RULES 1978 UNDERGROUND COAL MINES FIRE PRECAUTIONS

Similar documents
1. A fire certificate is issued under Section 76 of the Occupational, Safety and Health ActNo. 28 of 2005.


ENGINEERING STANDARD FOR FIRE STATIONS ORIGINAL EDITION NOV. 1993

ENGINEERING STANDARDA FOR FIRE FIGHTING HOSE BOX AND SHELTER FIRST EDITION APRIL 2015

ENGINEERING STANDARDA FOR FIRE FIGHTING HOSE BOX AND / OR SHELTER ORIGINAL EDITION NOV. 1993

TABLE OF CONTENTS Part 6 Legal Basis for Fire Safety Planning... 2

THE MAURITIUS FIRE AND RESCUE SERVICE ACT. Regulations made by the Minister under sections 18, 19 and 27 of the Mauritius Fire and Rescue Service Act

Guidance Document on Caravan and Camping Sites Fire Safety Equipment Requirements

NITOL INSURANCE COMPANY LIMITED

DISASTER MANAGEMENT PLAN 3.0 IDENTIFICATION OF MAJOR HAZARD POTENTIAL

THE FACTORIES A D OTHER PLACES OF WORK ACT (Cap 514)

TRIMAX ASIA ENGINEERING & CONSTRUCTION (PG U )

HOW TO GET YOUR SCHEME APPROVED

City of Chilliwack. Bylaw No A bylaw to regulate fire prevention and the protection of life and property

Following are the systems proposed as per NBC & Local Fire Authority:

MACKANTRA ENGINEERING PROJECTS cc

Technical write-up on Fire safety services

FIRE & EVACUATION PLAN PARADISE LOST

Subchapter 7. General Industry Safety Orders Group 27. Fire Protection Article 157. Portable Fire Extinguishers. Return to index New query

BERMUDA FIRE SAFETY ACT : 33

FIRE EMERGENCY ACTION PLAN (EAP)

Hiren Industrial Corporation

Australian/New Zealand Standard

The following checklists are to be used during an aerodrome RFFS inspection/ audit.

5.07 Air Replenishment Systems

RAMBLER PARK FIRE SAFETY INFORMATION

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e

District of Sicamous. Fire Department Bylaw No. 126, Effective Date February 26, 1996

AS/NZS :2008

DMP & RISK MANAGEMENT PLAN

Australian Standard. Fire hydrant installations. Part 1: System design, installation and commissioning AS

CORPORATION OF THE CITY OF KINGSTON. Ontario. By-Law Number A By-Law To Impose Fees For Automatic Alarms (False) False Alarm By-law

FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES

PASCOE S PTY LTD EMERGENCY RESPONSE MANUAL. (Public Version) SOP 517. July 2015

GUIDELINES FOR EMERGENCY PLANNING AND PREPAREDNESS. High-Hazard

BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT

GUIDELINES FOR THE APPROVAL OF HELICOPTER FACILITY FOAM FIRE-FIGHTING APPLIANCES

Fire Safety Protocol

AS Australian Standard. Portable fire extinguishers Guide to servicing. This is a free 7 page sample. Access the full version online.

Noise Control Amendment Regulation 1997

Australian Standard. Fire protection for mobile and transportable equipment AS AS

Fire Safety Plan Information. For Construction and Demolition Sites

TEN STEP PROCESS PREPARING FIRE SAFETY PLANS

GUILFORD COUNTY SCHOOLS

FIRE AND EVACUATION PLAN

City of Chilliwack. Bylaw No A bylaw to regulate fire prevention and the protection of life and property

Fire Safety Plan FOR. Business/Property Name: Address: Phone Number: Occupancy Classification. Approved by Fire Inspector: Date:

FACTORIES ORDINANCE (CAP.

THE FIRE SAFETY GUIDE FOR BUSINESS OWNERS

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring.

This place covers: Devices, apparatus and methods to prevent fires from happening, and to fight or contain active fires.

Fire Safety Policy. Billy Hanafin H & S and Operations Officer. Fife Cultural Trust. Version 1.0 October 2013 Page 1

Contractor Worksheet Underground Fires Major Hazard Standard

Workplace Guidelines

CHAPTER 05 - OFFICE OF STATE FIRE MARSHAL SUBCHAPTER 05A - FIRE AND RESCUE SECTION.0900 PUBLIC PROTECTION CLASSIFICATIONS FOR FIRE DISTRICTS

WATERFRONT FACILITY COMPLIANCE BOOKLET

1. These Regulations may be cited as the City of Corner Brook Fire Prevention Regulations.

Building Fire Safety Regulation 2008

Enclosure 4- RISK ASSESSMENT

EMERGENCY EVACUATION PLAN for FIRE

UNCONTROLLED IF PRINTED. Issued with the authority of the Chief Commissioner and General Manager of Scouts Australia NSW

INCIPIENT FIRE BRIGADE MEMBER MANIPULATIVE SKILL OBJECTIVES GENERAL

- CONSTRUCTION FIRE SAFETY STANDARDS

WILTSHIRE POLICE FORCE PROCEDURE. Fire Safety Management

Fire Risk Assessment. A safety guide for users of the hall

A FIRE SAFETY GUIDE FOR CARAVAN SITE OPERATORS. Information on Complying with Fire Safety Law in Northern Ireland

Fire alarm provisions for alerting the Fire Service

FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: DSFRS Log book Version 1.0 (October 2007)

PREMISES FIRE SAFETY LOGBOOK

THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY

Firefighting Monitors Tunnels Fire Protection Systems. Integrated Fire Safety and Security Solutions

Evacuation Fire Safety Program

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service

I. It shall be the responsibility of the department officers to implement this operating guideline.

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points.

Iranian Classification Society Convention and Legislation Department Code: Tech Contents

PASCOE S PTY LTD. EMERGENCY RESPONSE MANUAL & P.I.R.M.P (Public) SOP 529 (Public) Site Address:

Fire Policy and Procedures. Cañada Blanch Spanish School

Vancouver Airport Fuel Delivery Project. Fire Prevention, Preparedness and Emergency Response

ICC CODE CORNER 2015 International Fire Code

Notice on the implementation of the amendments to the FSS Code in resolution MSC.339(91)

Fire Evacuation Plan

Marquee Fire Evacuation Staff Training Marquee / Building Owner: Landlord Marquee Hire Ltd Function / Event: Date(s): 3 7 February 2017

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT

Safety Manual: Emergency Response

FORM MUST BE SIGNED AND RETURNED FOR VENDOR PARTICIPATION

IMO INTERPRETATIONS OF FIRE PROTECTION-RELATED PROVISIONS OF THE HSC CODE

AMENDMENTS NO. 3/2012 to

FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY

FIRE SAFETY POLICY Revised March 2013

Hot Work Permit. Can this job be avoided? Is there a safer alternative? Permit No.:

WORKPLACE AND SAFETY SIGNS

Nature Conservation (Protected Plants Harvest Period) Notice 2008

School of Fire & Safety, GSFC University

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard

FIREFIGHTER II: FIRE DEPARTMENT COMMUNICATIONS COMMUNICATIONS: SKILL SHEET #2 Define and Demonstrate Fire Department Radio Procedure

H&S Forum. Fire Safety Policy Glascote Academy

Fight or Flee? Extinguisher Basics Extinguisher Use Extinguisher Placement and Spacing Hydrostatic Testing OSHA Requirements Test Your Knowledge

The Corporation of the District of North Cowichan Fire Protection Bylaw Bylaw 3340

Fire Safety Plan (FSP) Review Checklist 1

Transcription:

rr. 1-3 163 UNDERGROUND COAL MINES FIRE PRECAUTIONS [Published Gazette 14 October 1978, pp. 499-504; and as amended by Rules published Gazette 26 January 1980, pp. 199-200; 30 May 1981, p. 1077; 3 December 1983, pp. 1470-72]. Department of Mines, Brisbane, 12 October, 1978. HIS Excellency the Governor, acting by and with the advice of the Executive Council, having, in pursuance of Section 111 of the Coal Mining Act 1925-1976, made amendments to Rules under the Act by- (i) repealing Rules 25 to 32 both inclusive of the Belt Conveyor Rules of 1964 and the headnotes "Fire Extinguishing Equipment", "Water Supply", and "Fire Extinguishers" relating thereto; and (ii) making additional Rules as set out hereunder, such amendments are published for general information. R. E. CAMM, Minister for Mines, Energy and Police. UNDERGROUND COAL MINES FIRE PRECAUTIONS RULES 1978 1. These Rules may be cited as the Underground Coal Mines Fire Precautions Rules 1978 and shall have application in respect of all underground coal mines. 2. It shall be the duty of a manager of an underground coal mine to ensure that compliance is made with the requirements of these Rules. 3. (1) A building or structure at the top of any shaft or outlet shall not be made of or comprise any flammable material likely to cause danger from fire to any person employed at the mine. (2) An engine room switch room, electric substation or motor room located in an underground coal mine shall not be made of or comprise any flammable material likely to cause danger from fire to any person employed in the mine. (3) There shall be provided at an underground coal mine suitable and sufficient means of extinguishing fires at each of the following places, that is to say: - (a) in every engine room or motor room; (b) at any place at which flammable material is permanently stored. (4) Except as hereinafter provided in these Rules- (a) an underground coal mine shall have a reticulated water supply system attached to a permanent source of supply capable of maintaining a delivery of not less than 35 litres of water per second to the colliery system; 11111111111111

164 r. 3 UNDERGROUND COAL MINES FIRE PRECAUTIONS Provided that when no such permanent source of supply is available or when the permanent source of supply is unable to supply 35 litres of water per second, a reservoir or tank or tanks with a capacity of not less than 200 000 litres shall be provided and maintained with that amount of water on the surface; (b) water for fire fighting shall be reticulated through the working parts of the mine and carried up to a point not more than 200 metres from the working faces in pipes of such a diameter as will ensure that a minimum quantity of 5 litres per second at a minimum pressure of 480 kilopascals is available at all times throughout the system without need to manually start pumps or open valves other than the control hydrant; (c) reducing valves or some other method of controlling the water pressure shall be introduced into the reticulation so that at no point in the system shall the flow pressure exceed 1 750 kilopascals; (d) all reticulation systems shall be sectionalised and each section shall be capable of having pipes inserted or removed without the need to cut off the water supply to the entire system; (e) test points shall be placed along the reticulation system commencing from the surface of the mine or the shaft bottom as the case may be and thereafter at intervals of approximately 30 metres of vertical depth. Each test point shall be provided with a means for using a pressure gauge and a flow test meter; (f) a person or persons shall check the water pressure in each working panel prior to the beginning of each mineral producing shift; (g) at the bottom of the shaft or the belt conveyor drift an automatic alarm shall be installed and such alarm shall give visible and audible warning in the event of the water pressure falling below the pressure required by these Rules; (h) standard wheel valve hydrants with waterways at least 60 millimetres in diameter and threads of the pattern used by Fire Brigades provided and maintained under the Fire Brigades Act 1964-1977 or other approved fitting shall be fitted at intervals of not more than 100 metres for fire fighting purposes; (i) for fire fighting and other purposes 25 millimetre outlet valves with appropriate fittings permanently attached for use with 20 millimetre or 25 millimetre internal diameter hose shall be provided at intervals of not more than 30 metres on the reticulation system in belt conveyor roadways;

UNDERGROUND COAL MINES FIRE PRECAUTIONS r.3 165 (j) a standard wheel valve hydrant (as described in paragraph (1i) of this Rule) shall be placed in the reticulation main at a point approximately 25 metres on the intake side of all belt conveyor drive heads, loading points, transfer, switchrooms, electric substations, oil depots and filling stations, and at the end of all mains in the reticulation system so that at any time it is possible to direct water on to any part of the working faces or to any part of the mine where the risk of fire is high. (5) Sufficient equipment for fire fighting purposes shall at all times be readily available in an underground coal mine and without prejudice to the generality of the foregoing such equipment shall include- (a) approved fire fighting hoses with an internal diameter not less than 35 millimetres and designed to withstand a pressure when new of 3 000 kilopascals. Such hose shall be- (i) in minimum lengths of 30 metres when new; (ii) fitted with suitable type male and female couplings; (iii) capable of withstanding rough usage; (iv) unaffected by mildew and treated to protect against rot; (v) stored in containers provided for the purpose. (b) other approved hoses, which, shall be- (i) of internal diameter not less than 20 millimetres; (ii) of smooth bore reinforced moulded rubber or other suitable materials; (iii) in minimum lengths of 30 metres when new; (iv) fitted with suitable type male and female couplings. (6) (a) (i) Portable fire extinguishers shall be provided on the intake side of and near to all the locations mentioned in sub-rule (3) of Rule 3 and paragraph (j) of sub-rule (4) of Rule 3 of these Rules. (ii) In the case of switch rooms, electric sub stations, oil depots and filling stations there shall be provided, in addition to the fire extinguishers required by paragraph (1) hereof not less than two water proof containers, each of at least 25 kg. capacity, of ground limestone. (b) Fire extinguishers installed and used in pursuance of these Rules shall be of a type constructed in accordance with Australian Standards 1840 to 1848-"Portable Fire Extinguishers" and shall- (i) be maintained in accordance with Australian Standard- 1851, "Installation and Maintenance of Portable Fire Extinguishers and Fire Hose Reels" and be ready for immediate use; (ii) in the case of fire extinguishers carried for use in locomotives, shuttle cars or other mobile machines have a minimum rating of 20B:C or a minimum capacity of 4 kilograms; and (iii) in any other case have a minimum rating of 60B:C or a minimum capacity of 12 kilograms.

166 r. 3 UNDERGROUND COAL MINES FIRE PRECAUTIONS (c) Where in this sub-rule reference is made to rating of fire extinguishers it shall be taken as meaning a rating established in accordance with Australian Standard 1850-"Classification, Fire Testing and Rating of Portable Fire Extinguishers". (7) (1) Depots for fire fighting purposes shall be set up in an underground coal mine at intervals of not more than 400 metres on roadways where belt conveyors are installed and also at a point approximately 25 metres on the intake side of the locations mentioned in sub-rule (3) of Rule 3 and paragraph (j) of sub-rule (4) of Rule 3 of these Rules. (2) At such depots the following equipment shall be provided:= (a) at least 100 metres of fire fighting hose with appropriate couplings; provided that at face depots sufficient hose capable of at all times reaching the working face shall 'be provided and, except in the case where the couplings are 'snap on' couplings, two hose coupling spanners; (b) at least one 1 into 2 breeching piece fitted with a manually operated cut-off valve; (c) at least two branch pipes and nozzles with a 12 millimetre diameter outlet; (d) at least one diffuser or fog nozzle; (e) at least one adapter suitable for.use with the hoses provided under these Rules; (f) at least two 9 kilogram fire extinguishers. (8) A properly constructed fire station shall be set up at an underground coal mine in close proximity to the shaft or tunnel entrance. Such fire station shall contain at least- (a) 300 metres of 35 millimetre minimum diameter fire hose fitted with suitable male and female couplings and, except in the case where the couplings are 'snap on' couplings, two hose coupling spanners; (b) twelve lengths, each of 30 metres of 12 or 20 millimetre high pressure hose fitted with the necessary appropriate couplings and suitable nozzles; (c) three breeching pieces fitted with manually operated cut-off valves; (d) two 12 millimetre and two 15 millimetre diameter nozzles; (e) four 9 kilogram fire extinguishers; (f) two complete sets of tools each consisting of at least a shovel, an axe, a saw, a pick and a hammer; (g) sufficient spare fittings and pipe tools to be used in the case of an emergency; (h) a copy of the fire fighting plan as required by these Rules; (i) 100 litres of approved foam making compound.

UNDERGROUND COAL MINES FIRE PRECAUTIONS r.3 167 (9) (1) A properly constructed fire substation shall be set up in an underground coal mine in close proximity to the entrance to every zoned area in the mine. Such fire substation shall contain at least- (a) 150 metres of fire hose fitted with suitable male and female couplings and, except in the case where the couplings are `snap on' couplings, two hose coupling spanners; (b) two breeching pieces with manually operated cut-off valves; (c) three branch pipes; (d) two 12 millimetre diameter nozzles; (e) two fog or diffuser nozzles; (f) two 30 metre lengths of 12 millimetre or 20 millimetre high pressure hose fitted with suitable couplings and spray jet nozzles; (g) spare fittings and pipe tools; (h) 65 litres of approved foam making compound; (i) an approved type of foam making branch applicator; (j) two 9 kilogram fire extinguishers; (k) a copy of the working plan of the zoned area. (2) In any underground coal mine where the working faces are more than 3 kilometres from the surface, foam making generators and additional foam making compound shall be kept at fire substations if the Chief Inspector by notice to the manager so requires. (10) Fire fighting brigades shall be formed at an underground coal mine and the members of such brigades shall undergo a form of fire fighting instruction and training based on methods used by Fire Brigades provided and maintained under the Fire Brigades Act 1964-1977, and shall be instructed in the use of mine plans and become familiar with the workings of the mine. After instruction and training has been completed the members of such brigades shall at least once in every two months carry out practices to ensure their efficiency in fire 'fighting operations. The training, instructing and practising shall be carried out to the satisfaction of the district inspector. (11) (1) An emergency telephone shall be incorporated with the telephone system of an underground coal mine so that in an emergency immediate telephonic communication is available from any telephone underground to some point at the surface of the mine which is manned whilst men are underground. (2) An emergency telephone and 300 metres of telephone cable with suitable attachments for connection to the telephone system of an underground coal mine shall be kept at the surface of the mine ready for instant use. (12) A plan shall be kept at an underground coal mine showing the position in which are placed- - (a) pipe mains, hydrants, valves, fire depots and fire substations; and

168 r. 3 UNDERGROUND COAL MINES FIRE PRECAUTIONS (b) stoppings, over casts, ventilation doors, regulators, belt conveyors, electric cables and apparatus and telephones. The plan shall also show the direction of ventilation in the roadways and shall indicate the extent of the zoned areas (if any). (13) (1) Rules shall be made in respect of an underground coal mine to cover the evacuation of any or all the employees from underground in the event of an emergency. All employees shall be made familiar with these Rules. (2) A copy of such Rules shall be- (a) posted in suitable places at the mine; and (b) forwarded to the inspector for the district and to the superintendent of the rescue station for the Mines Rescue District in which the mine is situated. (3) A glossary of fire fighting terms as used by Fire Brigades provided and maintained under the Fire Brigades Act 1964-1977 shall be posted in suitable places at an underground coal mine. (4) The location of all underground fire depots, fire sub stations, fire extinguishers (which are separate from the foregoing) and hydrants installed to satisfy Rule 3 (4) (h) hereof, shall be indicative by reflective signs so fixed that they can be easily seen by persons travelling towards them. (14) Clear instructions to employees as to their procedure on discovering a fire at an underground coal mine shall be posted in suitable places thereat. (15) (1) An underground coal mine, for the purpose of fire fighting organisation, shall be divided into zones to the satisfaction of the district inspector. (2) Provisions shall be made for the isolation of each zone in the case of emergency if the Chief Inspector so requires by notice given to the manager. (16) (1) At an underground coal mine a person designated as a fire officer, who has undergone the course of instruction required under Rule 10 of these Rules shall be appointed in writing by the manager and such person shall be responsible for the training of fire fighting brigades. (2) The fire officer or such other persons authorised by the manager shall be responsible for the maintenance of all fire fighting equipment and shall, at least once in every month, inspect all fire fighting, equipment and record its condition in a book to be kept at the mine for the purpose. (17) The Chief Inspector may direct that any Rule or part thereof of these Rules be varied or otherwise modified in respect of the working of a particular underground coal mine. As amended by Rules pubd. Gaz. 26 January 1980, pp. 199-200; 30 May 1981, p. 1077; 3 December 1983, pp. 1470-72;