MODELS B3CH 048 AND 060 (WORLD 50 HZ)

Similar documents
MODELS B1PA024, 030 AND 036

SUNLINE 2000 ELECTRIC / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: N7Y (993) 530.

MODELS B3CH 090 & 120A25, A46 MODELS B4CH090 & 120A58 (9 EER) 208/230/575 VOLT MODELS ONLY 208/230/460 VOLT MODELS ONLY

Supersedes: N2W (398) N2Z (1298) MODELS BCCB 090 & 120, MODELS BECB090 & 120 (9 EER) 208/230/460 VOLT MODELS ONLY

INSTALLATION MANUAL SUNLINE 2000 SINGLE PACKAGE HEAT PUMP BCH 036, 048 & 060

Supersedes: N2Y (498) N2Y (799) MODELS B1HH018 THRU THRU 5 TON (12 SEER)

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

SUNLINE 2000 SINGLE PACKAGE AIR-COOLED AIR CONDITIONERS DESCRIPTION FEATURES

SUNLINE 2000 GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: N2YI (1096)/ A-0204

SUNLINE SERIES SINGLE PACKAGE AIR CONDITIONERS. INSTALLATION INSTRUCTION Supersedes: Nothing N3Y (394) MODELS D*SC360 & 480 INSPECTION

INSTALLATION MANUAL AFFINITY SERIES SINGLE PACKAGE AIR CONDITIONERS ELECTRIC/ELECTRIC, AIR-COOLED. MODELS: D1EB036 thru Thru 5 Ton (10 SEER)

INSTALLATION MANUAL SUNLINE 2000 SINGLE PACKAGE HEAT PUMP BP

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

SUNLINE PLUS GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: A A-0204

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

Supersedes: N1Y (1099) N1Y (0500) MODELS B1HA018 THRU THRU 5 TON (10 SEER)

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

R-410A AFFINITY SERIES DEX DEY Ton

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

INSTALLATION INSTRUCTION

MODELS K2EU060A, K4EU090A, & K3EU120A

Supersedes: A-0202 MODELS B1HA018 THRU THRU 5 TON (10 SEER)

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

INSTALLATION INSTRUCTION

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

MODELS D1EH018 THRU 060, 1-1/2 THRU 5 TON (12 SEER) AND MODELS D1EM036 THRU 060, 3 THRU 5 TON (13 SEER)

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

R-410A AFFINITY SERIES

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72

MODELS W1LC220, 260 AND 320 STYLE B

INSTALLATION INSTRUCTIONS

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT

INSTALLATION MANUAL SINGLE PACKAGE HEAT PUMP. MODELS: BA-15 and BA-20. ASHRAE 90.1 Compliant. Model BA-15. Model BA-20

SUNLINE 2000 GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: N6Y (593) 530.

MODELS E1FB180 & E1FB240

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

INSTALLATION MANUAL (AIR COOLED) SPLIT-SYSTEM AIR CONDITIONER MODEL: LA120 NOTES, CAUTIONS AND WARNINGS SAVE THIS MANUAL B-0203

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: Nothing N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) GENERAL

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: N1Y (497) N1Y (998) MODELS E2FB090 & E1FB120 GENERAL

DESCRIPTION TECHNICAL GUIDE SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS D(HE, HG) 036, 048 & YTG-A-0506

INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS

ACCESSORY KIT INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTION Supersedes: N7YI (795) N7YI (299)

ELECTRIC / ELECTRIC & GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTRUCTION. Supersedes: N11W (1095) N11W(399)

STELLAR 2000 SINGLE PACKAGE AIR CONDITIONERS GAS/ELECTRIC, AIR-COOLED INSTALLATION INSTRUCTION

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

INSTALLATION INSTRUCTION

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

INSTALLATION INSTRUCTION Supersedes: N11Y (195) N11Y (399)

INSTALLATION INSTRUCTIONS

CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: N4 (778) N4Y (492)

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

THE WALL-MOUNT ONE TON AIR CONDITIONER. Green Refrigerant. 12,000 Btuh EER Right Side Control Panel. Engineered Features

PAR5. Product Specifications

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

INSTALLATION MANUAL SUNLINE GAS/ELECTRIC SINGLE PACKAGE AIR CONDITIONERS D(CE, CG) 036, 048, 060 & 072 D(HE, HG) 036, 048 & 060

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS. HB 180 & thru 20 Nominal Tons NOTES, CAUTIONS AND WARNINGS

PGF SERIES 7-1/2 Ton. Belt Drive CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT

PACKAGE AIR CONDITIONER

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195)

IN STAL LA TION IN STRUC TION

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Advance Release September 2009

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

50HJQ004, 005, 006, 007, 008 & 012 SINGLE-PACKAGE HIGH-EFFICIENCY HEAT PUMP UNITS WITH FIELD-INSTALLED ELECTRIC HEAT

PAD3. Product Specifications. 13 SEER PACKAGE AIR CONDITIONER, 2 to 5 TONS Single Phase, 208/230 V, 60 Hz REFRIGERATION CIRCUIT

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

INSTALLATION INSTRUCTION

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

INSTALLATION INSTRUCTIONS HIGH EFFICIENCY PACKAGED AIR CONDITIONER

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

Model 655A Sizes

INSTALLATION MANUAL - 50 Hz

THE WALL-MOUNT ONE TON AIR CONDITIONER GREEN REFRIGERANT R-410A. 10,800 Btuh 9.00 EER Right Side Control Panel. Engineered Features

Installation Instructions

48TF GAS HEATING/ ELECTRIC COOLING UNITS

Your safety and the safety of others are very important.

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

INSTALLATION INSTRUCTIONS

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

SUBMITTAL DATA SHEET FEATURES. SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15 & 20 TONS MODELS: NH-07 thru -20, 2-PIPE NJ-10 thru -20, 4-PIPE

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

Transcription:

SUNLINE 2000 SINGLE PACKAGE HEAT PUMPS INSTALLATION INSTRUCTION Supersedes: 5.3-NYI (900)/035-2984-000 035-2984-00-A-0204 MODELS B3CH 048 AND 060 (WORLD 50 HZ) GENERAL YORK Model BCH units are single package heat pumps designed for outdoor installation on a rooftop or a slab. Supplemental electric heaters are available as field-installed accessories. The units are manufactured under ISO 9002 Quality System Certification. Units are completely assembled on rigid, permanently attached base rails. All piping, refrigerant charge, and electrical wiring is factory-installed and tested. The units require only electric power and duct connections at the point of installation. The supplemental electric heaters have nickel-chrome elements and utilize single point power connection. INSPECTION As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by the carrier's agent should be made in writing. See local distributor for additional information. REFERENCE Additional information on the design, installation, operation and service of this equipment is available in the following reference forms: 55.70-N 55.70-N2 530.8-N.2V 530.8-N.4V 530.8-N.6V -General Installation -Pre-start & Post-start Check List -Economizer Accessory -Fixed Outdoor Air Damper Accessory -Motorized Outdoor Air Damper Accy. 530.8-N7.V 530.8-N7.2V Renewal Parts: -Electric Heater Accessory -Fuse Block Accessory Refer to Parts Manual for complete listing of replacement parts on this equipment. All forms referenced in this instruction may be ordered from: APPROVALS Standard Register Toll Free Tel: (405) 69-26 Toll Free Fax: (405) 799-7746 These units are designed and manufactured as follows:. For use as a heat pump only unit or a heat pump unit with supplemental electric heat. 2. For outdoor installation only. CAUTION THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE W ITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES. WARNING INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE. Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not handled properly.

TABLE OF CONTENTS General... Inspection... Reference... Approvals... Nomenclature...2 INSTALLATION Limitations...3 Location...3 Condensate Drainage Precaution...3 Rigging and Handling...3 Clearances...3 Ductwork...3 Filters...4 Condensate Drain...4 Service Access...4 Blower Speed Selection...4 Disconnect Switch Bracket For Optional Belt-Drive...4 Compressors...4 Thermostat...4 Power and Control Wiring...4 Electric Heaters...4 Optional Economizer Rain Hood...6 OPERATION Cooling System...2 Preliminary Operation Cooling...2 Cooling Sequence of Operation...2 Heating Sequence of Operation...2 Defrost Sequence of Operation...2 Lockout Control...3 Checking Supply Airflow...3 Secure Owner's Approval...4 MAINTENANCE Normal Maintenance...4 TABLES No. Description Page Unit Application Data... 3 2 Air Flow Limitations... 5 3 Physical Data... 7 4 Supply Air Perferformance BCH048... 0 5 Supply Air Performance BCH060... 0 6 Motor and Drive Data - Belt-Drive Blower.. 0 7 Static Resistances... 0 8 Electrical Data Basic Unit... 9 Electrical Data Heat Pump... 0 Belt-Drive Supply Air Motor Pulley Adj... 3 FIGURES No. Description Page Center of Gravity... 3 2 Recommended Drain Piping... 4 3 Typical Field Wiring... 5 4 Economizer Rain Hood Assembly... 6 5 Adjusting Enthalpy Setpoint... 7 6 Dimensions and Clearances... 8 & 9 7 Defrost Initiation Times... 2 8 Ambient Modified Time/Temp. Control... 2 9 Belt Adjusment... 3 0 Hole Loc. for Press. Drop Readings... 3 Press. Drop versus Supply Airflow... 3 PRODUCT NOMENCLATURE B 3 C H 0 4 8 A 5 0 PRODUCT CATEGORY B = Single Package Heat Pump (Air Cooled) VOLTAGE CODE 50 = 380/45-3+N-50 PRODUCT GENERATION 3 = Third Generation PRODUCT IDENTIFIER CH = Heat Pump NOMINAL COOLING CAPACITY 048 = 4 Ton 060 = 5 Ton FACTORY INSTALLED HEAT A = No Supplemental Heat 2 Unitary Products Group

LIMITATIONS These units must be installed in accordance with national and local or municiple safety codes: Refer to Table for Unit Application Data. If components are to be added to a unit to meet local codes, they TABLE - UNIT APPLICATION DATA Cooling Heating are to be installed at the dealer's and / or the customer's expense. LOCATION Voltage Variation Min. / Max. Wet Bulb Temperature of Air on Indoor Coil, Min./Max. Dry Bulb Temperature of Air on Outdoor Coil, Min./Max. Minimum Dry Bulb Temperature of Air on Outdoor Coil Use the following guidelines to select a suitable location for these units.. Unit is designed for outdoor installation only. 2. Outdoor coil must have an unlimited supply of air. 3. For ground level installation, use a level concrete slab with a minimum thickness of 02mm (4 in.). The length and width should be at least 52mm (6 in.) greater than the unit base rails. Do not tie slab to the building foundation. 4. Roof structures must be able to support the weight of the unit and its options and / or accessories. Unit must be installed on a solid level roof curb or appropriate angle iron frame. CAUTION: If a unit is to be installed on a roof curb or special frame other than a YORK roof curb, gasketing must be applied to all surfaces that come in contact with the unit underside. 5. Maintain level tolerance to 3mm ( 2 in.) maximum across the entire length or width of the unit. 6. Elevate the unit sufficiently to prevent any blockage of the air entrances by snow in areas where there will be snow accumulation. Check the local weather bureau for the expected snow accumulation in your area. OUTDOOR COILCONDENSATE DRAINAGE PRECAUTION Condensate drains from the outdoor coil during the heating and defrost cycles. Normally this condensate may be allowed to drain directly onto the ground/roof. A gravel bed is recommended to prevent mud splashing. WARNING:The unit should not be installed in an area where mud or ice could cause personal injury. Remember that condensate drips from the outdoor coil during heat and defrost cycles and that this condensate freezes when the temperature of the outdoor air is below 0 C (32 F). INSTALLATION 342 / 457 C 4 / 22 F 57 / 72 C 7 / 49 F 45 / 20 C -23 F -0 RIGGING AND HANDLING Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails. Spreaders, whose length exceeds the largest dimension across the unit, MUST be used across the top of the unit. BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY. Units may also be moved or lifted with a forklift. Slotted openings in the base rails are provided for this purpose. LENGTH OF FORKS MUST BE A MINIMUM OF 067mm (42 in.). Remove the nesting brackets from the four corners on top of the unit. All screws that are removed when taking these brackets off must be replaced on the unit. APPROXINATE CENTER OF GRAVITY FIG. - CENTER OF GRAVITY Refer to Table 3 for unit weights and to Figure for approximate center of gravity. CLEARANCES All units require certain clearances for proper operation and service. Refer to Figure 6 for the clearances required for combustible construction, servicing, and proper unit operation. WARNING:Do not permit overhanging structures or shrubs to obstruct outdoor air discharge outlet. DUCTWORK A closed return duct system shall be used. This does not preclude use of economizers or outdoor fresh air intake. The supply and return air duct connections at the unit should be made with flexible joints to minimize the transmission of noise. The supply and return air duct systems should be designed for the airflow and static requirements of the job. They should NOT be sized to match the dimensions of the duct connections on the unit. CAUTION: When fastening ductwork to the side duct flanges on the unit, insert the screws through the duct flanges only. DO NOT insert the screws through the casing. Outdoor ductwork must be insulated and waterproofed. Refer to Figure 6 for information concerning side and bottom supply and return air duct openings. FILTERS 502 40 44 7 9 3 4 8 035-2984-00-A-0204 Each unit is supplied with 25mm ( in.) filters. Replacement 5mm (2 in.) filters may be used without modification to the filter racks. Filters must always be installed ahead of the evaporator coil and must be kept clean or replaced with same Unitary Products Group 3 BACK 035 40 3 4 CONDENSER COIL END FRONT 2089 82 4

size and type. Dirty filters reduce the capacity of the unit and result in frosted coils or safety shutdown. Minimum filter area and required sizes are shown in Table 3. CONDENSATE DRAIN Plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install a condensate drain line from the 9mm ( 3 4 in.) PVC female connection on the unit to 5 2" 76 3" FIG. 2 - RECOMMENDED DRAIN PIPING spill into an open drain. NOTE: The condensate drain line MUST be trapped to provide proper drainage. See Figure 2. SERVICE ACCESS Access to all serviceable components is provided by the following removable panels: Compressor compartment Heater compartment Blower compartment Main control box Filter compartment Motor Access (on units w/belt-drive option) Refer to Figure 6 for location of these access panels. BLOWER SPEED SELECTION Three blower motor speeds are available on the BCH048 units. The speed selection is determined by the airflow and ESP requirements of the applications. BCH060 units have an adjustable motor pulley to achieve the above conditions. BCH048 units are shipped with the black wire (labeled #8) connected to the high speed tap on the blower motor. If a lower blower speed is desired, this wire should be moved to the medium or low speed tap on the motor. DISCONNECT SWITCH BRACKET FOR UNITS WITH OPTIONAL BELT-DRIVE BRACKET A special bracket for mounting a field-supplied disconnect switch is provided in each BCH060. The bracket is shipped inside the blower compartment taped to the top of the blower housing. Install the bracket on the left hand side of the unit as shown in Figure 6. Several existing screws at the top of the unit and one approximately midway down from the top will be used for mounting the bracket. Screws should be loosened only - NOT REMOVED. Mounting holes in the bracket have elongated keyways allowing easy installation. Re-tighten screws after bracket is in place to ensure panels will remain leak tight. COMPRESSORS On some units the compressor is mounted on springs which have been tightened down for shipment only. After this unit is installed, back out the compressor bolts until the sleeve clears the top grommet. CAUTION: Do Not loosen compressor mounting bolts. THERMOSTAT The room thermostat should be located on an inside wall approximately 422mm (56 in.) above the floor where it is not subjected to drafts, sun exposure, or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with thermostat for general installation procedure. Color coded insulated wires (#8 AWG) should be used to connect thermostat to unit. See Figure 3 for wiring details. NOTE: On units with economizer, remove jumper J" from terminals 8 and 0 on plug connector J3/P7 on the relay board in the unit control box. Refer to the unit wiring labels located on the inside of the control box access panel. An Emergency Heat position is provided with the thermostat. In the Emergency Heat position, the thermostat allows electric resistance heat only. The compressor is locked out. A pilot light on the thermostat indicates that the switch is on EM HT. POWER AND CONTROL WIRING Voltage tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table. The wiring harness furnished with this unit is an integral part of the unit. Field alteration to comply with electrical codes should not be required. A disconnect switch should be field provided for the unit. The switch must be separate from all other circuits. Refer to Figure 6 for installation location. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram. Electrical lines must be sized properly to carry the load. USE COPPER CONDUCTORS ONLY. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly protected. CAUTION: When connecting electrical power and control wiring to the unit, waterproof type connectors MUST BE USED so that water or moisture cannot be drawn into the unit during normal operation. The above waterproofing conditions also apply when installing a field-supplied disconnect switch. Refer to Figure 3 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information. Refer to Tables 8 and 9 for electrical data. ELECTRIC HEATERS Supplemental electric heaters may be ordered as a fieldinstalled accessory. Refer to Form 530.8-N7.V for installation instruction. These approved heaters are located within the central compartment of the unit (see Figure 6 for access panel) with the heating elements extending into the supply air chamber. Fuses are supplied, where required, by the factory. Some kw sizes require fuses and others do not. Refer to the electric 4 Unitary Products Group

TABLE 2 - AIR FLOW LIMITATIONS NOMINAL HEATER SIZE KW 7 0 5 20 30 VOLTAGE 380/45-3+N-50 UNIT MODEL SIZE, NOMINAL TONS 4 5 MINIMUM SUPPLY AIR CFM,300,300,300,300,600,600,600,600,600 CONTROL WIRING Typical 24-volt thermostat with subbase -2ET03700424 for manual changeover. 2 Only required on units with supplemental electric heat. Note: The thermostat terminals shown above are typical. Check thermostat and unit wiring diagrams for correct wiring connections. TO REMOTE SENSOR 2ET0470324 IF USED Typical Electronic programmable thermostat 2ET047024 with subbase for either manual or automatic changeover. 2 Only required on units with economizer. Remove jumper L2 from terminals 4 and 9 on jumper plug P7. The outdoor air intake dampers will return to their fully closed position when the thermostat switches to the unoccupied mode. 3 Second stage cooling may be used on units with economizer. Remove jumper J from terminals 8 and 0 on jumper plug connector P7. 4 Only required on units with supplemental electric heat. POWER WIRING CONTACTOR NEUTRAL TERMINAL BLOCK FIELD-SUPPLIED DISCONNECT GROUND LUG REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, THE WIRING AND THE OVERCURRENT PROTECTION. FIG. 3 - TYPICAL FIELD WIRING Unitary Products Group 5

heater accessory installation instruction for the heater electrical data. The minimum air flow limitations across these heaters are listed in Table 2. OPTIONAL ECONOMIZER RAIN HOOD The following procedure should be used when assembling an economizer rain hood onto a unit. Refer to Figure 4. The outdoor and return air dampers, damper actuator, the linkage and all the controls are factory mounted as part of the economizer option. All of the hood components, including the filters, the gasketing and the hardware for assembling are located above the top filter racks within the filter section. The outdoor air sensor is in the bag of parts located at the bottom of the return air section.. With filter section access panel removed, take out hood components, filters and sensor described above. Remove and discard outdoor air opening cover on back unit (Upper right hand corner). 2. Remove the 3mm ( 2 in.) knockout (A) in the units rear panel (located to the right side of the outdoor air opening). Insert the two loose wires from inside the unit, into the 3mm ( 2 in.) bushing provided. Insert wires and bushing into knockout. Snap bushing into place. 3. Mount the outdoor air sensor to the rear panel, just below the knockout described in Step 2. Secure with two selfdrilling screws at dimples (B) provided in the panel. NOTE: Sensor must be positioned so that the sensing ports are at the top (louvers pointing downward) and terminal connections to the right. 4. Connect the two wires, indicated in Step 2, to the sensor as follows: Wire #73 to terminal (+) Wire #74 to terminal (S) 5. Assemble the LH and RH side plates to the top cover (2 screws each side) to form the hood. Apply gasketing to the flange surface on each side plate. Extend gasketing 6mm ( 4 in.) beyond top and bottom of each flange to insure adequate corner sealing. Secure this assembly to the unit back panel (upper right hand corner). First, remove screw (C) on unit top cover. Then slip flange of hood cover in under flange of unit top cover, replace screw (C), engaging hole (E) in hood flange and tighten. Attach the two side plates to the unit panel by using two self-drilling screws for each side plate at dimples (D) provided in the panel. 6. Position fillpiece at bottom of hood, between the two side plates but do not secure at this time. (Slotted openings MUST be downward for drainage). After fillpiece is properly positioned, note where contact is made with the unit panel. Remove fillpiece and apply gasket material to this area to provide a seal. Reposition fillpiece and secure with 2 screws. 7. Install the two filters into the hood assembly, sliding down along retainers on side plates, into fillpiece at bottom of hood. NOTE: Install filters so that Air Flow arrows point toward the unit. 8. Install filter cover over the end of the hood with one screw (center of hood), securing filters into position. CAUTION: When proceeding with steps 9 and 0, extreme care must be exercised while turning both the set point and minimum position adjusting screws to prevent twisting them off. 9. The enthalpy set point for the dampers may now be set by selecting the desired set-point from graph in Figure 5. For a single enthalpy economizer, carefully turn the set-point adjusting screw to the A, B, C or D setting corresponding to the lettered curve. For a dual enthalpy economizer, carefully turn the set-point adjusting screw fully clockwise past the D setting. 0. To check that the damper blades move smoothly without binding, carefully turn the minimum position adjusting GASKETED FLANGE FILTER COVER HOOD COVER E D D OUTDOOR AIR OPENING COVER B C A D D OUTDOOR AIR SENSOR GASKET L. H. SIDE PLATE GASKETED FLANGE FILTER SECTION ACCESS PANEL FILTERS R. H. SIDE PLATE SIDE DUCT APPLICATION SHOWN FILLPIECE FIG. 4 - ECONOMIZER RAIN HOOD ASSEMBLY (OPTION) 6 Unitary Products Group

FIG. 5 - ENTHALPY SET POINT ADJUSTMENT TABLE 3 - PHYSICAL DATA SUPPLY AIR BLOWER INDOOR COIL OUTDOOR FAN OUTDOOR COIL MODELS CENTRIFUGAL BLOWER (Dia. x Wd.,mm/in.) FAN MOTOR HP (Direct-Drive Units) FAN MOTOR HP (Belt-Drive Units) ROWS DEEP FINS PER 25mm ( inch) FACE AREA (m 2 /ft 2 ) PROPELLER DIA. (mm/in.) FAN MOTOR kw/hp NOM. CFM TOTAL ROWS DEEP FINS PER 25mm ( inch) FACE AREA (m 2 /ft 2 ) QUANTITY PER UNIT (4" x 20" x ") QUANTITY PER UNIT (4" X 25" X ") TOTAL FACE AREA (m 2 / ft 2.) BCH 048 060 305 x254 2 x 0 0.75 NA 3 5 0.47 / 5. 60 / 24 0.37 / 0.5 4,200 20 7. 2 6.3 305 x 254 2 x 0 NA.5 3 5 0.47 / 5. 60 / 24 0.37 / 0.5 4,500 20 7. 2 6.3 AIR FILTERS (SEE NOTE) CHARGE REFRIGERANT 22 (kg / lbs./oz.) 4.2 / 9.2 3.7 / 8/4 NOTE: Filter racks are adapted for " or 2" thick filters. WEIGHTS (kg/lbs) 048 270 / 595 Basic Unit 060 28 / 620 OPTIONS / ACCESSORIES 5-7 kw 8.2 / 8 Electric Heat (Nominal Kw) 0-5 kw 0.4 / 23 20-30 kw 2.7 / 28 Economizer 22.7 / 50 Motorized Outdoor Air Damper 2.8 / 48 Barometric Relief/Fixed Outdoor Air Intake Damper 4.5 / 0 Roof Mounting Curb 4.7 / 92 Belt-Drive Blower 2.3 / 5 Unitary Products Group 7

(Direct-Drive Units) OUTDOOR COIL 829 32-5/8" 2090 82-/4" RETURN AIR 40 44-7/8" 64 2-/2 SUPPLY AIR 292 -/2" OUTDOOR AIR 37 5-3/8 445 7-/2" 7 200 6-3/4" 7-7/8" 206 8-/8" 65 6-/2" 445 7-/2" OUTDOOR AIR (Economizer) All dimensions are in millimeters and inches. They are subject to change without notice. Certified dimensions will be provided upon request. 23 8-3/8" UTILITIES ENTRY DATA KNOCKOUT HOLE SIZE (DIA.) A 5mm (7/8") * B 5mm (2") * USED FOR Control Wiring (Side or Bottom)** Power Wiring (Side or Bottom) *Knockouts in the bottom of the unit can be located by the slice in the insulation. **Do not remove the 2" knockout ring. Front 60mm (24") Back 25mm (2") (Less Economizer) 94mm (36") (With Economizer) Left Side (Filter Access) 60mm (24") (Less Economizer) 94mm (36") (With Economizer) Right Side (OD Coil) 60mm (24") Below Unit 0mm (0") Above Unit 2 829mm (72") (For Outdoor Air Discharge) NOTE: Units and ductwork are approved for zero clearance to combustible materials when equipped with electric heaters. FIGURE 6 - DIMENSIONS & CLEARANCES Units may be installed on combustible floors made from wood or class A, B or C roof covering material. 2 Units must be installed outdoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet. 8 Unitary Products Group

REAR VIEW 437 7 2 SIDE SUPPLY AND RETURN AIR DUCT OPENINGS 65 6 2 437 7 2 200 7 7 8 292 2 76 3" 292 2 7 4 5 8 DUCT COVERS - Units are shipped with all air duct openings covered. For side duct applications;.remove and discard the supply and return air duct covers. 2.Connect ductwork to duct flanges on the rear of the unit. For bottom duct applications;. Remove the side supply air duct cover to gain access to the bottom supply air knockout panel. 2. Remove and discard the bottom knockout panel. 3. Replace the side duct cover. 4. With filter section access panel removed from the unit, remove and discard the bottom return air knockout panel. 698 27 2 4 5 8 638 27 2 3 4 CONDEN- SATE DRAIN CONN. (Must be trapped) 502 9 3 4 REAR VIEW DETAIL A UNIT WITH ECONOMIZER RAINHOOD 267 9 2 40 44 7 8 L.H. END VIEW REAR VIEW 454 84 7 7 7 4 8 46 6 3 8 DETAIL B UNIT WITH FIXED OUTDOOR AIR / BAROMETRIC RELIEF RAINHOOD 7 4 5 8 260 340 0 4 44 7 8 L.H. END VIEW B 260 0 4 89 3 2 A 4 3 8 20 8 4 FIGURE 6 - DIMENSIONS & CLEARANCES (continued) Unitary Products Group 9

TABLE 4 - SUPPLY AIR PERFORMANCE - BCH048 380 / 45 VOLTS - SIDE DUCT APPLICATIONS MODEL 048 MODEL 048 MOTOR SPEED HI MED LOW MOTOR SPEED HI MED LOW Available External Static Pressure - Pa* m 3 /s Watts m 3 /s Watts m 3 /s Watts m 3 /s Watts m 3 /s Watts m 3 /s Watts m 3 /s Watts m 3 /s Watts m 3 /s Watts - - - - 0.94 00 0.92 975 0.90 945 0.87 90 0.83 825 0.78 825 0.72 775 0.85 90 0.84 880 0.82 850 0.80 825 0.79 800 0.76 775 0.74 740 0.70 700 0.66 660 0.77 80 0.76 780 0.75 760 0.73 740 0.73 730 0.7 75 0.69 690 0.66 660 0.6 65 Available External Static Pressure - IWG* 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90.00 CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts - 80 635-90 80-780 60-880 780 2000 740 580 00 850 760 950 700 555 *INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND " FILTERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS. 975 825 740 905 665 540 945 800 730 840 620 50 90 775 75 770 560 460 825 740 690 660 480 400 825 700 660 530 390 300 775 660 65 TABLE 5 - SUPPLY BLOWER PERFORMANCE - BCH060 MODEL AIR FLOW m 3 /s / CFM Available External Static Pressure -Pa/ IWG* 223 / 0.90 248 /.00 273 /.0 298 /.20 322 /.30 347 /.40 372 /.50 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts.8 / 2500 - - - - - - - - - - - - - -.3 / 2400 93 665 - - - - - - - - - - - -.08 / 2300 70 580 202 620 - - - - - - - - - -.04 / 2200 48 480 80 530 - - - - - - - - - - 0.99 / 200 2 385 55 425 90 475 - - - - - - - - 060 0.94 / 2000 00 285 33 340 69 385 205 445 - - - - - - 0.90 / 900 079 80 0 240 43 280 78 330 222 375 - - - - 0.85 / 800 058 060 090 35 22 90 58 240 96 295 - - - - 0.80 / 700 035 960 07 030 03 00 34 40 64 75 97 205 - - 0.75 / 600 020 900 056 965 088 035 8 065 45 05 70 30 98 50 0.7 / 500 004 860 038 880 070 925 0 980 30 045 58 075 84 0 *INCLUDES ALLOWANCES FOR A WET INDOOR COIL AND " FILTERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN HEAT PUMP UNITS WITH SIDE DUCT AIRFLOWS. TABLE 6 - MOTOR AND DRIVE DATA - Belt-Drive Blower MODEL BLOWER RANGE (RPM) kw/hp RPM MOTOR* FRAME SIZE SERVICE FACTOR BCH060 850-80 0.75/.0 450 56.5 ADJUSTABLE MOTOR PULLEY PITCH BORE DIA. mm (in.) mm (in.) 7-97 (2.8-3.8) FIXED BLOWER PULLEY PITCH BORE DIA. mm (in.) mm (in.) PITCH LENGTH (mm in.) BELT DESIG- NATION 22 27 (5.0) 25 () 947 (37.3) A36 *All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device. TABLE 7 - STATIC RESISTANCES* EXTERNAL STATIC PRESSURE DROP RESISTANCE, Pa/IWG DESCRIPTION m 3 /s/cfm 0.47/000 0.57/200 0.66/400 0.75/600 0.85/800 0.94/2000.04/2200.3/2400.232600 Economizer/Motorized Damper, 2 7 / 0.07 20 / 0.08 22 / 0.09 27 / 0. 32 / 0.3 37 / 0.5 42 / 0.7 50 / 0.20 57 / 0.23 Electric Heaters 5-5 KW 0 / 0.04 2 / 0.05 5 / 0.06 7 / 0.07 20 / 0.08 25 / 0.0 30 / 0.2 35 / 0.4 40 / 0.6 20-30 KW 5 / 0.06 7 / 0.07 20 / 0.08 22 / 0.09 27 / 0. 32 / 0.3 37 / 0.5 42 / 0.7 50 / 0.20 Bottom Duct Connections 5 / 0.06 7 / 0.07 20 / 0.08 22 / 0.09 25 / 0.0 27 / 0. 30 / 0.2 35 / 0.4 40 / 0.6 Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table. 2 The pressure thru the economizer is greater for 00% outdoor air than for 00% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation. 0 Unitary Products Group

TABLE 8 - ELECTRICAL DATA - Basic Unit MODEL BCH POWER SUPPLY VOLTAGE LIMITATIONS COMPRESSOR OUTDOOR FAN MOTOR, FLA MIN. MAX. RLA LRA SUPPLY AIR BLOWER MOTOR, FLA TOTAL UNIT AMPACITY, AMPS MAX. FUSE SIZE, (SEE NOTE ) AMPS MAX. HACR BREAKER SIZE, MIN. WIRE SIZE, AWG (SEE NOTE 2) AMPS 048 380/45-3+N-50 342 457 9.6 66.8 4.0 8.3 25 25 0 (6MM 2 ) 060 380/45-3+N-50 342 457 0.0 75.8 2.6 6.9 25 25 0 (6MM 2 ) NOTES:. Dual element, time delay type. 2. Based on 75 C copper conductors. TABLE 9 - ELECTRICAL DATA - Heat Pump with Supplemental Electric Heat MODEL BCH POWER SUPPLY 048 380/45-3+N-50 060 380/45-3+N-50 HEATER ACCESSORY MODEL NUMBER 2CE0450746* 2CE045046* 2CE045546* 2CE0452046* 2CE0450746* 2CE045046* 2CE045546* 2CE0452046* 2CE0453046* SUPPLY AIR BLOWE R MOTOR FLA 4.0 2.6 ELECTRIC HEATERS KW STAGES TOTAL AMPS 4.3 / 5. 6.3 / 7.5 8.5 / 0.2 2 / 4.6 4.3 / 5. 6.3 / 7.5 8.5 / 0.2 2 / 4.6 8 / 22 2 2 2 7. 0.5 4. 20.3 7. 0.5 4. 20.3 30.0 TOTAL UNIT AMPACITY AMPS 26.5 30.3 34.5 4. 25.7 30.0 34.6 42.2 54.3 MAX. FUSE SIZE, (SEE NOTE ) AMPS 30 35 40 45 30 35 40 45 60 MAX. HACR BREAKER SIZE, AMPS 30 35 40 45 30 35 40 45 60 MIN. WIRE SIZE, AWG (SEE NOTE 2) 0 (6mm 2 ) 8 (0mm 2 ) 8 (0mm 2 ) 8 (0mm 2 ) 0 (6mm 2 ) 8 (0mm 2 ) 8 (0mm 2 ) 8 (0mm 2 ) 6 (6mm 2 ) Unitary Products Group

screw fully clockwise and then energize and de-energize terminals R to G. With terminals R to G energized, turn the minimum position screw counterclockwise until the desired minimum position has been attained.. Replace the filter section access panel. COOLING SYSTEM The unit has an air-cooled condenser and is factory-charged with Refrigerant-22. The compressor is hermetically sealed, internally sprung, mounted on spring isolators and inherently (internally) protected. If there is an abnormal temperature rise in the compressor, the protector opens to shut down the compressor. PRELIMINARY OPERATION COOLING After the installation has been completed, the crankcase heater of the compressor must be energized for at least 4 hours before starting the unit. After this initial warm-up, the compressor should be given three false starts (energized just long enough to make a few revolutions) with a 5 minute delay between each start before being put into full time service. NOTE: Prior to each cooling season, the crankcase heater must be energized at least 0 hours before the system is put into operation. COOLING SEQUENCE OF OPERATION When the thermostat calls for cooling, the compressor and the outdoor fan motor will be energized through terminal Y" and the supply air blower motor will be energized through terminal G" (if the fan switch on the subbase is set in the AUTO position). The supply air blower motor will run continuously if the fan switch is set in the ON position. The reversing valve is energized thru the O circuit when the subbase is in the cooling mode. HEATING SEQUENCE OF OPERATION The following sequence of operation is based on using a standard YORK heat pump thermostat with two heating stages. FIRST STAGE HEAT When the thermostat calls for heating, the compressor and the outdoor fan motor will be energized through terminal Y" and the supply air blower motor will be energized through terminal G" (if the fan switch on the subbase is set in the AUTO position). The supply air blower motor will run continuously if the fan switch is set in the ON position. OPERATION TIME BETWEEN DEFROST CYCLES, MINUTES 250 200 50 00 50 0 T3-0 Minute Setting (Factory Set Point) T - 50 Minute Setting FIG. 7 - DEFROST INITIATION TIMES adjusted to defrost at 80 minutes (T2) or 50 minutes (T) in areas with high humidity. The curve in Figure 7 shows how defrost initiation times are automatically compensated for changes in outdoor temperature. EXAMPLE: If the time is factory set on pin T-3 (0 minutes at 2 C (35 F) outdoor) and the outdoor temperature climbs to 7 C (45 F), the time initiation cycle decreases to 00 minutes. If the outdoor temperature drops to -2 C (0 F) where ice is less likely to form, the 0 minute interval increases to 50 minutes. Two requirements must be met before a defrost cycle can be initiated.. The defrost time cycle must be complete. T2-80 Minute Setting -0 0 0 20 30 40 50 OUTDOOR AMBIENT, DEG. F 2. The liquid line temperature must be less than -2 C (28 F). Defrost terminates when the liquid line sensor reaches 3 C (55 F) or after 0 minutes. The defrost time cycle restarts 0 minutes after the start of the defrost cycle even though the liquid sensor terminated defrost after 3 minutes. T2-80 MINUTE SETTING T3-0 MINUTE SETTING (Factory Set Point) 60 T - 50 MINUTE SETTING SECOND STAGE HEAT If compressor operation can not satisfy the heating requirements, second stage heat will energize supplemental electric heat (if supplied) thru the W" circuit. DEFROST SEQUENCE OF OPERATION The BCH has a unique ambient modified time-temperature defrost control that automatically adjusts to changes in the outdoor temperature. The defrost control will shorten the defrost initiation time periods above 2 C (35 F) and will extend the defrost initiation time periods below 2 C (35 F). The control is factory set to defrost at 0 minutes (T3), but it can be field SHORTING PEGS TO OVERRIDE TIMER FOR SERVICE MOVABLE JUMPER WIRE TO CHANGE DEFROST TIMER FIG. 8 - AMBIENT MODIFIED TIME/TEMPERATURE CONTROL 2 Unitary Products Group

During troubleshooting, the defrost time can be reduced to 20 seconds by shorting out the SW test pegs on the module. The pegs are 3mm ( 2 in.) long, mm ( 3 6 in.) apart and are mounted on a white base. See Figure 8. 035-2984-00-A-0204 LOCKOUT CONTROL Any one of four conditions will put the system into a lock-out condition during the heating or cooling mode:. The discharge line temperature reaches 24 C (255 F) (02 C [25 F] reset) or, 2. The discharge pressure reaches 2770 kpa (398 PSIG) (258 kpa [30 PSIG] reset) or, 3. The suction line freezestat equals -3 C (26 F) (3 C [38 F] reset) or, 4. The low-pressure cut-out equals 49 kpa (7 PSIG) (53 kpa [22 PSIG] reset). A lock-outl energizes the emergency heat light on the thermostat and the red LED light on the unit relay board. Turning the thermostat switch to Off then back to On, will reset the system. NOTICE TO OWNER: If a lockout occurs, check for the following problems before calling a serviceman:. Dirty filters. 2. Snow accumulation. 3. Leaf or debris blockage. After eliminating the problem, attempt to restart the system as follows: turn the system switch on the thermostat to its OFF position for 0 seconds. turn it back to its original position. If the unit doesn't start, call a serviceman. NOTE: Models with an anti-recycle accessory will have a 5- minute delay before starting. CHECKING SUPPLY AIRFLOW The speed of the supply air blower will depend on the required airflow, the unit accessories and the static resistances of both the supply and the return air duct systems. With this information, the speed for the supply air blower can be TABLE 0 - BELT-DRIVE SUPPLY AIR MOTOR PULLEY ADJUSTMENT TURNS BLOWER DRIVE RANGE (RPM) OPEN* 060 5 850 4 96 3 982 2 048 4 0 80 *Pulley can be adjusted in half-turn increments. determined from the blower performance and static resistance data on Tables 4, 5 and 7. Knowing the required blower RPM and the blower motor kw (HP), the speed setting for the supply air motor can be determined. The setting (turns open) for the optional belt-drive supply air pulley can be determined from Table 0. OPTIONAL BELT-DRIVE BLOWER All units with belt-drive blowers have single speed motors. The variable pitch pulley on the blower motor can be adjusted to FIG. 9 - BELT ADJUSTMENT obtain the desired supply airflow. Refer to Table 6 for blower motor drive data. The tension on the belts should be adjusted as shown in Figure 9. Start the supply air blower motor. Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space. The job specifications may require that this balancing be done by someone other than the equipment installer. To check the supply airflow after the initial balancing has been completed: DAMPER ASSEMBLY FILTERS DUCT FLANGES (Back of Unit) 49 6 435 7 2 8 L.H. END VIEW (Filter Access End) INDOOR COIL 5 6 HOLES FRONT OF UNIT FIG. 0 - HOLE LOCATIONS (PRESS. DROP READING). Drill two 8mm ( 5 6 in.) holes in the side panels as shown in Figure 0. 2. Insert at least 203mm (8 in.) of 6mm ( 4 in.) tubing into each of these holes for sufficient penetration into the air flow on both sides of the indoor coil. NOTE: The tubes must be inserted and held in a position perpendicular to the air flow so that velocity pressure does not affect the static pressure readings. Unitary Products Group 3 533 2"

3. Using an inclined manometer, determine the pressure drop across a dry indoor coil. Since the moisture on an indoor coil may vary greatly, measuring the pressure drop across a wet coil under field conditions would be inaccurate. To ensure a dry coil, the compressors should be de-energized while the test is being run. 4. Knowing the pressure drop across a dry coil, the actual airflow through the unit can be determined from the curve in Figure. WARNING: Failure to properly adjust the total system air quantity can result in poor system performance. After readings have been obtained, remove the tubes and seal the drilled holes in the side panels. 8mm ( 5 6 in.) dot plugs (P/N 029-3880) are available through normal parts ordering procedures. NOTE: DE-ENERGIZE THE COMPRESSORS BEFORE TAKING ANY TEST MEASUREMENTS TO ENSURE A DRY INDOOR COIL. SECURE OWNER'S APPROVAL: When the system is functioning properly, secure the owner's approval. Show him the location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust temperature settings within the limitations of the system. MAINTENANCE NORMAL MAINTENANCE CAUTION: Prior to any of the following maintenance procedures, shut off all power to the unit to prevent personal injury. FILTERS - Inspect once a month. Replace disposable or clean permanent type as necessary. DO NOT replace permanent type with disposable. MOTORS - Indoor fan and outdoor fan motors are permanently lubricated and require no maintenance. OUTDOOR COIL - Dirt should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit. Cleaning should be as often as necessary to keep coil clean. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean coil, be sure power to the unit is shut off prior to cleaning. NOTE: Exercise care when cleaning the coil so that the coil fins are not damaged. Do not permit the outdoor air discharge to be obstructed by overhanging structures of shrubs. 4 Unitary Products Group

Unitary Products Group 5