Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink

Similar documents
Performance Study of Triple Concentric Pipe Heat Exchanger

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Temperature Control of Heat Exchanger Using Fuzzy Logic Controller

Design and Experimental Studies on Modified Solar Dryer

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Heat transfer and heating rate of food stuffs in commercial shop ovens

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Performance of Shell and Tube Heat Exchanger under Varied Operating Conditions

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Experimental Investigation of a Brazed Chevron Type Plate Heat Exchanger

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

A Study of Heat Transfer Using Corrugated Al 2 o 3 microparticles

Simulation Of Pneumatic Drying: Influence Of Particle Diameter And Solid Loading Ratio

EFFECT OF DIVERSE STREAM PATTERNS ON THE PERFORMANCE OF SOLAR AIR HEATER

"A Case Study of Three Drum Parameter Control in Boiler Using Discrete PID Controller Based on Simulation"

2. HEAT EXCHANGERS MESA

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Heat Transfer in Evacuated Tubular Solar Collectors

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

Design and Development of Water Cooled Condenser for Domestic Refrigerator

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET) AN EXPERIMENTAL STUDY OF HEAT TRANSFER IN A CORRUGATED PLATE HEAT EXCHANGER

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

A STUDY ON COMPACT HEAT EXCHANGERS AND PERFORMANCE ANALYSIS

STUDY OF HEAT TRANSFER IN A CORRUGATED PLATE HEAT EXCHANGER USING AL 2 O 3 MICROPARTICLES

Experimental & Analytical Investigation on Modified Solar Dryer with Recirculation of Air

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Computer Modelling and Simulation of a Smart Water Heater

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Enhancement of COP in Vapour Compression Refrigeration System

Abstract. Introduction. Central Heating Test System

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance

Exercise 2-4. Heat Exchangers (Optional Exercise) EXERCISE OBJECTIVE DISCUSSION OUTLINE. Description of a brazed plate heat exchanger DISCUSSION

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Compression of Fins pipe and simple Heat pipe Using CFD

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

HEAT TRANSFER COEFFICIENT ENHANCEMENT IN NATURAL CONVECTION FROM HORIZONTAL RECTANGULAR FIN ARRAYS WITH PERFORATIONS

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Evaluation of a dynamic model for a cold climate counter flow air to air heat exchanger

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Hot Reservoir Stainless-Methanol Variable Conductance Heat Pipes for Constant Evaporator Temperature in Varying Ambient Conditions

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

Experimental Study And CFD Based Simulation of Closed Loop Pulsating Heat Pipe Using of Refrigerants (R-134a)

Adsorption refrigeration system using waste heat

Model Predictive Control of Pilot Spray Dryer Unit Designed and implemented for an Educational Institute

Numerical Simulation of Fluid Flow and Heat Transfer in a Water Heater

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Performance Analysis Of Double Inclination Ribbed Solar Air Heater Rectangular Duct By Liquid Crystal Thermography

Global Journal of Engineering Science and Research Management

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL

Incorporating Aluminum Honeycomb to Increase Efficiency of U-tube Removable Heat Exchanger

Fuzzy Ventilation Control for Zone Temperature and Relative Humidity

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

A study of Transient Performance of A Cascade Heat Pump System

Performance Evaluation of VCRS with Nested Helical Shaped Condenser by Using R134a as Refrigerant

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Experiment 12 Shell and Tube Heat Exchanger. Aim of this Experiment

INDOOR HUMAN THERMAL COMFORT OPTIMAL CONTROL WITH DESICCANT WHEEL COOLING SYSTEM

Simulation of Full-scale Smoke Control in Atrium

Analysis to speed up of the start-up of steam boiler OP-380

[Gupta* et al., 5(7): July, 2016] ISSN: IC Value: 3.00 Impact Factor: 4.116

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

DESIGN AND ANALYSIS OF PIPE HEAT EXANGERS WITH INSIDE FINS

STEAM BOILER DRUM TRANSIENT RESPONSE AND DISTURBANCE REJECTION

Fuzzy Controller for Adjust the Indoor Temperature and Preservation the Buildings

Experimental analysis of condensation heat transfer enhancement of steam at low pressures using modified twisted tape insert

Smart Defrost Control for Refrigeration System

THE GATE COACH All Rights Reserved 28, Jia Sarai N.Delhi-16, ,-9998

Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

Consolidation Stress Effect On Strength Of Lime Stabilized Soil

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Solar Drying Techniques And Performance Analysis: A Review

Effect of Impeller Clearance and Multiple Impeller Combinations on Solid Suspension in a Standard Flat Bottom Agitated Vessel

Performance of Geosynthetics in the Filtration of High Water Content Waste Material

1.1. SCOPE OF THE WORK:

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

Experimental Studies on Aero Profile Thermosyphon Solar Water Heating System

Shortcut Model for Predicting Refrigeration Cycle Performance

A Novel VLSI Based Pipelined Radix-4 Single-Path Delay Commutator (R4SDC) FFT

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics

Transcription:

Dynamic Simulation of Double Pipe Heat Exchanger using MATLAB simulink 1 Asoka R.G, 2 Aishwarya N, 3 Rajasekar S and 4 Meyyappan N 1234 Department of Chemical Engineering Sri Venkateswara College of Engineering, Tamil Nadu, India. 602117. Abstract This paper deals with the control dynamics of double-pipe heat exchanger using simulation tool. The transfer function can be taken as first order system plus dead time (FOPDT). The effect of step change in flow rate of hot water is analysed also observed its effect on the temperature of cold water and it was found that the temperature of cold water is increased with respect to the inlet step change. For any system the temperature needs to be accurately regulated to control the downstream processing s. Steady state and dynamic simulation of a double-pipe heat exchanger, in counter flow arrangement has been studied and the simulation results for step change in hot water flow rate have been discussed. Keywords FOPDT, step change, steady state I. INTRODUCTION The heat exchanger is a device used to transfer heat from one liquid to another either by direct contact or by an indirect contact. A plate or a tube type of a thermally conducting element is being used to separate the two fluids which allow transfer of heat from one fluid to another without mixing. [1] The behaviour of the heat exchanger should be predicted for transient operating condition and steady-state operating condition to reduce future possible failures and loss in maintenance costs. [2] A minimum cost heat exchanger network synthesis is a difficult process and much needed design problem. Here two things are mainly concerned, one is the flexibility and the other is the controllability. Feasible operation at different operation modes refer their flexibility and stability at a given operation mode and also transition from one operation mode to another in a safer manner refer their controllability. [3] A simple double pipe heat exchanger consists of concentric pipes. It is commonly used in applications involving relatively low flow rates and high temperature or pressure, for which they are well suited. [4] The amount of heat transfer per section is small, that makes the double pipe heat exchangers a suitable heat transfer device in applications where a large heat transfer surface is not required. [5] A transfer type of a heat exchanger is the one in which both fluids pass simultaneously through the device and heat is transferred through separating walls. A model was formulated for a counter flow heat exchanger, which has been taken into account for the variation of the heat transfer coefficient with respect to fluid flow rates and temperature. To know the stability of the heat exchanger the experiment was carried out and a transfer function was derived for the hot and cold water flow in the heat exchanger, simulations were done using a Proportional Integral Derivative (PID) controller and the results are shown. The experimental investigation was done for various step changes. II. PID CONTROLLER If there is no control to the process, the process with an overshoot and considerable delay time gives an inverse response. But in case of PID control being implemented, the problems of overshoot, delay time and inverse response are removed considerably and are controlled in the ongoing process. And also a fuzzy logic controller can be used to reduce the rise time and settling time. [6] In case of Proportional Integral (PI)/PID based control, there are two control schemes present. They are multiloop control and decoupling control. In multiloop control, a controller is designed and implemented on each loop as the Multi Input Multi Output (MIMO) processes are treated as a collection of multi-single loops, and by taking loop interactions into account. The reasonable performances, robustness and structure simplicity, lead the multiloop control to be well accepted by the process control industry and this made efforts to improve the performance of multiloop PI/PID controllers. However the decentralized controller design method for PID controllers fails to show acceptable responses when there exists severe loop interactions. In the decoupling control, it requires two steps; they are design of the decoupler and design of the main loop controllers. Synthesis of a controller for a nonlinear MIMO process, that ensures optimal control (decoupling) and process variables constraints fulfilling is offered within Model Predictive Control (MPC) framework. [7] Any type of abstract description that captures useful relevant features of a process can be said as a model.[8] Modelling can mean many different things, from the extraction of some simple features of a transient response to the development of a traditional control model in terms of a transfer function or an impulse response. Thus a model for the double pipe E-ISSN: 2394-5370 www.internationaljournalssrg.org Page 6

heat exchanger was derived and it was simulated in MATLAB using a PID controller circuit which was tuned under Cohen-Coon tuning rules. III. EXPERIMENTAL SETUP This setup consists of two thin wall tubes mounted concentrically on a panel. The water flow through the annular tube can be reversed for either counter current or parallel flow. The hot water flows through the centre tube and cold water flows through the annular region. parallel flow conditions respectively. The counter flow conditions are achieved by shutting the valves 1 and 3 and opening the valves 2 and 4, while the parallel flow conditions are obtained by shutting the valves 2 and 4 and opening the valves 1 and 3.Thus direction of flow and flow rates can be determined by opening or closing the appropriate valves. (All globe valves are totally opened or totally closed.) The metering valves at the outlets are used to control flow rates. The system must be allowed to reach steady state condition before taking the measurements. Five readings are taken for hot and cold flow configuration. The two heat exchanger groups must work together once the flow has been initiated because the adjustment of flow in one group will affect the other team s flows. The overall heat transfer rate in the heat exchanger can be calculated by assuming that the heat losses from the outer tube stream as negligible. Therefore the overall rate of heat transfer is equal to either the heat released from the hot stream or the heat absorbed by the cold stream, namely [9]: Fig. 1: Counter Current Double Pipe Heat Exchanger Construction: 1) Valves are used to set up desired flow conditions (rate and direction). The cold water valve was set in the correct position to achieve either countercurrent or parallel flow. 2) The thermometers are placed near the entrance, midpoint and exit of each pipe. The thermometers will give coarse readings. 3) The flow rate of the fluid is set at scale of liter/min. It is adjustable for the purpose of zeroing the reference mark on the tube. The flow rate is read for both the cold and hot water flow by turning the appropriate valves. Water is heated by two heaters. An insulated pipe is used to pump the hot water from the tank into the inner tube. Water returns to the tank through valve 5. The cold water is supplied through the mains and drains through valves 2 and 3 in the counter flow and Where, Q Heat content (W) m Mass flow rate (kg/s) Cp Heat capacity of water, kjkg -1.K -1 T Temperature difference, K IV. RESULTS AND DISCUSSION The system can be represented by first order system plus dead time (FOPDT): Where, G(s) Transfer function Ʈ D Transport delay, (s) k Process gain, (k.s.kg-1) Ʈ Time constant, (s) The following table shows the heat exchange between the hot and cold fluid at varying hot water flow rate. E-ISSN: 2394-5370 www.internationaljournalssrg.org Page 7

TABLE 1: CHANGE IN TEMPERATURE OF HOT AND COLD WATER AT VARYING HOT WATER FLOW RATE HOT WATER COLD WATER FLOW RATE T in ( ₒ c) T out ( ₒ c) FLOW RATE T in ( ₒ c) T out ( ₒ c) (l/min) (l/min) 1.5 71 60 1.5 33 45 2 70 65 1.5 33 49 2.5 73 68 1.5 33 53 3 75 69 1.5 33 54 3.5 74 69 1.5 33 54 Fig. 2: Temperature response for step change in hot water flow rate The following table shows the heat exchange between the hot and cold fluid at varying cold water flow rate. TABLE 2: CHANGE IN TEMPERATURE OF HOT AND COLD WATER AT VARYING COLD WATER FLOW RATE HOT WATER COLD WATER FLOW RATE T in ( ₒ c) T out ( ₒ c) FLOW RATE T in ( ₒ c) T out ( ₒ c) (l/min) (l/min) 3 75 60 3.5 33 43 3 75 64 3 33 46 3 75 68 2.5 33 50 3 75 69 2 33 53 3 75 69 1.5 33 54 E-ISSN: 2394-5370 www.internationaljournalssrg.org Page 8

Fig. 3: Temperature response for step change in cold water flow rate A closed loop system was developed for double pipe heat exchanger and a servo problem was considered using MATLAB Simulink via 0.5 step change in set point of controlled variable which is the outlet temperature of cold and hot water stream. The initial tuning constants Kc, Ʈ I, Ʈ D for PID controller were found using empirical model (Cohen-Coon method). TABLE 3: DERIVED VALUES OF PROCESS PARAMETERS OF THE DOUBLE PIPE HEAT EXCHANGER Varying hot water flow rate Varying cold water flow rate Transfer function Time delay 0.175 0.1 Kc 2.5469 4.9475 Ʈ I 0.4279 0.2451 Ʈ D 0.0634 0.03629 Where, Kc Ʈ I Ʈ D Controller gain Integral time of controller Derivative time of controller The response of outlet cold and hot water temperatures using step change in hot water and cold water flow rates is shown in fig. 3 and 4. A process reaction curve was used to find the process parameters. E-ISSN: 2394-5370 www.internationaljournalssrg.org Page 9

Fig 5: Block diagram of closed-loop system for hot water using PID controller Fig 6: Response of closed loop for hot water using PID controller E-ISSN: 2394-5370 www.internationaljournalssrg.org Page 10

Fig 7: Block diagram of closed-loop system for cold water using PID controller Fig 8: Response of closed loop for cold water using PID controller PID controller removed the offset but the settling time response is large for the step change in hot fluid flow rate than the cold fluid flow rate. So, one can see the time required for the response curve to reach steady state contains no offset. A stability of closed loop response using bode diagram was also studied and it indicates that the system is stable as gain and phase margin are positive. E-ISSN: 2394-5370 www.internationaljournalssrg.org Page 11

Fig 9: Bode diagram for open loop system for varying hot water flow rate Fig 9: Bode diagram for open loop system for varying cold water flow rate V. CONCLUSION Steady-state and transient response of double pipe heat exchanger using PID controller in Simulink model using MATLAB has been studied for various step change in cold and hot fluid flow rates. The simulation results shows that change in cold fluid flow rate will reach steady state faster than the change in hot fluid flow rate. Heat exchange between the hot and cold fluid explained with simulation results. Model which is developed for double pipe heat exchanger is validated with bode stability plot. The stability of the process was analyzed with bode plot results. The results show that the system is stable for given step change in hot and cold fluid flow rates as gain margin and phase margin are positive. Hence the model which is developed for double pipe heat exchanger may be considered for further studies. E-ISSN: 2394-5370 www.internationaljournalssrg.org Page 12

References [1] Agniprobho Mazumder, Dr. Bijan Kumar Mandal, Numerical Modeling and Simulation of a Double Tube Heat Exchanger Adopting a Black Box Approach Int. Journal of Engineering Research and Applications, ISSN: 2248-9622, Vol. 6, Issue 4, (Part - 2), pp.35-41, April 2016. [2] Stefano Bracco, Ilka Faccioli, and Michele Troilo, A Numerical Discretization Method for the Dynamic Simulation of a Double-Pipe Heat Exchanger, International Journal Of Energy, Issue 3, Vol. 1, 47-58, 2007. [3] S. Papastratos, A. Isambert, D. Depeyre, Computerized Optimum Design And Dynamic Simulation Of Heat Exchanger Networks, European Symposium on Computer Aided Process Engineering-2, S329-S334. [4] Robert w.serth, Process heat transfer principles and applications, Elsevier science and technology book, 2007 [5] Abdelmessih, A. N., and Bell, K. J., Effect of Mixed Convection and UB ends on the Design of Double Pipe Heat Exchangers, Heat Transfer Engineering, vol. 20, no. 3, 1999. [6] Shaocheng Tong and Han-Xiong Li, Fuzzy Adaptive Sliding-Mode Control for MIMO Nonlinear Systems, IEEE Transactions On Fuzzy Systems, Vol. 11, No. 3, June 2003. [7] D. Mayne, J. Rawlings, C. Rao, and P. Scokaert, Constrained model predictive control: Stability and optimality, Automatica, vol. 36, no. 6, 789 814, June 2000. [8] K.J. Astrom, T. Hagglund, C.C. Hang and W.K. Ho., Automatic Tuning and Adaptation for PID Controllers - A Survey, Control Eng. Practice, Vol. 1, No. 4, pp. 699-714, 1993. [9] M. A. Mehrabian, M. Hemmat, "The overall heat transfer characteristics of a double pipe heat exchanger: comparison of experimental data with predictions of standard correlations, Transactions on Modelling and Simulation, vol. 30, 2001. E-ISSN: 2394-5370 www.internationaljournalssrg.org Page 13