MAXI & MAXI PLUS Floor mounted Pressure manager TECHNICAL DOCUMENTATION. Issue 06/14

Similar documents
1 Dimensions Installation Mains/boosted cold water inlet Connection to the system Drain Dimension for fixing 6

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION

TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03. Technical Data Electrical Details Connection Details Dimensions Standing Losses

Fusion 200, 300 & 500

Pressurisation units & expansion vessels

Extreme Domestic Hot Water Loading System TECHNICAL DOCUMENTATION. Issue 11/09

Gas Safety Products. Installation, operating and maintenance 09/05/2016. Merlin CT1650+ Gas Interlock System. S&S Northern Ltd 1

IMPRESS AND IMPRESS ADVANCED PRESSURISATION SETS INSTALLATION AND OPERATING INSTRUCTIONS

Transfer Switch Features

Transfer Switch Features

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

INSTALLATION & TECHNICAL MANUAL

2200 and 2200L ALARM CONTROL SYSTEMS

REDI CONTROLS, INC. Installation, Operation & Maintenance Manual

Intelligent Security & Fire Ltd

Broag Pressurisation equipment

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

CRU-S Series Stainless Steel Condensate Recovery Unit

Installation, operating and servicing instructions

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

ECONOPLATE H1-heat only HEAT INTERFACE UNIT. Installation, Commissioning and Servicing Instructions for vented systems.

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C, 140 AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

ECONOPLATE H1-heat only HEAT INTERFACE UNIT. Installation, Commissioning and Servicing Instructions for unvented systems.

LMR Electric Fire Pump Controllers Features

GS100M Gas Detection Controller

- Data Brochure Steam Control 279

LMR Electric Fire Pump Controllers Features

BX444-Mc Gas Detector

Cast Iron Boilers. G Series ( kW)

INSTALLATION & TECHNICAL MANUAL

DMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual

FDF Foam Pump Controllers Features

Mira Platinum Wireless Controller

Flopurge TS. Operation Manual

Container Refrigeration

The Professional s Choice

2000 SERIES DIAGNOSTIC ALARM CONTROL SYSTEM

QA16 Addressable System

Model 76 Dehumidifier Control Installation Instructions

user manual Document No , Revision 03 November 2015

KELCO F29 PROGRAMMABLE FLOW SWITCH

GeyserWise MAX. Instruction manual. All in one hot water management

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector)

Installation Instructions / Operating & Maintenance Manual Ablution Plant Model BTHW-1

ivector HEATER/COOLER 2 AND 4-PIPE MODELS.

Flostop TS D7E and A8E. Operation Manual

IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

UNDERCOUNTER SERVICE MANUAL. Ecoboiler UC4L 2.4kW Ecoboiler UC10L 2.8kW Ecoboiler UC10L 5.6kW Ecosmart UC4L 2.

The Professional s Choice

CONTENTS. Page. Contents 1. Introduction, features and benefits 2. PART ONE Overview of the softening process 4-5

Control Panel User Guide (TO BE RETAINED BY THE USER)

Document No Issue 4 user manual

ELECTRIC COMBINATION BOILER. (European Patent No: Design Right Protected.) TH12-450U MRK 2

Demand Duo Principle of Operation:

Troubleshooting Guide

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

SmartVent. Keypad Controller User Guide Manual. NZ s Home Ventilation Specialists

SmartVent. Digital Controller User Guide Manual. NZ s Home Ventilation Specialists

Installation, Operation and Maintenance Instructions for PlantPac Steam Plate Heat Exchanger Package

Please read this sheet as it contains important information

The Professional s Choice

Alpha FlowSmart 25 and 50

SYSTEM DESIGN REQUIREMENTS

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

3750 Pulpress pressurisation unit. Installation and operating instructions

GS100M Gas Detector. Technical Specification

Operator's Manual Dielman Rock Island Industrial Dr. St. Louis, MO Tel:(314)

MANUAL. OEM (Unit) OZONE GENERATOR (100VA, 200VA and 300VA) INDEX

Installation Instructions

The EN54 Part 2 and 4 Fire System

Quickheat 30 weather compensated boiler control

Troubleshooting Guide

DIESEL Engine Fire Pump Controllers Features

Application Manual Loop Water Controller

UPON COMMENCMENT OF INSTALLATION IT IS OF PARAMOUNT IMPORTANCE THAT THE STEP BY STEP GUIDE (INCLUDED) IS FOLLOWED COMPLETELY

Smoke Vent Control Panel PCB4 V4 Installation Manual

extreme HIGH EFFICIENCY HOT WATER SYSTEMS

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA The first totally integrated multiple boiler management control.

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Water heating for your PV system. Installation and user guide. v1.1

SMARTELEC 2 ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL

Engineers manual. Under counter machines

Installation, Operation and Maintenance Instructions Thermaflow E Plate Heat Exchanger Package OM013

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

CEM-24 Series. Owner's Manual - Installation and Operating Instructions

Extended Range. PRESFIX Packaged Pressurisation Sets AUTOMATIC MAKE-UP UNITS FOR SEALED HEATING AND CHILLED WATER SYSTEMS.

CRU 200 and 500 Series Condensate Recovery Unit Installation and Maintenance Instructions

3 In 1 AIR CONDITIONER with REMOTE CONTROL MODEL NO: CA9000 PART No: OPERATION & MAINTENANCE INSTRUCTIONS

The EN54 Part 2 & 4 Fire System

Product Instructions. Basic Digital Snow Melt Control II. Applications. Features. Specifications

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

INSTALLATION AND QUICK COMMISSIONING INSTRUCTIONS EWC WARM WATER TIME CLOCK WATER SOFTENERS

FT60 Reduced Voltage - Autotransformer

Electronically Controlled Instantaneous Water Heaters Models: CEX-O & CEX-U

Door Release Power Supply

LC2200 Level Controller Installation and Maintenance Instructions

Flomate Mains Boost Pump Installation & Maintenance Instructions

Gas Safety Products. Installation, operating and maintenance. Merlin 1000VW+ Gas Interlock, Gas Proving, Electric & Water Isolation System

Transcription:

INSPIRED EFFICIENCY MAXI & MAXI PLUS Floor mounted Pressure manager TECHNICAL DOCUMENTATION Issue 06/14

Content ontents Technical Data 3 1 Installation 4 1.1 Mains/boosted cold water supply 4 1.2 Connection to the system 5 1.3 Overflow Connection 5 1.4 Dimensions 6 2 Electrical connections 7 2.1 Electrical diagram 7 3 Keypad Function 8 4 Status Display 8 4.1 Pressure correct 8 4.2 Filling stopped due to low mains water pressure 8 4.3 Hours run facility 8 4.4 Hours run reset 8 5 Alarm conditions 9 5.1 Low Water Level Alarm 9 5.2 Optional System Failure/leak alert 9 5.3 High or low pressure alarms 9 5.4 Pump Failure 9 5.5 Frequent use alarm 10 5.6 Frequent use reset 10 6 Fault diagnosis 11 7 Manual override 12 8 Audible alarm override 12 9 Service Mode ( adjusting settings ) 12 10 Menu functions 13 11 Maintenance 13 12 Pump Curve and Data 14 2

Technical Data Electrical Details Maxi Single Maxi Single (HP) Maxi Plus Maxi Plus (HP) Supply Voltage 230 Volt 230 Volt 230 Volt 230 Volt Full Load Current 2.5 Amp 4.5 Amp 2.5 Amp 4.5 Amp Start Current 2.5 Amp 4.5 Amp 2.5 Amp 4.5 Amp Fuse Rating 5 Amp 8 Amp 5 Amp 8 Amp Max Load BMS Relays 5 Amp 5 Amp 5 Amp 5 Amp Connection Details W ater Inlet Water Outlet 15mm Compression 15mm Compression 3/4 BSP Max Coldfill Pressure Maxi 3.0 Bar / Maxi HP 6.0 Bar Dimensions Unit Weight Height Width Depth 27 Kg 35 Kg 29 Kg 38 Kg 600mm 465mm 390mm 3

Maxi & Maxi Plus pressurisation units The Maxi range is a fully automatic heating / chiller system pressurisation device, and is suitable for the water management in all domesticand commercialheating and cooling systems. It is supplied as a fully commissionedunit and should require no "on site" commissioning. 1 Installation All productsshould be installed by a competent person with regard to the relevant requirements of the Health and Safety Regulations, Building Regulations, IEE Regulations, Water Supply (water Regulations, Water Bye-laws (Scotland) and any other local bye-laws or planning requirements. The Maxi is intended for mounting: the unit should be situated in such a position as to enable the liquid crystal display to be easily read. 1.1 Mains/boosted cold water supply The Maxi is designedto be connected directly to the mains cold water supply, or a boostedcold water supply, the unit is suppliedcomplete with all necessary isolating valves, but an inlet water isolating valve is recommended.the water inlet is 15mm compression and should be connected to the mains cold water supply by 15mm copper tube or equivalent approved plastic pipework. If the Maxi is sited some distance from the mains cold water supply it may be advisable to install a single check valve adjacent to the mains cold water supply. To reduce the pressure drop on very long supply routes then 22mm supply pipework is recommended. 4

1.2 Connection to the system The Mikrofill Maxi is connected to the heating/chiller system by way of the 15mm outlet valve, the pipework from the unit should be made in 15mm copper or similarly approved plastic pipework. A suitably sized expansion vessel should be incorporated into the system at this point. Please refer to typical installation diagram on page 3. If you require any assistance regarding vessel sizing please contact our technical sales department. The final connection into the heating/chiller systemshould be sized accordingly, recommendations are shown below: Vessel size up to 100L Vessel size up to 300L Vessel size up to 1000L 1/2" (15mm) expansion pipework. 3/4" (22mm) expansion pipework 1" (28mm) expansion pipework. For vessel sizes in excess of 1000L capacity please contact our technical sales department. IMPORTANT NOTE The expansion vessel nitrogen/air charge must be set at the same pressure as the cold fill pressure of the system.* All Mikrofill expansion vessels are factory commissioned to the correct pressure. * When the installed height of the expansion vessel is different to that of the MAXI then please contact our service department who will advise on the nitrogen/air charge. 1.3 Overflow connection The Maxi is supplied with a 3/4" bsp plastic overflow (warning pipe) connection which should be led to a drain and be visible at point of discharge, MIKROFILL SYSTEMS LTD cannot accept any responsibility for flood damage caused by failure to connect the overflow. 5

Dimensions 480 320 540 600 390 465 View on arrow 'A' Front view Typical installation diagram Safety valve Pump Flow Return The expansion vessel is usually connected on the inlet side of the pump on the system return. For systems exceeding 90 o C contact our technical department for advice. See notes on pipework sizing on page 5. Mains cold water Overflow Alternative pump position 6

2 Electrical connections The Mikrofill Maxi requires a permanent 230V 50Hz 1 phase supply rated at 6 amp. The unit is internally fused at 5 amp (see electrical installation diagram). The Maxi also incorporates two BMS relays offering volt free contacts for the remote indication of high or low pressure conditions within the heating/chiller system. These relays are also independently fused at 5 amp to protect the Mikrofill Maxi from external electrical faults. A further volt free relay is included in the unit, this is to interlock the boiler or chiller control circuits. Should either of the alarm relays operate then the relay will shut down the boiler or chiller, indication of any alarmsituation will be indicated on the display. The relays are suitable for use on control voltages up to 250V. Once the Mikrofill Maxi has been correctly connected the unit is ready for use. Ensure that the unit has an adequate water supply and the service valves are open. Check for water leaks. Although every Maxi unit is factory tested it is still advisable to vent the pump(s) before operation. This is achieved by slackening the brass plug (14mm A/F).situated on the pump housing, until all air is eliminated. Switch on electrical supply to the unit and the on/off switch to the lower right hand side of the unit and the unit will start to pressurise the system. When the system has achieved the set pressure, the unit will stop filling, and go to standby. Important note, " pump type" pressurisation units are not designed to fill systems fromempty, they are only capable of " top up" and pressurisation. The system should be filled by other means in compliance with the water regulations. The Mikrofill Maxi is capable and approved to fill heating/chiller systems. 2.1 Electrical diagram Electrical data Supply: 230V 1ph 6 amp Full load current: 2.5 amp Start current: 4.5 amp Fuse rating: 5 am p / 8 amp BMS relays and boiler/chiller relays: volt free contacts rated at 250VAC at 5 amp All relays are independently fused at 5 amp Low pressure alarm High pressure alarm Boiler/chiller common alarm 230 VAC 50Hz 7

3 Keypad function System Data Button This button operates a scroll function normally for information only. When in the service mode, it allows selection of particular setting parameters. Button - used when in service mode to increase parameter values Button - used when in service mode to decrease parameter values Service Mode A multi-function button that, when in operational mode, is used to mute alarm conditions. In normal mode the keypad buttons are for information only and do not affect any of the parameters preset in the service mode. ( For information on service mode see section 8,page12 ) 4 Status Display 4.1 Pressure Correct The Maxi continuously monitors the system pressure, when the system pressure is within the set parameters the unit will show Pressure Correct on the LCD display 4.2 Hours run /water usage This is accessed by scrolling the system data button. 4.3 Hours run / water usage reset This is achieved by depressing the buttons simultaneously. 8

5 Alarmconditions Please note the Maxi is a factory pre-commissioned product, should you require to change any of the preset parameters - please see " Settings". 5.1 Low water level alarm The Maxi continuously monitors the water level in the feed tank. If this falls to below an acceptable level then the unit will operate a safety shut down. When water level is reinstated the unit will automatically reset. 5.2 Optional system failure/leak alert The Maxi can differentiate between normal system fill rates and excessive water demand usually due to a severe system leakage. If this situation occurs the Maxi will shut down, and issue a leak alert warning showing System Failure on the LCD. This alert must be reset manually, by switching off the Maxi and switching back on. If the leak has been rectified the unit will operate as normal. In some cases it may be required to disable or enable the leak alert facility. To disable/enable the leak alert press and hold the service button until the display shows Service mode on the LCD display. Use the system data button to scroll through the settings to leak alert and enable / disable using the or buttons 5.3 High or low pressure alarms If, for any reason the system water pressure reaches a high or low condition, as determined by the preset parameters the LCD will show the alarm message, the relevant BMS relay will operate and the Boiler/chiller control relay will shut down the boiler or chiller. When normal operating pressure is resumed the unit will automatically reset, 5.4 Pump failure The Maxi can also determine whether a pump has developed a fault. This is achieved by monitoring the systempressure and if an increase in pressure is not sensed in a set period of time it will stop operation of that pump and the " pump failure" message will appear on the LCD. If the Maxi Plus is used, it will automatically change to the remaining pump, and a pump failure message will be displayed. 9

5.5 Frequent use alarm This alarmis to assist in diagnosing any leaks that may be present in the heating (or cooling system). If in any 24 hr period the Maxi operates more than a preset limit i.e. 5, then a frequent use alarmwill show, (the operation of the systemwill not be affected, this function is for information only). 5.6 Frequent use reset This is achieved by switching the power supply to the unit off and on again. 10

6 Fault diagnosis System faults will be apparent from the alarm message displayed. The Maxi itself has a full self-diagnostic microprocessor unit which continually self-checks the operation. If an internal fault is diagnosed then the fault will be displayed on the screen, e.g. sensor failure. Fault conditions Fault indications Low water level Cause No water in tank Remedies Reinstate water supply to tank Sensor failure Possible sensor fault Incoming voltage instability 1. Switch unit off and back on, if sensor failure does not reappear on the display see note 2. If sensor failure does reappear check sensors are connected to the printed circuit board correctly. If the problem persists ring our service department. 2. If this occurs switch the unit off and back on, the unit should then operate as normal. If this fault appears on a regular basis then a mains electrical filter (anti surge device) is required. Ring our service department for advice. Low pressure alarm Systempressure low Check system for leaks. Switch unit off and back on to reinstate. Check Low Alarmsetting. High pressure alarm Systempressure high Reduce pressure in system and check expansion vessel air charge/size. Check High Alarmsetting. Systemfailure Possible excess water leak on the system Check system for leaks, then switch unit off and back on to reinstate. Pump failure Possible pump fault Switch unit off and back on to reinstate, if pump does not operate when required replace pump. If pump operates, dry run setting may need to be increased. Frequent use alarm Possible persistent leak on system If the unit operates more than the set value in a 24hr period the unit will bring up the frequent use alarm, this will not stop the unit from operating but indicates that there may be a small leak on the system. Switch the unit off and back on to reinstate. Investigate possible leak. The Mikrofill Maxi and Maxi Plus have been designed such that most apparent 'faults' can be remedied on site, if in doubt ring our service department on 08452 606020 11

7 Manual override In the unlikely event of a sensor failure the unit may give incorrect readings and could cause alarm conditions. If this occurs, a manual override can be employed by depressing the and the service mode buttons simultaneously for 3 seconds; thus reinstating the BMS relays in the unit. Before operating the manual override you must ensure there is sufficient pressure in the system. The manual override must not be employed if the unit has shown a flood alarm condition or, if there is insufficient pressure in the system. 8 Audible alarm mute If the Mikrofill Maxi does indicate a fault, an audible alarm will sound. This can be muted by depressing the service mode button. 9 Service Mode ( adjusting settings ) The settings can be adjusted on site as follows: 9.1 Press and hold the service mode button for approx 8 seconds 9.2 The display will indicate that you are now in the service mode 9.3 Use the system data button to scroll through the settings, each setting can be adjusted by use of the buttons. 9.4 After adjusting the settings, the unit will return to its normal operating mode approximately 30 seconds after release of the buttons. 12

O&M Maxi 1109 10 Menu Functions Cold fill pressure - this is the required pressure of the system when the system is cold Alarm low - the pressure at which the low pressure alarm relay will operate. Usually set 0.6-0.7 bar below the cold fill pressure. Alarm high - the pressure at which the high pressure alarm relay will operate. Usually set 0.2 bar below the system safety valve setting. Usage - for information on water used in the system, no setting required - please note, to zero the usage, the buttons need to be pressed simultaneously for 3 seconds. minutes ) the less responsive the flood protection, set at 0.00 to disable pump failure. prevents under shoot, decreasing time prevents over shoot. Frequent use - this setting warns of frequent use which would indicate a system leak and will show a warning message if in any 24hr period the unit operates in excess of the frequent use setting. caused when pumps start. Contrast adjust - alters the contrast of the LCD display. Fault log - Logs the last five faults MP - Low mains water pressure LP - Low system pressure alarm HP - High system pressure alarm SF - Sensor failure DR - Leak alert due to no increase in pressure while filling FS - Leak alert due to drop in pressure while filling 11 Maintenance Maxi - The filter which is housed in the inlet ball valve to the pump should be checked and cleaned annually. EXPANSION VESSELS - Charge pressure should be checked annually, when the system is cold the air charge must be equal to the cold fill pressure of the Maxi. 13

12 Pump Curve and Data 7 6 Mikrofill Pump Range Performance Maxi Pump Maxi HP Pump 5 Head (bar) 4 3 2 1 0 0 5 10 15 20 25 30 35 Flow (l/min) PRODUCT DATA Pump Max Pressure (bar) Max Flow (l/min) Input Power (W) Current (A) Supply Voltage Frequency Size (mm) L x W x H Weight (kg) Maxi Pump 3.65 29 510 2.53 230V ± 10% 50 Hz 210 x 145 x 185 8.3 Maxi HP 6.2 31 960 4.3 230V ± 10% 50 Hz 220 x 145 x 185 9.5 14

Mikrofill Systems Ltd West Court Merse Road Redditch B98 9HL T +44 (0) 8452 606020 F +44 (0) 8452 606021 W mikrofill.com E info@mikrofill.com