TEC2100 Series Networked Thermostats

Similar documents
TEC210x-2 Series Networked Thermostats

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

TEC1100 Series Thermostats

T606MSx-4 and T606MSx-4+PIR Series Multi-Stage

TEC Networked Multi-Stage Thermostat

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

TEC Networked Single-Stage Thermostat

T600MEP-2 Programmable Economizer Thermostat

TEC3000 Series Stand-Alone and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

TEC Networked Multi-Stage Economizer Thermostat

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

T500 Series Non-Programmable Thermostats

Document # R01

TEC and TEC PIR BACnet MS/TP Networked Multi-Stage Thermostat Controllers

MR3CCUHV Temperature/Defrost Control

TEC and TEC PIR N2 Networked Single-Stage Thermostat Controllers

P266 Series Single-Phase Condenser Fan Speed Control

TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page

Installation Instructions

MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack

TEC and TEC PIR BACnet MS/TP Network Multi-Stage Temperature and Humidity Controllers

NS Series Network Sensors

TEC BACnet MS/TP Networked Thermostat Controller with Single Proportional Output and One-Speed Fan Control

T60xDFH-3 and T60xDFH-3+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

TEC21x7-2 Series N2 Networked Thermostat Controllers with Two Outputs

TEC20x7-2 Series Wireless Thermostat Controllers with Two Outputs

TEC22x2-4 and TEC22x2-4+PIR LONWORKS Networked Heat Pump Thermostat Controllers

TEC1100 Series Thermostat

T62xx-0 Fan Coil Retrofit Thermostat Controller and R-xxxxx-0 Fan Coil Retrofit Relay Packs

TEC2664Z-2 BACnet MS/TP Rooftop Controller for Stand-Alone and Networked Zoning Systems Part No , Rev. C

Surface-Mounted NS Series Network Sensors without LCD

T600HCx-3 Single-Stage Thermostats

ET10 Series Stand-alone LCD Fan Coil Thermostat

Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors with LCD

CD-Px Series Duct Mount CO 2 Transmitters

NS Series Network Sensors

F261 Series Fluid Flow Switches

CONTENTS. Installation Guide. VT7200 Series

RDY2000 Commercial Room Thermostat

Johnson Controls Fan Coil Units and Direct Digital Controls

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

RS332N BUTTON OPERATION INTRODUCTION. Installation and Operation Instructions for REMOVING THE THERMOSTAT FROM THE BACKPLATE

WT-4000 Series Pneumatic-to-Direct Digital Control (DDC)

Installation Instructions. Applications. North American Emissions Compliance. Installation. Part No , Rev. Issued February 8, 2010

T5000 LCD Digital Fan Coil Thermostat

ACT2-CS Convenience Store Controller

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

VH7200 Humidistat Series For Humidification & Dehumidification Control For Commercial HVAC Applications (Issue Date January 22, R7)

ETAF Series VDC Fan output LCD Fan Coil Thermostat

TB7200 Series Communicating Zone Thermostats

Document # R00

System 350 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

TC-9102 Applications

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFH24F3XYZ2 Stand-alone with Internal Humidity Sensor

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE

SE7200 Series Installation Guide

DT92 WIRELESS DIGITAL ROOM THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

Net/X US32 Universal Setback Communicating Thermostat

SEE DISCLAIMER ON REVERSE

Safety & Installation Instructions

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

TH146-N-2H1C. 1. Introduction. 2. Installation. 1.1 Applications. 2.1 Control Module (CT280-2H1C) 1.2 Supplied Parts. 1.

Models available. Features and benefits. Models available with internal humidity sensing Advanced occupancy functions

Facility Explorer One-to-One Wireless Room Sensing System

TOUCHSCREEN. COMFORTSENSE Day Programmable Thermostat. 4 Heat / 2 Cool Universal Multi Stage MODEL NUMBER IDENTIFICATION L U FEATURES

York 25-Ton VAV Rooftop Unit

CommStat 4 Controller

PIR Ready VT7200 Series 24 Vac Low Voltage Zoning Thermostats For Commercial HVAC Applications September 1, 2010

EL-TSTAT-8820 Safety & Installation Instructions

T5000 T5000 LCD Digital Fan Coil Thermostat--More Models

INSTALLATION MANUAL. This manual covers TopTech models: TT-N-851. Need Help? Power Type. Thermostat Applications Guide. Page.

Installer Guide. WARNING Important Safety Information. 1 Specifications

RC300 IntelliFire Plus Multifunction Remote Control Installation & Operating Instructions

OWNER S MANUAL Venstar Inc. 08/07

INSTALLATION MANUAL. Need Help? This manual covers the following models: T915. Power Type. Thermostat Applications Guide. Page.

User s Manual

Small Digital Thermostat Controller Temperature Control

Safety & Installation Instructions

DT8050A DUAL TEC Motion Sensor with Anti-Mask - Installation Instructions


T8000 Series T8600 MODBUS Touch Screen Thermostat

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

TB7300 Series Communicating Fan Coil Thermostats 24 VAC/FOR COMMERCIAL AND LODGING HVAC APPLICATIONS

TH146-P-2H1C. 1. Introduction. 2. Installation. 1.1 Applications. 2.1 Control Module (CT280-2H1C) 1.2 Supplied Parts. 1.

System 350 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules

INSTALLATION MANUAL. * If using remote sensors the thermostat must be hardwired. Need Help?

W43A Humidistat. Features and Benefits

Product Manual SZ1009

Owner s Manual. Digital Thermostat. Heat/Cool & Heat Pump 7-Day Programmable S1-THEM22P7S COMMERCIAL. Model HVAC SERVICE PARTS

Installation and Setup Guide

Programmable Thermostat

SC Installation, Operation & Application Guide

HEAT HEAT HEAT COOL COOL

Phone-A-Stat. MODEL Command Center With Thermostat Operation, Maintenance & Installation Manual. Introduction.

Installation Guide. Model TBZ48A Battery Powered Z-Wave Thermostat. This thermostat is compatible with most HVAC systems, including the following:

HEAT COOL. Meets Commercial California Title 24

Transcription:

Product Bulletin Issue Date February 11, 2004 TEC2100 Series Networked Thermostats The TEC2100 Series of thermostats is a family of highly advanced thermostats specifically designed for control of equipment such as rooftop units (with and without economizers), heat pumps, and single and multi-stage heating/cooling equipment. The TEC2100 features Metasys system N2 Bus communication capability that enables remote monitoring and programmability for efficient space control. The TEC2100 uses an intuitive, plain text, menu driven backlit display that makes setup and operation quick and easy. The TEC Series includes four models: Single-stage (TEC2101-1), Heat Pump (TEC2102-1), Multi-stage (TEC2103-1), and Economizer (TEC2104-1). All thermostats use a unique proportional control algorithm that virtually eliminates temperature offset associated with traditional differential-based thermostats. Figure 1: TEC2100 Series Thermostat Metasys N2 Open Communication Liquid Crystal Display (LCD) Backlit Display Five Easy-to-Use Interface Keys Two Digital Inputs Over Twenty Configurable Parameters Economizer Output (TEC2104-1) Features and Benefits Provides compatibility with a proven communication network; N2 Bus is widely accepted by Heating, Ventilating, and Air Conditioning (HVAC) control suppliers Provides real-time control status of the environment in easy-to-read plain text messages Incorporates a low level back light during normal operation which brightens during user interaction Allow for easy adjustment of the thermostat s many options (eliminates the need for dip switches) Provides additional inputs for service or filter alarms Enables the thermostat to adapt to any installation Controls economizer operation for single and multi-stage unitary rooftop equipment 2004 Johnson Controls, Inc. 1 Code No. LIT-1201660 www.johnsoncontrols.com

Product Overview The TEC2100 Series of thermostats are specifically designed for networked control of the most common commercial heating and cooling equipment. In addition to superior temperature control and application flexibility, the TEC2100 provides the advantage of the Metasys N2 Network communication, so the user can view operation or make adjustments at the thermostat or from a remote workstation. For local interface, the plain text menus, backlit display, and five interface keys make setup and operation of the thermostat extremely simple. IMPORTANT: Use this TEC2100 Series networked thermostats only as an operating control. Where failure or malfunction of these thermostats could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the TEC2100 Series thermostats. Additional Features The TEC2100 Series also offers many other features: Menu Driven Options Eliminates the need for dip switches, setup of all configurable parameters is menu driven. Two Configurable Digital Inputs Provides additional inputs, configurable for service or filter alarms at the thermostat. These inputs can also be user defined at the workstation for other functions. Adjustable Heating/Cooling Deadband Adjusts the minimum heating/cooling deadband from 2 to 4F (1 to 2C ). Remote Indoor and Outdoor Sensing Accommodates remote indoor and outdoor sensors. Up to three indoor sensors can be average. Adjustable Anti-Short Cycling Timer Adjusts the minimum on and off times for the equipment from 0 to 5 minutes. Three Levels of Keypad Lockout Provides three different levels of keypad lockout that can be set up through the menu and interface keys. Concealed Key to Access Configuration Parameters Enables access to all configurable parameters while limiting unwanted parameter tampering once the thermostat is set up. Three Light-Emitting Diodes (LEDs) Provides fan, heating, and cooling status at a glance. Adjustable Temporary Occupancy Time Adjusts the temporary occupancy time from 0 to 12 hours. Frost Protection Turns the heat on when the zone temperature drops below 42 F (5.5 C) regardless of the thermostat s mode. Dry Bulb Economizer Function (TEC2104-1) Provides a 0-10 VDC output for economizer control. Economizer functions include dry bulb changeover, minimum damper position, mixed air temperature setpoint, and control of how mechanical cooling interacts with economizer function. Adjustable Heating/Cooling Cycles per Hour Configurable for the number of heating and cooling cycles in a one-hour period, balancing temperature control and equipment cycling. High and Low Balance Point Adjustments (TEC2102-1) Enables more precise control of heat pump operation based on outdoor air temperature. System Mode Lockout Allows the heating and cooling modes to be locked out based on outdoor air temperature when an outdoor air sensor is connected. Non-Volatile EEPROM Memory Prevents loss of adjusted parameters during power failure. Network Addressing and Viewing Allows network addressing through the menu driven user interface. Additionally, for quick viewing of the N2 address, pressing the YES and NO keys simultaneously on the user interface displays the N2 address of the TEC. 2 TEC2100 Series Networked Thermostats Product Bulletin

Remote Access Allows the user to read and access TEC2100 parameters from an Operator Workstation or through the N2 Dialer Module (NDM). Binary inputs or the temperature alarm causes the NDM to connect to the workstation upon Change-of-State (COS). Heating and Cooling Stage Enable/Disable (TEC2102-1, TEC2103-1, and TEC2104-1) Allows operation of the second-stage heating or cooling to be disabled, reverting the thermostat to single-stage operation, on heat pump and multi-stage thermostats. Thermostat Interface Keys The TEC2100 interface consists of five keys on the front cover and one configuration key (Figure 2) that can be accessed by removing the front cover. The functions of the keys are as follows. Use the: YES key to confirm a selection and move onto the next menu item NO key when you do not desire a parameter change, and to advance to the next menu item MENU key to access the Main User Menu or exit the menu DOWN arrow key to scroll through menu selections or adjust values UP arrow/scroll key to: stop the Status Display Menu from scrolling manually scroll to the next parameter on the menu adjust values Note: When left unattended for 45 seconds, the display resumes scrolling. Configuration Key Figure 2: Configuration Key Location Backlit LCD The TEC2100 uses a two-line, eight-character backlit display. Low level backlighting is present during normal operation and it brightens when any user interface key is pressed. The backlight returns to the lower level when the thermostat is left unattended for 45 seconds. Light-Emitting Diodes (LEDs) Three LEDs are used to indicate the status of the fan, call for heat, or call for cooling on the TEC2101-1, TEC2103-1, and TEC2104-1. When: the fan is on, the FAN LED lights up heating is on, the HEAT LED lights up cooling is on, the COOL LED lights up On the TEC2102-1, the three LEDs indicate heat pump operation. When: the fan is on, the FAN LED lights up the auxiliary heat is on, the AUX HEAT LED lights up the heat-pump compressor is on, the HEAT-PUMP LED lights up Backlit, plain text, Liquid Crystal Display (LCD) is easy to read in any condition. RoomTemp 75.0ºF Light-Emitting Diodes (LEDs) indicate system activity. Five keys on the TEC make operation easy and intuitive. Figure 3: TEC2100 Front Cover TEC2100 Series Networked Thermostats Product Bulletin 3

Menu Overview There are three menus used to view, program, and configure the TEC2100 Series thermostats. The menus are: Status Display Menu Main User Menu Installer Configuration Menu The following sections outline the functions and contents of each menu. Status Display Menu The Status Display Menu is displayed during normal thermostat operation. The menu continually scrolls through the following parameters: Room Temperature System Mode Schedule Status Outdoor Temperature (requires outdoor air temperature sensor) Applicable Alarms Press the up arrow/scroll key to temporarily stop the scrolling. Main User Menu The Main User Menu is used to access and change the thermostat s basic operating parameters. Access the Main User Menu by pressing the MENU key during normal thermostat operation. This menu is most commonly used by the zone occupant and is comprised of the following parameters: Temperature Setpoints System Mode Fan Mode The Main User Menu uses Auto Help. Auto Help is displayed automatically in the Main User Menu when there is a pause in programming activity. Installer Configuration Menu The Installer Configuration Menu is used to set up the thermostat for application specific operation. The menu is accessed by removing the front cover and pressing the configuration key, labeled CONFIG (Figure 2). This Installer configuration Menu is used by the installer/commissioning technician and contains the following parameters: Digital Input Configuration Keypad Lockout Levels Power Delay on Power-up Frost Protection Maximum Heating Setpoint/Minimum Cooling Setpoint Anti-Short Cycle Timings Heating Stages Cycles per Hour Cooling Stages Cycles per Hour Minimum Deadband Heating Fan Control End of Cycle Fan Delay Temporary Occupancy Time Room Sensor Calibration Outdoor Air Sensor Calibration Number of Heating Stages (TEC2103-1 and TEC2104-1 only) Number of Cooling Stages (TEC2103-1 or TEC2104-1) Number of Heat Pump Stages (TEC2102-1) Outdoor Air Temperature Heating Lockout Outdoor Air Temperature Mechanical Cooling The following parameters are for the TEC2102-1 only: Low Balance Point High Balance Point Comfort/Economy Heat Pump Operation Reversing Valve Operation Compressor/Auxiliary Interlock The following parameters are for the TEC2104-1 only: Outdoor Air Changeover Setpoint Outdoor Air Damper Minimum Position Mechanical Cooling Enable/Disable with Economizer Operation Mixed Air Temperature Setpoint Mixed Air Temperature Display 4 TEC2100 Series Networked Thermostats Product Bulletin

Dimensions 4.94 125 RoomTemp 75.0ºF 3.38 86 1.13 29 Ordering Information Figure 4: TEC2100 Dimensions (in./mm) Code Number Description Applications TEC2101-1 Networked Single-Stage Thermostat Fan Coil Unit, Unit Heaters, and Single-Stage Packaged Heating/Cooling Equipment TEC2102-1 Networked Heat Pump Thermostat Heat Pump with up to 3 Heating/2 Cooling Stages TEC2103-1 Networked Multi-Stage Thermostat Multi-Staged Packaged Heating/Cooling Equipment TEC2104-1 Networked Multi-Stage, Economizer Thermostat Packaged Rooftop Units with Economizers Accessories Code Number SEN-600-1 SEN-600-2 SEN-600-3 Description Remote Indoor Temperature Sensor Outdoor Air Temperature Sensor Duct Mount Temperature Sensor TEC2100 Series Networked Thermostats Product Bulletin 5

Technical Specifications Product TEC2101-1 TEC2102-1 TEC2103-1 TEC2104-1 Thermostat with N2 Bus, Single-Stage Thermostat with N2 Bus, Heat Pump Thermostat with N2 Bus, Multi-Stage Thermostat with N2 Bus, Multi-Stage with Economizer Control Power Requirements 20-30 VAC, 50/60 Hz, 24 VAC nominal, Class 2 Relay Contact Rating Maximum Inductive Digital Inputs Economizer Output Recommended Wire Size Thermostat Measurement Range Sensor Type: Resolution: Control Accuracy Outdoor Air Temperature Indication Range Control Range 1 ampere with in-rush surges up to 3 amperes, 30 VAC maximum, Class 2 Relay dry contact only across the C terminal to DI1 and DI2 0 to 10 VDC into 2 K ohm resistance minimum (TEC2104-1 only) 18 gauge maximum, 22 gauge recommended -40 to 122 F (-40 to 50 C) Local 10 K ohm NTC thermistor ± 0.2F (± 0.1C ) ± 0.9F (± 0.5C ) @ 70 F (21 C) typical calibrated -40 to 122 F (-40 to 50 C) Cooling: 54 to 100 F (12 to 37.5 C) in 1/2 degree increments Heating: 40 to 90 F (4.5 to 32 C) in 1/2 degree increments Minimum Deadband (Between heating and cooling) 2F or 1C Ambient Operating Conditions 32 to 122 F (0 to 50 C); 0 to 95% RH noncondensing Ambient Storage -22 to 122 F (-30 to 50 C); 0% to 95% RH noncondensing Conditions Dimensions (H x W x D) 4.94 x 3.38 x 1.13 in. (125 x 86 x 29 mm) Shipping Weight 0.75 lb (0.34 kg) UL and cul Listing File E27734 with CCN s XAPX (US, UL 873) and XAPX7 (Canada, CSA C22.2 No. 24) CE Compliance CE Directives EN50091-1: 1992 EMC Emissions; EN50082-2 EMC Immunity (Pending) FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. This device complies with Class A Part 15 of the FCC rules. It was also verified to Class B. Operation is subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation. This Class A digital apparatus meets all of the requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numérique de la Classe A respecte toutes les exigences du Règlement sur le materiél brouilleur du Canada. Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 Published in U.S.A. www.johnsoncontrols.com 6 TEC2100 Series Networked Thermostats Product Bulletin