CHILLED WATER SYSTEM 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods

Similar documents
University of Delaware

HEAT GENERATION 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods

A. Detail drawing M1 Standard Chilled Water Schematic 1.03 DESCRIPTION OF THE PULLMAN CAMPUS CENTRAL CHILLED WATER LOOP SYSTEM:

Water Piping and Pumps

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

CONTENTS. B. System Design and Performance Requirements

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 "Building Services Piping.

HVAC BASIC MATERIAL AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI "Hydraulic Institute Standards."

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

Existing Mechanical System Operation

UW Purchase Specification Section Steam Condensate or Hot Water Meter Page 1 of 9

DISTRIBUTION SYSTEMS. Water Piping and Pumps

High Efficiency Heating and Cooling Systems for Community Colleges Kirk Mescher, PE, LEED AP Principal ICCCFO

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

Phillips. HORIZONTAL AND VERTICAL ASSEMBLIES For Ammonia (R-717) and Halocarbon Refrigerants

CONTROLLED CHILLED BEAM PUMP MODULE

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

TECHNICAL. Series 18. Pump Packages

CONTROLLED CHILLED BEAM PUMP MODULE

The Book of AERMEC NRL Sequence of Operation

SECTION SECTION DESIGN REQUIREMENTS

DIVISION 15 MECHANICAL

Method to test HVAC equipment at part load conditions

Contact Information. Steven Potratz, P.E. WSU Facilities Services, Engineering Services Manager Phone

1.1 This section applies to air handling units for HVAC Systems.

MACH N-407 Heat Pump Air-Cooled Chiller

SECTION : CAMPUS CENTRAL METERING SYSTEM DESIGN

SECTION HYDRONIC PIPING AND SPECIALTIES

DUKE UNIVERSITY DESIGN GUIDELINES

Computing Services Center

ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

HVAC Water chiller selection and optimisation of operation

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

AMERICAN EQUIPMENT SYSTEMS A Division Of Trevor-Martin Corporation th Terrace North Clearwater, Florida 33762

MAC N-407 Air-Cooled Chiller

4. OVERVIEW OF MECHANICAL SYSTEM

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION WATER TREATMENT

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall.

System and equipment drains shall be piped to a floor drain. Gauges shall be provided on the suction and discharge side of all pumps installed.

This guide will discuss the scope of work, and technical requirements of connecting to the Energy Transfer Station(s) (herein referred to as ETS).

June Copyright Climatec

District Heat Montpelier. Customer Training

9/18/2017. Nicholas Thornton, CEM. Systems: HVAC, Electrical, and Technology. Overview. Today s Goals Introductions HVAC Electrical Technology Q&A

Technical Criteria for District Energy Ready Buildings Master Requirement ENG 108 Building Department: ,

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

A. This Section includes the following domestic water piping specialties:

PITTSBURG STATE UNIVERSITY. HVAC and BUILDING AUTOMATION SYSTEM STANDARDS

Integrated Automation Instrumentation & Terminal Devices

Element Z General Design Requirements Existing Facilities Information

PROJ. NO SECTION REFRIGERANT PIPING

Owner s Manual Therma-Stor II Heat Recovery System

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

(2) 325 tpd York Chlorine Liquefier Systems

Architectural Engineering Senior Thesis Mechanical System Redesign

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL

PRE-ASSEMBLED RADIANT CONTROL PANEL INSTALLATION MANUAL

007100S01 - PROGRAM DESIGN CRITERIA

Installation, Operation, and Maintenance Information

Water-to-Water Heat Pump Product Data Catalog R-134a Modules MR010AN, MR015AN, MR020AN, MR030AN, MR040AN, MR050AN, MR070AN, MR085AN

SECTION LABORATORY and DE-IONIZED WATER SYSTEMS STANDARD CONSTRUCTION STANDARD

Modular Chiller Systems. Application Guide

SYSTEM DESIGN REQUIREMENTS

DISTRIBUTION SYSTEMS. Water Piping and Pumps

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL

PACKAGED AIR COOLED Product Data Catalog

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

Energy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters

.2 Section Waste Management and Disposal.

Wallace & Tiernan Gas Feed Systems V2000 Chlorinator

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

Call us today! (800)

Mission Critical. Fuel Supply Systems

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Power and Energy Management Solutions

SECTION DOMESTIC WATER PIPING SPECIALTIES

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

OKLAHOMA STATE UNIVERSITY - BUILDING DESIGN STANDARDS

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps

MAC-120HE-03 Air-Cooled Chiller

SPECIFICATIONS - DETAILED PROVISIONS Section Magnetic Flowmeters C O N T E N T S

MZCool Chiller Installation and Operation Manual

Delta T Systems Variable Speed Chillers Technical Specifications for 1-30 Air Cooled and 2-30 Water Cooled Chillers

THERMAL ICE STORAGE: Application & Design Guide

GP SERIES Packaged Chillers

Civil Engineering Building

APPA Institute for Facilities Management. Energy & Utilities Cooling Production (316) Purpose of Today s Presentation. Agenda

KLDJ : Task 2 Farm Bill Geothermal Heat Pump Template Appendix A. Appendix A Engineering Design

Job Name Control Systems Description Date

70E Pressure Booster. Bell & Gossett. Bulletin D-215D. Efficient Operation. Easy to Select and Install. Quick Set-up through EZ Start

MAC Chiller Installation and Operation Manual

PRESSURE INDEPENDENT CONTROL VALVE TECHNOLOGY. 3/16/2012 Fred Ferrara 1

Transcription:

230510 CHILLED WATER SYSTEM PART 1: GENERAL 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS A. Section 230000 Basic HVAC Requirements B. Section 230500 HVAC Basic Materials and Methods C. Section 230523 Valves D. Section 232500 HVAC Water Treatment E. Section 238216 Coils F. Section 230900 Building Automation and Control System Guidelines 1.02 RELATED STANDARD DETAILS A. Detail 3.1.1, Chilled Water System Pressure Sustaining Valve Detail B. Detail 3.1.2, Building Chilled Water Piping Schematic C. Detail 3.1.4, Process Cooling Schematic D. Detail 3.1.7, Electromagnetic Chilled Water Meter Installation Detail E. Detail 3.1.8, Ultrasonic Chilled Water Meter Installation Detail F. Detail 3.4.3, Differential Pressure Transmitter Detail 1.03 CHILLED WATER SOURCE A. The Campus Chilled Water System is a district cooling system comprised of the following, all pumping into a common piping system: 1. Two (2) central plants with two chillers and a total of 6,000 tons capacity located at Chilled Water Plant 3 2. Seven (7) plate and frame heat exchangers located at the Lake Source Cooling (LSC) Chilled Water Plant 4 facility with 18,000 tons capacity 3. One (1) 4.4 million gallon chilled water thermal storage tank B. The chilled water plant and thermal storage tank provide peaking capacity and back up for LSC. DATE: 6/30/17 DATE: 6/30/15 Page 1 of 5

C. System temperature differential is critical to the operation of LSC, which is a large non-contact cooling system based on 39-41ºF deep Cayuga Lake water (no mechanical refrigeration is used). A higher temperature differential increases the capacity of the facility. The system is operated year round with a campus supply temperature of 43-45 ºF, and a supply/return pressure differential of 2 to 30 psid depending on the location in the system. D. Each chiller has a constant volume loop with a dedicated constant speed pump that is separate from the distribution pumps. E. The LSC facility heat exchangers are piped in a parallel arrangement, which in turn are in series with the distribution pumps. The number of heat exchangers on-line is dependent on the total chilled water flow through the plant. The LSC plant chilled water pumping is a variable volume, variable head loop out to the campus distribution system using variable speed pumps in parallel. The distribution pump speeds are varied to maintain constant differential pressure at various low differential points located in the piping system. 1.04 BUILDING CHILLED WATER CONNECTIONS A. Building chilled water service connections to the campus distribution system is accomplished using a variable volume, primary-secondary interface with a temperature controlled two-way mixing valve. The recirculating loop control valve is modulated to maintain a mixed building supply water temperature of 47 ºF when needed for summer air conditioning; and 48-52 ºF when needed for winter air conditioning and process cooling loads. B. The hydraulic separation (primary-secondary interface) at each building consists of a short section of full size pipe and a low pressure, drop, line size globe style, silent lift check valve with isolation valves. This section of pipe is referred to as the recirculating loop bypass line. C. A portion of the campus distribution system is coated steel, and has cathodic protection to prevent external corrosion. For building systems that connect to the steel campus main distribution piping, a monolithic dielectric isolation fitting shall be provided on the building side of the main isolation valves. No hangers or connections (other than capped vent and drain valves) shall be installed between the isolating joints and the wall penetration. Monolithic dielectric isolation fittings are not required when connecting to HDPE campus distribution piping systems. The consultant is instructed to contact Cornell for project specific design parameters. D. Building chilled water connections are to be accomplished as shown in Cornell Standard Detail 3.1.2, Building Chilled Water Piping Schematic. DATE: 6/30/17 DATE: 6/30/15 Page 2 of 5

PART 2: DESIGN GUIDELINES 2.01 GENERAL A. The designer s goal should be to design a system that can function as close as possible to variable flow constant temperature rise over the entire load range (all seasons). The designer should attempt to get as high a temperature rise as possible. B. For facilities with chilled water loads at an elevation over 940 feet above sea level, a pressure sustaining valve shall be used as shown in Cornell Standard Detail 3.1.1, Pressure Sustaining Valve Detail. Acceptable models shall be as follows: 1. CLA-VAL Model 750-01 2. Watts Regulator Model F-116 C. Design pressure for all components shall be at least 150 psig at 100 F. D. Do not pipe any equipment drains directly to drain. Provide isolation valve, brass hose adapter, cap, and chain on all vents and drains. E. In general, do not connect refrigeration condenser heat rejection systems to the campus chilled water system. It is preferable to use air cooled condensers and mechanical room ventilation. The use of campus chilled water for this application should be a last resort, requiring a process chilled water loop separated from the campus chilled water system with a plate and frame heat exchanger. F. Major building renovations should include replacement of the building isolation valves with epoxy coated high performance butterfly valves. 2.02 PUMPING A. The building chilled water pump head shall be selected with a reasonable safety factor for strainer plugging and future pipe roughness and flow. Providing extra capacity (flow) is acceptable. The building pump head is only necessary for piping, accessories, coils and process heat exchangers within the building loop. B. Loads with similar pressure drops should be grouped together on a single building loop. More than one building loop can be designed into each building. C. Process (continuous) loads and air conditioning loads (seasonal) shall be separated into separate loops. Design process loops with as high a supply temperature and temperature rise as possible. DATE: 6/30/17 DATE: 6/30/15 Page 3 of 5

D. If the process chilled water loop services equipment other than fan coil units in the lab spaces, the process loop or the loads must be separated from the campus system via a plate and frame heat exchanger. Do not provide user connection points to campus chilled water. E. Large air handlers can be designed with pumped coils. This entails bringing the distribution piping to each air handler and setting up a dedicated constant volume secondary loop for each air handler coil and controlling the mixing valve on leaving air temperature. F. Building chilled water pumps will be variable speed to enable pump capacity control with minimum energy usage. Pump speed should be controlled by one or more differential pressure transducers located at remote points in the building piping. Show the transmitter location(s) on the plans and schematic riser diagram. G. Booster pumps in series shall not be used unless they are variable speed. H. Provide two 100% pumps instead of multiple smaller pumps. I. All pump schedules included on the contract drawings shall, as a minimum, include the following: 1. Pump head (FT) 2. Pump efficiency (%) 3. Motor efficiency (%) 4. Drive efficiency (%) 5. Pump capacity (GPM) 6. Pump spare capacity (GPM) 7. Pump speed (RPM) 8. Motor size (HP) J. Provide a complete riser diagram/flow schematic on the contract drawings, which shall, as a minimum, include the following information: 1. All line sizes 2. All loads with flows 3. Riser flows 4. Control valves 5. Pumps with design flows and head 6. Differential pressure transmitter locations 7. Future pump and piping capabilities 2.03 CONTROL VALVES A. Recirculating Loop Valve (2-Way): See Cornell Design and Construction Standard 230900, Building Automation and Control System Guidelines. DATE: 6/30/17 DATE: 6/30/15 Page 4 of 5

B. Coil valves (Load Control Valves): See Cornell Design and Construction Standard 230900, Building Automation and Control System Guidelines. 2.04 METERING A. Temperature and flow metering points are to be designed as shown on Cornell Standard Detail 3.1.2, Building Chilled Water Piping Schematic. B. Chilled water BTU metering includes a flow meter, two temperature sensors, and a BTU processor, which is connected to the University EMCS. Basis of design shall use an electromagnetic meter. Contact Cornell for special conditions requiring the use of an ultrasonic meter. Acceptable manufacturers and models shall be as follows: 1. Basis of Design: Siemens Sitrans MAG 3100 (electromagnetic). 2. Alternate: Flexim FLUXUS ADM 7407 (ultrasonic). C. Temperature sensors associated with the chilled water meter shall be Resistance Temperature Device (RTD) as manufactured by JMS Southeast, Inc. Model 3X(X=3TF3)SBK6BZZ312ZWZ2AX(X=Fully Potted). Probe shall have date of manufacture stamped on the surface. Thermowells shall be JMS model 51AT2CUK ½ inch step shank, 316 stainless steel, 0.260 bore sized to insert a minimum of 1/3 pipe diameter into flow stream. The junction box shall be a 2 x 4 handy box connected to the thermowell with CPVC nipples from the well to the head. Terminal connections shall be to a termination strip on the back of the handy box so probe can be removed through the front with the handy box cover removed. Provide a spare test well (identical to the sensing well) with brass cap and chain at all sensor locations. D. The flow meter and temperature sensors shall be coupled to a BTU meter flow processor FP93 as manufactured by EMCO. The flow processor shall be connected to the University EMCS via Ethernet. E. Install meter as shown on Cornell Standard Detail 3.1.7 Electromagnetic Chilled Water Meter Installation Detail or Cornell Standard Detail 3.1.8 Ultrasonic Chilled Water Meter Installation Detail. F. If more than one building loop, or sub meters are required in a single building, multiple FP93 meters shall be connected to the University EMCS via Ethernet. Contact Cornell for metering needs beyond one total building meter. G. Do not disconnect existing chilled water metering until new metering or communications are in place. DATE: 6/30/17 DATE: 6/30/15 Page 5 of 5