Research to Assist in the Development of Safety Standards and Building Codes for the Use of Flammable Refrigerants

Similar documents
Update on Codes and Standards Research. Karim Amrane, Ph.D. Senior Vice President

Research for the Development of Safety Standards

AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP)

Update on ASHRAE 15 Safety Standard for Refrigeration Systems Karim Amrane Air Conditioning, Heating & Refrigeration Institute (AHRI)

GWP Alternative Refrigerants

Effectively Managing the Transition to Lower GWP Refrigerants

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

March 2014 AHRI Presents Research Findings at Low-GWP AREP Conference

AIRAH Victoria Refrigerants Update

2017 Climate & Refrigerants Outlook. Stephen Yurek President & CEO

Effectively Managing the Transition to Lower GWP Refrigerants

A2L Refrigerants Leaks and Ignitions Testing under Whole Room Scale

SEMINAR 48 (ADVANCED) International Codes and Standards Issues Impacting use of A2L Refrigerants in Unitary Heat Pump and Air-Conditioning Equipment

ASHRAE Standard 15: Proposed Changes to Incorporate 2L Refrigerants

New Refrigerants Designation and Safety Classifications

Flammability and New Refrigerant Options

FLAMMABLE REFRIGERANTS UPDATE FOR HVAC&R EQUIPMENT IN NORTH AMERICA

Safety research of A2L/A3 refrigerants and risk assessment in Japan. Eiji Hihara The University of Tokyo

New Case studies on Low GWP alternative refrigerants for HFCs. ABHIJEET KUDVA

Industry co-operation on Natural Refrigerant technology development Kenji Matsuda

Safety concerns for A2L refrigerants in AC service procedures

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

TEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

Flammability and the Low GWP Refrigerant Challenge

Possibilities of the RAC sector transformation a technical perspective

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

see notes on refrigerant type Refrigerant Type ASHR AE Refrigerant Composition (Mass % ) Zeotropes

ASHRAE WILL GIVE YOU THE WORLD

A Primer on HFOs. Hydrofluoro-olefins Low-GWP Refrigerants. Brett Van Horn, PhD Arkema Inc.

Seminar 34 Refrigerants Today, Tomorrow, and Beyond

The Current Path of Refrigerants

Japanese market and issue of Heat Pump Kenji Matsuda

Hot Surface Ignition Testing of Low GWP 2L Refrigerants ABSTRACT

Making Sense of the Latest Rulemaking on Acceptable Refrigerants. E360 Webinar

A2L Refrigerants. Objectives 14/09/2017

DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION

Transitioning to Alternatives and Challenges in Japan

Contents TERI. Part I Background. Part II Introduction of Research on Flammability of Lower GWP Refrigerantds by TERI.

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

Challenges and responses in refrigerant conversion

Solstice 452A (R-452A) Reduced GWP and Discharge Temperature for Transport Refrigeration, Plug-Ins and Condensing Units

Understanding Applications for Alternative Refrigerants

UL's Effort to Harmonize Product Safety Requirements for A2L, A2, and A3 Refrigerants. San Antonio, Texas 2012 Annual Conference

January 16 th, 2014 New York City

Understanding Applications for Alternative Refrigerants

Hot Surface Ignition Testing of Low GWP 2L Refrigerants

Overview of refrigerant alternatives in the air conditioning sector *

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

New Refrigerants & Selecting Capital Equipment

Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies

R-407A R-448A R-449A

Grow your business: Get ready for flammable refrigerants!

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

Low GWP Refrigerants for Air Conditioning and Chiller Applications

Standards and Regulations Update for Flammable Refrigerants

Gary Parker Refrigerants Product Manager

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

Safety standard developments within ASHRAE 15 and ISO UNEP workshop on safety standards, Bangkok

Stay in business: STOP installing R-404A / R-507A! R-404A R-507A

PREPARE FOR CHANGE LOW GWP ALTERNATIVES. November 17

Embraco Position Paper: Light Commercial Refrigeration

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

R-404A Alternative with Low Compressor Discharge Temperature

SOLSTICE L40X (R-455A)

Compressor Explosion Accident at Pump-Down of Air Conditioners

Overview of Alternatives and Climate Impact Scenarios Report of Decision XXV/5 Montreal Protocol

DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER

Study of R161 Refrigerant for Residential Airconditioning

HFO-1234yf Performance in a Beverage Cooler

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration

Standards to facilitate the HCFC phase-out

Overview of New Refrigerants and Expected Market Trends

Description of the European standard EN 378: Refrigerating systems and heat pumps Safety and environmental requirements

Development of centrifugal chiller and heat pump using low GWP refrigerant

Sustainable Refrigerant Solutions for HVAC-R. Laurent Abbas, Wissam Rached, Brett Van Horn

DOE and EPA Impacts to Commercial Refrigeration

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

FACT SHEET 9 Large Air-Conditioning (air-to-air)

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

Refrigerant & Energy Regulations Update

Gary Parker Refrigerants Product Manager

Framtidens köldmedier

Oct. Newly Developed Refrigerants for Refrigeration, meeting Global Warming Regulations. Hitomi ARIMOTO / Product R&D Department, Chemicals Division

Refrigerant and Energy Regulations Update

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

Risk Assessment of Mildly Flammable Refrigerants

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

New F-Gas Regulation (2014): Guidance for Food and Drink Manufacturers. REI Guide 4a. The 2014 EU F-Gas Regulation

Leakage of Mildly Flammable Refrigerants into a Room

Artificial Trees and Fire Performance

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

OWNER S MANUAL (English)

Current status of Japan s legislation on F-gases and RACHP using Low-GWP Refrigerants

Roof Coatings Manufacturers Association October 18, 2012

Challenges from flammability concerns and related safety standards, possibilities for compact systems limiting charge sizes

Update on Next Generation Low GWP Refrigerants for Chillers Products. Steve Kujak Director, Next Generation Refrigerant Research

Transcription:

Research to Assist in the Development of Safety Standards and Building Codes for the Use of Flammable Refrigerants Karim Amrane, Ph.D. Senior Vice President

Low GWP AREP Cooperative research & testing program to identify suitable alternatives to high GWP refrigerants Evaluation of candidates strongly desired by OEMs The program is NOT to prioritize refrigerants, rather test and present objective results in a consistent manner Phase I was completed at the end of 2013. 38 refrigerants were evaluated in Phase I AHRI published 40 test reports Phase II started in 2014, testing concluded in Dec.2015 17 new refrigerants, high ambient testing 34 additional reports were published Final reports available to the public http://www.ahrinet.org/site/514/resources/research/ahri Low GWP Alternative Refrigerants Evaluation

List of Low GWP Candidates in Phase I Baseline Refrigerant Composition (Mass%) Classification (Note 1) GWP 100 (Note 2) ARM 32a R 32/R 125/R 134a/R 1234yf (25/30/25/20) A1 1577 LTR4X R 32/R 125/R 134a/R 1234ze(E) (28/25/16/31) A1 1295 N20 R 32/R 125/R 134a/R 1234yf/R 1234ze(E) (12.5/12.5/31.5/1 3.5/30) A1 975 R22 D52Y R 32/R 125/R 1234yf (15/25/60) A2L 979 L20 R 32/R 152a/R 1234ze(E) (45/20/35) A2L 331 LTR6A R 32/R 744/R 1234ze(E) (30/7/63) A2L 206 R290 R290 100 A3 11 R1270 R1270 100 A3 11 AC5X R 32/R 134a/R 1234ze(E) (7/40/53) A1 622 ARM 41a R 32/R 134a/R 1234yf (6/63/31) A1 943 D 4Y R 134a/R 1234yf (40/60) A1 574 N13a R 134a/R 1234yf/R 1234ze(E) (42/18/40) A1 604 N13b R 134a/R 1234ze(E) (42/58) A1 604 R 134a XP 10 R 134a/R 1234yf (44/56) A1 631 AC5 R 32/R 152a/R 1234ze(E) (12/5/83) A2L 92 ARM 42a R 134a/R 152a/R 1234yf (7/11/82) A2L 117 R1234yf R1234yf 100 A2L 4 R1234ze R1234ze 100 A2L 6 R600a R600a 100 A3 11 R290/R600a R290/R600a (40/60) A3 11 Notes: Refrigerants classifications or intended classifications according to the ASHRAE Standard 34 (ASHRAE, 2013). GWP values are calculated based on IPCC AR-4 100 year.

List of Low GWP Candidates in Phase I Baseline Refrigerant Composition (Mass%) Classification (Note 1) GWP 100 (Note 2) ARM 32a R 32/R 125/R 134a/R 1234yf (25/30/25/20) A1 1577 DR 33 R 32/R 125/R 134a/R 1234yf (24/25/26/25) A1 1410 N40a R 32/R 125/R 134a/R 1234yf/R 1234ze(E) (25/25/21/9/20) A1 1346 R404A R410A N40b R 32/R 125/R 134a/R 1234yf (25/25/20/30) A1 1331 ARM 30a R 32/R 1234yf (29/71) A2L 199 ARM 31a R 32/R 134a/R 1234yf (28/21/51) A2L 491 D2Y65 R 32/R 1234yf (35/65) A2L 239 DR 7 R 32/R 1234yf (36/64) A2L 246 L40 R 32/R 152a/R 1234yf/R 1234ze(E) (40/10/20/30) A2L 285 R 32 R 32 100 A2L 675 R 32/R 134a R 32/R 134a (50/50) A2L 1053 R290 R 290 100 A3 11 ARM 70a R 32/R 134a/R 1234yf (50/10/40) A2L 482 D2Y60 R 32/R 1234yf (40/60) A2L 272 DR 5 R 32/R 1234yf (72.5/27.5) A2L 490 HPR1D R 32/R 744/R 1234ze(E) (60/6/34) A2L 407 L41a R 32/R 1234yf/R 1234ze(E) (73/15/12) A2L 494 L41b R 32/R 1234ze(E) (73/27) A2L 494 R32 R32 100 A2L 675 R 32/R 134a R 32/R 134a (95/5) A2L 713 R 32/R 152a R 32/R 152a (95/5) A2L 647

List of Low GWP Candidates in Phase II Baseline Refrigerant Composition (Mass%) Classification (Note 1) GWP 100 (Note 2) DR 93 R 32/R 125/R 1234yf/R 134a 20/20/31/29 A1 1251 N 20b R 32/R 125/R 134a/R 1234yf 13/13/31/43 A1 988 R22/R 407C R404A R410A R 449B R 32/R 125/R 1234yf/R 134a 25.2/24.3/23.2/27.3 A1 1412 ARM 20b R 32/R 1234yf/R 152a 35/55/10 A2L 251 DR 3 R 32/R 1234yf 21.5/78.5 A2L 148 L 20a (R 444B) R 32/R 1234ze/R 152a 41.5/48.5/10 A2L 295 ARM 35 R 32/R 125/R 1234yf 12.5/61/26.5 A1 2220 DR 34 (R 452A) R 32/R 125/R 1234yf 11/59/30 A1 2140 R 32/R 125/R 134a/R 1234yf/R N 40c (R 448A) 1234ze 26/26/21/20/7 A1 1387 ARM 20a R 32/R 1234yf/R 152a 18/70/12 A2L 139 HDR110 R 32/R 1234yf/CO2 21.5/75.5/3 A2L 148 ARM 71a R 32/R 1234yf/R 1234ze(E) 68/26/6 A2L 460 DR 5A (R 454B) R 32/R 1234yf 68.9/31.1 A2L 466 DR 55 R 32/R 125/R 1234yf 67/7/26 A2L 698 HPR2A R 32/134a/1234ze(E) 76/6/18 A2L 600 L 41 1 (R 446A) R 32/R 1234ze/Butane 68/29/3 A2L 461 L 41 2 (R 447A) R 32/R 1234ze/R 125 68/28.5/3.5 A2L 583 Notes: Refrigerants classifications or intended classifications according to the ASHRAE Standard 34 (ASHRAE, 2013). GWP values are calculated based on IPCC AR-4 100 year.

Low GWP AREP Viable low GWP alternatives exist Many promising refrigerants are classified 2L under ASHRAE 34 (mildly flammable) ASHRAE 15 does not currently differentiate between class 2 and 2L refrigerants IEC 60335 2 40 does not currently have requirements for 2L refrigerants

Risks of Flammable Refrigerants What are 2L Refrigerants: Exhibit flame propagation when tested at 60 C LFL > 0.10 kg/m³ HOC < 19000 kj/kg S U 0.1 m/s Increasing probability of a combustion event Lower Flammability Limit (kg/m³) 0.1 Subclass 2L Class 2 Class 3 0.1 Maximum Burning Velocity (m/s) Heat of Combustion (kj/kg) 19000 Increasing severity of a combustion event Slide Source: P. Johnson, ASHRAE 2012 Annual Meeting Seminar 11

Class 2 & 3 Restrictions In general, it is very restrictive A2 or A2L refrigerants allowed in self contained systems with less than 3kg (residential) or 10kg (commercial), depending on location in the building The current Standard 15 does not differentiate class 2 and 2L refrigerants because 2L is the sub class of class 2 A3 cannot be used except if allowed by AHJ Exceptions: Laboratories with more than 100 ft 2 (9.3 m 2 ) area per person Industrial occupancies Portable unit systems containing less than 0.331 lb (150 g) of refrigerant charge

AHRTI Flammable Refrigerants Research We surveyed relevant codes and standards committees and organizations on: The main knowledge gaps for the use of 2L and 3 flammable refrigerants Any standing issues and gaps that require additional research Current and past research activities on flammable refrigerants Through this survey, we have: Identified the gaps in existing flammable refrigerant research Developed a roadmap with priorities and a timeline to complete the critical research toward the safe use of flammable refrigerants

AHRTI Flammable Refrigerant Research Joint effort by AHRTI, ASHRAE and US DOE The objective is to produce publicly available technical results to support code and standard activities related to the use of flammable refrigerants. Ensure a timely completion of relevant standard revision. AHRTI/ASHRAE/ DOE Research to support ASHRAE 15 revisions Summer 2017: draft ASHRAE 15 completed for PPR End of 2017: publication of the updated ASHRAE 15 including 2L refrigerants Jan 2018: 2021 IMC: change proposals are due

Funding for Top Priority Research Projects on Flammable Refrigerants 7top priority projects were identified Funding commitments are in from: U.S. Government: $3 million : $1 million : $1.2 million

Identified top priority project AHRTI 9007: Benchmarking Risk by Real Life Leaks and Ignitions Testing Cost: $600,000, Duration : 9 months Objectives: Conduct A2L refrigerant leak and ignition testing under realistic conditions Understand the risk relative to the A1 refrigerants while considering ambient conditions and refrigerant lubricants. Findings will: Provide input to the next ASHRAE 15 code cycle and follow on revisions to building codes Benchmark/validate risk Determine the type of (or need for) hazard mitigation strategies

Identified high priority project ASHRAE RP: Flammable Refrigerants Post ignition Risk Assessment Cost: $800,000, Duration 12 months Objectives: Understand the severity of events where flammable refrigerants are being ignited. Assess the overall risks of using flammable refrigerants taking into account both event probability and severity. Findings will: Aide in the proper design and the associated fire mitigation and detection methods. Update existing risk assessments by adding the event severity to the overall risk (probability x severity) Help further refine the accuracy of Safety Standards currently being developed for flammable refrigerants and the associated Building Codes.

Identified high priority project AHRTI 9008: Investigation of Hot surface Ignition Temperature (HSIT) for A2L Refrigerants Cost: $100,000, Duration: 6 months Objectives: Establish a standard HSIT test method Conduct the HSIT testing at various ambient conditions with oil and air velocity effects included Findings will: Determine/define appropriate HSIT limits for appropriate HVACR equipment and safety standards.

Identified high priority project AHRTI 9009: Leak Detection of A2L Refrigerants in HVACR Equipment Cost: $50,000, Duration: 6 months Objective: Assess sensor technologies that can be used to detect A2L refrigerants and easily integrated into HVACR equipment Main tasks are: Review existing and new sensor technologies Identify key known failure modes Propose a suitable reliability testing program/procedure to address the potential failure modes

Identified high priority project ASHRAE RP: Servicing and Installing Equipment using Flammable Refrigerants Assessment of Field made Mechanical Joints Cost:$80,000, Duration: 6 months Objective: Assess effectiveness of joints made in the field, taking into account human and mechanical factors. Findings will Help determine whether common types of joints other than brazed or soldered joints should or should not be allowed in the ASHRAE Standard 15.2 and relevant codes and standards.

Identified high priority project ASHRAE RP: Guidelines for flammable refrigerant handling, and equipment servicing and installation Cost: $80,000, Duration: 6 months Objectives: Review existing requirements/practice for safe handling of flammable refrigerants Review technician licensing or certification requirements Propose requirements for servicing and installing HVACR products using flammable refrigerants Findings will support revisions of relevant sections in ASHRAE and UL safety standards.

Identified high priority project DOE/ORNL: Determination of setting charge limits for various types of equipment employing Flammable Refrigerants Cost: $1,000,000, Duration: 12 months Objectives: Determine the effectiveness to mitigate the risk of current m1/m2/m3 refrigerant charge limits in the IEC 60335 2 40 Annex GG Main tasks: Evaluate existing CFD results effectiveness for setting the charge limit and mitigation requirements Identify gaps and develop CFD matrix to account for: Equipment room layout leak scenarios (rates and location) mitigation strategies Conduct CFD simulations

Execution Plan

Thank you for your attention!