# amp # amp 12/24 VDC POWER SUPPLY INSTALLATION MANUAL. 4202/4MA, Rev. E 0804

Similar documents
Model 4001 Series Single Channel Controller

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

SP-1000X. Panic Device Power Controller Installation Guide. Rev

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

Installation Guide for models:

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

Installation Guide for models:

Model 17A00 Expansion Enclosure

Series. Access Power Controllers. Installation Guide

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Commercial and Light Industrial Fire Alarm Control Panel

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Rack Mount Series Installation Guide

MODEL B2 INSTALLATION MANUAL

631RF Amp Power Supply

AL800ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide

Access Power Controllers with Power Supplies

ESSEX ENGINEERING CORPORATION

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

AL600ULX Series. Power Supply/Charger. Installation Guide

Public Safety DAS Annunciator Panel

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

July 14, 1999 DF C-100.

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA OBSOLETE

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

Installation, Operating and Maintenance Manual

PDD-8PCI. Power Distribution Board With Supervised Interface. Installation and Specifications Manual

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Addendum for STI-6406 with Dual Access Control

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

CALL YOUR SALES CONSULTANT TODAY,

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

10-175UL INSTALLATION. Power Supply UL. Access Control Power Supply/Charger. Installation and Specifications Manual

ACM8 & ACM8CB. Access Power Controllers Installation Guide. - Fused Outputs - Fused Outputs. - PTC Outputs - PTC Outputs. Models Include: Rev.

Specification/ Data Sheet

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input

Booster Power Supply Manual

Operation and Maintenance Manual

PDD-FT-3. Fire Panel Interface With EOL Trigger. Installation and Specifications Manual

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

FLOAT BATTERY CHARGERS

Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input

June 10, 2002 DF C S2424

Power Transfer Devices. Access Control Accessories. How To Order. How to Order

ECC-50/100(E) Emergency Command Center

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

ECC-50/100C. Emergency Command Center

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

ACM4 Series UL Listed Sub-Assembly Access Power Controllers

Application, Installation, Operation & Maintenance Manual

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

CAUTION & SYMBOL DEFINITIONS:

Fire Control/Communicator

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

KT-100 Door Controller

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

120 VOLT POTENTIAL PRESENT. MAKE SURE POWER INPUT TO UNIT IS TURNED OFF DURING INSTALLATION AND WIRING PROCEDURE.

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

OPERATION AND INSTALLATION MANUAL

ISIMET Series Shop Controller

CM-RQE70 PIR REQUEST TO EXIT DETECTOR

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

Sierra Series 900 Single & Dual Channel System. Instruction Manual

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

NU2 Smart Power Supply (SPS) Manual

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

Transcription:

#4202 2 amp #4204 4 amp 12/24 VDC POWER SUPPLY INSTALLATION MANUAL 4202/4MA, Rev. E 0804

4202/4204 Power Supply Fused 115 V Input Low Battery Indicator DC Output Adjustable 0.7 to 3.7 Volts from nominal of 12 or 24 VDC Field Selectable 12 or 24 VDC Output Maximum Cooling Extra Large Heat Sink Optional Manual Fire Alarm Reset (Connect Remote Push Button to J2) Switched DC Output On/Off Switch (Does not control Continuous DC output) Low Battery Alarm (Optional) Loss of Alarm (Optional) Low Voltage (28 V Input) LOW BATTERY 12 POWER LOSS 24 A B On Off FIRE ALARM RELAY BAT SFAR FAR SWITCHED DC CONTINUOUS DC Slave Fire Alarm Output (Multiple Power Supplies) Switched DC Output 12 or 24v (Power off during fire alarm) Continuous DC Output 12 or 24v (No power loss during fire alarm) Ground Fault Protected Fire Alarm Input Signal Fused DC Output (2 or 4 amp) Indicator Compact 3" x 71/8" Size (SnapTrack Mounting) RF Access Control Compatible (100KHz with EMI Filtering) DC Output Ripple less than 0.002 volts DC Output Regulated to within 0.2% Proudly Made in the USA Automatic Battery Charging DC Output Indicator LED's SPECIFICATIONS: Physical Size Board Only 3 wide x 71/8 long x 23/8 high (including heat sink). Mounting Standard 3 SnapTrack or attachment with standoffs. Enclosure 12 1/8 wide x 16 high x 4 deep with hinged cover. Electrical Input 115 V/60 Hz, 480mA (4202), 1.06A (4204) @ max. load Fused @ 115 V terminal block to transformer. #4202 2 amp Output @ 12 or 24 VDC (28 volt 2.8 amp transformer) #4204 4 amp Output @ 12 or 24 VDC (28 volt 4.6 amp transformer) DC Voltage Range Field adjustable from.7 volts below to 3.7 volts above jumper selected DC output. Example: with the jumper selected for 12VDC, the output voltage range can be adjusted from 11.3 to 15.7 VDC (27 VDC adjusted maximum @ 24 volt selection). DC Regulation Accurately regulated to within 0.2% of voltage setting. DC Filter Ripple almost nil, measuring only.002 @ 24 volts DC (Main DC output). 2

4202/4204 Power Supply FEATURES: Standard Features 12 or 24 VDC Output Field selectable by the onboard jumper. (Universal 28 V stepdown transformer). Power Switch Slide switch provides On/Off control of switched DC output. (This switch controls the FAR relay coil to cutoff power at the switched DC output.) DC Output Two DC outputs provide a total power output of 2 amps for the #4202 or 4 amps for the #4204 at either 12 or 24 volts DC as selected by the onboard jumper. One DC output supplies continuous DC power while the other DC output is controlled through the fire alarm and may be switched off by the fire alarm input or the onboard On/Off switch. Heat Sink Extra large heat sink provides sufficient cooling to guarantee long life and maximum operation under full load. LED Status Indicators Onboard LEDs provide a visual indication of power supply operating conditions. An illuminated amber LED indicates proper Battery/DC voltage condition, a green LED is lit to indicate the presence of power and two red LEDs are provided to indicate DC power at each DC output. This allows quick determination of the power supply status including the fire alarm input condition. FailSafe Fire Alarm Relay The innovative design of this power supply assures the release of the onboard fire alarm relay in an emergency by automatically detecting ground faults in wiring to the fire alarm panel. This is accomplished by providing a positive 12volt output from the FAR (out) terminal to be wired to the dry contact at the fire alarm panel. After connecting the field wiring through the fire alarm contact (open under alarm conditions) this positive lead is brought back to the FAR (in) terminal where it is wired internally to the FAR relay coil (). If any insulation is scraped on the field wiring to the fire alarm panel and the wire is grounded, it will cause a shorted condition and shut down the Switched DC output only. Slave FAR Output This form C dry contact output, from the fire alarm relay, can be used to connect multiple power supplies using only a single contact on the fire alarm panel. Each power supply, daisy chained off of this output, is electrically isolated from any others. This output can also be used as an alarm input for other monitoring devices. 3

Standard Features continued Battery Charging Adjustable trickle charge factory set @ 300 ma for 12 volt battery back up. A low battery, automatic cutoff is builtin to prevent total battery discharge. The battery circuit is thermally protected against shorts. When under battery backup operation, battery power is routed through the main DC fused output. Proximity RF Compatible Operating at 100kHz, these power supplies are harmonically compatible with your favorite RF reader devices. Extensive filtering eliminates ripple and EMI to provide only clean, noninterfering DC power to the devices. Security Cabinet Lock A key lock is installed to prevent unauthorized access into the power supply. Cabinet Tamper Switch The tamper switch, with a SPDT dry contact output, is provided to detect unauthorized access into the power supply cabinet. The power supply can remain secure and be fully monitored when the optional remote LED status display, and alarm outputs for loss of and low battery, are incorporated with the standard cabinet lock and tamper switch. Optional Features Power Line Cord (Order with xpc suffix) A 3conductor 6 0 power cord is available when required. This allows the power supply to be connected to a standard 115 V duplex outlet by 3prong grounded plug. Rechargeable Batteries (Order with xbat suffix) Includes two (2) 7AH 12 volt rechargeable batteries and universal hookup cables (for 12 or 24volt back up) to connect batteries to power supply. Two batteries, each measuring 6" x 21/2" x 4" tall, will fit in the lower portion of the standard 12 1/8 x 16 x 4 enclosure. Multiple Enclosures NEMA enclosures are available in several sizes to accommodate additional modules within the power supply enclosure: 12 1/8 x 16 x 4 (Standard) 15 x 18 x 4 (Order with 1824 suffix) Not evaluated by UL 24 x 24 x 6 (Order with /2424 suffix) Not evaluated by UL Additional sizes can be ordered. (Call the factory for more information.) Remote LED Indicators (Order with xrem suffix) Not evaluated by UL. An optional LED display can be mounted on the enclosure door to provide visual indication of low battery, and DC output failure. This allows quick determination of power supply status without unlocking and opening the cabinet. Alarm Relay Outputs (Order with xao suffix) Form C dry contact outputs are available as an option to monitor and report abnormal power supply conditions to an independent alarm system. One set of SPDT relay outputs is triggered upon loss of 115 power input and a second SPDT output upon a low battery condition when operating offline. 4

Optional Features continued Terminal Strips (Order with xterm suffix) Not evaluated by UL. This option provides one 10position, double row, barrier strip with screw terminals (61/2 long overall). Typically used to allow convenient connection of field wiring or integration of other modules for custom applications. Fused Power Distribution (Order with xfo suffix) Not evaluated by UL. This module provides eight individually fused outputs to prevent one shorted circuit from cutting off power to the other powered devices. The 12 or 24 volt ( or DC) main power input is fused to 2 or 4 amps(dependent on power supply), and each of the eight outputs is individually fused to 1.6 amps. each. Onboard LEDs provide visual indication of main power input and for each of the outputs. (Note this option may require a larger nonstandard power supply enclosure if ordered with battery backup or relay modules.) Power Distribution with Auxiliary Relay (Order with xfo/aux suffix) This module provides eight individually fused outputs with LEDs as described above plus an auxiliary control relay. This relay can be used as the fire alarm interface relay to deactivate devices connected to the outputs. This is normally used when some devices should remain powered but others should be cutoff during a fire alarm condition. The relay operating voltage is matched to the desired input voltage when the power supply is initially ordered, i.e. 24v relay used with 24VDC input. See manual for Fused Output module for additional information. (Note this option may require a larger nonstandard power supply enclosure if ordered with battery backup or relay modules.) Isolation Relay Module (Order with xro suffix) Not Evaluated by UL. A 4relay module is available as an option to provide powerisolated control to powered devices. Each of the DPDT relays is equipped with one fused common and one nonfused common. See manual for Relay Output module for additional information. (Note this option may require a larger nonstandard power supply enclosure if ordered with battery backup or fused output modules.) 24/7 Programmable Timer (Order with x24/7dt suffix) Not Evaluated by UL. A programmable seven day, twentyfour hour timer is available to control powered devices. This timer is field programmable with one / dry contact output to provide up to fifty Events. 5

4202/4204 Power Supply ELOSURES: Standard 12 1/8 x 16 x 4 Layout 28 V Transformer 2.8 or 4.6 amp. Grounding Stud #4202 or #4204 Power Supply 16" High Maintain at least 1/4" spacing between power limited wiring (VDC outputs) and nonpower limited wiring (V and battery lines). TO BATTERIES Optional 12 Volt 7 amp hour Battery Optional 12 Volt 7 amp hour Battery 12 1/8" Wide 6

Optional 15 x 18 x 4 Layout (Custom) Not Evaluated By UL 28 V Transformer 2.8 or 4.6 amp. #4202 or #4204 Power Supply Shown with Optional xro (4Relay Modules) & xfo (8Fused Output Modules) 18" High 15" Wide 7

4202/4204 Power Supply INSTALLATION: The unit must be installed within the protected premise in accordance with the National Electric Code (ANSI/NFPA 70), local codes, and the authorities having jurisdiction. Mounting Instructions Locate equipment in a dry environment. Room temperatures should range between 32 and 120 degrees Fahrenheit. Anchor enclosure securely to a vertical surface. Protect electronics from metal shavings, and other debris of the mounting process. 115 V Wiring Instructions Connect the incoming ground wire to the enclosure. Remove the fuse holder in the 115 V terminal block before connection of any power wiring. This deactivates all and DC power. Wire 115 V to separate fused terminal block marked for this connection. If the optional (xpc) power cord is used, the cord must be plugged into a grounded UL listed receptacle. The receptacle must not be controlled by a switch. Low Voltage Transformer Each power supply is shipped with a 115 to 28 V transformer installed and wired to the power supply circuit board. The high side (115 V input) is protected through the fuse located in the 115 hookup terminal block. The secondary (28 V) output of the transformer is factory wired to the input terminal. Do not substitute transformer with one of lower voltage or lower current output. The design of this power supply requires a minimum of 28 V at the current specified to perform at the rated DC output (2 amp @ 12/24 VDC or 4 amp @ 12/24 VDC). The DC output is fused at 2 amps for the #4202 and 4 amps for the #4204 power supply. DO T USE FUSES OF A GREATER AMPERAGE RATING. 8

Adjust 12 or 24 VDC Output SWITCHED DC Output On/Off Switch Alarm Output Low Battery Alarm Output Power Loss #4202 or #4204 Power Supply To 2nd Power Supply To Fire Alarm Contact 12 or 24 VDC Switched Output 12 or 24 VDC Continuous Output Select 12 or 24 VDC Output To BackUp Batteries DC Output Wiring Instructions Remove the fuse for the 115 V input (see above) to deactivate all power in the power supply. Remove the fuse for the DC output adjacent to the DC output terminal strips to deactivate all DC power from the batteries and the supply. (The slide switch next to the FAR interface will only cut off power from the DC switched output terminals. When Off this FAR interface also opens the dry contact output marked SFAR. With the 115 V power deactivated, select desired DC output voltage (12 or 24) by the plugon jumper located on the input end of the power supply board. Connect (with and DC power deactivated) battery backup cables according to selected main voltage output (12 or 24) per diagram. Use the potentiometer next to the 12/24 selection jumper to increase DC charging voltage to 13.5 or 27.0 volts maximum. Maintain at least ¼ spacing between power limited wiring (VDC outputs) and nonpower limited wiring (V and battery lines). Connect fire alarm input (dry contact closed in nonalarm condition). If a fire alarm signal is to unlock doors in an emergency (wire all controlled devices to the switched DC output terminals), remove the factoryinstalled jumper on the FAR terminals. Connect to the fire alarm panel dry contact using these terminals to provide a () 12 VDC output to the fire alarm panel relay contact and back to the FAR interface relay coil. A short to ground in this field wiring will result in the cutoff of 12 VDC power to this circuit. 9

If a manual reset is required after a power cutoff by the fire alarm, remove the reset jumper adjacent to the slide switch. Connect the momentary normally open FAR reset switch (provided as an option) to the 3pin reset header. After fire alarm restore or poweron by slide switch, the reset switch contact must provide a momentary closure between pins A B, to restore the FAR interface to operating status and provide power on the main DC output. If additional power supplies are to be operated off of the same fire alarm panel, connect the SFAR (Slave Fire Alarm Release) dry contact output to the FAR terminals of the second power supply. Additional supplies may be connected similarly. If this power supply is to remain powered continuously (not connected to a fire alarm panel), leave the FAR jumper in place (or utilize the continuous DC output terminals to connect the powered devices). 10

BATTERY HOOKUP Maintain at least 1/4" spacing between power limited wiring (VDC ouputs) and nonpower limited wiring (V and battery lines). On Off LOW BATTERY 12 POWER LOSS 24 FIRE ALARM RELAY BAT SFAR FAR SWITCHED CONTINUOUS () () () () 7 AH 12 Volt Lead Acid Battery 7 AH 12 Volt Lead Acid Battery TYPICAL HOOKUP FOR 24 VOLT BATTERY BKUP (Select proper DC voltage output by onboard jumper) From BAT Output () () () () () () 7 AH 12 Volt Lead Acid Battery 7 AH 12 Volt Lead Acid Battery TYPICAL HOOKUP FOR 12 VOLT BATTERY BKUP (Select proper DC voltage output by onboard jumper) 11

4202/4204 Power Supply FIRE ALARM INTERFE On Off LOW BATTERY 12 POWER LOSS 24 FIRE ALARM RELAY SFAR FAR BAT SWITCHED CONTINUOUS 12 or 24 VDC To Batteries To Normally Closed Contact (Nonalarm State) TYPICAL HOOKUP FOR FIRE ALARM INTERFE On Off LOW BATTERY 12 POWER LOSS 24 FIRE ALARM RELAY SFAR FAR BAT SWITCHED CONTINUOUS 12 or 24 VDC To Batteries TYPICAL HOOKUP FOR SLAVE FIRE ALARM INTERFE 12

4202/4204 Power Supply ALARM OUTPUTS On Off LOW BATTERY 12 POWER LOSS 24 FIRE ALARM RELAY SFAR FAR BAT SWITCHED CONTINUOUS Dry Contacts (Open on Loss of ) Dry Contacts (Open on Low Battery) HOOKUP FOR OPTIONAL ALARM RELAY OUTPUTS 13

4202/4204 Power Supply TROUBLE SHOOTING No DC Power @ Continuous DC Output Red LED off Check Main DC Output fuse @ F1 Check Input @ Transformer secondary Green LED should be on Check 115 V Input fuse @ 115 V Terminal Block Check Backup Battery Connections (for reversed or shorted wiring) No DC Power @ Switched DC Output Red LED off Check DC Output On/Off Switch @ SW1 Check Main DC Output fuse @ F1 Push FAR Reset Switch (if installed) Check Input @ Transformer secondary Green LED should be on Check 115 V Input fuse @ 115 V Terminal Strip Check Backup Battery Connections (for reversed or shorted wiring) Check that jumper is present on FAR input if not connected to fire alarm system Wrong DC Voltage @ T5 DC Output Check Voltage Selection @ Jumper J1 Adjust Main DC Output Voltage @ R2 Measure Input Voltage @ Transformer secondary terminal T1 (Should be 28 to 31 V) Measure 115 V Input @ 115 V Terminal Block Check 115 V Input fuse @ 115 V Terminal Block DC Output Normal Batteries Not Charging Check Voltage Selection @ Jumper J1 Adjust Main DC Output Voltage @ R2 Check Backup Battery Connections (for incorrect wiring) 14