DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL

Similar documents
DAVE DEMMA REDUCING ELECTRICAL CONSUMPTION

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation

PAYING THE PIPER TABLE 1 NEOPRENE TYPE W SWELL RATES

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

A Treatise on Liquid Subcooling

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

Head Pressure Control Application Guide

THERMOSTATIC EXPANSION VALVES Part 1

The Saturation process

refrigeration THE GOODS ON OIL FAILURE TRIPS

AE October 1965 Reformatted October Hot Gas Bypass Control Systems

Sporlan Valve Division Parker Hannifan/CIC Group

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

Warm Case Troubleshooting Guide 9/18/2014

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

A Series Inertia Compressor Applications. Application Bulletin 115

USING THE P-T CARD AS A SERVICE TOOL

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

Air-Cooling Evaporators

Application Engineering

Understanding Head Pressure Control. Walter H Langille, M.A.Sc., P.Eng Sales Engineer KeepRite Refrigeration

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1

THERMOSTATIC EXPANSION VALVES Part 2

ThermoSaver TM Hot Gas Defrost System

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Everything You. NEED to KNOW. TXV does this by keeping the coil supplied

Energy Use in Refrigeration Systems

Bulletin , March Electric Hot Gas Bypass Valves

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

HVAC/R Refrigerant Cycle Basics

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

Floating Head Pressure Control System

SERVICE ASSISTANT OVERVIEW FDSI Online Training

System Design, Commissioning, Operation

H29A Series Compressor Applications. Application Bulletin 139

ThermoSaver TM Hot Gas Defrost System

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

System Considerations for Refrigerant Blends with Temperature Glide

Cascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case:

Are uncontrollable humidity problems costing you a bundle?

PowerPoint Presentation by: Associated Technical Authors. Publisher The Goodheart-Willcox Company, Inc. Tinley Park, Illinois

SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS

Pressure Enthalpy Charts

HEAT PUMPS. Carrier Corporation GT72-01 Cat. No

EXPANSION VALVES. See Red Dot Catalog Also. * 2 ton valves - all other valves are 1 1/2 ton (1) Includes M1 Adapter 71R8050 EX02280

CO2 TRANSCRITICAL BOOSTER SYSTEMS

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

Industrial Refrigeration Defrost Solutions TM Package. Brochure R-222

QuickTips. Do you have questions? We have answers.

RDT Refrigeration Book

HVAC Fundamentals & Refrigeration Cycle

Vehicle Level Heating and Air Conditioning Description and Operation A/C System - Manual. A/C System - Manual

SECTION 9 DOMESTIC APPLIANCES UNIT 47 ROOM AIR CONDITIONERS

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES

Condensing Unit Installation and Operating Instructions

Technical Information

HVAC Service Technicians Training Center

5. ASSESSMENT RECOMMENDATIONS

Peachtree City is home office for America located about 30 miles south of the Atlanta airport this is were all KM cubers as well as Flakers are built.

Condensing Unit Installation and Operating Instructions

R.A.S.E.R.S System. Installation Guide

Technical Bulletin (TB-0037)

GRF Series Non-Cycling Refrigeration Dryers ANDARD ELECTRONIC DRAIN STANDARD ELEC SS EXPANSION VALVE F PRESSURE DEWPOINT

Fundamentals of Refrigeration Part 2 Refrigeration 1

A Design for True Performance and Energy Savings In Refrigerated Compressed Air Dryers The Digital Scroll Dryer

Superheat charging curves for technicians

Steam System Best Practices Document No. 11

Chapter-8 Capacity Control of Refrigeration Systems

Installation, Operation, and Maintenance Information

NON-CYCLING REFRIGERATED AIR DRYERS. GSRN Series

Eclipse Technical Training CME686 CME810 CP686 CP886 CP1086

C. Samples for Initial Selection: For units with factory-applied color finishes.

Residential Piping and Long Line Guideline

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

Air Conditioning Clinic. Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

Evaporative Condenser Engineering Manual

Otherwise, you can continue reading the file on the following pages.

REFRIGERATION AND AIR CONDITIONING RÉFRIGÉRATION ET CLIMATISATION POST-SECONDARY NIVEAU POSTSECONDAIRE

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

AMERICAN EQUIPMENT SYSTEMS A Division Of Trevor-Martin Corporation th Terrace North Clearwater, Florida 33762

SECTION (15530) - REFRIGERANT PIPING

User s Information and Installation Instructions

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Chapter 2.3: Steam System

PROJ. NO SECTION REFRIGERANT PIPING

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Transcription:

BY DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL In the September/October 2005 issue of HPAC Magazine, the case was made for reducing head pressure to increase compressor efficiency, thereby lowering its operating expenses. It was also noted that there is a limit as to how low the head pressure can be reduced; not below the point where it causes the available pressure drop ( P) across the thermostatic expansion valve (TEV) port to yield insufficient capacity to meet the load demand of the evaporator. There are several different methods of maintaining head pressure and it is important to understand the principles of how each one operates so they can be set correctly. In addition, on systems that utilize more than one method of head pressure control, setting them to operate together is imperative. The common methods of head pressure control are: 1. Fan cycling. 2. Condenser flooding. 3. Condenser splitting. FAN CYCLING The capacity of the condenser mentioned in the previous article, rated at 150,000 Btuh (at 110F and a 10F TD), is based on all of the fans operating. If this is an eight-fan condenser, we can reduce the condenser capacity as needed by cycling off the fans. Typically, fan motors one and two would be controlled by a pressure control, fan motors three and four by another pressure control, etc. This would allow for four stages of fan cycling. A typical pressure control setup is shown in Table 1. Excluding a cold windy day, where the wind is able to TABLE 1 - TYPICAL FAN CYCLE CONTROL SET POINTS Condenser Set Point blow through the tube bundle on the condenser, the head pressure would never fall below 160 psig with this control strategy. While this is a simple method of control, it does have a few disadvantages. For example: on a cool day, when the head pressure reaches 170 psig, pressure control number two will open the control circuit for the contactors powering fan motors three and four. Once fan motors three and four cycle off, the head pressure will gradually start to rise, as the reduction in air flow has reduced the condenser capacity. The corresponding refrigerant saturation temperature will also rise. In the receiver, where liquid and vapour are present, the refrigerant will always be at a saturated condition (R404A is 78F at 170 psig). For simplicity, assume the pressure in the receiver is equal to the head pressure. In an operating system there would be some pressure loss in the piping and flow controls, resulting in a receiver pressure that would be less than the head pressure. When the switch in pressure control number two closes at 190 psig, the temperature of the refrigerant in the receiver will be 85F (saturation temperature at 190 psig). With the second bank of fan motors operating, the head pressure will fall rapidly, as will the corresponding saturation temperature. Fan # Cut-In Cut-Out 1 & 2 180 psig 160 psig 3 & 4 190 psig 170 psig 5 & 6 200 psig 180 psig 7 & 8 210 psig 190 psig The temperature reduction of saturated refrigerant in the receiver is accomplished by liquid flashing into vapour. As a portion of the liquid flashes, it absorbs enough heat from the remaining liquid to lower its temperature to the new saturation condition. Depending on the refrigerant level in the receiver, and how quickly the pressure falls, the ability to provide vapour free refrigerant to the liquid header may be temporarily compromised. If there is little or no subcooling in the liquid line, flashing may occur all the way to the TEV inlet. This temporary disruption of vapour free refrigerant to the TEV results in erratic operation and poor superheat control. In addition, as the pressure controls cycle the fan motors, and the pressure fluctuates between cutins and cut-outs, the available P across the TEV port will vary. In a perfect world the condition of the refrigerant at the TEV inlet would be constant year around. Allowing the head pressure to fluctuate up and down every few minutes will result in TEV capacities that proportionally fluctuate. CONDENSER FLOODING The ability to maintain constant head pressure (liquid pressure) during varying periods of low ambient operation would be ideal. One method of achieving this is to use condenser flooding valves. In larger systems, two valves are required (see Figure 1). The first, commonly referred to as the condenser holdback valve, is installed at the outlet of the condenser. Its function is to maintain a constant pressure in the condenser. The condenser holdback valve is normally closed, and opens on a rise of inlet pressure. If the condenser holdback valve was set to maintain 180 psig, it would simply remain closed until the condenser pressure increased to that level. While the condenser holdback valve is closed, CONTINUED ON PAGE 44 42 HPAC NOVEMBER/DECEMBER 2005

St. Lawrence Chemical Inc. Exclusive distributor of Genetron rerigerants in Canada Ontario and Western Canada, Tel: 416-243-9615 Fax: 416-243-9731 Quebec and the Maritime Provinces, Tel: 514-457-3628 Fax: 514-457-9773 Circle #30

CONTINUED FROM PAGE 42 the compressor continues to pump refrigerant into the condenser. As heat is removed from the superheated discharge vapour it will start to condense into a liquid, and the liquid refrigerant will start backing up from the inlet of the closed condenser holdback valve, flooding a portion of the condenser. That portion of the condenser that is full of liquid 44 HPAC NOVEMBER/DECEMBER 2005 Circle #31 refrigerant (flooded) no longer serves as a condenser. Flooding a portion of the condenser reduces its effective heat transfer surface, and therefore its capacity. When the appropriate amount of condenser flooding has occurred, the reduced condenser capacity will cause the pressure to increase to 180 psig. At this point, the condenser holdback valve will begin to open and allow refrigerant to flow into the receiver. Pressure regulating valves can control either upstream pressure or downstream pressure, but not both. When the condenser holdback valve throttles, maintaining constant condensing pressure by flooding the condenser, it does so at the expense of its outlet pressure (receiver pressure). The condenser holdback valve may influence receiver pressure, but it cannot maintain it at a constant level. Without an additional regulating valve, the pressure in the receiver will be erratic during periods of low ambient operation due to the condenser holdback valve throttling. A second valve is necessary to maintain constant receiver pressure. It is commonly referred to as the receiver pressurizing valve (see Figure 1). The receiver pressurizing valve is normally open, and closes on a rise in outlet pressure, and is typically set to maintain a pressure approximately 20 psig less than the condenser holdback valve set point. As the condenser holdback valve throttles, maintaining constant condenser pressure and interrupting the flow of refrigerant to the receiver, it is the receiver pressurizing valve, which maintains a constant pressure in the receiver. The benefit of condenser flooding is the ability to provide very consistent liquid pressure in the receiver during periods of low ambient operation. Consistent liquid pressure will result in very stable TEV operation during the winter months. There are two drawbacks to this method of head pressure control: 1. Extra refrigerant is required to accomplish condenser flooding. During extreme low ambient conditions, it may be necessary to flood upwards of 85 per cent of the condenser. Depending on the size of the condenser, this may require several hundred pounds of extra refrigerant. In today s marketplace, this can become quite expensive. 2. Receivers should be sized such that they are at 80 per cent of capacity while containing the entire system charge. If extra charge is needed in the system for condenser flooding, a larger receiver will be required. The extra refrigerant added to flood the condenser during periods of

FIGURE 1 HEAD PRESSURE FLOODING VALVES FIGURE 2 SPLIT CONDENSER VALVE low ambient will be in the receiver during the warmer months. In systems where the additional refrigerant charge has not been considered in the receiver sizing, the technician will have to remove refrigerant every spring to prevent high discharge pressures at design ambient, only to add it back in the fall when it will be required for flooding. CONDENSER SPLITTING Reducing the amount of extra charge needed for condenser flooding can be accomplished by splitting the condenser into two identical circuits: one for summer/winter operation, and the other for summer operation only. The summer condenser will be cycled off as needed during periods of low ambient. This requires the addition of a condenser splitting valve; a three way valve which will be installed in the discharge line (see Figure 2). When the condenser splitting valve is de-energized, the main valve piston is positioned to enable refrigerant flow from the inlet port to flow equally to the two outlet ports, feeding both condenser halves. When required, energizing the solenoid coil will shift the main piston, closing off the flow of refrigerant to the port on the bottom of the valve. This removes the summer half of the condenser from the circuit, and now the minimum head pressure can be maintained by flooding the summer/ winter half of the condenser. To prevent the summer condenser from logging refrigerant during low ambient periods, a check valve is installed at its outlet. This will eliminate the possibility of refrigerant backflow into the idle summer condenser. While a check valve is not necessary at the outlet of the summer/winter condenser for backflow prevention, it is added so that the P though each condenser is equal. This is necessary to insure equal refrigerant flow through the two condensers. During periods of split condenser operation, it is recommended that the refrigerant in the idle condenser be transferred back into the system. This can be accomplished by using a split condenser valve with a bleed hole in its upper piston. The refrigerant will flow through the piston, into the valve s pilot assembly, and back to the suction header. If the correct valve is not used, a dedicated pump out solenoid valve is required, which vents the idle condenser to the suction header through a restriction such as a cap tube. The pump out line must also have a check valve installed to prevent backflow during conditions where the ambient temperature (condenser location) is lower than the saturated suction temperature of the rack. As an alternative to a three-way split condenser valve, two normally open solenoid valves can be used (see Figure 3). In this application there would be a normally open solenoid at the inlet of the summer condenser, which would cycle closed during low ambient conditions. An identical solenoid is installed at the inlet of the summer/winter condenser. It does not require a solenoid coil; this valve is installed to maintain equal pressure drop through the two condensers. As in the three way split condenser valve application, a check valve will be necessary for the outlet of each condenser. With this method, a dedicated normally closed pump out solenoid valve will be required to vent the refrigerant from the idle summer condenser into the suction header. In summary, allowing the head pressure in supermarket refrigeration systems to operate at reduced levels during periods of low ambient has several benefits. Head pressure has a direct affect on available P across the TEV port, which in addition to evaporator and liquid refrigerant temperatures, will determine the TEV capacity. The minimum P required to deliver the necessary TEV capacity to meet the load demand of the evaporator is the limiting factor on how low the head pressure can be allowed to float. Once this is calculated, based on TEV capacity data, the minimum head pressure can be determined and used to CONTINUED ON PAGE 46 NOVEMBER/DECEMBER 2005 HPAC 45

CONTINUED FROM PAGE 45 FIGURE 3 SPLIT CONDENSER WITH TWO NORMALLY OPEN SOLENOID VALVES ability to reduce the condenser capacity by 50 per cent during low ambient conditions. After cycling off the summer condenser, the remaining summer/ winter condenser can utilize the flooding method with a minimum of additional refrigerant to maintain constant head pressure. Dave Demma is senior application engineer supermarket refrigeration with Sporlan Valve Division Parker Hannifin Corporation. He can be reached at tel. 636-239-1111 or by e-mail dgdemma@parker.com. He joins HPAC as a regular columnist in 2006. establish the set points of the head pressure control devices. While several methods of head pressure control are available, one that allows the head pressure (liquid pressure) to remain constant is desirable. This is best accomplished by condenser flooding valves, which maintain consistent head pressure by flooding a portion of the condenser with liquid refrigerant. While condenser flooding valves provide the most consistent head pressure, this method requires adding extra refrigerant to the system. Using a three-way condenser splitting valve (or two normally open solenoid valves) will offer the RATE THE ARTICLE! Will this information be useful? Please circle the appropriate number on the Reader Postcard. Thank you. VERY USEFUL........ 139 USEFUL........... 140 NOT USEFUL........ 141 ANOTHER GREAT PRODUCT FROM It s as easy as 1, 2, 3... 1. Serviceability has been simplified - the time spent out on a service call is reduced, and repairs are easier to manage. 2. The hinged front door allows quick access to the forward facing evaporator. 3. No tools are required to remove the water tray, water pump, or distribution tube. Manitowoc continues to be America s #1 selling ice machine! www.manitowocice.com 800.545.5720 2005 Manitowoc 3201 Circle #32 The new line of Marcell high quality ductless air conditioner mini splits are powered by a world famous compressor and backed by a 5 year warranty on the compressor and 2 years on the other components. All units are ETL approved. Low voltage units (35 volts) and regular voltage units (115-230 volts) are available. Sold Exclusively Through Wholesalers. Circle #33 www.marcellhvac.com 905-944-8738 1-866-MAR-HVAC 46 HPAC NOVEMBER/DECEMBER 2005