DAVE DEMMA REDUCING ELECTRICAL CONSUMPTION

Similar documents
DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL

GORD COOKE. issues associated with humidification and dehumidification systems. In this article, humidification

Understanding Head Pressure Control. Walter H Langille, M.A.Sc., P.Eng Sales Engineer KeepRite Refrigeration

A Treatise on Liquid Subcooling

PAYING THE PIPER TABLE 1 NEOPRENE TYPE W SWELL RATES

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

Sporlan Valve Division Parker Hannifan/CIC Group

refrigeration THE GOODS ON OIL FAILURE TRIPS

USING THE P-T CARD AS A SERVICE TOOL

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

AE October 1965 Reformatted October Hot Gas Bypass Control Systems

ThermoSaver TM Hot Gas Defrost System

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

The Saturation process

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Application Engineering

DTI Kenneth Bank Madsen Global Application Expert Food Retail

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Welkom. Optimalisatie CO2 systemen m.b.v. ejecteur

Energy Use in Refrigeration Systems

ThermoSaver TM Hot Gas Defrost System

HVAC/R Refrigerant Cycle Basics

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

REFRIGERATION AND AIR CONDITIONING RÉFRIGÉRATION ET CLIMATISATION POST-SECONDARY NIVEAU POSTSECONDAIRE

Head Pressure Control Application Guide

Bulletin , March Electric Hot Gas Bypass Valves

PPL Electric Utilities Energy Efficiency and Conservation Program

Application Guide. Refrigerant Piping Manual for Small Split Cooling and Heat Pump Systems SS-APG006-EN

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

Pressure Enthalpy Charts

Installation, Operation, and Maintenance Information

THERMOSTATIC EXPANSION VALVES Part 1

5. ASSESSMENT RECOMMENDATIONS

AE R1 March 1993 Reformatted November Compressor Overheating

HEAT PUMPS. Carrier Corporation GT72-01 Cat. No

How to Diagnose a TXV Failurek

System Design, Commissioning, Operation

Cascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case:

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

Otherwise, you can continue reading the file on the following pages.

System Considerations for Refrigerant Blends with Temperature Glide

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES

Air Cooled Packaged Systems AIRAH Back to Basics

THERMAL MASS CYCLING REFRIGERATED AIR DRYERS. GTRC Series

PULSE WIDTH MODULATING VALVES

REFRIGERANT CHANGEOVER

Technical Information

Installation Manual for. Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT

PRODUCT. TWB Two-Way Air Defrost Unit Coolers PRODUCT DATA & INSTALLATION. High Temperature (35 o F / 1.7 o C or Higher) Applications

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

General information on refrigerant controllers

Suction Accumulators. Introduction. Suction Accumulators

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

The Essentials Of Working With R-410A

The Book of AERMEC NRL Sequence of Operation

Checking the Charge on a Heat Pump in the Winter

How to Cut Chiller Energy Costs by 30%

KE2 EvaporatorEfficiency Theory of Operation

THERMOSTATIC EXPANSION VALVES Part 2

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

KCC Centrifugal Fan Air Cooled Condensers

EXPANSION VALVES. See Red Dot Catalog Also. * 2 ton valves - all other valves are 1 1/2 ton (1) Includes M1 Adapter 71R8050 EX02280

PoleStar Smart Refrigerated Air Dryers don t just cycle, cycle Smart.

HIGH INLET TEMPERATURE REFRIGERATED AIR DRYERS. GHRN Series

RDT Refrigeration Book

Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant

NON-CYCLING REFRIGERATED AIR DRYERS. GSRN Series

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

(Refer Slide Time: 00:00:40 min)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Air-Conditioning Buying Guide

Efficient Steam System Design

HX Series. Compressed Air Dryers 10 to 2400 scfm. Setting a new standard in Quality and Reliability DRYMAX DRYMAX DRYMAX

START UP FORM PACKET

ORTEC INDUSTRIAL FLUID CHILLERS FC SERIES ( TONS) Compressed Air, Gas & Fluid Technologies. i e n d. l y. t a. R e. f r. i g e.

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

SERVICE ASSISTANT OVERVIEW FDSI Online Training

Technical Bulletin (TB-0037)

SM/SV Series PRODUCT COOLERS. Technical Bulletin: SMSV_005_ Products that provide lasting solutions.

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

A Series T 3. Unit Coolers - Technical Catalog. Product Benefits: Comdustrial TM Refrigeration. Adaptability- Durability- Serviceability-

Use this Construction/HVAC Glossary to answer the questions below.

600-10,000 scfm AES Series. AES Series Energy Saving. Refrigerated Air Dryer ,000 scfm. Front Page

ENERGY EFFICIENCY PROJECTS. NO-COST AND LOW-COST UPGRADES FOR YOUR FACILITY In partnership with: Refrigerating Engineers & Technicians Association

Air Conditioning Clinic. Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN

WIBR SERIES. Unit Coolers - Technical Catalog Hunt St - Pryor, OK Fax

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

The Electronic Newsletter of The Industrial Refrigeration Consortium Vol. 11 No. 1, 2011

Transcription:

BY DAVE DEMMA REDUCING ELECTRICAL CONSUMPTION It is said that necessity becomes the mother of invention. As energy prices soared in the 1970s, supermarket owners sought ways to reduce their enormous utility bills. Unlike comfort cooling equipment, which may only operate during the warmer months, supermarket compressors run year round. As such, the refrigeration equipment accounts for approximately 50 per cent of the total electrical consumption in the typical supermarket every month, with compressors as the largest user. With this in mind, there is the potential for conservation measures to have a huge impact on monthly utility bills. REDUCING MOTOR AMPERAGE One means of reducing a compressor s electrical consumption is to lower the discharge (head) pressure. The head pressure will be at its highest during the heat of summer, when the ambient temperature is close to design conditions. This is also when the compressor motor amperage will be at its highest. Because more work is required to compress a vapour to a higher pressure, it logically follows that more electrical energy is required to accomplish this. There is a proportional relationship between head pressure and compressor motor current draw. When head pressure is either raised or lowered, the motor current draw will increase or decrease in proportion. For example, one manufacturer s 20 hp compressor, using R404A, and operating at -25F SST (13 psig) and 110F SCT (272 psig), with five degree Fahrenheit liquid subcooling, and a 50F return gas temperature, will deliver 61,389 Btuh. At this condition the compressor motor s current draw is 40 amps. This may be one of several compressors (of varying sizes) on the low temperature rack in a supermarket. A 30F reduction in condensing temperature (110F to 80F) will reduce the current draw to 37.3 amps. While a 6.75 per cent reduction is significant, it is only part of the story. The typical supermarket compressor rack will run a reasonably constant suction pressure, regardless of head pressure. This is determined by the saturated suction temperature requirement of the lowest operating system connected to the rack and maintained by the energy management system. SOURCE OF REAL SAVINGS Unless the suction pressure requires readjustment, the only reduction in compression ratio(ratio of absolute discharge pressure/absolute suction pressure) will come from lowering the head pressure. In this case, lowering the condensing temperature to 80F(175 psig) will yield a significantly lower compression ratio (10.35:1 versus 6.87:1). Using the same compressor data, the net result of this lower compression ratio is a 31 per cent increase in compressor capacity. So, in addition to a 6.75 per cent reduction in current draw, the 31 per cent increase in compressor capacity means that fewer compressors will be required to operate to achieve the same pumping capacity. This is where the real savings come from: increased compressor volumetric efficiency. INCREASED CAPACITY Condenser capacities are based, in part, on the temperature difference (TD) between the ambient and the refrigerant condensing temperature. As the ambient falls, and the TD increases, the condenser capacity will increase. For example, a condenser rated at 150,000 Btuh at a 110F and 10F TD, would have a capacity of 750,000 Btuh with a 50F TD. In layman s terms, it has now become five times larger than it needs to be. An oversized condenser means lower head pressure, and reduced electrical consumption. When the actual ambient is below the design ambient, we can take advantage of the now greater condenser capacity, allow the head pressure to fall and start reaping the benefits to a point. Too much of any good thing can become problematic, and reducing head pressure is no exception. If the head pressure is allowed to fall below certain minimums, system performance can be adversely affected in the following areas: 1. Underfeeding thermostatic expansion valves (TEVs) and starving evaporators. 2. Oil logging. 3. Reduced compressor efficiency and higher discharge temperatures. 1. Underfeeding TEVs and Starving Evaporators There are several factors that determine TEV capacity: refrigerant type, evaporator temperature, pressure drop ( P) across the TEV port, and liquid temperature. The nominal valve capacity (the capacity listed on the box) is that capacity which the valve will deliver at the nominal rating condition. The rating condition for high pressure refrigerants (such as R404A, R507, or R22) is a 40F evaporator temperature, 100 psig P across the valve port, and l00f liquid temperature. If the actual conditions are different than the nominal rating condition, then the actual valve capacity will be different than the nominal capacity. Similarly, altering either the liquid temperature (see Table 1) or the P across the valve port (see Table 2) from the rating condition will result in a different valve capacity. Pressure drop across the TEV port is CONTINUED ON PAGE 42 40 HPAC SEPTEMBER/OCTOBER 2005

St. Lawrence Chemical Inc. Exclusive distributor of Genetron rerigerants in Canada Ontario and Western Canada, Tel: 416-243-9615 Fax: 416-243-9731 Quebec and the Maritime Provinces, Tel: 514-457-3628 Fax: 514-457-9773 Circle #30

CONTINUED FROM PAGE 40 FIGURE 1 P Across TEV Port 226 psi (liquid pressure) [45 psi (TEV outlet) 10 psi (evaporator inlet)] = 181 psi not simply the difference between liquid pressure and evaporator pressure. If there is a refrigerant distributor in the circuit, its P must be considered in the equation as well. When correctly sized, the typical refrigerant distributor/tube assembly in a high pressure refrigerant system will provide approximately a 35 psig P. Referring to Figure 1, the TEV P is calculated as follows: 226 psig (liquid pressure) minus 45 psig (the sum of 35 psig distributor/tube assembly P and 10 psig evaporator inlet pressure), resulting in a 181 psig P across the TEV port. As the head pressure lowers, the available P across the TEV port is also lowered. While lowering the head pressure results in a reduced pressure drop which will decrease TEV capacity, this is accompanied by a lower liquid temperature (a result of the lower condensing temperature). This will increase the TEV capacity. The effects of lower P (reduced valve capacity) and lower liquid temperatures (increased valve capacity) tend to negate each other without any significant change in TEV capacity. A supermarket rack that utilizes a mechanical liquid subcooler is a different story. A reduction in P without an offsetting reduction in liquid temperature will result in a lower TEV capacity. While the lower head pressure yields reduced motor current and increased compressor efficiency, if lowered too far, eventually the TEV capacity will not be able to meet the demands of the evaporator load. When this occurs, a portion of the evaporator will cease to effectively transfer heat, as liquid refrigerant would no longer be available to feed it. This will be evidenced by the higher superheat at its outlet. That portion of the evaporator which only sees refrigerant vapour has essentially become an extension of the suction line; it performs no useful work at all. Reducing the TEV capacity, which leads to a starving evaporator, has in effect, reduced the evaporator capacity. The end result is increased discharge air temperatures. 2. Oil Logging Because the refrigerant and oil do not completely mix, a minimum refrigerant velocity in the suction line (particularly the riser) is required for the oil to properly return to the compressor. There is a delicate balance between an oversized suction line, which would adversely affect proper oil return, and an undersized suction line, which would cause unnecessary pressure drop and result in decreased capacity. At a full load condition, the suction riser P, and refrigerant velocity will be at their peak. If sized correctly, the P will be tolerable and the velocity great enough for proper oil return. When the ambient temperature has decreased to that point where the TEV capacity cannot meet the evaporator load demand (from lower head pressure; available P), the refrigerant mass flow in the evaporator will start decreasing. This then reduces the refrigerant velocity in the suction riser. There is some leeway in maintaining proper oil return with slightly reduced velocities. However, as the ambient temperature continues to fall (reducing P, TEV capacity, mass flow and velocity), eventually the velocity will be too low for oil to return up the suction riser; it will log in the evaporator. Not only does this use valuable evaporator surface necessary for heat transfer, but if serious enough it may rob the available oil from the compressors for adequate lubrication. This will lead to compressor oil failure controls tripping, and the appearance of low oil levels in the system. There may be temporary periods CONTINUED ON PAGE 44 TABLE 1 Pressure Drop Correction Factors for R404A Evaporator Temp. F 30 50 75 100 125 150 175 200 225 250 275 40F 0.55 0.71 0.87 1.00 1.12 1.22 1.32 1.41 1.50 1.58 1.66 20F & 0F 0.49 0.63 0.77 0.89 1.00 1.10 1.18 1.26 1.34 1.41 1.48-10F & 20F 0.45 0.58 0.71 0.82 0.91 1.00 1.08 1.15 1.22 1.29 1.35-40F 0.41 0.53 0.65 0.76 0.85 0.93 1.00 1.07 1.13 1.20 1.35 TABLE 2 Liquid Temperature Correction Factors for R404A 20F 30F 40F 50F 60F 70F 80F 90F 100F 110F 120F 130F 140F 1.84 1.74 1.64 1.54 1.43 1.33 1.22 1.11 1.00 0.89 0.77 0.65 0.53 42 HPAC SEPTEMBER/OCTOBER 2005

CASH _ air flow The new, high SEER Halcyon IAQ Mini-Split lets you spend less time and make more money. Your time is valuable, so use it wisely. Our air-cooling and purifying systems install in a third of the time required to install a central air system with ductwork. Now you can install up to three times as many systems this summer, make more money and totally satisfy your customers needs. The 2005 additions to the Halcyon IAQ line include 14-SEER 9,000 BTU models and 13-SEER 12,000 BTU models. In fact, Fujitsu is the first with a 14-SEER mini-split. And our innovation continues by January 2006, all of our systems will be 13-SEER or higher and will use R410A refrigerant. Model BTU SEER Refrig 9CQ 9,000 A/C 14.3 R410A 9RQ 9,000 HP 14.3 R410A 12CQ 12,000 A/C 13.5 R410A 12RQ 12,000 HP 13.7 R410A 18CXQ 18,000 A/C 12.0 R22 18RXQ 18,000 HP 12.0 R22 24CXQ 24,000 A/C 12.0 R22 24RXQ 24,000 HP 12.0 R22 Our systems not only cool, but purify the air, removing smoke, allergens, and even pet odors. Improve their air flow and your cash flow with Halcyon. Visit Halcyon products at fujitsugeneral.com. T H E P O S S I B I L I T I E S A R E I N F I N I T E Circle #31

CONTINUED FROM PAGE 42 where the load is high enough (for example after a defrost cycle) for adequate velocity to allow the logged oil to return. Large amounts of oil sitting in the evaporator, if allowed to return in bulk, could seriously damage a compressor. This is a situation which should be avoided. 3. Reduced Compressor Efficiency And Higher Discharge Temperatures It might seem a little odd for a compressor to operate less efficiently and at higher discharge temperatures, from a reduced load condition. However, this is the result when the reduced load comes in the form of an underfeeding TEV and the resulting high superheats. High superheat at the evaporator outlet means the suction vapour temperature entering the compressor will be warmer too. The specific volume (in cubic feet/lb) of the refrigerant vapour will decrease as the temperature increases. While the compressor will continue to pump the same volume of refrigerant, the mass flow (in lbs/min) will decrease, reducing its effective pumping capacity. In addition, increasing the suction vapour temperature will result in higher discharge temperatures. In fact, for every 1F increase in suction gas temperature, there is an approximate 1F increase in discharge temperature. So while the underfeeding TEV will reduce the Btu load on the compressor, it will also cause less efficient operation at higher discharge temperatures. We have now made the following case: reducing head pressure lowers the operating expense of the compressor, however reducing it too much can very adversely affect the health and longevity of the system. We can also conclude that the determining factor in deciding what the minimum allowable head pressure should be is the minimum TEV P required for its capacity to meet the demands of the evaporator load. Once that has been determined, it becomes a simple matter of adjusting the head pressure controls on the system to maintain that minimum. There are several different methods of maintaining head pressure, and it is important to understand the principles of how each method operates so they can be set correctly. Fan cycling, condenser flooding and condenser splitting will be explored in HPAC S November/ December 2005 issue. Dave Demma is senior application engineer supermarket refrigeration with Sporlan Valve Division Parker Hannifin Corporation. He can be reached at tel. 636-239-1111 or by e-mail dgdemma@parker.com. RATE THE ARTICLE! Will this information be useful? Please circle the appropriate number on the Reader Postcard. Thank you. VERY USEFUL........ 112 USEFUL........... 113 NOT USEFUL........ 114 Recovery System Product Solutions for All Seasons Bacharach s Complete Line of, Monitors and Detectors. The heating season is approaching fast, save time and increase profits with the complete line of Bacharach s rugged and reliable products and tools. For almost a century Bacharach, the leader in portable and Monitors, has been developing innovative combustion products, gas leak detection and analysis technology for customers world wide that makes Bacharach The Measurable Difference Carbon Monoxide Environmental Combustion Leak Detection Circle #32 Bacharach of Canada: 250 Shields Court, Unit #3 Markham, Ontario L3R 9W7 Phone: 800-328-5217 Fax: 905-470-8963 Website: www.bacharach-inc.com 44 HPAC SEPTEMBER/OCTOBER 2005