MODELS K2EU060A, K4EU090A, & K3EU120A

Similar documents
SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

INSTALLATION MANUAL (AIR COOLED) SPLIT-SYSTEM AIR CONDITIONER MODEL: LA120 NOTES, CAUTIONS AND WARNINGS SAVE THIS MANUAL B-0203

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

INSTALLATION INSTRUCTION

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

MODELS B1PA024, 030 AND 036

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT

INSTALLATION INSTRUCTION-50 Hz

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

R-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES

INSTALLATION INSTRUCTION

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195)

R-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM HEAT PUMPS 60 HZ MODELS: EF-10 & FF-10

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72

INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS

CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: N4 (778) N4Y (492)

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804

MODELS E1FB180 & E1FB240

APPLICATION DATA SHEET

40 RM/RMS Packaged Air-Handling Units

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

INSTALLATION INSTRUCTION

CONDENSING UNITS SPLIT-SYSTEM COOLING 6-1/3 TONS INSTALLATION INSTRUCTION MODELS H*DB076 NOMENCLATURE GENERAL LIMITATIONS INSPECTION REFERENCE

SUBMITTAL DATA SHEET FEATURES. SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15 & 20 TONS MODELS: NH-07 thru -20, 2-PIPE NJ-10 thru -20, 4-PIPE

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS. HB 180 & thru 20 Nominal Tons NOTES, CAUTIONS AND WARNINGS

SUNLINE SERIES SINGLE PACKAGE AIR CONDITIONERS. INSTALLATION INSTRUCTION Supersedes: Nothing N3Y (394) MODELS D*SC360 & 480 INSPECTION

INSTALLATION INSTRUCTION

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

INSTALLATION INSTRUCTION

INSTALLATION MANUAL - 50 Hz

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: N1Y (497) N1Y (998) MODELS E2FB090 & E1FB120 GENERAL

Supersedes: N2W (398) N2Z (1298) MODELS BCCB 090 & 120, MODELS BECB090 & 120 (9 EER) 208/230/460 VOLT MODELS ONLY

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

VertiCool Aurora Engineering Guide

SUNLINE 2000 ELECTRIC / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: N7Y (993) 530.

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

TECHNICAL GUIDE COMMERCIAL SPLIT-SYSTEM HEAT PUMP FOUR PIPE SYSTEM DESCRIPTION E*FB180 & 240 F*EH180 & & 20 NOMINAL TONS INDOOR UNIT

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

ACCESSORY KIT INSTALLATION INSTRUCTIONS

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: Nothing N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) GENERAL

PACKAGE AIR CONDITIONER

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

Supersedes: N2Y (498) N2Y (799) MODELS B1HH018 THRU THRU 5 TON (12 SEER)

FILTERS MANIFOLD CABINET REFRIGERANT CONNECTION LOCATION

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: TABLE OF CONTENTS LIST OF FIGURES

Installation Instructions

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Installation, Operation, and Maintenance Information

MODELS B3CH 048 AND 060 (WORLD 50 HZ)

INSTALLATION MANUAL SINGLE PIECE STANDARD ECM AIR HANDLERS MODELS: AHX61 SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

MODELS W1LC220, 260 AND 320 STYLE B

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY UIM-C-0214

Installation Instructions

C13-Series Engineering Guide

INSTALLATION INSTRUCTIONS

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

INSTALLATION MANUAL AFFINITY SERIES SINGLE PACKAGE AIR CONDITIONERS ELECTRIC/ELECTRIC, AIR-COOLED. MODELS: D1EB036 thru Thru 5 Ton (10 SEER)

Installation, Start-Up and Service Instructions

MODELS B3CH 090 & 120A25, A46 MODELS B4CH090 & 120A58 (9 EER) 208/230/575 VOLT MODELS ONLY 208/230/460 VOLT MODELS ONLY

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

MERIT SERIES Up Flow / Horizontal

SECTION AIR HANDLING UNIT

1.1 This section applies to air handling units for HVAC Systems.

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

COMMERCIAL AIR HANDLER

Installation, Start-Up and Service Instructions

Installation, Start Up and Service Instructions

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

AllStyle Coil Company, LP 7037 Brittmore Houston, TX Phone Fax

Installation, Start-Up and Service Instructions

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHR / AHE SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

technical guide Water-Cooled Self-Contained Units

Transcription:

AIR COOLED SPLIT-SYSTEM AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: 550.23-N2Y (589) 550.23-N2Y (399) MODELS K2EU060A, K4EU090A, & K3EU120A 035-16672 GENERAL These completely assembled 5, 7-1/2 and 10 ton blower units include a well insulated cabinet, a DX cooling coil with copper tubes and aluminum fins, an expansion valve, a distributor, throwaway filters, a centrifugal blower, a blower motor contactor and a small holding charge of refrigerant-22. Blower motors and adjustable drives are factory-installed on all units. The units are shipped in the vertical position ready for field installation. For horizontal installation, reverse the solid bottom panel and the return air duct flange on the front of the unit. INSPECTION As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier s freight bill. A separate request for inspection by carrier s agent should be made in writing. RENEWAL PARTS Refer to Parts Manual for complete listing of replacement parts on this equipment for complete listing of replacement parts. The forms referenced in this instruction may be ordered from: Publications Distribution Center Unitary Products Group P.O. Box 1592, York, PA. 17405 This instruction covers the installation and operation of evaporator blower units. For information on the operation of the matching condensing unit, refer to Forms 550.46-N1Y, 550.46-N2Y, 550.38-N1Y, 550.38-N6Y and 550.23-N1Y. Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and / or equipment damage may result if installation procedure is not handled properly.

TABLE OF CONTENTS TABLES General... 1 Renewal Parts... 1 Inspection... 1 INSTALLATION Limitations... 3 Location... 3 Clearances... 3 Rigging and Handling... 4 Vertical / Horizontal Installation... 4 Duct Connections... 4 Refrigerant Mains... 5 Drain Connection... 6 Supply Air Blower Adjustment... 6 Power and Control Wiring... 11 MAINTENANCE Filters... 12 Evaporator Coil... 12 Drain Pan... 12 Lubrication... 12 Belts... 12 NOMENCLATURE No. Description Page 1 Unit Application Data... 3 2 Physical Data... 5 3 Blower Motor Pulley Adjustment... 7 4 Blower Performance... 8 5 Accessory Static Resistance... 8 6 Blower Motor and Drive Data... 8 7 Electrical Data... 11 FIGURES No. Description Page 1 Unit Suspension Mounting... 3 2 Vertical & Horizontal Application... 4 3 Supply Air Duct Connection... 4 4 Electric Heater Accessory... 5 5 Supply Air Plenum Accessory... 5 6 Base Accessory... 5 7 Return Air Grille Accessory... 5 8 Recommended Drain Piping... 6 9 Motor Mounting Assembly... 7 10 Hole Locations for Pressure Readings... 7 11 Pressure Drop vs. Supply Air CFM... 7 12 Unit Dimensions & Clearances (5 tons)... 9 13 Unit Dimensions & Clearances... 10 (7-1/2 & 10Tons) 14 Typical Field Wiring... 11 " - 7 ' )!! 2 4, 7 + 6 + ) 6 - / 4 ; 5 F EJ 5 O I JA - L = F * M A H 9 EJD J H= @, HEL A 8 6 ) / - +, - $ &! $!! &! " $! $ 2 4, 7 + 6 / - - 4 ) 6 1. ) + 6 4 ; 1 5 6 ) -, 0 - ) 6 @ / A A H = J E!! H @ / A A H = J E ) J ) F F E? = > A " " J D / A A H = J E 1 ) + 1 / + ) 2 ) + 1 6 ; 2 4, 7 + 6 1, - 6 1. 1-4 $ # 6-7 - L = F H= J H* M ' AH % 6 6 2 Unitary Products Group

LIMITATIONS This unit must be installed in accordance with all national and local safety codes. If no local codes apply, installation must conform to the appropriate national code. The unit is designed to meet National Safety Code Standards. If components are to be added to a unit to meet local codes, they are to be installed at the dealer s and/or the customer s expense. See Table 1 for application limitations. LOCATION These Evaporator Blowers are not designed for outdoor installation. They must be located within the building structure, either inside or outside the conditioned space. These Evaporator Blower sections allow for vertical or horizontal installation in any area offering proper electrical supply, duct and drain connections. They may be installed either with ductwork or matching plenum and inlet grille. INSTALLATION The units should be located as close to the condensing units as practical and positioned to minimize bends in the refrigerant piping. Units being installed vertically or horizontally can be set directly on a floor or platform, or metal or wooden beams can support them. Units being installed horizontally can be suspended from above. Four 3/8" weld nuts are provided in the unit frame to accommodate hanger rods. Knockouts must be removed from the unit panels to expose these weld nuts. Refer to Figure 1 for their location and the individual load on each hanger rod. WARNING: Be careful when attaching the hanger rods. They must not be allowed to turn or slip. CLEARANCES Refer to the unit dimension details, Figures 12 and 13 for clearances required for servicing and for proper unit operation. TABLE 1 - UNIT APPLICATION DATA Model Voltage Supply Air Entering Air Temperatures, F Power Variation* CFM Supply Cooling Coil - db/wb Heating Coil - db Min. Max. Min. Max. Min. Max. Min. Max. K2EU060A06 208/230-1-60 187 252 1600 2400 65/57 95/72 40 77 K4EU090A33 K3EU120A33 208/230-3-60 460-3-60 208/230-3-60 460-3-60 187 432 187 432 * Utilization Range "A" in accordance with ARI Standard 110 252 504 252 504 2400 3600 65/57 95/72 40 77 3200 4800 65/57 95/72 40 77 "! & $ 9 -, 7 7 6 5 34-1/2 (KEU060) " - 7 $ 49-1/4 (KEU090, 120)! & - 7 ' W1 + - 6-4. / 4 ) 8 1 6 ; ) W2 W3 # & * 37-9/16 (KEU060) 44-7/8 (KEU090, 120) W4 AIR IN AIR OUT RETURN AIR GRILLE, HOT WATER COIL AND STEAM COIL ACCESSORIES INSTALLED ON ON THIS END OF THE UNIT. 5 7 2 2 ; ) 1 4 2-7 ), - - + 6 4 1 + 0 - ) 6-4 ) + + - 5 5 4 1-5 1 5 6 ) -, 6 0 1 5 -,. 6 0-7 1 6 Model Center of Gravity Dimensions (in.) Weight Distribution (Lbs.) A B W1 W2 W3 W4 TOTAL KEU060 22-3/8 15-1/4 60 65 40 45 210 KEU090 26-1/4 23-3/4 85 93 70 77 325 KEU120 26-5/8 24-1/8 85 95 70 80 330 FIG. 1 - UNIT SUSPENSION MOUNTING (Horizontal Application) Unitary Products Group 3

RIGGING AND HANDLING Be careful when moving the unit. Do not remove any packaging until the unit is near its final location. The packaging consists of a bottom wooden skid that can be lifted with a fork truck from any direction, a corrugated container that covers the entire unit, and strapping that secures the container to the skid. These units can be rigged with slings under the bottom skid CAUTION: Spreader bars should be used to prevent the slings from crushing the unit panels and frame. Before rigging any unit, determine its weight from Table 2. Before rigging a unit for horizontal installation, determine its center of gravity from Figure 1, and make sure that its weight will be distributed equally. VERTICAL/HORIZONTAL INSTALLATION These evaporator blowers are shipped for vertical installation with vertical air discharge as shown in Figure 2(A) but may be converted for horizontal installation as shown in Figure 2(B) by interchanging the solid bottom panel and the return air duct flange. DUCT CONNECTIONS Design and install all ducts in accordance with all national and/or local codes. Refer to Figure 3 for suggested method of connecting supply air ductwork. Ducts should be sized no smaller than the duct flanges on the unit or the electric heater (if used). Refer to the unit dimension details (Figure 12 and 13) and the heater detail (Figure 4) for theses sizes. Refer to Form 550.12-N10.1U for installation instructions on the electric heater. Use flexible fiber glass or plastic cloth collars or other non-flammable material at the unit duct connections to minimize the transmission of noise and vibration. Insulate all ductwork running through unconditioned areas to prevent moisture condensation and to provide more economical operation. The return air duct flange is factory-mounted on the front of the unit, but it can be reversed with the solid bottom panel for horizontal applications. When the return air grille is used, the duct connection frame is not used. NOTE: If return air duct is not used, applicable installation codes may limit the unit to installation only in a single story residence. A supply air plenum (Figure 5), a base (Figure 6), and a return air grille (Figure 7) are available as field-installed accessories, and one of the following respective instruction forms will be packed with each. 550.13-N10.2U - Supply Air Plenum 550.13-N10.3U - Return Air Grille 550.12-N10.4U - Base The supply air plenum and the return air grille should be used in lieu of ductwork only when a free blow/free return application is practical. ) 1 4 7 6 8-4 6 1 + ) 2 5 1 6 1 REFRIGERANT MAINS Many service problems can be avoided by taking adequate precautions to provide an internally clean and dry system and by using procedures and materials that conform with established standards. * 9-4 * 9-4 6 4 + ) 6 1 4-6 7 4 ) 1 4, 7 + 6. ) / - + 1 ) 1 4 1 ) 5 1, * 6 6 2 ) -. ) ) * - + ) 4, 7 + 6. ) / -,, 7 + 6 + - + 6 1. 1-,. ) * 4 1 + ) 6 -, 4-6 7 4 ) 1 4, 7 + 6. ) / - ) 1 4 1 + 1 5 1, * 6 6 2 ) - 0 4 1 6 ) 2 5 1 6 1 * 9-4 ) 1 4 7 6 5 7 2 2 ; ) 1 4, 7 + 6. ) / - ) 1 4 7 6 * 9-4 / ) 5-6 * ; 1 5 6 ) - 4 * 9-4 6 4 + ) 6 1 * FIG. 2 - VERTICAL AND HORIZONTAL APPLICATION FIG. 3 - SUPPLY AIR DUCT CONNECTION 4 Unitary Products Group

TABLE 2 - PHYSICAL DATA DESCRIPTION UNIT MODEL 060 090 120 Rows Deep x Rows Wide 3 x 24 3 x 27 3 x 32 Finned Length - inches 30 46 46 EVAPORATOR COIL Face Area - square feet 5.0 8.6 10.2 Tube OD - inches 3/8 3/8 3/8 Fins per inch 13 13 13 CENTRIFUGAL BLOWER (Forward Curve) Diameter x Width - inches 10 x 10 15 x 15 15 x 15 MOTORS 1 Nominal HP Rating 3/4 1-1/2 2 FILTERS Quantity Per Unit 16" x 25" x 1" 2 4 4 (Throwaway) Face Area - square feet 5.6 11.1 11.1 DISTRIBUTOR One Per Unit 4-3-6-1 2 5-3-10-1 2 5-3-12-1 2 Basic Unit 210 325 330 Accessories Supply Air Plenum 90 102 102 Return Air Grille 12 15 15 Hot Water Coil 56 82 82 OPERATING Weight, Lbs. 3 Steam Coil 57 85 85 Base 45 60 60 Electric Heat: 10 KW 60 63 63 16 KW 64 66 66 26 KW 68 71 71 36 KW - 74 74 Tubes OD, inches 1/2 (Copper) Rows Deep 2 HOT WATER COIL Fins Per Inch 12 (Aluminum) Face Area, square feet 3.6 6.8 6.8 Connections (Supply & Return) 1" NPTE Outer Tube OD, inches 1 (Brass) Rows Deep 1 Fins Per Inch 8 (Aluminum) STEAM COIL Face Area - square feet 3.7 6.6 6.6 Connection Inlet 1-1/2" NPTE Outlet 1-1/2" NPTE ELECTRIC HEAT Heater Elements % Nickel 59.2 %Chromium 16.0 Watt Density, watts/sq. in. 59.0 Face Area, square feet 3.0 SHIPPING VOLUME - Cubic Feet (Basic Unit) 30 53 53 1 Refer to Blower Motor and Drive Data for additional blower motor and drive information. 2 The first digit refers to inlet diameter (1/8"), second digit refers to tube diameter (1/16") and the third digit refers to number of tubes and the fourth digit refers to number of distributors. 3 Refer to the unit installation instruction for the distributed weight of the evaporator blower unit: Form 550.23-N1Y (060, 090 and 120) Hard drawn copper tubing should be used where no appreciable amount of bending around pipes or other obstructions is necessary. Use long radius ells wherever possible with one exception. Use short radius ells for traps in all vertical suction risers. If soft copper must be used, avoid sharp bends, which may cause a restriction. Fiberglass insulation and a sealing material such as permagum should be packed around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility. Support all refrigerant lines at minimum intervals with suitable hangers, brackets or clamps. Braze all copper-to-copper joints with Sil-Fos 5 or equivalent brazing material. Do not use soft solder. Never braze or solder the liquid and suction lines together. The complete suction line should be insulated with no less than 1/2" ARMAFLEX or equivalent. If the liquid and suction lines are to be taped together for support purposes, they must be completely insulated from one another. INSTALLING REFRIGERANT MAINS The units are evacuated and dehydrated at the factory and shipped with a holding charge of Refrigerant-22. The suction and liquid connections are sealed with copper discs. Refer to the appropriate condensing unit installation instructions for charging data. Unitary Products Group 5

8-4 6 1 + ) ) 4 4 ) / - - 6 5 0 9 5 7 2 2 ; ) 1 4 6 2 2 ) - ) 6-4 ) 6 - ) 1 4, 1 5 + 0 ) 4 / -, 7 + 6. ) / - * * 9-4 7 1 6 ) / 4 1-0 - ) 6-4 - - - 6 + 0 ) * - 4 J7 = F F H L A @ M EJD E I J= = JE B= 5 K F F O ) EH2 A K =?? A I I HO HM EJD = - 7 $ K EJ E I J = A @ D H E J = O + 6 4 * : ) + + - 5 5 2 ) - MODEL 5 TON 7-1/2 & 10 TON A 16-7/8 19-1/4 B 20-1/8 22-1/4 FIG. 4 - ELECTRIC HEATER ACCESSORY 8-4 6 1 + ) ) 4 4 ) / - - 6 5 0 9 5 7 2 2 ; ) 1 4 * 9-4 7 1 6 2 A K I D K @ > A B EA @ K J A @ J D A I K F F O = EH A @ B > M A H K EJI B HA EJD A HL A HJE? = HD HE J= = F F E? = JE. HHA = H@ EI? D = HC A H J = J A F A K & @ A C H A A I. H D H E J = @ EI? D = H C A = D H E J = K EJ JD A C= HE A A F = @ J D A J F F = A M E > A = H H = C A @ @ EB B A H A J O 4 A B A H J. H # #! 7 B H E I J = = J E = @ = I I A > O E I J H K? J E I FIG. 5 - SUPPLY AIR PLENUM ACCESSORY * 9-4 7 1 6. 4 8-4 6 1 + ) ) 4 4 ) / - - 6 ; * 9-4 7 1 6 9 0-7 6, 4 ) 14 15 4-3 7 14 -, ) 0 - + ) * *-) 5-2 ) - + 7 6 1 * ) + 2 ) -. 4 + - + 6 1 /, 7 + 6 9 4 8-4 6 1 + ) ) 4 4 ) / - - 6 5 0 9 FIG. 6 - BASE ACCESSORY CAUTION: Always puncture sealing caps and discs with a small drill bit before unbrazing to prevent the pressure in the line from blowing them off. Before starting installation of the mains be sure the unit has not developed a leak in transit by drilling a small hole in the sealing discs. If pressure still exists, the circuit may be considered leak free. If pressure does not exist the coil should be leak tested. NOTE: To minimize the possibility of system failure due to dirt and moisture, a filter-drier must be installed in the liquid line as close to the evaporator as possible. Filter-driers are not supplied with the evaporator blowers. They are supplied with the matching condensing sections. If check valves are required, they must be purchased and installed in the field. The temperature required to make or break a brazed joint is sufficiently high to cause oxidation of the copper unless an inert atmosphere is provided. CAUTION: Dry nitrogen should flow through the system at all times when heat is being applied and until the joint has cooled. The liquid and suction connections must be piped outside the unit. Refer to the unit drawing for locations and the dimensions of these connections. Before brazing the refrigerant lines to these connections, remove the short panel from the unit frame and slide it (along with the grommets) onto the refrigerant lines. After the brazed joints have cooled, slide the panel back into place and secure it to the unit frame. FIG. 7 - RETURN AIR GRILLE ACCESSORY NOTE: These units can only be piped from one side of the unit. EXPANSION VALVE BULB On KEU060 and 090 units, the expansion valve bulb must be fastened in a 4 o clock position to the suction line outside the cabinet after the piping connections have been made. On KEU120 units, fasten the expansion valve bulb on the suction header 8" below the top of the header, and adjacent to the coil. Use the clamps provided with the valve to secure the bulb in position. DRAIN CONNECTION The drain line must be trapped because the coil is located on the negative side of the supply air blower. It must be protected from freezing temperatures. A 7/8" O.D. drain connection extends through right hand side of cabinet. Refer to Figure 8 for recommended drain piping. The drain connection is located on the same side of the unit as the refrigerant connections. The line should be insulated where moisture dripping will be objectionable or cause damage to the area. The 3" dimension must equal or exceed the negative static pressure developed by the supply air blower. If it does not, the condensate will not drain properly and may overflow the drain pan. The trap must be at least 2-1/2" deep to maintain a water seal under all operating conditions, especially during blower start-up. 6 Unitary Products Group

PLASTIC ELL STEEL STUB CONNECTION DRAIN PAN +, 6 5 - * 6 4 7 6 3" 6 4 2" EVAPORATOR COIL HOSE CLAMPS DRAIN PLUG FIG. 8 - RECOMMENDED DRAIN PIPING NOTE: Refer to Figure 12 or 13 for minimum clearance requirements. SUPPLY AIR BLOWER ADJUSTMENT The RPM of the supply air blower will depend on the required CFM, the unit accessories and the static resistances of both the supply and the return air duct system. With this information, the RPM for the supply air blower can be determined from the blower performance shown in Table 4. Knowing the required blower RPM and the blower motor HP, the setting (turns open) for the supply air motor pulley can be determined from Table 3. Each motor pulley has: 1. A threaded barrel with two flats (or notched recesses) 180 degrees apart. 2. A movable flange with one set screw. FIG. 9 - TYPICAL MOTOR MOUNTING ASSEMBLY of 2 to 3 pounds. Moving the blower motor mounting plate makes this adjustment. Refer to Figure 9. Turning the adjustment bolt (B) moves the motor mounting plate up or down. Note - NEVER loosen the two nuts (C). Two hex nuts (A) have to be loosened to move the mounting plate and retighten after the mounting plate has been moved to the proper position. 4. All pulleys are factory aligned. 5. All supply air motor pulleys are factory set at 3 "turns open". ) After the movable flange has been rotated to the proper number of "turns open"; the set screw should be tightened against the flat on the barrel to lock the movable flange in place. If the pulley includes a locking collar, the locking collar must be loosened to adjust the setting of the movable flange. ) # $ 0 - Note the following: 1. The supply air CFM must be within the limitations shown in Table 1. - 8 ) 2 4 ) 6 4 + 1 + * 2. All Pulleys can be adjusted in half turn increments. 3. The tension on the belt should be adjusted for a deflection of 3/16 of an inch per foot of belt span with an applied force TABLE 3 - SUPPLY AIR BLOWER MOTOR PULLEY ADJUSTMENT TURNS OPEN* KEU060 810-1110 DRIVE RANGE (RPM) KEU090 655-880 KEU120 700-950 5 810 655 700 4 870 700 750 3 930 745 800 2 990 790 850 1 1050 835 900 0 1110 880 950 * Pulleys can be adjusted in half-turn increments. ) 1 4 1. 1 6-4 5 # $ 0 - DIMENSIONS (in.) MODEL A B C D KEU060 9-1/2 2-1/4 19 10-1/4 KEU090 3 3 14 12 KEU120 3 3 14 12 NOTE: Shut down the refrigeration system before taking any test measurements to assure a dry evaporator coil. FIG. 10 - HOLE LOCATIONS (PRESSURE DROP READINGS), Unitary Products Group 7

2 4-5 5 7 4 -, 4 2 19 /! - 7 ' - 7 $ % & '! " 2-4 + - 6 1 ) +. FIG. 11 - PRESSURE DROP ACROSS A DRY EVAPORATOR COIL VS. SUPPLY AIR CFM After the supply air blower motor is operating, adjust the resistances in both the supply and the return duct systems to balance the air distribution throughout the conditioned space. The job specifications may require that this balancing be done by someone other than the equipment installer. To check the supply air CFM after the initial balancing has been completed: 1. Drill two 5/16-inch holes in the side panel as shown in Figure 10. 2. Insert at least 8" of 1/4 inch tubing into each of these holes for sufficient penetration into the airflow on both sides of the evaporator coil. NOTE: The tubes must be inserted and held in a position perpendicular to the airflow so that velocity pressure will not affect the static pressure readings. 3. Using an inclined manometer, determine the pressure drop across a dry evaporator coil. Since the moisture on an evaporator coil may vary greatly, measuring the pressure drop across a wet coil under field conditions would be TABLE 4 - SUPPLY AIR BLOWER PERFORMANCE 1 RPM SP 2 BHP 3 CFM KW SP 2 BHP3 KW SP 2 BHP 3 KW SP 2 BHP 3 KW SP 2 BHP 3 KW 060 1600 1800 2000 2200 2400 800 0.43 0.38 0.34 0.30 0.45 0.41 0.16 0.52 0.48 - - - - - - 810 0.45 0.39 0.35 0.32 0.46 0.42 0.18 0.53 0.49 0.02 0.61 0.56 - - - 900 0.64 0.48 0.43 0.53 0.56 0.51 0.40 0.64 0.59 0.25 0.73 0.68 0.10 0.82 0.77 1000 0.87 0.58 0.53 0.77 0.67 0.63 0.65 0.76 0.71 0.51 0.86 0.81 0.37 0.97 0.90 1100 1.12 0.69 0.64 1.03 0.78 0.73 0.92 0.89 0.83 0.79 1.00 0.94 0.66 1.13 1.04 1110 1.15 0.70 0.65 1.06 0.79 0.74 0.95 0.90 0.84 0.82 1.02 0.95 0.69 1.16 1.08 1200 1.39 0.80 0.75 1.30 0.90 0.84 1.20 1.02 0.95 1.09 1.15 1.07 0.97 1.30-090 2400 2700 3000 3300 3600 600 0.35 0.62 0.59 0.26 0.70 0.66 0.13 0.78 0.73 - - - - - - 655 0.49 0.70 0.66 0.41 0.78 0.72 0.30 0.87 0.82 0.07 0.96 0.90 - - - 700 0.60 0.77 0.73 0.53 0.85 0.80 0.43 0.95 0.89 0.29 1.06 0.99 0.12 1.17 1.09 800 0.92 0.97 0.90 0.85 1.06 0.99 0.77 1.18 1.10 0.65 1.30 1.21 0.49 1.42 1.32 880 1.18 1.11 1.04 1.11 1.24 1.16 1.03 1.37 1.28 0.91 1.50 1.38 0.77 1.64 1.53 900 1.24 1.15 1.07 1.18 1.28 1.19 1.10 1.42 1.32 0.98 1.55 1.43 0.84 1.70 1.57 1000 1.58 1.35 1.26 1.53 1.48 1.38 1.46 1.63 1.48 1.37 1.81 1.65 1.24 2.02 1.85 120 3200 3600 4000 4400 4800 700 0.49 1.01 0.94 0.34 1.17 1.09 0.14 1.33 1.24 - - - - - - 800 0.84 1.25 1.16 0.71 1.42 1.32 0.53 1.60 1.48 0.30 1.80 1.64 - - - 900 1.18 1.48 1.38 1.06 1.70 1.57 0.91 1.92 1.75 0.70 2.18 1.99 0.43 2.45 2.24 950 1.37 1.61 1.50 1.26 1.86 1.71 1.11 2.12 1.95 0.91 2.39 2.18 0.65 2.67 2.44 1000 1.56 1.75 1.62 1.46 2.02 1.85 1.32 2.30 2.10 1.13 2.60 2.38 0.87 2.90 2.65 NOTE: Refer to Form 550.13-AD1 for blower performance curves. RPM range for the standard, factory-mounted drive components. Exceeds the BHP limitation of the standard factory mounted blower motor. 1 Unit resistance is based on a wet evaporator coil and clean filters. 2 Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the respective tables for the resistance of these accessories and for additional motor and drive data. 3 Motors can be selected to operate into their service factor because they are located in the moving air stream, upstream of any heating device. Units with steam or hot water coils are the only exception. On these units, the BHP must not exceed the nominal HP rating of the motor. 8 Unitary Products Group

TABLE 5 - STATIC RESISTANCES FOR UNIT ACCESSORIES (IWG) Unit Model 060 090 120 Accessory CFM 1600 1800 2000 2200 2400 10 KW 0.01 0.01 0.01 0.02 0.02 Electric Heaters 16 KW 0.01 0.02 0.02 0.03 0.04 26 KW 0.02 0.03 0.04 0.05 0.08 Supply Air Plenum 0.03 0.04 0.05 0.07 0.10 Return Air Grille 0.03 0.04 0.05 0.07 0.10 Hot Water Coil 0.16 0.21 0.24 0.28 0.32 Steam Coil 0.13 0.16 0.19 0.22 0.26 2400 2700 3000 3300 3600 10 KW 0.01 0.01 0.01 0.02 0.02 Electric Heaters 16 KW 0.01 0.02 0.02 0.03 0.04 26 KW 0.03 0.04 0.05 0.06 0.07 36 KW 0.05 0.07 0.08 0.10 0.11 Supply Air Plenum 0.03 0.03 0.04 0.05 0.06 Return Air Grille 0.02 0.03 0.04 0.05 0.06 Hot Water Coil 0.11 0.14 0.17 0.20 0.23 Steam Coil 0.10 0.12 0.14 0.16 0.19 3200 3600 4000 4400 4800 10 KW 0.02 0.02 0.03 0.03 0.04 Electric Heaters 16 KW 0.03 0.04 0.05 0.06 0.07 26 KW 0.06 0.07 0.09 0.11 0.13 36 KW 0.09 0.11 0.14 0.17 0.20 Supply Air Plenum 0.05 0.06 0.07 0.08 0.10 Return Air Grille 0.05 0.06 0.07 0.08 0.10 Hot Water Coil 0.19 0.24 0.30 0.35 0.40 Steam Coil 0.16 0.19 0.23 0.27 0.31 TABLE 6 - BLOWER MOTOR AND DRIVE DATA MODELS MOTOR HP BLOWER (RPM) ADJUSTABLE MOTOR PULLEY PITCH DIA. (IN.) BORE (IN.) FIXED BLOWER PULLEY PITCH DIA. (IN.) BORE (IN.) DESIG- NATION BELTS PITCH LENGTH (IN.) 060 3/4 810-1110 2.8-3.8 5/8 6.0 3/4 A32 33.3 090 1-1/2 655-880 2.8-3.8 7/8 7.5 1 A36 37.3 120 2 700-950 2.8-3.8 7/8 7.0 1 A36 37.3 NOTES: 1. All motors are 1750 RPM and have a 56 frame, inherent protection and permanently lubricated ball bearings. The 3/4 HP motor is split phase and has a resilient base and a 1.25 service factor. The 1-1/2 and 2 HP motors have a solid base and a 1.15 service factor. 2. Three-phase motors are be wired for a 460 volt power supply. Refer to the wiring diagram inside the motor terminal box when motor leads have to be reconnected for a 208 or 230 volt power supply. inaccurate. To assure a dry coil, the refrigeration system should be de-activated while the test is being run. 4. Knowing the pressure drop across a dry coil, the actual CFM through the unit can be determined from the curve in Figure 11. If the CFM is above or below the specified value, the supply air motor pulley may have to be re-adjusted. After one hour of operation, check the belt and pulleys for tightness and alignment. WARNING: Failure to properly adjust the total system air quantity can result in extensive blower damage. After readings have been obtained, remove the tubes and seal up the drilled holes in the side panel 5/16" dot plugs (P/N 029-13880) are available through normal parts ordering procedures. Unitary Products Group 9

8-1/2 13-1/4 36-1/8 7/8" HOLE W/BUSHING IN REAR PANEL (For Low Voltage Control Panel) 1-23/32 KNOCKOUT (Removed only when Electric Heat Accessory is used) AIR OUT 1 3-7/8 7/8" KNOCKOUT IN REAR PANEL (For Power Wiring) 4-1/2 3/4 2-1/4 11-5/8 2-5/16 11-1/2 22-3/4 BLOWER MOTOR AND DRIVE ACCESS PANEL (This side inly) 20 1-5/8 3-7/8 2 FILTER ACCESS PANEL(This side only) HOLE WITH GROM- MET FOR 3/8 O.D. LIQUID LINE HOLE WITH GROM- MET FOR 7/8 O.D. SUCTION LINE 43-1/8 10-3/8 1-3/8 1-3/16 2 AIR IN 1-1/8 32 22 7/8 O.D. DRAIN CONN. (Must be trapped) ACCESSORIES ELECTRIC HEATER - Add 13" to unit height when used. SUPPLY AIR PLENUM - Add 24-1/4" to unit height when used. BASE - Add 20" to unit height when used. MINIMUM CLEARANCES Side with RETURN AIR opening 24" Side with SUPPLY AIR opening 24" 1 Side with PIPING CONNECTIONS 36" 2 Side opposite PIPING CONNECTIONS 12" Side with access for both POWER & CONTROL WIRING - 3 Bottom - 4 2 All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. 1 Overall dimension of the unit will vary if an electric heater, a supply air plenum or a base is used. 2 This dimension is required for removal of the coil. Only 26" is required for normal service. 3 Although no clearance is required for service and operation, some clearance may be required for routing the power and control wiring. 4 Allow enough clearance to trap the condensate drain line. FIG. 12 - UNIT DIMENSIONS & CLEARANCES (KEU060) 10 Unitary Products Group

1-23/32 KNOCKOUT (Removed only when Electric Heat Accessory is used) 15-3/8 18-7/8 AIR OUT 52-1/4 1 1-3/8" KNOCKOUT FOR POWER WIRING (Back Panel) Do not remove this knockout when the unit is equipped with an Electric Heat Accessory. Refer to detail of the Heater Accessory for power wiring access opening 7/8" HOLE W/BUSHING FOR CONTROL WIRING (Back Panel) 3-5/8 4-1/4 6-3/4 5/8 2-1/4 15 16-1/8 25-7/8 BLOWER MOTOR AND DRIVE ACCESS PANEL (This side only) HOLE WITH GROM- MET FOR 1/2 O.D. LIQUID LINE 51-1/8 23 4 1-5/8 HOLE WITH GROM- MET FOR 1-1/8 O.D. 8-3/8 SUCTION LINE 2-5/8 1-3/8 3-1/4 1-3/4 2 ACCESSORIES ELECTRIC HEATER - Add 14-1/4" to unit height when used. SUPPLY AIR PLENUM - Add 27-1/2" to unit height when used. BASE - Add 20" to unit height when used. MINIMUM CLEARANCES Side with RETURN AIR opening 24" Side with SUPPLY AIR opening 24" 1 Side with PIPING CONNECTIONS 52" 2 Side opposite PIPING CONNECTIONS 12" Side with access for both POWER & CONTROL WIRING - 3 Bottom - 4 FIG. 13 - UNIT DIMENSIONS & CLEARANCES (KEU090 & 120) AIR IN 48 1 25-1/8 2 1-1/8 7/8 O.D. DRAIN CONN. (Must be trapped) FILTER ACCESS PANEL (When unit is installed in a horizontal position,do not block this area with refrigerant piping) All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. 1 Overall dimension of the unit will vary if an electric heater, a supply air plenum or a base is used. 2 This dimension is required for removal of the coil. Only 26" is required for normal service. 3 Although no clearance is required for service and operation, some clearance may be required for routing the power and control wiring. 4 Allow enough clearance to trap the condensate drain line. Unitary Products Group 11

TERMINALS ON SUPPLY AIR BLOWER MOTOR CONTACTOR 10M R Y G TERMINALS ON 1ST STAGE COOLING THERMOSTAT 2TH12700424 WITH SUB-BASE 2TB08700124 GROUND SCREW 24-VOLT CONTROL WIRING R B Y O W X 53 G 60 66 1-PHASE LINE VOLTAGE POWER SUPPLY POWER WIRING DISCONNECT SWITCH AND FUSING TO BE SUPPLIED BY FIELD 24-VOLT CONTROL WIRING 1-PHASE KEU060 TERMINALS ON COMPRESSOR CONTACTOR M OF THE CONDENSING UNIT TERMINALS ON SUPPLY AIR BLOWER MOTOR CONTACTOR 10M R Y G TERMINALS ON 1ST STAGE COOLING THERMOSTAT 2TH12700424 WITH SUB-BASE 2TB08700124 24-VOLT CONTROL WIRING GROUND SCREW NOTE: USE COPPER CONDUCTORS ONLY R B Y O W X 53 G 60 66 3-PHASE LINE VOLTAGE POWER SUPPLY POWER WIRING DISCONNECT SWITCH AND FUSING TO BE SUPPLIED BY FIELD 24-VOLT CONTROL WIRING V T C 3-PHASE KEU090, 120 TERMINALS ON COMPRESSOR CONTACTOR 3TB OF THE CONDENSING UNIT The field wiring connected to dummy terminals R and Y on 4TB can be routed directly from the condensing unit to the thermostat if desired. WIRE IN ACCORDANCE WITH LOCAL AND NATIONAL ELECTRICAL CODES FIG. 14 - TYPICAL FIELD WIRING POWER AND CONTROL WIRING Install electrical wiring in accordance with the latest National Electrical Code (NFPA Standard No. 70 and/or local regulations). The unit must be grounded in accordance with these codes. POWER WIRING Remove the knockout from the units rear panel (7/8" for KEU060, 1-3/8" for KEU090, and 120) for power wiring conduit through this opening. Connect the conduit to the required field-supplied fitting and the power wiring to blower motor contactor 10M in unit control box. If the unit includes an electric heat accessory, route the power wires into heater control box in lieu of the unit. Refer to electric heat instruction 550.13-N10.1U for additional installation information. Refer to Figures 12 and 13 for location of power and control wiring openings in rear panel of the unit. Refer to Figure 14 for typical field wiring. Refer to Table 7 to size the disconnect switch, the power wiring and the fuses. NOTE: Three phase motor rotations may be incorrect when unit is first started. Reverse phase (leads L1 and L2) at blower motor contactor to obtain correct rotation. Blower unit Model KEU060 contains a low voltage control transformer (1T), which supplies the 24-volt control voltage for its operation and for the operation of the condensing unit. CAUTION: To prevent possible interconnection between 24- volt circuits, the condensing unit being used with Model KEU060 blower unit must NOT contain its own 24-volt power supply. CONTROL WIRING Route the low voltage control wiring through the 7/8" hole (with bushing) in the units rear panel. Add a 1/2" conduit fitting to the 7/8" hole in the unit control box, route control wiring through this opening and connect them to the terminals on block 4TB. 12 Unitary Products Group

TABLE 7 - ELECTRICAL DATA - Cooling Only Unit Model Motor Blower HP Power Supply Full Load Amps Maximum Fuse Size 1, Amps Maximum Wire Length 2, Feet 060 3/4 208/230-1-60 5.5 10 191 208-3-60 5.7 10 191 090 1-1/2 230-3-60 5.2 10 233 460-3-60 2.6 5 933 208-3-60 7.5 10 145 120 2 230-3-60 6.8 10 178 460-3-60 3.4 5 714 1 Dual element, time delay fuses. 2 Based on three, 60 C, 14 AWG, insulated copper conductors in steel conduit and a 3% voltage drop. TABLE 8 - ELECTRICAL DATA - Units with Electric Heat Model Basic Nominal Heater Power Supply Full Load Amps Total Ampacity, Max. Fuse Min. Wire Max. Wire Unit 1 KW 2 Voltage 3 Heater Blower Motor Amps Size 4, Amps Size 5, AWG Length 6, Ft. 10 208 20.9 5.5 36 40 8 130 230 24.0 5.5 39 40 8 134 060 16 208 33.4 5.5 51 60 6 144 230 38.5 5.5 57 60 4 228 26 208 54.3 5.5 77 80 3 191 230 62.6 5.5 87 90 2 240 208 20.9 5.7 36 40 8 130 10 230 24.0 5.2 39 40 8 134 460 12.0 2.6 20 20 12 208 208 33.4 5.7 51 60 6 144 16 230 38.5 5.2 57 60 4 228 090 460 19.3 2.6 29 30 10 229 208 54.3 5.7 77 80 3 191 26 230 62.6 5.2 87 90 2 240 460 31.3 2.6 44 45 6 373 208 75.1 5.7 104 110 2 180 36 230 86.7 5.2 117 125 1 223 460 43.4 2.6 59 60 4 440 208 20.9 7.5 40 40 8 117 10 230 24.0 6.8 42 45 6 196 460 12.0 3.4 21 25 10 316 208 33.4 7.5 55 60 6 134 16 230 38.5 6.8 60 60 4 217 120 460 19.3 3.4 30 30 10 221 208 54.3 7.5 81 90 2 231 26 230 62.6 6.8 90 90 2 232 460 31.3 3.4 45 45 6 365 208 75.1 10.6 107 110 2 174 36 230 86.7 9.6 120 125 1 217 460 43.4 4.8 660 30 4 433 1 Units with an electric heat accessory will always be wired for a single power supply. 2 Refer to the HEATING CAPACITY table for the actual KW and MBH ratings of each heater at the different voltages. 3 All voltages are for 3-phase, 60 hertz operation. 4 Inverse time circuit breakers may be used in lieu of dual element, time delay fuses. 5 Based on three, insulated copper conductors in steel conduit 60 C wire when the total unit ampacity is below 100 amps. 75 C. wires when the total unit ampacity is above 100 amps. 6 Based on a 3% voltage drop. FILTERS The filters must be cleaned or replaced as often as necessary to assure good airflow and filtering action. Refer to the unit dimension detail (Figure 12 or 13) for the location of the filter access panel. EVAPORATOR COIL Do not allow dirt to accumulate on the evaporator coil or other parts of the evaporator air circuit. Clean as often as necessary to assure good system performance. Use a brush, vacuum cleaner attachment or other suitable means. MAINTENANCE DRAIN PAN The drain pan should be inspected regularly to assure proper drainage. LUBRICATION The bearings for the blower shaft and the blower motor are permanently lubricated and should not require and additional lubrication. BELTS Maintain belt tension to extend belt life. Replace when signs of failure begin to appear. Unitary Products Group 13

14 Unitary Products Group

Unitary Products Group 15

Unitary Products Group 5005 York Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A Copyright by York International Corporation 1999. All Rights Reserved. 550.23-N2Y