP and its ability to maintain the space relative humidity. Thus, the effect of heat transfer accompanied by the moisture transfer is neglected in this work. However, it is assumed that the heat transferred by the HAMP is included in the total heat transfer of the radiant ceiling panels. In order to decide on the salt solution concentration and temperature used for either humidification or dehumidification, it is important to define the set point humidity ratio for each case and look closely at how the HAMP surface humidity ratio changes with LiCl concentration and temperature. Figure 3 shows this relation at four different salt solution temperatures. It is shown in the Figure that for a constant solution temperature the surface humidity ratio decreases as the salt concentration increases while for a constant concentration the humidity ratio increases as temperature increase. The set point humidity ratio for humidification is at 4.91 g/kg which corresponds to a temperature of 22ºC and relative humidity of 3% RH of the space air. Thus, it is required to keep HAMP surface humidity ratio, W s, above this value to create a mass transfer potential as indicated in equation (2). In order to use a suitable temperature assuming that humidification takes place with heating, a temperature greater than 2ºC is used. The salt solution is thus provided at 22ºC and 34% concentration for humidification which corresponds to W s of 5.55 g/kg. 12 T=16 C T=2 C T=22 C T=25 C 1 Ws (g/kg) 8 6 4 2 1 2 3 4 5 Solution Concentration (%) Figure 3: Relation between the HAMP surface humidity ratio and the salt solution concentration at different solution temperatures for LiCl http://esim.ca Page 181 of 614 May 1-4, Halifax Nova Scotia

On the other hand, the set point humidity ratio for dehumidification is at 9.3 g/kg which corresponds to a temperature of 24ºC and 5% RH of the space air. It is required to keep W s below this value to allow moisture to be transferred to the HAMP which has the lower mass transfer potential. It is assumed that dehumidification takes place with cooling which means that the temperature of the solution should be kept lower than 2ºC. Thus, the salt solution is provided at 16ºC and 24% concentration for dehumidification which corresponds to W s of 6.75 g/kg. 3. Results and discussion 3.1. Space temperature To be able to ensure that the radiant ceiling panel is capable of removing the heating and cooling loads, the temperature inside the zone was monitored and compared to the set point temperature in both cities. The set point temperature is 24ºC for cooling and 22ºC for heating. The set point temperature varies according to the building load. In summer, the set point temperature is higher during the night; however, it does not go higher than 28ºC. In winter, the set point temperature is lower during the night; however, it does not go lower than 15ºC. Figure 4 shows the variation of the space temperature on the winter day with the highest heating load and in the summer day with the highest cooling load for both cities. As shown in the Figure, there is a delay in winter to reach the required set point temperature while there is almost no delay in cooling. This is due to the fact that the convective heat transfer coefficient for ceiling cooling is higher than ceiling heating. However, this problem can be minimized by properly designing the radiant ceiling panels system. It also should be noted that the zone temperature is maintained even overnight and in the morning when the set point temperature is lower in winter or higher in summer. This is caused by the liquid in the radiant ceiling panel. This means that, although the flow of water is stopped and the heating or cooling equipment is turned off, it takes time for the water inside the tubes to reach steady state with the room air. http://esim.ca Page 182 of 614 May 1-4, Halifax Nova Scotia

(a) 3 (b) 3 Temperature (ºC) 25 2 15 1 5 Temperature (ºC) 25 2 15 1 5 4 8 12 16 2 24 Day time (hr) 4 8 12 16 2 24 Day time (hr) (c) Temperature (ºC) 3 25 2 15 1 5 Figure 4: Comparison of zone temperature to set point temperature in Saskatoon on (a) Jan 15, (b) Aug 22, and in Toronto on (c) Jan 14, and (d) Aug 2 3.2. Relative humidity 4 8 12 16 2 24 Day time (hr) Weekday Set point The resulting relative humidity in the building in the three cases stated in Table 2 were analyzed and are represented in Figure 5 for Saskatoon and Figure 6 for Toronto. (d) Temperature (ºC) 3 25 2 15 1 5 4 8 12 16 2 24 Space Saturday Day time (hr) http://esim.ca Page 183 of 614 May 1-4, Halifax Nova Scotia

Frequency 9 8 7 6 5 4 3 2 1 Case A Case B Case C 1 2 3 4 5 6 7 8 9 1 RH (%) Figure 5: Frequency of relative humidity inside the building throughout the year in Saskatoon Saskatoon is characterized by dry weather. Figure 5 shows the ability of the HAMP in case C to humidify the space in comparison with the other cases. The space relative humidity is maintained above 22%. The HAMP was able to dehumidify to lower levels than the other two cases. The space relative humidity is maintained below 55%. In cases A and B the space relative humidity in many hours was below 22% or higher than 55%. As mentioned previously, it is recommended that the space relative humidity stays in the range of 3% t 7%. Case C shows the greatest resemblance to the recommendation. Toronto has a more humid climate than Saskatoon. Again, the HAMP proved to be able to humidify the air in the space and maintain the relative humidity levels above 23% which is slightly higher than Saskatoon due to less dry weather. It was also able to do dehumidification and maintain the space relative humidity below 57%. Frequency 9 8 7 6 5 4 3 2 1 Case A Case B Case C 1 2 3 4 5 6 7 8 9 1 RH (%) Figure 6: Frequency of relative humidity inside the building throughout the year in Toronto http://esim.ca Page 184 of 614 May 1-4, Halifax Nova Scotia

To be able to control the amount of moisture added or removed by the HAMP, equation (2) shows that it is directly proportional to the HAMP area, the mass transfer coefficient, and the humidity ratio potential between the surface of the HAMP and the space. The HAMP area is generally limited to the space area but can have a great effect on moisture transfer. For humidification, the humidity ratio potential can be much higher than the potential for dehumidification; W s can be as high as 5 g/kg while for dehumidification; it is restricted to as low as.1g/kg. Thus, the humidity ratio potential is limited in the case of dehumidification. The last parameter we can vary is the mass transfer coefficient which was calculated according to the heat-mass transfer analogy. This means that it depends on the value of the heat transfer coefficient which was calculated based on natural convection. Thus, the moisture transfer by the HAMP can also be enhanced if used with mixed or forced convection rather than natural convection. Some research was done to investigate the effect of mixed convection on the performance and first cost of radiant ceiling panels. Awbi and Hatton (2) studied mixed convection from a room heated ceiling. Novoselac et al. (26) developed new correlations for cooled ceiling panels in a room with mixed and stratified flow. 3.3. Energy Figure 7 shows the heating, cooling, and total space thermal load in the three cases in both cities. In Saskatoon case B saves 35% total energy compared to case A. This shows that radiant ceiling panels consume less energy than conventional DOAS system which was shown in previous research and was expected. In this stage of testing the HAMP, it is challenging to decide on how the salt solution will be practically regenerated. More research is needed to estimate the amount of energy that will be needed for regenerating the HAMP salt solution, thus the regeneration energy is not included in Figure 7. However, the latent load added or removed by the HAMP is added to the space loads for case C and represented in Figure 7. In Toronto case B saves 37% total energy compared to case A. The humidification load that was added by the HAMP into the space is 9.5 MWhr in Saskatoon and 1.6 MWhr in Toronto, while the dehumidification load that was removed by the HAMP is 5.6 MWhr in Saskatoon and 3.4 MWhr in Toronto. The latent load is 12% of the total load in Saskatoon and 13% in Toronto. Energy (MWhr) 14 12 1 8 6 4 Dehumidification Cooling Humidification Heating Total latent Total sensible 2 A B C A B C Saskatoon Toronto Figure 7: Energy consumption in Saskatoon and Toronto in the three cases http://esim.ca Page 185 of 614 May 1-4, Halifax Nova Scotia

4. Conclusion The applicability of the HAMP was tested in a typical 1-storey office building in Saskatoon and Toronto. Three cases were tested using conventional DOAS system, radiant ceiling panels with mechanical ventilation, and adding the HAMP to the latter. The HAMP proved to be able to humidify the space to acceptable relative humidity levels; above 22% in Saskatoon and 23% in Toronto. This directly affects the comfort level of the occupants as low humidity levels cause itchy skin, dryness, and lower concentration and productivity. On the other hand, the HAMP also proved to provide the adequate moisture transfer for dehumidification. The HAMP was able to maintain space relative humidity levels below 55% for Saskatoon and 57% for Toronto. Further sensitivity studies need to be done to test the effect of mixed or forced convection heat transfer coefficients correlations on the performance of the HAMP. The use of radiant ceiling panels showed more favourable energy consumption than conventional DOAS system. The energy saving is 35% in Saskatoon and 37% in Toronto. More research needs to be done to be able to estimate the energy required to regenerate the salt solution in the HAMP. The total latent load removed or added by the HAMP from or to the space is 12% of the total load in Saskatoon and 13% in Toronto. The energy consumption of using the HAMP should be compared to mechanical systems that use energy to remove the same latent load. 5. Acknowledgements This work is funded by NSERC and their support is hereby greatly acknowledged. 6. Nomenclature 7. References Density of dry air, kg/m 3 Area of HAMP, m 2 Moisture added or removed from space air, kg/s Convective heat transfer coefficient of air, W/m 2 K Mass transfer coefficient, m/s Temperature, ºC Space air temperature, ºC Radiant ceiling panel surface temperature, ºC Heat transfer coefficient, W/m 2 K Space air humidity ratio, kg/kg HAMP surface humidity ratio, kg/kg ASHRAE, 28. ASHRAE Handbook HVAC Systems and Equipment, SI ed., Atlanta, Georgia, USA: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Chapter 6. ASHRAE Standard 9.1, 24. Energy Standard for building except low-rise residential buildings, SI ed., Atlanta, Georgia, USA: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. http://esim.ca Page 186 of 614 May 1-4, Halifax Nova Scotia

ASHRAE Standard 62.1, 27. Ventilation for Acceptable Indoor Air Quality (IAQ), Atlanta, Georgia, USA: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Awbi, H.B., & Hatton, A., 2. Mixed convection from heated surfaces, Energy and Buildings, 32, 153-166 Beckman, W.A., Broman, L., Fiksel, A., Klein, S.A., Lindberg, E., Schuler, M., & Thornton, J., 1994. TRNSYS, the most complete solar energy system modeling and simulation software, Renewable Energy, 5, 486 488. Bornehag, C.G., Blomquist, G., Gyntelberg, F., Jarvholm, B., Malmberg, P., Nordvall, L., Nielsen, A., Pershagen, G., & Sundell, J., 21. Dampness in Buildings and Health - Nordic Interdisciplinary Review of the Scientific Evidence on Associations between Exposure to Dampness in Buildings and Health Effects, Indoor Air, 11, 72-86. Briggs, R., Crawley, D., & Belzer, D., 1987. Analysis and categorization of the office building stock. Pacific Northwest Laboratory, for Gas Research Institute. Busweiler, U., 1993. Air conditioning with a combination of radiant cooling, displacement ventilation, and desiccant cooling, ASHRAE Transactions, 99(2), 53-51 Conroy, C.L., & Mumma, S.A., 21. Ceiling Radiant Cooling Panels as a viable Distributed Parallel Sensible Cooling Technology integrated with Dedicated Outdoor Air Systems, ASHRAE Transactions, 17(1), 578-585. Energy Information Administration. Nonresidential Building Energy Consumption Survey, Energy Information Administration, USA: U.S. Department of Energy, 1986. Fauchoux, M.T., Simonson, C.J., & Torvi, D.A., 29. Tests of a Novel Ceiling Panel for Maintaining Space Relative Humidity by Moisture Transfer from an Aqueous Salt Solution, Journal of ASTM International, 6(4). Fauchoux, M.T., Simonson, C.J., & Torvi, D.A., 28. Investigation of a novel ceiling panel for heat and moisture control in buildings, in: C. Rode (Ed.), Proceedings of the 8th Symposium on Building Physics in the Nordic Countries, Danish Society of Engineers, Copenhagen, Denmark, 1269 1276. Fauchoux, M.S., 26. Review of energy building simulation tools that include moisture storage in buildings materials and HVAC systems, M.Sc. thesis, University of Saskatchewan. ISO Standard 773, 1994. Moderate thermal environments determination of the PMV and PPD indices and specification of the conditions for thermal comfort, Geneva, Switzerland: International Standards Organization,. Klein, S.A., 2. TRNSYS A Transient System Simulation Program, Engineering Experiment Station Report 38-13, Madison, USA: Solar Energy Laboratory, University of Wisconsin. Kosonen, R., & Tan, F., 24. Assessment of productivity loss in air-conditioned buildings using PMV index, Energy and Buildings, 36, 987-993. Kulpmann, R.W., 1993. Thermal Comfort and air quality in rooms with cooled ceilings- Results of scientific investigations, ASHRAE Transactions, 99(2), 488-52. Miriel, J., Serres, L., & Trombe, S., 22. Radiant ceiling panel heating-cooling systems: experimental and simulated study of the performances, thermal comfort and energy consumptions, Applied Thermal Engineering, 22, 1861-1873. http://esim.ca Page 187 of 614 May 1-4, Halifax Nova Scotia

Mumma, S.A., 21. Ceiling Panel Cooling Systems, ASHRAE Journal, 43(11), 28-32. Novoselac, A., Burley, B.J., & Srebric, J., 26. New convection correlationsfor cooled ceiling panels in room with mixed and stratified airflow, HVAC&R Reseach, 12(2), 279-294 Simmonds, P., 1997. Radiant systems offer users greater comfort control, Energy users news, 3, 34-35. Sodec, F., 1999. Economic viability of cooling ceiling systems, Energy and Buildings, 3, 195-21. Vangtook, P., & Chirarattananon, S., 27. Application of radiant cooling as a passive cooling option in hot humid climate, Building and Environment, 42, 543-556. Vangtook, P., & Chirarattananon, S., 26. An experimental investigation of application of radiant cooling in hot humid climate, Energy and Buildings, 38, 273-285 http://esim.ca Page 188 of 614 May 1-4, Halifax Nova Scotia