Instruction Manual - Anti-Siphon Ejector Chlorine & Sulfur Dioxide 500 PPD (10 kg/h) Maximum Capacity

Similar documents
CAPITAL CONTROLS SERIES 480

Instruction Manual Series 1650/1660 Gas Detector Sensor CAPITAL CONTROLS

Capital Controls Series 480 All vacuum gas feeders designed for manual or semi-automatic gas regulation.

Instruction Manual CHLORALERT TM Series T17CA4000 Chlorine Gas Leak Detector CAPITAL CONTROLS

Electrochemical Chlorine Sensor Module Addition or Replacement Series 1610B And 1620B

TIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL

Clean & Clear. Cartridge Filter System Owner s Manual IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

Models Series Series

SuperKlean Washdown Products

LC Series - Light Commercial Pump Station Installation and Operation Manual

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

BURWELL BIDET TOILET SEAT INSTALLATION

Instruction Manual Vaporizer for Chlorine or Sulfur Dioxide Series VAX4600

Wallace & Tiernan Gas Feed Systems V2000 Chlorinator

Models Series Series

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

ONE PIECE TOILET LT3. Model: MPN: B0940 INSTALLATION INSTRUCTIONS. Version: 1.0

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Models: FM FM WARNING

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Model Series ELECTRIC WATER SYSTEM PUMP. PumpAgents.com - buy pumps and parts online. Model Series. Automatic Multi-Outlet FEATURES

Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT


INSTALLATION & OPERATING INSTRUCTIONS

The Danger signal indicates an immediately hazardous situation which, if not avoided, will result in death or serious injury.

Model Series Series

Series 1140 and 1141 Temperature Regulators

AC6 & AC8 HORIZONTAL SERIES Sealed Metallic Centrifugal Pumps Installation and Maintenance Instructions

SuperKlean Washdown Products

VERTICAL GLANDLESS PUMP

CHAMPION PUMP OWNER S MANUAL

SERVICE MANUAL. Bradford White ElectriFLEX HD (Heavy Duty) Commercial Electric Water Heater CEHD SERIES Immersion Thermostat Models

Audi-Larm Audible Alarm

OWNERS GUIDE TO INSTALLATION AND OPERATION

GETZ MANUFACTURING PART NO.: MODEL: SV1 100 PR VACUFILL SYSTEM (Revised 6/7/05)

CAPITAL CONTROLS SERIES WP70CV3 GAS FEEDERS

Venco 75mm (3 ) Standard and De-airing Pugmill

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER

HE120, HE160 Humidifier Installation Kit

EDGEMERE DUAL CONTROL WIDESPREAD LAVATORY FAUCET INSTALLATION INSTRUCTIONS

SMF PUMP OWNER S MANUAL

ECONO FLO 2.7HP VARIABLE SPEED PUMP OWNER S MANUAL

DAD-500 (130026) DESICCANT AIR DRYING SYSTEM

Installation S

HE360 Humidifier Installation Kit

JOHN DEERE GATOR HPX/XUV 2 PASSENGER HEATER INSTALLATION INSTRUCTIONS (p/n: 9PH20S30)

Installation S

Installation S

HX Field Replacement Kit

HE220, HE260 Humidifier Installation Kit

Installation S

Operating Manual. Model: Float-Controlled Condensate Trap, PN Safety instructions. 2 General description and usage

Elite Primer Baldor Series External Pond Pump

Food Waste Disposer Instruction Manual

INSTALLATION INSTRUCTIONS

K Specifications. Max. Water Volume

SYSTEMS for CATALYTIC FILTERS

KC22/32 SERIES Sealless Non-Metallic Centrifugal Pumps Installation and Maintenance Instructions

SELF-PRIMING CENTRIFUGAL PUMPS BMLS-M & BMLS-H

INFINITY FLUIDS CORPORATION

"S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16

SHURFLO BLASTER II MARINE WASHDOWN PUMP PRODUCT TECHNICAL DATA SHEET

HALLMARK INDUSTRIES INC. HALLMARK INDUSTRIES INC. Safety WARNING WARNING. Must reset the voltage! Shallow Well Jet Pumps

TECHNICAL INSTRUCTIONS

OWNER S MANUAL FOR AIR ADMIRAL VACUUM/PRESSURE STATION MODELS:

INSTALLATION INSTRUCTIONS

2 SPEED PUMP INSTRUCTION MANUAL READ THIS MANUAL CAREFULLY BEFORE USING YOUR 2 SPEED PUMP

INSTALLATION INSTRUCTIONS

INSTRUCTION AND REPAIR MANUAL

MEMOIRS VITREOUS CHINA TOILETS

Niles Steel Tank Hot Water Generator Installation and Operation Manual

541D19 SERIES. Technical Manual. A Division of Aquion Partners L.P.

GETZ EQUIPMENT INNOVATORS PART NO.: 9G58619 MODEL: SV1 150 PR VACUFILL SYSTEM (Revised 2/25/14)

Mini Tank water heater Electric undersink Water heaters GL GL 4 - GL 6+

Model: 1200 Model: 1200-G Model: 1200-N Float-Controlled Condensate Trap, PN 40

Installation Manual PS-200 & PS-201

REVE ORDERING INFORMATION NOTES T01-A INSTALLATION INSTRUCTIONS 现代型分体座便器 CONTEMPORARY TWO-PIECE TOILET K-17178T-S/K-17178T-SP

OWNER S MANUAL CAVN SERIES SELF CONTAINED RETRACTABLE NOZZLE VACUUM SEALER WITH GAS PURGE

Instant Hot Water Dispenser Owner s Manual

13-1. Temperature Regulator

Safety. Rinse Kit for Multi-Pro 1200 and 1250 Turf Sprayers Model No Safety and Instructional Decals. Installation Instructions

IB 835. Installation Manual. Integrated Bidet Toilet TABLE OF CONTENTS

DRY AIR SYSTEMS, INC Metro Boulevard Maryland Heights, Missouri (314) fax (314)

Powers TM Controls TH 188 Unit Mounted Thermostat

MAXI PUMP INSTRUCTION MANUAL NE6151B /NE6171B READ THIS MANUAL CAREFULLY BEFORE USING YOUR MAXI PUMP

Welcome! Today s topic: Small Home Repairs. November 14, 2015

PURest Air Dryer Installation and Maintenance

INSTALLATION INSTRUCTIONS

OPERATING AND MAINTENANCE MANUAL FOR ELECTRIC STAINLESS STEEL HEATER FOR DEIONIZED (DI) WATER ELECTRIC HEATER COMPANY BASE MODEL D

Professional Series. Chemical Feed System Model # US Patent No. 6,752,930 B2

Installation Manual PS-225 & PS-275

OWNER S MANUAL AVN SERIES RETRACTABLE NOZZLE VACUUM SEALER WITH GAS PURGE

GASS Module. User Manual. Gas Analysis Sampling System PERMA PURE

MODEL A-316 CARBON MONOXIDE (CO) MONITOR AND ALARM FOR COMPRESSED AIR TESTING

Series 47 and 247 Mechanical Water Feeders. Series 47-2 and Combination Mechanical Water Feeder/Low Water Cut-Off ! WARNING

ECONO FLO VSA 165 VARIABLE SPEED PUMP OWNER S MANUAL

TECHNICAL INSTRUCTIONS

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Transcription:

- Anti-Siphon Ejector Chlorine & Sulfur Dioxide 500 PPD (10 kg/h) Maximum Capacity 100 PPD (2 kg/h) Chlorine or Sulfur Dioxide 250 & 500 PPD (5 & 10 kg/h) Chlorine or Sulfur Dioxide Anti-Siphon Ejector 122.6015.0

These instructions generally describe the installation, operation and maintenance of subject equipment. De Nora Water Technologies, Inc. reserves the right to make engineering refinements that have not been described herein. Questions that cannot be answered specifically by these instructions should be directed to your local sales representative or De Nora Water Technologies. De Nora Water Technologies takes all possible precautions in packaging each item to prevent shipping damage. Carefully inspect each item and report damages to the shipping agent for equipment shipped F.O.B. Colmar, or to De Nora Water Technologies for equipment shipped F.O.B. job site. Do not install any damaged equipment. Follow instructions given on labels and attached tags. Carefully inspect all packing materials before discarding to prevent loss of accessories, mounting hardware, spare parts, or instructions. 122.6015.0-2 - Anti-Siphon Ejector

Table of Contents 1 INTRODUCTION... 5 1.1 General............................................. 5 1.2 Specifications.......................................... 6 2 OPERATION... 7 2.1 General............................................. 7 2.2 Installation............................................ 7 2.3 Ejector Vacuum......................................... 8 2.4 Piping............................................. 9 2.5 Vacuum Connections...................................... 9 3 START-UP... 11 3.1 Vacuum Check......................................... 11 4 SERVICE... 13 4.1 Nozzle Cleaning.......................................... 4.2 O-Ring Replacement...................................... 13 4.3 Functional Test......................................... 13 4.4 Recommended Torque Values................................. 14 5 TROUBLESHOOTING CHART...17 FIGURES 1 Open Tank Installation...................................... 5 2 Pipeline Installation....................................... 5 3 Anti-Siphon Ejector Flow Diagram................................ 7 4 Gas Feed System Flow Diagram................................ 8 5 Dimensions........................................... 10 6 100 PPD (2 kg/h) Anti-Siphon Ejector Components...................... 14 7 250 & 500 PPD (5 & 10 kg/h) Anti-Siphon Ejector Components................ 15 Anti-Siphon Ejector - 3-122.6015.0

122.6015.0-4 - Anti-Siphon Ejector

1 INTRODUCTION 1.1 General The ADVANCE anti-siphon ejectors are expertly engineered and carefully tested to assure years of satisfactory operation. They are used when an ejector vacuum is created and gas continues to feed even though the ejector water supply is turned off. This can occur when: 1 1.1.1 The solution line drains down to the surface of the open basin being treated causing a vacuum which continues to feed gas (not solution) until the vacuum is satisfied. See Figure 1, or 1.1.2 If the application is into a pressurized pipe, the pressurized pipe may drain causing a vacuum in the ejector to continue to feed gas (not solution) until the vacuum is satisfied. See Figure 2. Figure 1 - Open Tank Installation Figure 2 - Pipeline Installation Anti-Siphon Ejector - 5-122.6015.0

The Capital Controls anti-siphon ejector consists of a pair of spring-loaded assemblies and a nozzle and diffuser. The spring loaded assembly above the nozzle is the DIAFRAMLESS check valve; the spring loaded assembly below the nozzle is a watertight diaphragm assembly with movable push pin rods. The nozzle is specifically designed for use with the anti-siphon ejector. The inlet provides a bleed port for the passage of water to and from the cavity above the lower diaphragm. The anti-siphon ejector may be used with all gas feeders up to and including 500 PPD (10 kg/h) chlorine and sulfur dioxide. Capacities available (as chlorine): 100 PPD (2 kg/h) 250 PPD (5 kg/h) 500 PPD (10 kg/h) Anti-siphon ejectors are constructed of the finest materials available for gas service. Correct installation and proper care will ensure best operation. Read these instructions carefully and save for future reference. This instruction manual only covers the Capital Controls Anti-siphon ejector (Reference 122.3013). NOTE: ADVANCE ejectors are designed for use with ADVANCE gas feeders. 1.2 Specifications 1.2.1 Gas Flow - Chlorine and Sulfur Dioxide Capacity Vacuum Tubing Size Inlet Nozzle 100 PPD (2 kg/h) 3/8" 3/4" hose 1" hose 3/4" NPT 250 PPD (5 kg/h) 1/2" 1 1/4" NPT 500 PPD (10 kg/h) 5/8" 1 1/2" hose Outlet Throat Universal - 3/4" NPT, spray or open-end, or 1" hose 1 1/4" NPT 1 1/2" hose Different inlet nozzle and diffuser combinations are available for the ejectors. Your particular combination was chosen for your application. 1.2.2 A universal diffuser can be used either as a spray diffuser, an open-end diffuser, a 3/4" threaded connection, or a 1" hose connection. Choose the type suited for the installation (spray is recommended for good mixing). If other than spray is desired, modify by cutting off the closed end. 1.2.3 The ejector (nozzle and check valve assembly) may be located near the vacuum regulator. A wall mounting bracket is available for field assembly, and the universal diffuser can be modified for a pipe or hose connection. 122.6015.0-6 - Anti-Siphon Ejector

2 OPERATION 2.1 General The DIAFRAMLESS ejector check valve assembly D is mechanically locked in a closed position by the push pin rods C (attached to diaphragm assembly B ) in the absence of water pressure in the ejector nozzle. Application of water pressure to the nozzle will fill cavity E through the nozzle bleed hole compressing spring A by the action of diaphragm assembly B. Push pin rods C are pulled away and the ejector check valve assembly D is free to open upon the creation of a vacuum by the nozzle. The anti-siphon ejector check valve assembly maintains a tight closure to 30" of mercury vacuum. (Figure 3) 2 2.2 Installation - Figure 4 Figure 3 - Anti-Siphon Ejector Flow Diagram The ejector may be installed in any position, since the check valve is spring actuated (however, downward water flow may cause cavitation and poor vacuum). Wall mounting is satisfactory (Figure 5). The point of injection should be carefully chosen so the water back pressure into which the gas is fed is as low as possible. If the ejector is installed in a pipe, the ejector/diffuser should not b e installed in the top of the pipe where gas may discharge and collect in an empty area of the pipe. Diffuser penetration into the pipe should not exceed 1/3 the diameter of the pipe. The ejector (nozzle and check valve assembly) may be located near the vacuum regulator. A wall mounting bracket is available for field assembly, and the universal diffuser can be modified for a pipe or hose connection. 2.2.1 Unscrew the diffuser from the assembly. Do NOT install ejector with the diffuser attached, or damage may occur. Anti-Siphon Ejector - 7-122.6015.0

Figure 4 - Gas Feed System Flow Diagram 2.2.2 If installed in pipeline, put teflon tape on the diffuser pipe threads and screw the diffuser into the pipe by hand. Tighten carefully with pliers. (Make sure that the holes in the spray tube diffuser are in the main stream). If the diffuser is modified to provide an open end, the end of the diffuser should not allow strong chemical solution to come in contact with pipe or fittings. (This can cause serious corrosion). 2.2.3 Re-connect nozzle and check valve assembly to diffuser. The nozzle may extend through the assembly from either side. A gasket should be on each side. Screw the nozzle into the diffuser HAND TIGHT. 2.3 Ejector Vacuum The ejector creates a vacuum only when water pressure is applied to the inlet nozzle and when sufficient pressure differential exists between the ejector inlet water versus the water outlet pressure. Vacu um will be lost when the water supply is shut off. For example, if the diffuser were discharging into an empty basin (zero back pressure), the supply pressure to the nozzle requires about 25 psig (2 bar) to create enough vacuum to operate a 50 PPD (1 kg/h) vacuum regulator. A lower supply pressure or a higher back pressure would reduce the gas flow rate. The water supply line to the nozzle must be large enough to allow sufficient water flow (3/4" or la rger pipe is recommended) and minimize friction losses. It should be at least the size of the nozzle connection. Is there is a solution line, this line should be less than the diameter of the ejector outlet. Depending upon the distance to the point of application, this line may have to be larger in diamete r to minimize hydraulic losses. 122.6015.0-8 - Anti-Siphon Ejector

2.4 Piping For most installations, the ejector water supply line should be brought to within 4-6 ft. (1-2 m) o f the nozzle with rigid copper or iron pipe. A shutoff valve followed by a Y-strainer, and a hose adapter should be installed. A pressure gauge between the Y-strainer and the ejector can be a useful service tool. A Y-strainer is not necessary for all applications particularly if the water is clean and free of materials that could cause nozzle pluggage. Connect the hose between the hose adapter and the ejector nozzle. If a hose connection is used, clamp the hose securely at both ends with single or double clamps. If the water supply piping is used, a threaded inlet connection on the inlet nozzle is required and the piping does not need a hose adaptor. A union connection is employed to permit servicing and the piping is plumbed accordingly. 2.5 Vacuum Connections See Figure 4 and Specification section. Black polyethylene tubing is normally used for the vacuum line between the vacuum regulator and ejector. Use a sufficient length of tubing for each line to allow vacuum regulator movement from one container to another. 2 Once the tubing length has been established, remove the connector nut from the vacuum regulator and ejector connections and slip each nut onto the tubing. Push the tubing onto each connector and tighten connector nuts HAND TIGHT. NOTE: The upper connection on the vacuum regulator is for vacuum tubing to ejector. Do not kink the tubing nor run the tubing near hot piping which could melt the polyethylene tubing. Anti-Siphon Ejector - 9-122.6015.0

Figure 5 - Typical Dimensions 122.6015.0-10 - Anti-Siphon Ejector

3 START-UP 3.1 Vacuum Check The ejector, its water supply and solution lines, must be properly installed and checked before operating the vacuum regulator. Unless the ejector is creating a vacuum, the vacuum regulator will not work. 3.1.1 Disconnect the vacuum tubing from the ejector. 3.1.2 Open the ejector water supply valve. The ejector should now be in operation and creating a vacuum. 3.1.3 Put your finger on the vacuum connector opening and feel the vacuum. Your finger should be held tight to the connector by the vacuum as an indication that sufficient vacuum exists. If there is no vacuum, be certain the supply pressure is sufficient and the nozzle or piping is not plugged. Correct the condition and obtain proper vacuum before proceeding with vacuum regulator operation. (Reference vacuum regulator instruction manual) 3.1.4 Reconnect the vacuum tubing to the ejector. Leave the ejector running. 3 Anti-Siphon Ejector - 11-122.6015.0

122.6015.0-12 - Anti-Siphon Ejector

4 SERVICE 4.1 Nozzle Cleaning 4.1.1 Shut off the water supply valve and remove the ejector. Refer to Figures 6 and 7 and remove the nozzle as follows: a. Remove the connecting hose or piping to the ejector assembly. b. For 100 PPD (2 kg/h) chlorine or sulfur dioxide ejectors, rotate the complete ejector body counter-clockwise. This loosens the threaded portion of the nozzle from the diffuser, eliminating the need for pliers on the hose connection which may damage the plastic. For 250 & 500 PPD (5 & 10 kg/h), remove the two (2) screws and loosen the flange to remove the nozzle. NOTE: Nozzle plugging can be caused by foreign material (pipe scale, stone, dirt accumulation). This can usually be blown out or pushed out with a wire. Build-up of deposits may caused by iron, manganese or other material can usually be remove by immersing the nozzle in muriatic acid and rinsing. Some waters may cause an inoperable ejector and require nozzle cleaning every two months. NOTE: Do not use a sharp object (screwdriver, awl, etc.) to clean the inside of the nozzle as this may cause damage to the nozzle and alter its vacuum producing characteristics. c. To re-install the nozzle, insert the nozzle through the ejector body and fasten to the diffuser using new gaskets, or o-rings on each side of the ejector body. NOTE : These parts are plastic and excessive tightening may cause breakage. For 100 PPD (2 kg/h) chlorine or sulfur dioxide ejectors, tighten only hand tight with the ejector body 90 to the left of its final position, then turn the complete assembly 90. d. Re-install the ejector supply hose or pipe and vacuum tubing. 4.2 O-Ring Replacement Anti-siphon ejectors are designed for on/off application, but will require occasional maintenance of the diaphragm bolt/o-ring assembly. On a regular basis, this o-ring should be checked and the o-ring/diaphragm bolt assembly replaced as necessary. 4.3 Functional Test When the ejector is re-assembled, a functional test of the check valve assembly is recommended to check for proper ejector assembly and prevent future flooding of the vacuum regulator. 4 4.3.1 Do not connect vacuum tubing to vacuum regulator. 4.3.2 Turn on water supply. 4.3.3 Verify vacuum at ejector. 4.3.4 Turn water supply off for approximately 5 minutes. If ejector is assembled properly, no water will leak from vacuum tubing. Anti-Siphon Ejector - 13-122.6015.0

4.4 Recommended Torque Values Torque values of 14 inch pounds for ejector body screws on units up to 500 PPD/10 kg/h are used at the factory, and are recommended guidelines for re-assembly of a repaired unit. Figure 6-100 PPD (2 kg/h) Anti-Siphon Ejector Components 122.6015.0-14 - Anti-Siphon Ejector

4 Figure 7-250 & 500 PPD (5 & 10 kg/h) Anti-Siphon Ejector Components Anti-Siphon Ejector - 15-122.6015.0

122.6015.0-16 - Anti-Siphon Ejector

5 TROUBLESHOOTING CHART Trouble Probable Cause Corrective Action 1. No ejector vacuum a. Faulty lower diaphragm pins. b. Damaged lower diaphragm. c. Plugged bleed hole. 2. Insufficient ejector vacuum. a. Y-strainer in water supply dirty. b. Supply pressure too low c. Back pressure too high 1. Solution valve, if supplied, not fully open. 2. Solution line if present, partially blocked. d. Velocity too low (cavitation) e. Nozzle 1. Flow restricted 2. Worn or damaged f. Incorrect nozzle size g. Improper installation 3. Flooded flowmeter. a. Dirt on o-ring. b. Improperly seated or defective o-ring. c. Improper application. a. Disassemble ejector body and examine pins. b. Disassemble ejector body and examine lower diaphragm. c. Clean bleed hole. NOTE: When reassembling, ensure pins reach diaphragm. a. Clean Y-strainer. b and c. Open solution valve, clean line, correct back pressure condition. d. Increase pressure to ejector e - g. Clean nozzle and/or throat. See Service section and Bulletin 123.3001. a. Clean or replace o-ring. See Service section. b. Replace o-ring. See Service section. c. See Bulletin 123.3001 on hydraulic conditions. 5 Anti-Siphon Ejector - 17-122.6015.0

Represented by: De Nora Water Technologies 3000 Advance Lane Colmar, PA 18915 ph +1 215 997 4000 fax +1 215 997 4062 web: www.denora.com mail: info.dnwt@denora.com Registered Trademark. 2015. All Rights Reserved. SEP 2015 122.6015.0-18 - Anti-Siphon Ejector