Technical and Dimensional Data. Saf-T Vent SC Plus

Similar documents
CVS. Venting System for Category II, III, and IV gas appliances. Listed to UL-1738 and ULC S636.

Saf-T Vent SC Plus/SC 316

Installation and Maintenance Instructions

Installation and Maintenance Instructions

200i. Vent/air manual. Installation instructions for vent and air piping. Also read and follow: 200i Boiler manual 200i Control manual

Installation and Maintenance Instructions

PelletVent Pro. Biofuel venting system. UL 641, ULC S609, and ULC/ORD C441.

Installation and Maintenance Instructions

Corr/Guard PRESSURE RATED VENTING SYSTEM IMPORTANT: DO NOT INSTALL WITHOUT FIRST READING THESE INSTRUCTIONS VERY CAREFULLY.

FLANGED CORR/GUARD CORR/GUARD INSTALLATION INSTRUCTIONS

Pellet Stove. Flex Pipe. Appliance Connector

Saf-T Vent Model EZ Seal Plus/EZ 316 Single Wall Gas Vent Connector Chimney Liner & Special Gas Vent (USA) / Type BH Vent Class I/II (Canada)

SMALL DIAMETER CORR/GUARD & SLEEVED CORR/GUARD

Installation and Maintenance Instructions. Double Wall AL 29-4C Stainless Steel Special Gas Vent and Type L Vent

PelletVent Multi-fuel venting system. UL 641.

NovaVent. Dimensional Data

Vent and air piped through a side wall (concentric termination)

By Bernard Dalsin Mfg. Co. Installation and Operating Instructions Read these instructions and keep them for future reference

Installation and Maintenance Instructions

Z-VENT MODEL SVE SERIES III INSTALLATION AND MAINTENANCE INSTRUCTIONS

DuraPlus HTC. All-fuel, double-wall chimney system. ULC S629.

Vertical Termination Part No: 3CGRVT 16 7/8" 18 Vent Pipe Extension Part No: 3CG18 9 7/8" Wall Hanger Part No: 3CGWH 7 7/8" 7 3/8"

DURAVENT POLYPRO VENTING PRODUCTS

Easy to assemble. Silicone gasket sealed. Laser-welded seams. Smooth joint connections. 360 Lock-Tab secure rotation

VP Pellet Pipe. For pellet burning stoves. FEATURES

ICC Model VIC SINGLE WALL SPECIAL GAS VENT INSTALLATION AND MAINTENANCE INSTRUCTIONS

DirectVent Pro CVS. Unitized, co-axial venting system for direct vent gas or propane stoves, and fireplaces.

INSTALLATION OF VENTING SYSTEM COMPONENTS WARNING

FasNSeal 80/90 FasNSeal & FasNSeal W2 FasNSeal Flex

SUBJECT: SELKIRK MODEL DT DIRECT VENT SYSTEM FOR PELLET & CORN FIRED APPLIANCES / TERMINATION CLEARANCES TO OPENINGS IN BUILDINGS

SL-VENT (oil and gas vent) For use with oil or gas fired appliances. Listed to ULC-609 and UL-641. Available in 5, 6, 7 and 8 I. D.

Gas Stoves. C34-10 Direct Vent Gas Stove. Side wall E F. Back wall F E. Model C34-NG10 C34-LP10

C. Manufactured double wall chimneys for fuel fired equipment. D. NFPA 54 - National Fuel Gas Code; National Fire Protection Association; 2009.

PelletVent Pro horizontal Kit. PelletVent Pro. PelletVent Pro Vertical Kit - Cathedral. PelletVent Pro Pellet Chimney

PelletVent Pro. Biofuel venting system. UL 641, ULC S609, and ULC/ORD C441.

PelletVent Pro. Biofuel venting system. UL 641, ULC S609, and ULC/ORD C441.

TW-Pro. Twin Wall Insulated Flue System EN T600 N1 W V2 L50040 G50 / O40

Ventis Direct Vent. Installation Instructions

Direct Vent System. for PELLET STOVES FEATURES. Includes all Selkirk Model VP Pellet Pipe and Direct-Temp components needed to complete a system

5"x 8" DIRECT VENT INSTALLATION INSTRUCTIONS FOR DECORATIVE GAS APPLIANCES AND DIRECT VENT HEATERS APPLICATION

SEPARATED COMBUSTION. General WARNING

Twin wall Air Gap Insulated Zalutite & Aluminium Commercial Gas Vent Chimney System

DT-M Direct-Temp for Multi Fuel L-Vent / Vent System for Pellet, Corn and other Bio-Fuel Burning Appliances

CQS POWER VENT. General. Venting Requirements. Venting Instructions PREEVA Indoor, Power-Vented Heater Model PDH

FasNSeal 80/90 FasNSeal & FasNSeal W2 FasNSeal Flex

Installation & Maintenance Instructions

Combustion Air System DVL. DuraBlack. Triple-wall stovepipe system designed to provide air for combustion through its components. ULC S641.

SEPARATED COMBUSTION WARNING

Installation Instructions

Venting Supplement. Direct Vent Through-Roof or Through-Unused-Chimney. Water Boiler Series 3 & 4

ANY EVERY ONE ONE No matter what the venting application, from gas fired to oil to all fuel heating equipment, Z-FLEX is your one-stop solution.

EUTECTIC EC-10DV Series

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

POWER VENT. Standard Power Vent, Fan Type Unit Heaters: Standard Power Vent, Blower Type Unit Heaters: General WARNING WARNING. Model UDAP & Model APD

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

Detroit Radiant Products Co.

INSTALLATION AND SERVICE MANUAL

INSTALLATION INSTRUCTIONS WALL MOUNT LINER INSERT

Mitchell Metal Products, Inc.

TYPE L VENT / VENT SYSTEM FOR PELLET BURNING APPLIANCES

INS A T LL T A ION, OPER T A ING AND SERVICE INSTRUCTIONS FOR FREEDOM CONDENSING HIGH EFFICIENCY DIRECT VENT GAS - FIRED HOT

ASX7-5-IOM-3 J

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Read and Save These Instructions All Hoods Must Be Installed By A Qualified Installer

Detroit Radiant Products Co.

FasNSeal. Installation Instructions

H35 Direct Vent Gas Stove. 17,500 BTU/h (5.13 kw) 34,000 BTU/h (9.97 kw) 15,000 BTU/h (4.39 kw) 28,500 BTU/h (8.35 kw)

H35 Direct Vent Gas Stove. 17,500 BTU/h (5.13 kw) 34,000 BTU/h (9.97 kw) 15,000 BTU/h (4.39 kw) 28,500 BTU/h (8.35 kw)

flexible venting simply perfect cost efficient convenient durable Est FREEDOM VENTING FLEX

INSTALLATION INSTRUCTIONS

INSTALLATION AND SERVICE MANUAL

SEPARATED COMBUSTION. General

All-fuel, double-wall chimney system. UL 103 HT, UL 103, and ULC S604.

Gas Stoves. H15-10 Direct Vent Gas Stove. Model H15-NG10 H15-LP10. Approved Venting Systems

Venting System For Pellet and Corn Stoves. PelletVent Pro. C o m p l e t e V e n t i n g S o l u t i o n s f o r t h e H e a r t h I n d u s t r y

OPTIMA RADIANT TUBE HEATING SYSTEMS. Operation, maintenance and servicing manual

BDM Direct Vent systems are for use with direct vent gas fired appliances.

PelletVent Pro. Installation Instructions. C o m p l e t e V e n t i n g S o l u t i o n s f o r t h e H e a r t h I n d u s t r y

VENT SYSTEM COMPONENTS

ASX7-4-IOM-6 J

St. Croix Greenfield Installation Manual

Combustion Air System DVL. DuraBlack. Triple-wall stovepipe system designed to provide air for combustion through its components. ULC S641.

SUBMITTAL RECORD. ULC S636 - PolyPro. Single-Wall Double-Wall Concentric Flex

Bring In the Fresh Air

INSTALLATION INSTRUCTIONS FOR THROUGH-THE-WALL VENTING COMPONENTS

Installation Instructions. Venting System for Pellet, Corn, Oil, and Biofuel appliances. PelletVent Pro

INSTALLATION INSTRUCTIONS

Installation Instructions. PolyPro Single-Wall Gas Vent System for Category II & IV Gas-Burning Appliances. PolyPro

Venting. Vent Material. Approved Venting Accessories Simpson Dura-Vent DV unless otherwise specified. Wall Thickness

TOYOTOMI U.S.A., INC. P.O. Box 176, Brookfield, CT

GV Series 4 Section Assembly

INSTALLATION INSTRUCTIONS

Gravity and Pneumatic Waste and Linen Handling Systems NFPA 82 Inspection Form

Installation Instructions. PolyPro Single-Wall Gas Vent System for Category II & IV Gas-Burning Appliances. PolyPro

INSTALLATION INSTRUCTIONS

ULC S636 System. PolyPro. PolyPro Flex. Terminations

INSTALLATION AND MAINTENANCE INSTRUCTIONS. 1700ºF Air-Cooled and Insulated ECO-STEEL Chimney Size 13

Special Gas Vent For Category II, III and IV Appliances UL/ULC Listed to UL1738 & ULC-S636

CAST 92. Boilers. As an ENERGY STAR Partner, PB Heat, LLC has determined that this product meets the ENERGY STAR guidelines for energy efficiency.

Transcription:

Technical and Dimensional Data Saf-T Vent S Plus 3"/5" & 4"/7" oncentric Reduced learance Double Wall for Special Gas Vent and/or Sealed ombustion Systems lso For Venting Listed Gas or Oil Fired ppliances Listed as Suitable For Venting With Type L Systems Tested and Listed to UL 1738/UL S636 UL641 & UL/ORD-441 by Underwriters Laboratories, Inc 5030 orporate Exchange lvd Grand Rapids, MI 49512 all (800) 772-0739 Fax (800) 972-1421 anada Sales: 888-735-5475 www.heatfab.com

Saf-T Vent S Plus Table of ontents ategory Part Description Page Introduction 3 ccessories Vertical / Horizontal In-Line Drain Section 4 ondensate Drain Tube Kit 4 dapters Single Wall dapter / ppliance dapter 5 ir Intake Tee 5 Elbows 45 Elbow 6 90 Elbow 6 Straight Lengths 6" Length 7 1' Length 7 2' Length 7 3' Length 7 djustable Length 7 Supports & Vertical Support Leg 8 Hanger 0" learance Support lamp 8 1" learance Support lamp 8 Outer Jacket Support lamp 8 Termination Firestop / Support / Wall Plate 9 ccessories Tall one Flashing / Support 9 Storm ollar 9 Horizontal Termination dapter 10 Vertical Termination dapter 10 Terminations Tee Termination with Screen 11 Mitered Termination with Screen 11 Elbow Termination with Screen 11 Screen Termination 12 Rain ap 12 2

Saf-T Vent S Plus Introduction: Saf-T Vent S Plus is an advanced concentric vent system designed for zero clearance installation in residential and light commercial applications. The inner wall is constructed from 316L Stainless Steel. The outer wall is 409 stainless steel, providing durability and a lasting finish. The double-wall construction of Saf-T Vent S Plus allows the system to be fully enclosed by combustible materials at zero or one-inch clearance depending on layout and flue gas temperature. Saf-T Vent S Plus is UL and UL Listed to UL 1738 / UL S636 (File MH16161). It may be used on negative, neutral, and positive pressure systems up to eight (8) inches w.c. s a Special Gas Vent system: Saf-T Vent S Plus is approved for use on NSI ategory I, II, III, and IV Gas-urning ppliances and certain Direct Vent appliances. Saf-T Vent S Plus is appropriate for use on appliances that specify an L 29-4 venting system. s a Sealed ombustion system: The unique concentric design of Saf-T Vent S Plus also allows it to function as a pipe-in-a-pipe vent. Products of combustion are exhausted out through the inner wall while combustion air is drawn in through the outer wall. n appliance can be direct-vented with only a single penetration through the building structure. This application must be approved by the ppliance Manufacturer. Note regarding sealant: Saf-T Vent S Plus includes an integral seal and does not require sealant. However, sealant may be necessary when connecting Saf-T Vent S Plus components directly to certain appliance flue collars and to the gasket-less Saf-T Vent G Plus/G 316 vent system. For applications up to 550 F/288, approved sealants include GE RTV 106, Dow orning 736, and SGV 550. For applications up to 300 F/149, approved sealants include GE RTV 106, Dow orning 732, and SGV 550. Seal weather exposed joints of the outer jacket with foil tape or an exterior grade silicone sealant. Material Thickness: Inner Vent Wall Thickness Inner Vent Outer Jacket Wall Thickness Outer Jacket 3" 5" 0.015" (28 ga) 4" 7" 0.018" (26 ga) 3

Saf-T Vent S Plus ccessories: Vertical/Horizontal In-Line Drain Section Use to drain away condensate from the vent system. The unique design of this part allows it to be installed in a horizontal, vertical or inclined orientation. ontinuous horizontal runs in excess of 30 feet require a condensate drain. Drains may also be required by the manufacturer. High temperature silicone rubber tubing is available separately, see below. Part Number DIM - DIM - DIM - DIM - D DIM - E Nominal Nominal Installed Drain Drain Vent Pipe Outer Jacket Length Location (OD) S03DRN 3 5 6.7 3.3 0.5 S04DRN 4 7 6.7 3.3 0.5 In-Line Drain Section E D ondensate Drain Tube Kit This kit contains a length of high temperature silicone rubber tubing, a clamp, and two cable ties. The silicone tubing is rated for 500 F, and is translucent to allow inspection of the P-trap. Larger diameter drains can be plumbed directly into a drain system. Part Number: 7000TUE 5 feet of 3/8" diameter tubing 7000TUE-10 10 feet of 3/8" diameter tubing 7001TUE 10 feet of 1/2" diameter tubing 4

Saf-T Vent S Plus dapters: Single Wall dapter/ppliance dapter Use to transition from single-wall to Saf-T Vent S Plus. The male end connects to Saf-T Vent EZ Seal Plus/EZ 316 or Saf-T Vent appliance adapters and flue collars. The outer diameter collar is vented and must not be blocked during installation or operation. Part Number DIM - DIM - DIM - Nominal Nominal Installed Vent Pipe Outer Jacket Length S03DEZ 3 5 4 S04DEZ 4 7 4 ottom View, Vented rea Single Wall dapter/ ppliance dapter ir IntakeTee Use to begin a Sealed ombustion system. The male end connects to Saf-T Vent EZ Seal Plus/EZ 316 or Saf-T Vent appliance adapters and flue collars. The tap on the outer wall should be connected to the combustion air inlet on the appliance using materials specified by the appliance manufacturer. Part Number DIM - DIM - DIM - DIM - D DIM - E Nominal Nominal Installed enterline of ir Intake Vent Pipe Outer Jacket Length Tap to Outlet onnection S03TD3 3 5 9 4.0 3 S03TD4 3 5 10 4.6 4 S04TD4 4 7 10 4.6 4 S04TD3 4 7 9 4.0 3 D ir Intake Tee E 5

Saf-T Vent S Plus Elbows: 45 Elbow Use to achieve offsets or changes in the direction of the vent system. The degree of these welded seam elbows is not adjustable. Part Number DIM - DIM - DIM - DIM - D DIM - E DIM F Nominal Nominal Rise Run ombined Offset Vent Pipe Outer Jacket Installed Height S03E45 3 5 3.1 3.7 11.60 4.8 S04E45 4 7 3.3 4.3 13.03 5.3 D E 45 45 Elbow F 90 Elbow Use to achieve offsets or changes in the direction of the vent system. The degree of these welded seam elbows is not adjustable. Part Number DIM - DIM - DIM - DIM - D DIM - E DIM F Nominal Nominal Rise Run ombined Offset Vent Pipe Outer Jacket Installed Height S03E90 3 5 6.1 7.0 13.1 13.25 S04E90 4 7 6.8 7.75 14.5 14.50 D E 90 90 Elbow F 6

Saf-T Vent S Plus Straight Lengths: Install vent with a continuous pitch of 1/4" per foot, sloping upward toward the termination (unless otherwise specified by the appliance manufacturer). It is important to provide adequate support to a Saf-T Vent S Plus system. Refer to installation instructions for support specifications. 6" Length Part Number DIM - DIM - DIM - Nominal Nominal Installed Length Vent Pipe Outer Jacket S03L6 3 5 3.88 S04L6 4 7 3.88 1' Length Part Number DIM - DIM - DIM - Nominal Nominal Installed Length Vent Pipe Outer Jacket S03L12 3 5 9.88 S04L12 4 7 9.88 2' Length Part Number DIM - DIM - DIM - Nominal Nominal Installed Length Vent Pipe Outer Jacket S03L24 3 5 21.88 S04L24 4 7 21.88 1.00 3' Length Part Number DIM - DIM - DIM - Nominal Nominal Installed Length Vent Pipe Outer Jacket Straight Length S03L36 3 5 35.38 S04L36 4 7 35.38 djustable Length Part Number DIM - DIM - DIM - Nominal Nominal Installed Length Vent Pipe Outer Jacket S03J 3 5 12.5-19.5 S04J 4 7 12.5-19.5 7

Saf-T Vent S Plus Supports: Vertical Support Leg For use on vertical systems to provide support. The 20-gauge stainless steel support legs can be used below or above the roof, and can be used in pairs for extra stabilization. Hardware to attach the support to the structure is not provided; attach using best construction methods. e sure to consider clearances when planning the system. Never drill or screw through the Saf-T Vent S Plus inner vent conduit. Part Number DIM - Hose lamp S03VSL 5.2 S04VSL 7.2 0" learance Horizontal / Vertical Support lamp For use on horizontal or vertical systems to provide support at zero clearance to combustible materials. When any horizontal run of Saf-T Vent S Plus extends for more than 6 feet, a horizontal support must be installed. Subsequent supports are required after every additional 6 feet and every elbow and tee. ttach the bracket to the structure using appropriate hardware (not provided). This part consists of a hose clamp and an 18-gauge stainless steel mounting bracket. e sure to consider proper pitch when planning the system. Never drill or screw through the Saf-T Vent S Plus inner vent conduit. Part Number DIM - Hose lamp S03SUP 5.5 S04SUP 7.5 Ø0.19 1" 23.5 2.25" 1" learance Support lamp Provides support to Saf-T Vent S Plus systems that require 1 inch clearance to combustible materials. When any horizontal run of Saf-T Vent S Plus extends for more than 3.00 6 feet, a horizontal support must be installed. Subsequent supports are required after every additional 6 feet and every elbow and tee. e sure to consider clearances and proper pitch when planning the system. Never drill or screw through the Saf-T Vent S Plus inner vent conduit. Ø.31 Ø Part Number DIM - Hose lamp Ø.31 1.00 LERNE TO OMUSTILES S03SUP1 5.5 S04SUP1 7.5 3 1" learance Support lamp Outer Jacket Support lamp For use on horizontal systems to provide support at the required 6-foot intervals. May be used singly as a saddle to rest the vent in and hung from two rods or cables. Use in pairs by clamping around the outer jacket and suspend from a single rod or cable. Support clamps by themselves do not maintain the necessary clearances to combustible materials; be sure to consider clearances and proper pitch when planning the system. Support clamps are sold in pairs, with two halfshells and two ¼-20 nuts and bolts. Never drill or screw through the Saf-T Vent S Plus inner vent conduit. Nominal Part DIM - Vent Number Nominal 3 4527SS 5 4 4727SS 7 8

Termination ccessories: Saf-T Vent S Plus Fire Stop / Support / Wall Plate fire stop may be required anytime Saf-T Vent S Plus penetrates combustible floors, walls, or ceilings. Remove any insulating material from the floor, wall, or ceiling cavity for at least 1 inch around the vent. Review fire codes and consult with local building code officials to determine the necessity for a firestop. This part provides added support when used at the bottom of a vertical chase. Hardware is supplied to attach the firestop to the vent. Mounting hardware is not provided. Part Number DIM - DIM - DIM - Hole Length Width S03FS 5 8 8 S03FS 5 12 12 S04FS 7 10 10 S04FS 7 12 12 Fire Stop Ø0.17 4X Tall one Flashing / Support Use as a vertical roof penetration and support for flat roof installations. This part must be installed with a 5 inch diameter storm collar (ordered separately). Hardware is not included with the tall cone flashing; attach to structure using best construction methods. The tall cone flashing may be used with a roof curb if necessary. Part Number DIM - DIM - DIM - DIM - D DIM-E Top of one ottom of one Face Plate Overall Height Pitch Range Opening Opening (Square) S03TF 5.5 7.5 12.5 6.0 FLT- 2/12 S03TF 5.5 7.5 12.5 6.0 2/12-6/12 S03TF 5.5 7.5 12.5 6.0 6/12-12/12 S04TF 7.5 9.5 14.5 6.0 FLT - 2/12 S04TF 7.5 9.5 14.5 6.0 2/12-6/12 S04TF 7.5 9.5 14.5 6.0 6/12-12/12 D Tall one Flashing E Storm ollar For use with the Tall one Flashing (sold separately) or other roof flashings to provide support to vertical installations. The storm collar may be tightened and sealed around the vent to prevent water from entering the building. It may also be used as a decorative shield to cover holes where the vent penetrates interior concrete and masonry walls. This part is made from Type 304 stainless steel and should not be installed in the direct path of flue gases. Nominal Part Number DIM - Vent Nominal 3 4526SS 5 4 4726SS 7 Storm ollar 9

Saf-T Vent S Plus Terminations: Horizontal Termination dapter Use to complete the Saf-T Vent S Plus system after penetrating an exterior wall. Standard Saf-T Vent terminations connect directly to the adapter. The screened openings release excess heat from the system and must not be blocked. On Sealed ombustion systems the screened openings supply combustion air to the appliance. Part Number DIM - DIM - DIM- Nominal Nominal Installed Vent Pipe Outer Jacket Length S03HT 3 5 5.3 S04HT 4 7 5.6 Termination ttaches Here Vertical Termination dapter Use to complete the Saf-T Vent S Plus system on vertical installations. Standard Saf-T Vent terminations connect directly to the adapter. The screened openings release excess heat from the system and must not be blocked. On Sealed ombustion systems the screened openings supply combustion air to the appliance. Part Number DIM - DIM - DIM - DIM - D Nominal Nominal Installed Vent Pipe Outer Jacket Length Protective and S03VT 3 5 3.8 7.1 S04VT 4 7 3.8 9.1 Termination ttaches Here D 10

Saf-T Vent S Plus Terminations: Tee Termination with Screen Use as a termination on horizontal or vertical systems, as specified or allowed by the appliance manufacturer. Part DIM - DIM - DIM - Number Nominal Installed Tee ody Length Width 9390TEE 3 5.5 6 9490TEE 4 6.0 7 SREEN, OTH ENDS Tee Termination with Screen Mitered Termination with Screen Use as a termination on horizontal or vertical systems, as specified or allowed by the appliance manufacturer. Part DIM - DIM - Number Nominal Installed Length 9390 3 6.25 9490 4 7.25 Mitered Termination with Screen Elbow Termination with Screen Use as a termination on horizontal or vertical systems, as specified or allowed by the appliance manufacturer. Part Number DIM - DIM - DIM - DIM - D Nominal enter enterline Overall to Edge Installed Installed Length Length 9314TERM (90 ) 3 4.5 5.3 6.8 9414TERM (90 ) 4 5.3 6.0 8.0 9311TERM (45 ) 3 2.9 5.0 6.2 9411TERM (45 ) 4 3.4 5.4 6.8 Elbow Termination with Screen 11

Saf-T Vent S Plus Terminations: Screen Termination Use as a termination on horizontal or vertical systems, as specified or allowed by the appliance manufacturer. Part Number DIM - Nominal 9392 3 9492 4 SREEN 1.25 INSTLLED LENGTH Screen Termination Rain ap Use as a termination on vertical systems. ategory I and II appliances require a raincap or other device to prevent rainwater from entering the vent. Vent systems for positive pressure appliances may omit the raincap if there are other provisions for draining rainwater from the system. The raincap may also be used as a horizontal termination. Part Number DIM - DIM - DIM - PPLITION Nominal ap Outer Height and 5300I 3 8.5 8 ll ategories 5400I 4 8.5 9 ll ategories S03R 3 5.5 5 ategory III & IV Only, if system has drain. S04R 4 6.3 7 ategory III & IV Only, if system has drain. S R Rain ap 5_00I 2017 Heatfab is a registered trademark of Johnson ontrols, Inc. in the United States and other countries. Pub # HF-TDD-PLUS-S 11/17