Rev B, 9/2/2009. Kodiak Chiller Overview

Similar documents
Part IV: Flow Side Components Flow Diagram

KODIAK RECIRCULATING CHILLERS TECHNICAL MANUAL RC006, RC009, RC011, RC022, RC030 and RC045 G03, H03 and J03 Series

Recirculating Chiller RC350G-RC400G RC1400G-RC3000G. Operating Manual

Trouble Shooting Guide PWA, 3-phase (D10571)

INSTALLATION AND OPERATING INSTRUCTIONS (2 Through 10-ton Air Cooled Single Stage Chillers)

INSTALLATION AND OPERATING INSTRUCTIONS (2 Through 10-ton Air Cooled Single Stage Chillers)

Operation and Maintenance Haskris LX-Series, R-Series, WW-Series, OPC-Series

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Prodigy Eclipse Cuber Technical Training

Owner s Manual Refrigerated Compressed Air Dryers Model F-100

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

Trouble Shooting Guide RAA, 1-phase (D3627)

Trouble Shooting Guide PAA, 1-phase (D3731)

Trouble Shooting Guide FAA, 3-phase (D3631)

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

Using the Model 1500 Portable Chilled Mirror Hygrometer

CHILLER. Operator s & Installation Manual

Installation, Operation and Maintenance Manual

OTC, OTM and OTI Series Options

Owner s Manual Refrigerated Compressed Air Dryers Models F-3528, F-3529, F-3530, F-3531 & F-3532

ISO Water Chiller HSO USER'S MANUAL

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

G-7s. Instruction Manual. G-Series Cooler COUNTERTOP COOLER. Part No.11IPA

Eclipse Technical Training CME686 CME810 CP686 CP886 CP1086

CHILLERS. Operator s & Installation Manual

INSTRUCTION MANUAL and DETAILED PRODUCT SPECIFICATION TRIPLEX PUMP CONTROL SYSTEM MODEL NUMBER CPC-3. M336 Rev F. November 21, 2000.

Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350

SCN60 Residential Nugget Ice Machine

G-10s. Instruction Manual. G-Series Cooler UPRIGHT COOLER. Part No.11IPA

Dear Valued Customer:

MAXIMUM SERIES. Maximum Series portable chillers can be used on a variety of process applications that require 20 F to 70 F chilled water.

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE I.O.M. #017 3/96

CHILLER. Model CH3000. Operator s & Installation Manual

347002K/177002K/34900

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

Bulletin (Jan 2011) And User s Guide

CH250 AND CH251 CHILLERS

EP1 Series Portable Chillers

MST, INC. MODEL 2002 OXYGEN MONITOR (AMBIENT-TYPE) OWNER S MANUAL

M4.9. NO LONGER IN PRODUCTION Some service parts may not be available for this product- Service and Parts Manual M4.9-0

π H-6621 INDUSTRIAL DEHUMIDIFIER WARNINGS SPECIFICATIONS uline.com WATER REMOVAL ELECTRICAL REQUIREMENTS BUILT-IN ELECTRICAL SAFETY

MST, INC. MODEL 2002 CARBON MONOXIDE MONITOR (AMBIENT-TYPE) OWNER S MANUAL

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

CH750, CH751 & CH951 CHILLERS

HX Series Recirculating Chiller. NESLAB Manual P/N Rev. 08/25/97. Installation, Operation, and Maintenance Manual

Aprilaire Dehumidifier Troubleshooting Manual Models 1830, 1850, 1870

OPTISENS TUR 2000 Technical Datasheet

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE. Master Rack Compressor Sequencer 7/21/2017

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

Covering Air-Cooled Models from 1 to 10 tons with M1 Chiller Control Instrument

Recirculating Coolers

AQUAMAC MODELS

Liebert Xtreme Density Chiller (XDC) Unit Warranty Inspection Check Sheet

Setting the New Standard in Chiller Technology ±0.1 C ZEROPOINT CHILLER SERIES

PDF Created with deskpdf PDF Writer - Trial ::

OPERATION MANUAL CMW30. Unit Serial Number Range: 0311XXXXCW3 to Present (From March 2011 to Present)

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F

STEAMPRO. Steam Generator Troubleshooting and Service Guide

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

Instruction Manual. Installation Start-up Operation Maintenance. For Your Haskris LX System. Rev

INSTRUCTION & USER MANUAL

Owner s Manual Refrigerated Compressed Air Dryer Model F-50

CHILLER. Modelli CWS BASIC CWS AQUACONTROL INSTALLATION MANUAL USAGE AND SCHEMATICS

GCG-9. Instruction Manual. G-Series Cooler. Manual is for the following models: GCG-9-N13EB G-9-N13EB GCG-9-B13EB UPRIGHT COOLER

DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions

INSTALLATION & OPERATION MANUAL

Owners Manual Refrigerated Air Dryer MHT SERIES

Installation, Operation and Maintenance Manual. LQ Series. Portable Chillers 7 to 40 Tons

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE

MacDonald Steel Limited

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE

RCM-2. Instruction Manual. G-Series Cooler. Manual is for the following models: RCM-2-N13EB. **Patent Pending** RECHARGE COLD MERCHANDISER

McQuay. Screw Chiller Water Cooled. WHS Vintage A. Last Manufactured: Replacement Parts List No New 07/2012

Installation and User Manual for Model UF424 and UN324

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS

RCM-77. Instruction Manual. G-Series Cooler. Manual is for the following model: RCM-77-N23EB. U.S. Patent No. 8,215,125 RECHARGEABLE COLD MERCHANDISER

Liebert CSU3000 Chiller

YCIV Hz & Hz

Cool IR. Model C104 - Cooling System. Instruction Manual

KitchenAid Food Stream Solutions Classic and Integrated Series

Installation, Operation and Maintenance Manual. LQ Series Portable Chillers

Please record your equipment s model and serial number(s) and the date you received it in the spaces provided.

AUTOTROL 363TC AUTOMATIC FILTER VALVE SERVICE MANUAL

Chiller installation, contractor s scope of work:

1020 Industrial Drive, Orlinda, TN fax

Service Manual for Cuber Model CS0415

Portable Chillers. Water-cooled models PCW-1.5 to PCW-30 and Air-cooled models PCA1.5 to PCA-30. Installation. Operation. Maintenance.

Unit 3 Machine Composition

RCM-2. Instruction Manual. G-Series Cooler. Manual is for the following models: RCM-2-N13EB. **Patent Pending** RECHARGE COLD MERCHANDISER

Service Manual. ETL Blast Chiller Series

GLYCOL CHILLER INSTRUCTIONS IMPORTANT: BEFORE OPERATING PLEASE SEE INSTRUCTIONS ON PAGE 5

OTC, OTM and OTI Series Options Index for PLC Control Systems:

SECTION ROTARY-SCREW WATER CHILLERS

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM

GCG-10. Instruction Manual. G-Series Cooler. Manual is for the following models: GCG-10-N33EB G-10-N33EB UPRIGHT COOLER

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE

Water-Cooled Dual Compressor Screw Chiller

PS SERIES PARALLEL RACK SYSTEM START UP GUIDE

Transcription:

930-0001 Rev B, 9/2/2009 Kodiak Chiller Overview

Presentation Outline Phone: 781-933-7300 Lytron Technical Support Contact Information 3 Introduction 4 Part I: Unpacking 5 Part II: Installation 7 Part III: Chiller Startup 13 Part IV: Flow Components 19 Part V: Refrigeration System 23 Part VI: Electrical System 27 Part VII: Draining and Storage 31 Conclusion 34

Lytron Technical Support Contact Information Lytron is available for technical support 24 hours a day, 7days a week. To contact us, please call 781-933-7300 When calling after hours, please select the System Service Group option to be connected to our on-call Service Engineer Page 3 of 34

Introduction This program is designed to train Kodiak chiller users. Topics covered include: unpacking, installation, the basic control functions and all the internal components of a Lytron Kodiak Chiller. The chiller models discussed in this presentation are the Kodiak RC006G03 through RC045H03 as they are presently manufactured. Always turn the unit "OFF" and disconnect the power cord from the power source before performing any service or maintenance procedures, or before moving the unit. Page 4 of 34

Part I: Unpacking Carefully unpack the chiller and check for shipping damage. If you notice shipping damage, immediately contact your freight carrier. Please note that Lytron is not responsible for any shipping damage. Save the packaging for any future shipping. If the chiller ever needs to be shipped to another location, or in the unlikely event that the chiller needs to be returned to Lytron, we recommend that you use the original packaging. Page 5 of 34

Part I: Unpacking - Chiller nameplate Confirm that the chiller you received is the correct one by checking the model and serial number found on the nameplate, on the rear of the unit. Kodiak nameplate Verify the chiller s power requirements and make sure that it has the proper electrical configuration for your facility s power supply. 930-0001 Rev B Page 6 of 34

Part II: Installation If the chiller arrived lying sideways or on its top, put it back upright and wait for at least one hour before turning it on. This will allow the compressor oil to settle. It is recommended to place the chiller with a 18 clearance on all sides to allow maximum air flow. Systems with a water cooled condenser have no minimum clearance requirements. 930-0001 Rev B Page 7 of 34

Part II: Installation - Chiller Coolant Connections Coolant supply out to your machine Remove the red caps for the return and the supply lines. Install hoses with ½ male NPT fittings. Coolant return coming from your machine Use thread sealant, such as Teflon tape, to eliminate the risk of leaks. Page 8 of 34

Part II: Installation Water Cooled Condenser Water-cooled systems use facility water or a building s chilled water system to cool the condenser. Remove the red caps for the return and the supply lines. Install hoses with ½ male NPT fitting. Page 9 of 34

Part II: Installation Adding Cooling Fluid Use a Philips screwdriver and open the small cover on the top of the chiller. It will expose the reservoir tank cover. Remove the reservoir cap. Phone: 781-933-7300 Fill the tank with water. For set points below 10 C please use a mixture of 30% ethylene or propylene glycol/water. Do not use automotive antifreeze. It contains additives that damage pump seals. Check the tank level using the level indicator and add water if necessary. Level indicator Replace both the reservoir cap and the cover when finished. Page 10 of 34

Part II: Installation Electrical Connections Verify that the chiller has the proper electrical configuration for your facility s power supply. The electrical configuration of the chiller is noted on the nameplate. Plug the chiller into your power source. Turn the circuit breaker on by flipping the switch found on the rear of the unit to the up position. Please note that this switch is not designed to be used as an on/off switch. The proper way of turning the chiller on, is to use the on/off button on the front keypad. Phone: 781-933-7300 Circuit breaker Power inlet You will notice a diagnostics countdown on the front display when you turn the unit on. This will occur every time power is restored to the chiller. Page 11 of 34

Part II: Installation Phone: 781-933-7300 Electrical Connections All chillers with controller packages 2 and 3 are equipped with dry contacts. Pin 5 is the common contact, pin 4 closes on fault and pin 6 opens on fault. These contacts are rated for 250V, 1/2 amp maximum. The RS-232 port option is only available with controller package 3 and is used to connect the chiller to a computer. Dry contacts RS-232 Port With RS232, you can use the Kodiak Host Software (provided by Lytron) that simulates the front control panel and all its functions. Alternatively, you can create your own software to interface with our system. Please consult the Host Interface Data Link section of the Kodiak manual. If you do not have this manual, you can download it from the Lytron website: http:///service/srv_manuals.htm Page 12 of 34

Part III: Chiller Startup On/off button There will be a diagnostics countdown on the front display after the power is turned on. Once the screen clears, press the on/off button and the chiller will start. Occasionally, the chiller may vibrate slightly and be noisy the first time it is started. Wait a few minutes and the noise should stop. If it doesn t, please contact the Lytron service department. Page 13 of 34

Part III: Chiller Startup Kodiak Function Buttons Phone: 781-933-7300 On/off button Mute button Pressure readout button Toggle buttons Set point button Pressing the SET button will allow you to change the temperature set point of the chiller using the toggle buttons. Pressing the pressure button will display the water pressure coming out of the chiller s supply line. Pressing the mute button will stop the alarm noise, when the audible alarm is beeping. 930-0001 Rev B Page 14 of 34

Part III: Chiller Startup Controller Menu Phone: 781-933-7300 You can access the controller menu by holding both toggle buttons down for five seconds. This allows the user to configure the chiller that will allow you to change certain settings. DEGC English or Metric Units: Changes the temperature readings on the display from C to F and pressure. This feature is not available if you have a 0.1 set point chiller. CAL Calibration Offset: Adjusts the reading on the display by the offset that you enter, from -4 C to 4 C (or -7 F to 7 F). This should read zero when you receive your chiller. Ar Auto Restart: When enabled this allows the chiller to start automatically in the event of a power failure or if the chiller is unplugged and plugged back in. If you manually press off on the chiller, the chiller will not startup automatically if Ar is enabled. Page 15 of 34

Part III: Chiller Startup Controller Menu Continued Ot Over Temperature Alarm Set Point (option available with controller package II and III) The indicator illuminates when the coolant temperature exceeds the over temperature set point. The over temperature set point should be at least 3 C (6 F) above the coolant set point to prevent nuisance alarms. Lt Low Temperature Alarm Set Point (option available with controller package II and III) The indicator illuminates when the coolant temperature falls below the low temperature set point. The low-temperature set point should be at least 3 C (6 F) below the coolant set point to prevent nuisance alarms. AL Audible alarm When this is enabled, an audible alarm sounds when any fault occurs. Page 16 of 34

Part III: Chiller Startup Controller Menu Continued FS Fault chiller shutoff (option available with controller package II and III) When enabled, this turns off the chiller when any fault occurs. rs Remote Start (optional feature) Allows the chiller to be started and stopped with a dry contact. bar Changes the pressure display from PSI to Bar. Page 17 of 34

Part III: Chiller Startup Phone: 781-933-7300 Low Flow: Error 4 Continued A low flow error may occur at startup and will be indicated by Err 04 on the display. This happens when the flow switch on the return side of the chiller does not detect enough flow. A low flow error can have a few different causes: Trapped air: When first starting the chiller, some air may be trapped in the system. Restarting the chiller a few times usually flushes the air out. As liquid returns to the reservoir tank, the air escapes out of the vent holes. If the chiller still shuts down on low flow, try loosening the supply hose connection slightly to allow air to exit the system. Flow restriction: If there is excessive pressure drop across the coolant lines (because of small fittings, excessively long lines, kinks in flexible hoses, etc.), the internal pump bypass will open, the net flow out of the pump will decrease, potentially causing a low flow error. Reducing the pressure drop or purchasing an external flow control valve or an external pressure relief valve may solve a low flow error caused by a flow restriction. Page 18 of 34

Part IV: Flow Side Components Flow Diagram Supply Phone: 781-933-7300 The supply is the outlet of the chiller. This is where cooled coolant exits. The return is the inlet of the chiller. This is where the warm liquid enters. Return The D.I. Cartridge is an option it aids in maintaining the high purity of D.I water. The evaporator is a heat exchanger. The coolant flows on one side, and cold refrigerant from the refrigeration system flows on the other side. Since the refrigerant is colder than the coolant, heat flows from the coolant to the refrigerant, and the coolant becomes colder. Please note that it is recommended to use ethylene glycol to prevent freezing when chiller s set point is under 10 C/50 F. The flow switch is designed to prevent low flow through the evaporator or liquid heat exchanger. Very low or no flow can freeze the coolant inside the evaporator and destroy it. The switch is found just after the inlet to the chiller. Page 19 of 34

Part IV: Flow Side Components Flow Diagram Supply Phone: 781-933-7300 The optional liquid filter (which is highly recommended) is attached outside of the chiller and connected to the supply port. It filters particles bigger than 5 microns. The pressure transducer sends the liquid pressure measurement to the control board. The drain allows you to empty your system of all coolant. It is located on the outlet of the evaporator. The reservoir tank helps regulate the system s liquid temperature. More liquid in the tank will result in a better temperature stability. The strainer can either be internal or external to the pump. It protects the pump against particulate. It is only present in systems with positive displacement pumps. Return The pump provides coolant circulation. The RTD sends temperature measurements to the control board. 930-0001 Rev B Page 20 of 34

Part IV: Flow Side Components Bottom Rear View of an RC006 Evaporator (wrapped in insulation foam) Return or inlet to the chiller (the supply outlet is on the upper half of the unit) Flow switch Line coming from the evaporator, splits to the drain and the reservoir tank. 930-0001 Rev B Page 21 of 34

Part IV: Flow Side Components Top View of a RC006 Phone: 781-933-7300 Reservoir RTD Supply or outlet to your application (the inlet is on the upper half of the unit) Pump motor Pump head Pressure transducer 930-0001 Rev B Page 22 of 34

Part V: Refrigeration System Please note that only a certified refrigeration technician should service the refrigeration side of a Kodiak chiller. We highly recommend returning the chillers to Lytron for any refrigeration servicing. Alternatively, you can contact the Lytron service department to coordinate onsite service by a Lytron approved refrigeration service technician. 930-0001 Rev B Page 23 of 34

Part V: Refrigeration System Refrigeration Diagram Phone: 781-933-7300 The evaporator is a crossflow heat exchanger with channels that pass refrigerant and coolant through thin plates. The two flows do not mix, but the close contact allows heat to transfer. Refrigerant enters the evaporator as a gas-liquid mixture, and exits as a low pressure gas. The hot gas bypass valve opens on low pressure, when the solenoid shuts flow off. This allows hot refrigerant gas to flow from the compressor to the evaporator. Bypassing refrigerant when not cooling maintains the compressor on at all times, thus extending its life. The solenoid valve is controlled by the chiller s the control board. It shuts off the refrigerant flow when no cooling is required. Alternatively, it turns the refrigerant flow back on to allow for more cooling to occur. The compressor takes refrigerant coming from the evaporator and converts it to high pressure, high temperature gas. Because of the hot gas bypass, the compressor does not cycle, extending its life significantly. 930-0001 Rev B The condenser is a heat exchanger. Heat from the refrigerant is transferred either to ambient air or to water (for water-cooled condensers). The refrigerant condenses from a gas into liquid. The capillary tube reduces the refrigerant pressure The filter drier cleans and removes moisture from the refrigerant before passing through the capillary tube.

Part V: Refrigeration System Bottom Rear View of a RC045 Condenser fan Compressor Refrigerant pressure control. Found on some 1hp or larger condensing units or all water cooled units. Evaporator (wrapped in insulation foam) 930-0001 Rev. A Capillary tube Hot gas bypass valve Page 25 of 34

Part V: Refrigeration System Bottom Side View of a RC045 Condenser Condenser fan Evaporator (wrapped in isolation foam) Compressor Filter drier Solenoid valve 930-0001 Rev B Page 26 of 34

Part V: Refrigeration System Side View of a Liquid Cooled Unit Facility water in Water cooled condenser Compressor Facility water valve Facility water out Page 27 of 34

Part VI: Electrical System Important Safety Information Please shut the unit off and disconnect it from the power supply before removing any panels and performing electrical work on the chiller. Please refer to the electrical diagram found in the Kodiak chiller manual. Kodiak chillers have one main wire harness that connects the control board to all of its input and outputs. Power comes in through the power inlet, goes through the circuit breaker and then goes to both the controller and the pump/condensing unit relay The control board controls the pump/condensing unit relay and the solenoid valve. Page 28 of 34

Part VI: Electrical System, Rear Panel Circuit breaker Power entry module Customer contacts (optional) RS232 (optional) On the top rear panel of the chiller you will find a circuit breaker, the customer contacts, and RS-232 serial port. It is not recommended to use the circuit breaker as an on/off switch. The name plate to the right provides the voltage, amperage, and any other relevant chiller information. 930-0001 Rev B Page 29 of 34

Part VI: Electrical System, Inside Panel DPST Relay Wires from the control board send out a 12V DC signal to activate the relay. The relay sends the main power to the pump motor and condensing unit. The controller will open the relay if problems occur. Circuit breaker When the circuit breaker is turned on, power is distributed to the control board and to the relay. Power inlet Power enters the chiller through the inlet receptacle. It is wired in series to the circuit breaker. 930-0001 Rev B Page 30 of 34

Part VI: Electrical System, Control Board RTD Temp. probe connector P1 Display/keyboard connector JP2 Main wire harness connector J1 Fuse holder F1 115V to 240V Jumper J3 Power inlet/solenoid connector J2 Page 31 of 34

Part VII: Draining and Storage Draining the Tank Phone: 781-933-7300 Drain your chiller before storage. Stagnant water can produce algae or freeze and damage the interior components. Lytron recommends using a wet/dry shop vacuum to remove all liquids. Shut off the system and unplug the chiller whenever removing panels. Unscrew the cover from the rear and remove it. Remove all of the liquid directly from the reservoir tank using a vacuum. Page 32 of 34

Part VII: Draining and Storage Draining the Reservoir Remove the left side panel to expose a drain hose. Uncap and drain the system of all liquid. Use the vacuum on the supply and return lines to ensure the chiller is completely drained. The chiller is not designed to withstand outdoor weather. Please do not store it outside. Page 33 of 34

Conclusion Please refer to the Kodiak manual for more detailed information on operating, troubleshooting, or any other inquires on Lytron s Kodiak line of recirculating chillers. The manuals are available on Lytron s website at the following link: http:///service/srv_manuals.htm Please contact Lytron s service department for comments or feedback on this training presentation. 930-0001 Rev B Page 34 of 34