Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Similar documents
Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Performance investigation of Air-conditioning system using ejector as expansion device

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

International Engineering Research Journal Performance Analysis of Ejector Based Solar Air Conditioning System

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

Thermodynamic Analysis of Ammonia-Water Absorption Refrigeration System with Ejector

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

International Journal of Research in Engineering and Innovation Vol-3, Issue-1 (2019), 1-5

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

A Novel Heat Recovery System for High Temperature and High Humidity Gas Qing Hao1, a, Meng Si2, b

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Adsorption refrigeration system using waste heat

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

A Review Paper on Extracting Waste Heat from the Engine Exhaust and Reutilizing in Car Air Conditioning

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Experimental Investigation of Hot water Fired R134A-DMAC VARS System at Various Heat Source Temperatures

Modelling the Performance of a Diffusion Absorption Refrigeration System

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Performance characteristics of low global warming potential R134a alternative refrigerants in ejector-expansion refrigeration system

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

A study of Transient Performance of A Cascade Heat Pump System

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

Energy and Exergy Analysis of an Ejector-Absorption Refrigeration Cycle with Using NH3-H2O as the Working Fluids

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

ANKUSH SHARMA & JAGDEV SINGH Department of Mechanical Engineering, Beant College of Engineering and Technology, Gurdaspur, Punjab, India

ADVANCES in NATURAL and APPLIED SCIENCES

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

International Journal of Informative & Futuristic Research ISSN (Online):

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Enhancement of COP in Vapour Compression Refrigeration System

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Jurnal UMP Social Sciences and Technology Management Vol. 3, Issue. 3,2015

Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

SOLAR PARABOLIC COLLECTOR ASSISTED EVAPORATIVE COOLING SYSTEM

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

η second law = Second law efficiency

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

Experimental Investigation of a Hybrid Evacuated Tube Solar Collector

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Experimental & Analytical Investigation on Modified Solar Dryer with Recirculation of Air

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Vapour Jet Refrigerator / Heat Pump R853

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

Improvement Of Energy Efficiency Ratio Of Refrigerant Compressor

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

Numerical Simulation of Window Air Conditioner

ADVANCES in NATURAL and APPLIED SCIENCES

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

*Corresponding author;

Department of MCE, Islamic University of Technology 2. Abstract

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN

IJARI. 1. Introduction: Heat Pipes. Volume 3, Issue 3 (2015) ISSN International Journal of Advance Research and Innovation.

EFFECT OF DIVERSE STREAM PATTERNS ON THE PERFORMANCE OF SOLAR AIR HEATER

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Transcription:

Available online at www.pelagiaresearchlibrary.com Advances in Applied Science Research, 2013, 4(5):232-237 ISSN: 0976-8610 CODEN (USA): AASRFC Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile Rohit Khajuria and Jagdev Singh Department of Mechanical Engineering, Beant College of Engineering and Technology, Gurdaspur, Punjab, India ABSTRACT Ejector refrigeration is a thermally driven technology which utilizes low grade thermal energy for its operation. This paper experimentally investigates the performance analysis of ejector refrigeration system with R404A as refrigerant. The ejector refrigeration system used exhaust emission of automobile as thermal energy for providing heat to refrigerant in the generator. Effect of different operating parameters on the performance of system has been investigated. The result shows that system using R404A as refrigerant can be used in the ejector refrigeration system for area ratio 7.84. Cooling capacity of the system increases with increase in evaporator temperature and generator temperature. Keywords: Generator, Ejector, Ejector refrigeration system, and R404A Nomenclature T e Evaporator temperature, o C T g Generator temperature, o C A Area ratio=a m /A t T c Condenser temperature, o C W p Mechanical pump input energy, kw m e Mass flow rate given to evaporator,kg.s -1 m g Mass flow rate given to generator,kg.s -1 Δh e Enthalpy difference between exit and inlet side of evaporator, kj.kg -1 Q e Cooling capacity, kw =m e.δh e Q g Total heat input to the generator, kw µ Entrainment ratio=m e /m g Subscripts c Condenser e Evaporator g Generator m Mixing chamber t Throat INTRODUCTION The demand of energy is increasing day-by- day. To meet the demands of energy new techniques are being developed. Ejector refrigeration system can be driven by the low grade thermal energy such as solar energy, waste 232

industrial heat and geothermal energy where as Conventional vapour compression refrigeration system runs with the help of high grade mechanical energy and electrical energy. Ejector refrigeration system in its current phase of development has a coefficient of performance very low than vapour compression systems but helps in saving the energy. Keenan J.H., Neumann E.P. and Lustwerk F. in 1950[1] conducted an investigation of ejector design by analysis and experiment. A one- dimensional method of analysis of ejector was presented. The analysis considered mixing of primary and secondary streams at constant pressure and mixing of streams at constant area. For the analytical condition considered, better performance obtained when constant pressure mixing is employed. Sun D.W. in 1999[2] did comparative study of the performance of an ejector refrigeration cycle operating with various refrigerants The results show that steam jet systems have very low coefficient of performance values, the system using R152a as refrigerant has better performance. Grazzini G. and Rocchetti A. in 2002[3] investigated the numerical optimisation of a two-stage ejector refrigeration plant. A simulation program numerically searches the maximum coefficient of performance at given external inlet fluid temperatures as a function of mass flows, dimensions and temperature differences in the heat exchangers. Alexis G.K. and Rogdakis E.D. in 2003[4] presents a paper on a verification study of steam- ejector refrigeration model. The model takes into account the shocking phenomena and assumes that the mixing process of the two streams, motive and secondary stream, takes place with constant pressure and the conservation of fluid momentum in effect. Selvaraju A. and Mani A. in 2004[5] did the analysis of an ejector with environment friendly refrigerants. Comparison of performance of the system with environment friendly refrigerants (R134a, R152a, R290, R600a and R717) is made. Among the working fluids considered, the system with R134a gives better performance. Sankarlal T. and Mani A. in 2006[6] conducted experimental studies on an ammonia ejector refrigeration system. The results showed that entrainment ratio and coefficient of performance of the system increase with increasing generator and evaporator temperatures and decrease with increasing condenser temperature. Alam S. in 2006[7] proposed a model for utilizing exhaust heat to run automobile air-conditioner. The analysis shows that the maximum amount of useful heat available in the exhaust gas is about 6 KJ/sec and the amount of heat required for generator is 3.02 KJ/sec. Butterworth M.D. and Sheer T.J. in 2007[8] studied high-pressure water as the driving fluid in an ejector refrigeration system, the purpose of which was to chill water. Elbel S. and Hrnjak P. in 2008[9] presented a review paper which gives an overview of historical and recent developments regarding airconditioning and refrigeration systems that use ejectors. Kashyap S. in 2011[10] conducted a simulation program on the basis of one dimensional mathematical model to analysis the performance of ejector refrigeration cycle with working fluid R410a and also compared with performance of R134a. A performance comparison is made on various operating condition and ejector geometry. The results showed that performance of R134a is better than R410a. Jain A., Agrawal S. K. and Pachorkar P. in 2012[11] described the exergy analysis of the solar-driven ejector refrigeration system. The largest portion of the exergy is lost in the solar collector followed by the ejector, the generator, the condenser, the evaporator and the expansion valve. Jaruwongwittaya T. and Chen G. in 2012[12] presents a paper on application of two stage ejector cooling system in a bus. The aim was to investigate the feasibility of implementing a two stage ejector cooling system in a bus. The results indicate that the application of a two stage ejector cooling system to replace the vapour compression system in a bus is a suitable alternative. Conventional refrigeration system in automobile can run with the help of engine power but gives extra load to engine. The addition of refrigeration system in automobile cause higher fuel consumption and increases the impact on the environment due to the increasing amounts of exhaust emission from the internal combustion engines. Mostly researchers has done a lot of work on improving the performance of vapour compression systems(vcs) by reducing the fuel consumption or installing system which does not include a compressor, such as the absorption system, adsorption system and ejector cooling system. Although these systems have drawback of low coefficient of performance but their advantages are that they do not need any power from the engine. Consequently, not only the fuel consumption is reduced but also the exhaust emissions are reduced which are the main cause for global warming. Such systems can help to improve the global warming situation which at present is a leading environmental problem. The ejector structure is characterised by the area ratio (A) which is defined as the cross-section area of the constant area section of mixing chamber of ejector (A m ) divided by that of the primary nozzle throat (A t ). Singh K. [13] has described that all the heat produced by the combustion of fuel in engine cylinder is not converted into useful power at the crankshaft. The heat which is converted into useful work at the crankshaft is 25 percent, loss to the cylinder walls is 30 percent, loss in exhaust gases is 35 percent and loss in friction is 10 percent. 233

Exhaust emission is emitted as a result of the combustion of fuels such as natural gas, petrol, diesel fuel, fuel oil or coal. According to the type of engine, it is discharged into the atmosphere through a pipe. Performance of ejector refrigeration system driven by exhaust emission of automobile with refrigerant R404A is analysed in this paper. The performance of the refrigerant R404A is investigated at evaporator temperature (6.9 o C to18.9 o C), condenser temperature (42.4 o C to 47.6 o C) and generator temperature (58 o C to 64 o C). MATERIALS AND METHODS The schematic diagram of experimental set-up has been shown in fig.1 and the ejector used in the system is shown in fig. 2. Fig.1 Experimental setup of the ejector refrigeration system Fig.2 Ejector diagram 2.1 Description of Experimental Setup The experimental set up consists of a generator, evaporator, condenser, ejector, capillary tube, a circulating pump, and measuring devices. The thermal energy (Q g ) required for vaporising the refrigerant in the generator is taken from the exhaust emission of automobile. The quantity of refrigerant entering into ejector from the generator and evaporator is measured with the help of Rotameter. Quantities of refrigerant from generator and evaporator are used for determining entrainment ratio. Pump used in the system gets power (W p ) the battery of automobile. The Bourdon tube pressure gauges within ±0.3 bar accuracy are used in the experimental setup to measure the pressure. Temperature indicator with ±0.1 C accuracy is used to measure the temperature at the outlet and inlet of components. 234

2.2 Description of Experimental procedure The refrigerant enters into the generator which is mounted over the silencer. Diesel engine exhaust is connected via exhaust pipe to the silencer which is also called muffler. The normal operating temperature range of exhaust gases is from 200 o C to 500 o C in diesel engine. To attain temperature in the generator required for vaporising the refrigerant, it is mounted over the silencer. Engine is made to run for half an hour, exhaust gases coming from the silencer provide thermal energy to the generator for attaining the required temperature. Refrigerant is made to flow through the Rota meter and then goes to condenser via ejector. Entrainment ratio (µ) is the ratio of mass flow rate given to evaporator (m e ) to the mass flow rate given to generator (m g ) and it is one of the important parameters of ejector refrigeration system. Refrigerant is divided on the basis of entrainment ratio by adjusting the needle valve from where one part of the refrigerant goes to the generator with the help of pump and the other part goes to the evaporator. Refrigerant from evaporator is sucked into the ejector and then two streams one coming from the generator and other from the evaporator mix in the constant area section(mixing chamber) of the ejector and then through the diffuser of ejector to recover the pressure. The refrigerant goes to the condenser where refrigerant condenses and again same procedure is repeated by changing the entrainment ratio. RESULTS AND DISCUSSION The performance of the ejector refrigeration system with R404A as refrigerant using the thermal energy of exhaust emission of the automobile is studied in this paper. The effect of different operating parameters on the system performance was studied. In the experiments, the ranges of the operation conditions were as follows: evaporator temperature from 6.9 o C to 18.9 o C, condenser temperature from 42.4 o C to 47.6 o C and generator temperature from 58 o C to 64 o C. Cooling capacity (Q e ) 26 24 22 20 18 16 14 12 10 Qe(Tg=58 C,Tc=44 C) Qe(Tg=60 C,Tc=44 C) Qe(Tg=62 C,Tc=44 C) Qe(Tg=64 C,Tc=44 C) 8 5 10 15 20 Evaporator temperature (T eo C). Fig.3 Effect of evaporator temperature on cooling capacity 3.1. Effect of evaporator temperature (T e ) The graph shown in the Fig. 3 shows the effect of evaporator temperature (T e ) on the cooling capacity of refrigerant for different generator temperatures and fixed condenser temperature. The result shows that the cooling capacity of refrigerant increases with increasing evaporating temperature because irreversibility decreases with increase in evaporator temperature. The performance of the ejector increases with increased evaporator temperatures because with the decrease in evaporator temperature, pressure of refrigerant coming from the generator decreases more in the 235

nozzle of ejector below the evaporator pressure to suck the refrigerant from the evaporator. With the increase in evaporator temperature at fixed generator temperature and condenser temperature, the heat given to the refrigerant in the generator decreases and pump work required to deliver the refrigerant from exit of condenser to inlet of generator decreases. Increased entrainment ratio is one of the main causes of increased cooling capacity of the system with increase in the evaporator temperature for fixed generator and condenser temperature. 3.2. Effect of generator temperature (T g ) Fig.4 depicts the effect of generator temperature (T g ) on entrainment ratio for different evaporator temperatures and fixed condenser temperature. The entrainment ratio of the system with the refrigerant R404A increases with the increasing generator temperature at given evaporator and condenser temperatures because as generator temperature increases temperature pressure of the refrigerant also increases and when high pressure refrigerant goes into nozzle section of ejector pressure energy is converted into kinetic energy which leads to the increase of entrainment ratio. Entrainment ratio(µ) 0.7 0.65 0.6 0.55 0.5 0.45 0.4 0.35 µ(te=6.9 C,Tc=44 C) µ(te=9.1 C,Tc=44 C) µ(te=11.2 C,Tc=44 C) µ(te=13 C,Tc=44 C) µ(te=15.1 C,Tc=44 C) µ(te=16.8 C,Tc=44 C) µ(te=18.9 C,Tc=44 C) 0.3 0.25 0.2 56 58 60 62 64 66 Generator temperature (T go C). Fig.4 Effect of generator temperature on entrainment ratio 3.3. Effect of entrainment ratio (µ) The variation of cooling capacity with change in entrainment ratio at given generator temperature and condenser temperature is shown by the Fig.5.Cooling capacity of the refrigerant increases with increase in entrainment ratio because entrainment ratio is directly proportional to mass flow rate given to evaporator. With the increase in generator temperature, entrainment ratio also increases. 236

26 24 Qe(Tg=60 C,Tc=44 C) Qe(Tg=64 C,Tc=44 C) 22 Cooling capacity(q e ) 20 18 16 14 12 10 8 0.2 0.3 0.4 0.5 0.6 0.7 Entrainment ratio (µ). Fig. 5 Effect of entrainment ratio on cooling capacity CONCLUSION The performance of ejector refrigeration system driven by exhaust emission of automobile with refrigerant R404A was experimentally investigated. The results of the experimental investigation show that cooling capacity of the system increases with increase in evaporator temperature and entrainment ratio. On the basis of result obtained it can be concluded that entrainment ratio increases with the increase in generator temperature. Ejector refrigeration system has used low grade thermal energy in the form of exhaust emission of automobile which saves costly fuel used for running automobile. REFERENCES [1]Keenan J.H., Neumann E.P. and Lustwerk F., Journal of Applied Mechanics (1950) 299-309. [2]Sun D.W., Energy Conversion & Management 40 (1999) 873-884. [3]Grazzini G., Rocchetti A., International Journal of Refrigeration 25 (2002) 621 633. [4]Alexis G.K., Rogdakis E.D, Applied Thermal Engineering 23 (2003) 29 36. [5]Selvaraju A., Mani A., Applied Thermal Engineering 24 (2004) 827 838. [6]Sankarlal T., Mani A., Experimental studies on an ammonia ejector refrigeration system, International Communications in Heat and Mass Transfer 33 (2006) 224 230 [7]Alam S., A Proposed Model for Utilizing Exhaust Heat to run Automobile Air-conditioner, The 2 nd Joint International Conference on Sustainable Energy and Environment (SEE 2006) Bangkok, Thailand. [8] Butterworth M.D., Sheer T.J., Applied Thermal Engineering 27 (2007) 2145 2152. [9]Elbel S., Hrnjak P., International Refrigeration and Air Conditioning Conference at Purdue, July 14-17, 2008. [10] Kashyap S., International Journal of Engineering Science and Technology (2011) ISSN: 0975-5462 2011 [11] Jain A., Agrawal S. K., Pachorkar P., IOSR Journal of Mechanical and Civil Engineering (2012), Volume 3, PP 30-36. [12] Jaruwongwittaya T., Chen G., Energy Procedia 14 (2012) 187 197. [13] Singh K., Automobile engineering Vol.2 Standard Publishers Distributors, Delhi, 2007. 237