Service Facts WARNING: GAM5-SF-1D. Convertible Air Handlers ! WARNING

Similar documents
Service Facts. Air Handler - Convertible Model: Series 2 Air Handlers ton GAT2A0B42S31SA GAT2A0C48S41SA GAT2A0C60S51SA WARNING: GAT2-SF-1B

Modular Multi-position Air Handlers

Modular Multi-position Air Handlers

Hyperion Field Reference Data TAM8

Modular Multi-position Air Handler

Modular Multi-position Air Handlers

Note: A/TZONE 950/850 communicating thermostats MUST be used for Variable Speed Outdoor units.

Multi-position, Upflow, Horizontal Left, or Horizontal Right, Modular Air Handlers

Submittal. 5 Ton Convertible Air Handler TEM3A0C60S51SA TEM3A0C60-SUB-1C-EN. July 2014 TAG:

Modular Multi-position Air Handlers

Submittal. 1 1/2 Ton Convertible Air Handler TEM3A0B18S21SA TEM3A0B18-SUB-1C-EN. July 2014 TAG:

Submittal. 2 Ton Convertible Air Handler TEM3A0B24S21SA TEM3A0B24-SUB-1C-EN. July 2014 TAG:

Variable Speed Convertible Air Handler 5 Ton

Variable Speed Convertible Air Handler 4 Ton

Ameristar SUBMITTAL M4AH4E26B1A00AA. 2.0 Ton Multi-position Air Handler M4AH4E26B1A00AA TAG:

Variable Speed Convertible Air Handler 2 1/2 Ton

2 Ton Convertible Air Handler TAM7A0A24H21SD Standard Coil TAM7A0A24H21EA Black Epoxy Coil

Product Data. Convertible Air Handlers 1 1/2 5Ton

Cooling/Heat Pump Convertible Air Handlers

Cooling/Heat Pump Convertible Air Handlers

Product Data. Convertible Air Handlers 1 1/2 5Ton

Cooling/Heat Pump Convertible Air Handlers

36,000-62,000 BTUH Nominal Capacity

2TEH3F18A1000A 2TEH3F24A1000A 2TEH3F30A1000A 2TEH3F36A1000A 2TEH3F42A1000A 2TEH3F48A1000A 2TEH3F60A1000A 1½

208/230/1/60 5/8 5/8 5/8 5/8 5/8 20 CLIMATUFF /230/1/

Vertical Upflow Horizontal Left Air Handlers

208/230/1/ CLIMATUFF /230/1/ YES NO NO PROPELLER 23-1 DIRECT / /230/1/ SPINE FIN

7/8 NO NO NO PROPELLER DIRECT / /230/1/ SPINE FIN /8 8 LBS., 0 OZ. YES 7/8 3/8

Product catalog. Hyperion TM split systems 60 Hz / R410A / 13 SEER SSA-PRC009-E4

4TTB3060D1000B 208/230/1/60 35 SCROLL /230/1/ /8

4TTB3030D1000B 208/230/1/60 4TTB3036D1000B 208/230/1/ RECIP /230/1/ RECIP YES YES

GAM5B0A18M11SA GAM5B0A24M21SA GAM5B0B30M21SA GAM5B0B36M31SA. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

4A6H5049E1000B 208/230/1/ /8 7/8 7/8 7/8 DURATION 208/230/1/ /230/1/ SPINE FIN 13 LBS., 10 OZ. YES

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTR6048-SF-1A. Split System Cooling 4TTR6048A1000A CAUTION CAUTION WARNING

Uncased Vertical Aluminum Upflow Cooling/HP Coils 2-5 Ton 4PXA. Heat Pump / Cooling Coils for R-410A PUB. NO

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTR6024-SF-1B. Split System Cooling 4TTR6024A1000B CAUTION CAUTION WARNING

4TTR6036B1000A 208/230/1/ CLIMATUFF - SCROLL 3/4 3/4 3/4 3/4 3/4 208/230/1/ NO YES NO PROPELLER DIRECT

Aluminum Cased Heat Pump / Cooling Coils 2-5 Ton

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTB6-SF-3. Split System Cooling 4TTB6048A1000A, 4TTB6049A1000A CAUTION

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

4A6H5042G1000A 208/230/1/ DURATION - SCROLL 3/4 208/230/1/ NO (Use BAYKSKT263) YES YES PROPELLER DIRECT

Submittal. Split System Cooling 5.0 Ton 4A7A3060D1000P TAG:

Submittal. Split System Cooling 4A7A6024J-SUB-1B-EN. January A7A6024J1000B TAG:

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

Split System Heat Pump Product Data

4YCC3048A3096A /3/ /

2YCC3060A1120A /1/ / YCC3060A1096A /1/ /

XC80 TUD2B060ACV32A TUD2B080ACV32A TUD2C080ACV42A TUD2B100ACV32A TUD2C100ACV52A TUD2D120ACV52A TUD2D140ACV52A

XV80i. Upflow/Horizontal 80% 2-Stage, Variable Speed Gas-Fired Furnace with Whole House Air Cleaner PUB. NO

Split System Heat Pump Product Data

Split System Cooling Product & Performance Data

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

Upflow/Downflow Horizontal Right or Left Gas-Fired Furnace

Submittal. Date: January 8, Customer P.O. Number: Customer Project Number: CARROLLTON, TX 75006

Aluminum Cased and Uncased Heat Pump / Cooling Coils 1 1/2-5 Ton 2/4TXA, 2/4TXC PUB. NO Heat Pump /Cooling Coils for R-22 and R-410A

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

PRODUCT SPECIFICATIONS 2YCC3036A1096A /1/ /

Service Facts. Split System Cooling 3.0 Ton 4A7A6036J-SF-1B-EN. January A7A6036J1000A

Split System Heat Pump Product Data

The Premium Quality Fan Coil Units for Vertical, Horizontal (Left or Right) Application with Direct Expansion, Hydronic or Electric Heat

FF1DNA, FF1DNE FAN COIL UNITS. Sizes 018, 024, 030. Form No. PDS FF1D.18.3 FEATURES FF1D

1-1/2 THRU 2-1/2 TONS SPLIT SYSTEM FWM Series

MACH N-407 Heat Pump Air-Cooled Chiller

Split System Heat Pump Product Data

PRODUCT SPECIFICATIONS 2YCC3048A1120A /1/ /

DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data

Split System Cooling Product & Performance Data

Fan Powered and Bypass Humidifiers

Service Facts. Split System Heat Pump 4A6H5019H-SF-1C-EN. August A6H5019H1000A

SPLIT SYSTEM HEAT PUMP 1½ 5 TON HERITAGE 13 MODELS 2A6H A American Standard Heating & Air Conditioning

Split System Heat Pump Product Data

MAC N-407 Air-Cooled Chiller

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

BCE4 PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER WITH VARIABLE SPEED APPLICATION INSTALLATION CABINET COMPONENTS CONTROLS WARRANTY

X341119P10 Gas Furnace Var. Speed Blower Var. Speed Inducer Two Stage Heat Direct Vent Models:

DVPVC. Multi-Position, Variable-Speed Air Handler. Comfortnet - Compatible ECM-based Inverter-tuned Internal TXV

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

Upflow/Horizontal 2-Stage, Communicating Variable Speed Gas Furnace Platinum SV

SERVICE FACTS WARNING M801-SF-1C. Gas Furnaces Upflow & Downflow Induced Draft 1 Stage Heat Models: DISCONNECT POWER BEFORE SERVICING M801P040AU24AA

HIGH EFFICIENCY TWO-STAGE ECONET ENABLED AIR HANDLER

Product Data /4WCC3018A through 2/4WCC3060A Single Package Convertible Heat Pump 13 SEER 1½ - 5 Ton R-22/R-410A

Upflow/ Horizontal Downflow/Horizontal Condensing, Direct Vent Gas-Fired Furnace

DVPEC. Multi-Position, Variable-Speed air handler. Comfortnet Compatible ECM-based Internal EEV, Inverter-tuned 2 to 5 Tons

Advance Release September 2009

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

Split System Cooling Product Data

Split System Cooling Product Data

Rheem High Efficiency Modulating EcoNet Enabled Air Handler

Submittal. Downflow Two Stage Condensing Gas Fired Furnace 100,000 BTUH S9V2C100D4-SUB-1-EN. March 2016 S9V2C100D4PSAA TAG:

IMPORTANT. HOSHIZAKI provides this manual primarily to assist qualified service technicians in the service and maintenance of the icemaker.

Submittal. Upflow/ Horizontal Left/Right Two Stage Condensing Gas Fired Furnace 80,000 BTUH S9V2B080U3-SUB-1-EN. February 2016 S9V2B080U3PSAA TAG:

Hyperion TM Split Systems

Submittal. Upflow/ Horizontal Left/Right Two Stage Condensing Gas Fired Furnace 80,000 BTUH S9V2B080U4-SUB-1-EN. February 2016 S9V2B080U4PSAA TAG:

Submittal. Upflow/ Horizontal Left/Right Two Stage Condensing Gas Fired Furnace 40,000 BTUH S9V2B040U3-SUB-1-EN. February 2016 S9V2B040U3PSAA TAG:

Split System Cooling Product Data

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

Submittal. Single Packaged Heat Pump 15 SEER Convertible 4WCY5024A-SUB-1A-EN. March WCY5024A1000A TAG:

Transcription:

Service Facts Convertible Air Handlers Models: Series 5 Air Handlers 1-1/2 to 5 Ton GAM5A0A18M11SA GAM5A0A24M21SA GAM5A0B30M21SA GAM5A0B36M31SA GAM5A0C42M31SA GAM5A0C48M41SA GAM5A0C60M51SA GAM5-SF-1D *For use with BAYEA series heaters ONLY WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING IMPORTANT --- This document contains a wiring diagram and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work.! WARNING SAFETY HAZARD! This information is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and/or property damage. The manufacture or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.! WARNING PRESSURIZED REFRIGERANT! SYSTEM CONTAINS OIL AND REFRIGERANT UNDER HIGH PRESSURE. RECOVER REFRIGERANT TO RELIEVE PRESSURE BEFORE OPENING THE SYSTEM. DO NOT USE NON-APPROVED REFRIGERANTS OR REFRIGERANT SUBSTITUTES OR REFRIGERANT ADDITIVES.! WARNING Note: This unit is certified to UL 1995. LIVE ELECTRICAL COMPONENTS! During installation, testing, servicing, and troubleshooting of this product, it may be necessary to work with live electrical components. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. The interior cabinet wall meets the following: - UL94-5VA Flame Class Listed - UL723 Steiner Tunnel Listed for 25/50 Flame/ Smoke - UL746C Listed for Exposure to Ultraviolet Light, Water Exposure and Immersion Table of Contents Product Specifications... 2 Airflow Performance... 3 Attribute Data... 10 Wiring Diagram... 13 Sequence of Operation... 14 Configuration Dip Switch Settings... 16 EVC Thermal Resistance and Voltage Table... 17 EEV Test Procedures... 18 Subcooling Adjustment... 19 Troubleshooting... 20 NOTICE: Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice. 2012 Trane

MODEL RATED VOLTS/PH/HZ. RATINGS 1 INDOOR COIL Type Rows F.P.I. Face Area (sq. ft.) Tube Size (in.) Refrigerant Control Drain Conn. Size (in.) 2 DUCT CONNECTIONS INDOOR FAN Type Diameter-Width (In.) No. Used Drive - No. Speeds CFM vs. in. w.g. No. Motors H.P. Motor Speed RPM Volts/Ph/Hz F.L. Amps FILTER Filter Furnished? Type Recommended No.-Size-Thickness REFRIGERANT Ref. Line Connections Coupling or Conn. Size in. Gas Coupling or Conn. Size in. Liq. DIMENSIONS Crated (In.) Uncrated WEIGHT Shipping (Lbs.) / Net (Lbs.) MODEL RATED VOLTS/PH/HZ. RATINGS 1 INDOOR COIL Type Rows F.P.I. Face Area (sq. ft.) Tube Size (in.) Refrigerant Control Drain Conn. Size (in.) 2 DUCT CONNECTIONS INDOOR FAN Type Diameter-Width (In.) No. Used Drive - No. Speeds CFM vs. in. w.g. No. Motors H.P. Motor Speed RPM Volts/Ph/Hz F.L. Amps FILTER Filter Furnished? Type Recommended No.-Size-Thickness REFRIGERANT Ref. Line Connections Coupling or Conn. Size in. Gas Coupling or Conn. Size in. Liq. DIMENSIONS Crated (In.) Uncrated WEIGHT Shipping (Lbs.) / Net (Lbs.) GAM5A0A18M11SA 208-230/1/60 See O.D. Specifications Plate Fin 3-14 3.67 3/8 EEV 3/4 NPT See Outline Drawing Centrifugal 11 X 8 1 Direct - 5 See Fan Performance Table 1-1/3 1050 208-230/1/60 2.8 No Throwaway 1-16 X 20-1 in. R-410A Brazed 3/4 3/8 H x W x D 51-3/8 x 20-1/2 x 25-3/4 49-7/8 x 17-1/2 x 21-3/4 126/120 GAM5A0C42M31SA 208-230/1/60 See O.D. Specifications Plate Fin 4-14 5.04 3/8 EEV 3/4 NPT See Outline Drawing Centrifugal 11 X 10 1 Direct - 5 See Fan Performance Table 1-1/2 1050 208-230/1/60 4.1 No Throwaway 1-22 X 20-1 in. R-410A Brazed 7/8 3/8 H x W x D 58-1/2 x 27-1/2 x 25-3/4 56-7/8 x 23-1/2 x 21-3/4 163/153 PRODUCT SPECIFICATIONS GAM5A0A24M21SA 208-230/1/60 See O.D. Specifications Plate Fin 3-14 3.67 3/8 EEV 3/4 NPT See Outline Drawing Centrifugal 11 X 8 1 Direct - 5 See Fan Performance Table 1-1/3 1050 208-230/1/60 2.8 No Throwaway 1-16 X 20-1 in. R-410A Brazed 3/4 3/8 H x W x D 51-3/8 x 20-1/2 x 25-3/4 49-7/8 x 17-1/2 x 21-3/4 126/120 PRODUCT SPECIFICATIONS GAM5A0C48M41SA 208-230/1/60 See O.D. Specifications Plate Fin 4-14 5.96 3/8 EEV 3/4 NPT See Outline Drawing Centrifugal 11 X 10 1 Direct - 5 See Fan Performance Table 1-3/4 1050 208-230/1/60 6.0 No Throwaway 1-22 X 20-1 in. R-410A Brazed 7/8 3/8 H x W x D 63-1/4 x 27-1/2 x 25-3/4 61-3/4 x 23-1/2 x 21-3/4 176/166 GAM5A0B30M21SA 208-230/1/60 See O.D. Specifications Plate Fin 3-14 4.13 3/8 EEV 3/4 NPT See Outline Drawing Centrifugal 11 X 10 1 Direct - 5 See Fan Performance Table 1-1/3 1050 208-230/1/60 2.8 No Throwaway 1-20 X 20-1 in. R-410A Brazed 3/4 3/8 H x W x D 53 x 24-1/4 x 25-3/4 51-1/2 x 21-1/4 x 21-3/4 140/132 GAM5A0C60M51SA 208-230/1/60 See O.D. Specifications Plate Fin 4-14 5.96 3/8 EEV 3/4 NPT See Outline Drawing Centrifugal 11 X 10 1 Direct - 5 See Fan Performance Table 1-1 1050 208-230/1/60 7.6 No Throwaway 1-22 X 20-1 in. R-410A Brazed 7/8 3/8 H x W x D 63-1/4 x 27-1/2 x 25-3/4 61-3/4 x 23-1/2 x 21-3/4 180/170 GAM5A0B36M31SA 208-230/1/60 See O.D. Specifications Plate Fin 3-14 5.04 3/8 EEV 3/4 NPT See Outline Drawing Centrifugal 11 X 10 1 Direct - 5 See Fan Performance Table 1-1/2 1050 208-230/1/60 4.1 No Throwaway 1-20 X 20-1 in. R-410A Brazed 7/8 3/8 H x W x D 57-1/4 x 24-1/4 x 25-3/4 55-3/4 x 21-1/4 x 21-3/4 150/142 1 These Air Handlers are A.R.I. certified with various Split System Air Conditioners and Heat Pumps (ARI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data. 2 3/4" Male Plastic Pipe (Ref.: ASTM 1785-76) GAM5-SF-1D 2

EXTERNAL STATIC (in w.g) AIRFLOW PERFORMANCE GAM5A0A18M11SA Speed Taps - 230 VOLTS AIRFLOW (CFM) Speed Taps - 208 VOLTS 5 4 3 2 1 5 4 3 2 1 0 1081 977 930 862 556 1078 974 927 858 553 0.1 1044 922 850 806 379 1038 916 844 800 373 0.2 995 880 787 702 202 987 871 778 693 193 0.3 956 830 738 621-944 819 727 610-0.4 914 788 692 562-900 774 677 548-0.5 872 749 646 502-855 732 629 485-0.6 838 707 590 445-819 687 570 425-0.7 802 650 528 389-779 628 505 367-0.8 755 598 478 327-730 573 453 302-0.9 708 539 420 - - 680 512 392 - - NOTES: 1. Values are with wet coil and without filters. 2. Contact your particular filter manufacturer for pressure drop data. 3. Electric heater pressure drop is negligible and is included within the airflow data. 4. Tap 1 is an continuous fan speed tap. 5. Factory Setting GAM5A0A18M11SA MINIMUM HEATER AIRFLOW CFM BAYEAAC05BK1AA BAYEAAC05LG1AA BAYEAAC08BK1AA BAYEAAC08LG1AA BAYEAAC10BK1AA BAYEAAC10LG1AA Without Heat Pump Minimum Air Speed Tap With Heat Pump Tap 3 Tap 4 Tap 3 Tap 4 Tap 3 1 Tap 5 1 BAYEAAC10LG3AA Tap 5 Tap 5 2 BAYEABC15BK1AA - - BAYEABC20BK1AA - - 1 not qualified for downflow installations 2 Approved for 240 V only Note: Heating and cooling speeds are the same, factory set at Speed Tap #4. Note: A G only signal from the comfort control will run the blower at a lower speed, factory set at Speed Tap #1. See the Sequence of Operation for additional information. 3 GAM5-SF-1D

EXTERNAL STATIC (in w.g) AIRFLOW PERFORMANCE GAM5A0A24M21SA Speed Taps - 230 VOLTS AIRFLOW (CFM) Speed Taps - 208 VOLTS 5 4 3 2 1 5 4 3 2 1 0 1081 977 937 928 579 1078 974 933 925 576 0.1 1044 922 868 844 418 1038 916 863 838 412 0.2 995 880 817 777 306 987 871 808 768 298 0.3 956 830 767 729-944 819 756 717-0.4 914 788 719 682-900 774 705 668-0.5 872 749 680 635-855 732 663 618-0.6 838 707 628 577-819 687 609 557-0.7 802 650 566 515-779 628 544 492-0.8 755 598 511 467-730 573 486 442-0.9 708 539 460 407-680 512 432 - - NOTES: 1. Values are with wet coil and without filters. 2. Contact your particular filter manufacturer for pressure drop data. 3. Electric heater pressure drop is negligible and is included within the airflow data. 4. Tap 1 is an continuous fan speed tap. 5. Factory Setting GAM5A0A24M21SA MINIMUM HEATER AIRFLOW CFM BAYEAAC05BK1AA BAYEAAC05LG1AA BAYEAAC08BK1AA BAYEAAC08LG1AA BAYEAAC10BK1AA BAYEAAC10LG1AA Without HP Minimum Air Speed Tap With HP Tap 3 Tap 4 Tap 3 Tap 4 Tap 3 1 Tap 5 1 BAYEAAC10LG3AA Tap 5 Tap 5 2 BAYEABC15BK1AA - - BAYEABC20BK1AA - - 1 not qualified for downflow installations 2 Approved for 240 V only Note: Heating and cooling speeds are the same, factory set at Speed Tap #4. Note: A G only signal from the comfort control will run the blower at a lower speed, factory set at Speed Tap #1. See the Sequence of Operation for additional information. GAM5-SF-1D 4

EXTERNAL STATIC (in w.g) AIRFLOW PERFORMANCE GAM5A0B30M21SA Speed Taps - 230 VOLTS AIRFLOW (CFM) Speed Taps - 208 VOLTS 5 4 3 2 1 5 4 3 2 1 0 1282 1150 979 856 678 1279 1146 976 853 675 0.1 1238 1094 931 797 482 1232 1088 925 791 476 0.2 1186 1047 863 725 285 1177 1039 854 716 276 0.3 1141 986 803 647 88 1130 975 791 636 77 0.4 1091 935 721 555-1076 921 707 540-0.5 1033 866 649 461-1016 849 632 444-0.6 977 799 554 388-958 779 534 369-0.7 914 732 490 318-892 710 468 296-0.8 846 646 429 - - 821 621 404 - - 0.9 771 587 376 - - 743 560 348 - - NOTES: 1. Values are with wet coil and without filters. 2. Contact your particular filter manufacturer for pressure drop data. 3. Electric heater pressure drop is negligible and is included within the airflow data. 4. Tap 1 is an continuous fan speed tap. 5. Factory Setting GAM5A0B30M21SA MINIMUM HEATER AIRFLOW CFM BAYEAAC05BK1AA BAYEAAC05LG1AA BAYEAAC08BK1AA BAYEAAC08LG1AA BAYEAAC10BK1AA BAYEAAC10LG1AA Without HP Minimum Air Speed Tap With HP Tap 2 Tap 3 Tap 3 Tap 4 Tap 3 Tap 4 BAYEAAC10LG3AA Tap 3 1 Tap 4 1 BAYEABC15BK1AA Tap 4 Tap 5 BAYEABC15LG3AA Tap 4 Tap 5 BAYEABC20BK1AA - - BAYEACC25BK1AA - - 1 208 V not approved for upflow installations Note: Heating and cooling speeds are the same, factory set at Speed Tap #4. Note: A G only signal from the comfort control will run the blower at a lower speed, factory set at Speed Tap #1. See the Sequence of Operation for additional information. 5 GAM5-SF-1D

EXTERNAL STATIC (in w.g) AIRFLOW PERFORMANCE GAM5A0B36M31SA Speed Taps - 230 VOLTS AIRFLOW (CFM) Speed Taps - 208 VOLTS 5 4 3 2 1 5 4 3 2 1 0 1438 1387 1197 1013 732 1435 1383 1194 1009 729 0.1 1394 1340 1143 945 552 1388 1334 1137 939 546 0.2 1350 1299 1090 892 413 1341 1291 1082 884 404 0.3 1301 1245 1031 817 305 1289 1233 1019 806 293 0.4 1253 1197 975 751 209 1239 1183 960 737 195 0.5 1205 1151 917 651-1188 1134 900 634-0.6 1155 1094 837 578-1136 1075 817 559-0.7 1099 1032 766 499-1077 1010 744 476-0.8 1039 972 691 453-1014 946 666 - - 0.9 964 889 633 409-936 861 605 - - NOTES: 1. Values are with wet coil and without filters. 2. Contact your particular filter manufacturer for pressure drop data. 3. Electric heater pressure drop is negligible and is included within the airflow data. 4. Tap 1 is an continuous fan speed tap. 5. Factory Setting GAM5A0B36M31SA MINIMUM HEATER AIRFLOW CFM BAYEAAC05BK1AA BAYEAAC05LG1AA BAYEAAC08BK1AA BAYEAAC08LG1AA BAYEAAC10BK1AA BAYEAAC10LG1AA Without HP Minimum Air Speed Tap With HP Tap 2 Tap 3 Tap 3 Tap 4 Tap 4 Tap 5 BAYEAAC10LG3AA Tap 4 Tap 5 BAYEABC15BK1AA Tap 4 Tap 5 BAYEABC15LG3AA Tap 4 Tap 5 BAYEABC20BK1AA - - BAYEACC25BK1AA - - Note: Heating and cooling speeds are the same, factory set at Speed Tap #4. Note: A G only signal from the comfort control will run the blower at a lower speed, factory set at Speed Tap #1. See the Sequence of Operation for additional information. GAM5-SF-1D 6

EXTERNAL STATIC (in w.g) AIRFLOW PERFORMANCE GAM5A0C42M31SA Speed Taps - 230 VOLTS AIRFLOW (CFM) Speed Taps - 208 VOLTS 5 4 3 2 1 5 4 3 2 1 0 1644 1575 1401 1266 752 1641 1572 1398 1263 749 0.1 1596 1525 1346 1215 665 1590 1519 1340 1209 659 0.2 1550 1480 1300 1157 569 1542 1471 1291 1148 560 0.3 1509 1437 1252 1110 492 1497 1425 1241 1099 480 0.4 1463 1391 1205 1058 384 1449 1377 1191 1043 370 0.5 1420 1345 1151 980 327 1403 1328 1134 963 310 0.6 1376 1301 1085 917 259 1356 1282 1066 898 239 0.7 1332 1251 1020 865-1310 1228 998 842-0.8 1271 1179 969 813-1246 1154 944 788-0.9 1199 1119 924 747-1171 1091 897 719 - NOTES: 1. Values are with wet coil and without filters. 2. Contact your particular filter manufacturer for pressure drop data. 3. Electric heater pressure drop is negligible and is included within the airflow data. 4. Tap 1 is an continuous fan speed tap. 5. Factory Setting GAM5A0C42M31SA MINIMUM HEATER AIRFLOW CFM BAYEAAC05BK1AA BAYEAAC05LG1AA BAYEAAC08BK1AA BAYEAAC08LG1AA BAYEAAC10BK1AA BAYEAAC10LG1AA Without HP Minimum Air Speed Tap With HP Tap 2 Tap 3 Tap 2 Tap 3 Tap 2 Tap 3 BAYEAAC10LG3AA Tap 2 Tap 3 BAYEABC15BK1AA Tap 3 Tap 4 BAYEABC15LG3AA Tap 3 Tap 4 BAYEABC20BK1AA - - BAYEACC25BK1AA - - Note: Heating and cooling speeds are the same, factory set at Speed Tap #4. Note: A G only signal from the comfort control will run the blower at a lower speed, factory set at Speed Tap #1. See the Sequence of Operation for additional information. 7 GAM5-SF-1D

EXTERNAL STATIC (in w.g) AIRFLOW PERFORMANCE GAM5A0C48M41SA Speed Taps - 230 VOLTS AIRFLOW (CFM) Speed Taps - 208 VOLTS 5 4 3 2 1 5 4 3 2 1 0 1913 1770 1694 1593 866 1910 1767 1691 1590 863 0.1 1874 1730 1653 1547 791 1868 1724 1647 1541 785 0.2 1834 1690 1611 1505 699 1825 1681 1602 1496 690 0.3 1791 1646 1567 1456 620 1780 1635 1556 1445 609 0.4 1748 1600 1521 1410 537 1734 1586 1506 1396 522 0.5 1708 1556 1476 1367 453 1691 1539 1459 1350 437 0.6 1668 1516 1436 1326 370 1648 1496 1416 1306 351 0.7 1629 1475 1394 1283-1607 1452 1372 1260-0.8 1588 1435 1352 1236-1563 1410 1327 1211-0.9 1541 1390 1304 1183-1513 1362 1276 1156 - NOTES: 1. Values are with wet coil and without filters. 2. Contact your particular filter manufacturer for pressure drop data. 3. Electric heater pressure drop is negligible and is included within the airflow data. 4. Tap 1 is an continuous fan speed tap. 5. Factory Setting GAM5A0C48M41SA MINIMUM HEATER AIRFLOW CFM BAYEAAC05BK1AA BAYEAAC05LG1AA BAYEAAC08BK1AA BAYEAAC08LG1AA BAYEAAC10BK1AA BAYEAAC10LG1AA Without HP Minimum Air Speed Tap With HP Tap 2 Tap 3 Tap 2 Tap 3 Tap 2 Tap 3 BAYEAAC10LG3AA Tap 2 Tap 3 BAYEABC15BK1AA Tap 3 Tap 4 BAYEABC15LG3AA Tap 3 Tap 4 BAYEABC20BK1AA Tap 3 Tap 4 BAYEACC25BK1AA Tap 4 Tap 5 Note: Heating and cooling speeds are the same, factory set at Speed Tap #4. Note: A G only signal from the comfort control will run the blower at a lower speed, factory set at Speed Tap #1. See the Sequence of Operation for additional information. GAM5-SF-1D 8

EXTERNAL STATIC (in w.g) AIRFLOW PERFORMANCE GAM5A0C60M51SA Speed Taps - 230 VOLTS AIRFLOW (CFM) Speed Taps - 208 VOLTS 5 4 3 2 1 5 4 3 2 1 0 2327 2020 1914 1819 1125 2324 2017 1910 1816 1122 0.1 2285 1980 1873 1780 990 2279 1974 1867 1774 984 0.2 2237 1944 1835 1740 831 2228 1935 1826 1731 822 0.3 2182 1908 1800 1705 600 2171 1896 1789 1693 589 0.4 2125 1869 1756 1659 331 2111 1854 1742 1645 317 0.5 2062 1830 1717 1620 249 2045 1813 1700 1603 232 0.6 1995 1747 1664 1575 187 1975 1727 1644 1555 168 0.7 1922 1707 1629 1540-1899 1685 1607 1518-0.8 1844 1673 1594 1502-1819 1648 1569 1477-0.9 1761 1629 1553 1464-1733 1601 1525 1436 - NOTES: 1. Values are with wet coil and without filters. 2. Contact your particular filter manufacturer for pressure drop data. 3. Electric heater pressure drop is negligible and is included within the airflow data. 4. Tap 1 is an continuous fan speed tap. 5. If the air handler is applied in downflow or horizontal configurations, the airflow should not exceed 2000 CFM. Airflow above 2000 CFM could result in water blow-off. 6. Factory Setting GAM5A0C60M51SA MINIMUM HEATER AIRFLOW CFM BAYEAAC05BK1AA BAYEAAC05LG1AA BAYEAAC08BK1AA BAYEAAC08LG1AA BAYEAAC10BK1AA BAYEAAC10LG1AA Without HP Minimum Air Speed Tap Note: Heating and cooling speeds are the same, factory set at Speed Tap #4. Note: A G only signal from the comfort control will run the blower at a lower speed, factory set at Speed Tap #1. See the Sequence of Operation for additional information. With HP Tap 2 Tap 3 Tap 2 Tap 3 Tap 2 Tap 3 BAYEAAC10LG3AA Tap 2 Tap 3 BAYEABC15BK1AA Tap 3 Tap 4 BAYEABC15LG3AA Tap 3 Tap 4 BAYEABC20BK1AA Tap 3 Tap 4 BAYEACC25BK1AA Tap 4 Tap 5 12 1 If the air handler is applied in downflow or horizontal configurations, the airflow should not exceed 2000 CFM. Airflow above 2000 CFM could result in water blow-off. 2 Tap 5 can be used but only when the external static pressure is.6" or above. 9 GAM5-SF-1D

Model No. No. of s Capacity Amps per WIRING DATA GAM5A0A18M11SA 240 VOLT 208 VOLT Minimum Ampacity Maximum Overload Protection Capacity kw BTUH kw BTUH Amps per Minimum Ampacity Maximum Overload Protection No - - - 2.8* 4 15 - - 2.8* 4 15 BAYEAAC05BK1A BAYEAAC05LG1A BAYEAAC08BK1A BAYEAAC08LG1A BAYEAAC10BK1A 1 BAYEAAC10LG1A 1 1 4.80 16400 20.0 29 30 3.60 12300 17.3 25 25 1 7.68 26200 32.0 44 45 5.76 19700 27.7 38 40 1 9.60 32800 40.0 54 60 7.20 24600 34.6 47 50 BAYEAAC10LG3A 2 1-3 PH 9.60 32800 23.1 32 35 7.20 24600 20.0 28 30 Note: * Motor Amps 1 not qualified for downflow installations 2 Approved for 240 V only with Heat Pump Model No. No. of s Capacity Amps per WIRING DATA GAM5A0A24M21SA 240 VOLT 208 VOLT Minimum Ampacity Maximum Overload Protection Capacity kw BTUH kw BTUH Amps per Minimum Ampacity Maximum Overload Protection No - - - 2.8* 4 15 - - 2.8* 4 15 BAYEAAC05BK1A BAYEAAC05LG1A BAYEAAC08BK1A BAYEAAC08LG1A BAYEAAC10BK1A 1 BAYEAAC10LG1A 1 1 4.80 16400 20.0 29 30 3.60 12300 17.3 25 25 1 7.68 26200 32.0 44 45 5.76 19700 27.7 38 40 1 9.60 32800 40.0 54 60 7.20 24600 34.6 47 50 BAYEAAC10LG3A 2 1-3 PH 9.60 32800 23.1 32 35 7.20 24600 20.0 28 30 Note: * Motor Amps 1 not qualified for downflow installations 2 Approved for 240 V only with Heat Pump GAM5-SF-1D 10

Model No. No. of s Capacity WIRING DATA GAM5A0B30M21SA 240 VOLT 208 VOLT Amps per Minimum Ampacity Maximum Overload Protection Capacity kw BTUH kw BTUH Amps per Minimum Ampacity Maximum Overload Protection No - - - 2.8* 4 15 - - 2.8* 4 15 BAYEAAC05BK1A BAYEAAC05LG1A BAYEAAC08BK1A BAYEAAC08LG1A BAYEAAC10BK1A BAYEAAC10LG1A 1 4.80 16400 20.0 29 30 3.60 12300 17.3 25 25 1 7.68 26200 32.0 44 45 5.76 19700 27.7 38 40 1 9.60 32800 40.0 54 60 7.20 24600 34.6 47 50 BAYEAAC10LG3A 1-3 PH 9.60 32800 23.1 32 35 7.20 24600 20.0 28 30 BAYEABC15LG3A 1 1-3 PH 14.40 49200 34.6 46 50 10.80 36900 30.0 41 45 BAYEABC15BK1A - 12 9.60 32800 40 54 60 7.20 24600 34.6 47 50 2 BAYEABC15BK1A - 2 4.80 16400 20 25 25 3.60 12300 17.3 22 25 Note: * Motor Amps 1 208 V not approved for upflow installations 2 MCA and MOP for circuit 1 contains the motor amps Model No. No. of s Capacity WIRING DATA GAM5A0B36M31SA 240 VOLT 208 VOLT Amps per Minimum Ampacity Maximum Overload Protection Capacity kw BTUH kw BTUH Amps per Minimum Ampacity Maximum Overload Protection No - - - 4.1* 5 15 - - 4.1* 5 15 BAYEAAC05BK1A BAYEAAC05LG1A BAYEAAC08BK1A BAYEAAC08LG1A BAYEAAC10BK1A BAYEAAC10LG1A 1 4.80 16400 20.0 30 30 3.60 12300 17.3 27 30 1 7.68 26200 32.0 45 45 5.76 19700 27.7 40 40 1 9.60 32800 40.0 55 60 7.20 24600 34.6 48 50 BAYEAAC10LG3A 1-3 PH 9.60 32800 23.1 33 35 7.20 24600 20.0 30 30 BAYEABC15LG3A 1-3 PH 14.40 49200 34.6 48 50 10.80 36900 30.0 42 45 BAYEABC15BK1A - 11 9.60 32800 40 55 60 7.20 24600 34.6 48 50 2 BAYEABC15BK1A - 2 4.80 16400 20 25 25 3.60 12300 17.3 22 25 Note: * Motor Amps 1 MCA and MOP for circuit 1 contains the motor amps 11 GAM5-SF-1D

Model No. No. of s Capacity WIRING DATA GAM5A0C42M31SA 240 VOLT 208 VOLT Amps per Minimum Ampacity Maximum Overload Protection Capacity kw BTUH kw BTUH Amps per Minimum Ampacity Maximum Overload Protection No - - - 4.1* 5 15 - - 4.1* 5 15 BAYEAAC05BK1A BAYEAAC05LG1A BAYEAAC08BK1A BAYEAAC08LG1A BAYEAAC10BK1A BAYEAAC10LG1A 1 4.80 16400 20.0 30 30 3.60 12300 17.3 27 30 1 7.68 26200 32.0 45 45 5.76 19700 27.7 40 40 1 9.60 32800 40.0 55 60 7.20 24600 34.6 48 50 BAYEAAC10LG3A 1-3 PH 9.60 32800 23.1 33 35 7.20 24600 20.0 30 30 BAYEABC15LG3A 1-3 PH 14.40 49200 34.6 48 50 10.80 36900 30.0 42 45 BAYEABC15BK1A - 11 9.60 32800 40 55 60 7.20 24600 34.6 48 50 2 BAYEABC15BK1A - 2 4.80 16400 20 25 25 3.60 12300 17.3 22 25 Note: * Motor Amps 1 MCA and MOP for circuit 1 contains the motor amps Model No. No. of s Capacity WIRING DATA GAM5A0C48M41SA 240 VOLT 208 VOLT Amps per Minimum Ampacity Maximum Overload Protection Capacity kw BTUH kw BTUH Amps per Minimum Ampacity Maximum Overload Protection No - - - 6.0* 8 15 - - 6.0* 8 15 BAYEAAC05BK1A BAYEAAC05LG1A BAYEAAC08BK1A BAYEAAC08LG1A BAYEAAC10BK1A BAYEAAC10LG1A 1 4.80 16400 20.0 33 35 3.60 12300 17.3 29 30 1 7.68 26200 32.0 48 50 5.76 19700 27.7 42 45 1 9.60 32800 40.0 58 60 7.20 24600 34.6 51 60 BAYEAAC10LG3A 1-3 PH 9.60 32800 23.1 36 40 7.20 24600 20.0 32 35 BAYEABC15LG3A 1-3 PH 14.40 49200 34.6 50 50 10.80 36900 30.0 44 45 BAYEABC15BK1A - 11 9.60 32800 40 58 60 7.20 24600 34.6 51 60 2 BAYEABC15BK1A - 2 4.80 16400 20 25 25 3.60 12300 17.3 22 25 BAYEABC20BK1A - 11 9.60 32800 40 58 60 7.20 24600 34.6 51 60 2 BAYEABC20BK1A - 2 9.60 32800 40 50 50 7.20 24600 34.6 43 45 BAYEACC25BK1A - 11 9.60 32800 40 58 60 7.20 24600 34.6 51 60 BAYEACC25BK1A - 2 3 9.60 32800 40 50 50 7.20 24600 34.6 43 45 BAYEACC25BK1A - 3 4.80 16400 20 25 25 3.60 12300 17.3 22 25 Note: * Motor Amps 1 MCA and MOP for circuit 1 contains the motor amps GAM5-SF-1D 12

Model No. No. of s Capacity WIRING DATA GAM5A0C60M51SA 240 VOLT 208 VOLT Amps per Minimum Ampacity Maximum Overload Protection Capacity kw BTUH kw BTUH Amps per Minimum Ampacity Maximum Overload Protection No - - - 7.6* 10 15 - - 7.6* 10 15 BAYEAAC05BK1A BAYEAAC05LG1A BAYEAAC08BK1A BAYEAAC08LG1A BAYEAAC10BK1A BAYEAAC10LG1A 1 4.80 16400 20.0 35 35 3.60 12300 17.3 31 35 1 7.68 26200 32.0 50 50 5.76 19700 27.7 44 45 1 9.60 32800 40.0 60 60 7.20 24600 34.6 53 60 BAYEAAC10LG3A 1-3 PH 9.60 32800 23.1 37 40 7.20 24600 20.0 34 35 BAYEABC15LG3A 1-3 PH 14.40 49200 34.6 52 60 10.80 36900 30.0 46 50 BAYEABC15BK1A - 11 9.60 32800 40 60 60 7.20 24600 34.6 53 60 2 BAYEABC15BK1A - 2 4.80 16400 20 25 25 3.60 12300 17.3 22 25 BAYEABC20BK1A - 11 9.60 32800 40 60 60 7.20 24600 34.6 53 60 2 BAYEABC20BK1A - 2 9.60 32800 40 50 50 7.20 24600 34.6 43 45 BAYEACC25BK1A23-11 9.60 32800 40 60 60 7.20 24600 34.6 53 60 BAYEACC25BK1A - 2 3 9.60 32800 40 50 50 7.20 24600 34.6 43 45 BAYEACC25BK1A - 3 4.80 16400 20 25 25 3.60 12300 17.3 22 25 Note: * Motor Amps 1 MCA and MOP for circuit 1 contains the motor amps 2 If the air handler is applied in downflow or horizontal configurations, the airflow should not exceed 2000 CFM. Airflow above 2000 CFM could result in water blow-off. 3 Tap 5 can be used but only when the external static pressure is.6" or above. DISTANCE FROM BELLY BAND TO SHAFT FACE OF MOTOR FOR MINIMUM VIBRATION BLOWER HOUSING WHEEL BELLY BAND A MOTOR A is determined per chart Wheel is centered in Blower Housing MODEL DIM "A" GAM5A0A18M11SA 1-1/8 GAM5A0A24M21SA 1-1/8 GAM5A0B30M21SA 1-1/8 GAM5A0B36M31SA 1-1/2 GAM5A0C42M31SA 1-1/2 GAM5A0C48M41SA 2-1/4 GAM5A0C60M51SA 2-1/4 13 GAM5-SF-1D

WIRING DIAGRAM FOR GAM5 GAM5-SF-1D 14

SEQUENCE OF OPERATION FOR GAM5 AIR HANDLERS GAM5 Sequence of Operation: Abbreviations TDR = Time Delay Relay EVC = Expansion Valve Control EEV = Electronic Expansion Valve YI = Y signal into the EVC from the comfort control YO = Y signal out of the EVC from the comfort control OEM = Original Equipment Manufacturer See unit, electric heat, and field wiring diagrams for additional information. Continuous Fan IMPORTANT: If the indoor air exceeds 60% relative humidity or simply feels uncomfortably humid, it is recommended that the indoor fan only be used in the AUTO mode. 1. R-G contacts close on comfort control sending 24VAC to the G terminal on the fan TDR 2. Low speed contacts close in the TDR and send 24VAC on terminal labeled LOW. 3. Blower motor will now run on low speed. Speed is field selectable. Heat Pump OD (cooling) 1. R-Y contacts close on the comfort control sending 24VAC to Y terminal on TDR and the YI (Y In) terminal on the EVC. 2. R-G contacts also close on the comfort control sending 24VAC to the G terminal on the TDR. (The combination of 24VAC on terminals Y and G on the TDR will close the high speed contacts of the TDR) 3. R-O contacts on the comfort control close sending 24VAC to the O terminal on the EVC. This signals the EVC that the unit is in cooling mode. The EVC will control the EEV to maintain the correct superheat. 4. Normally closed contacts on the EVC will pass 24VAC to the YO terminal providing power to the outdoor unit control circuit 5. The blower motor will now run on high speed. Speed is field selectable. Heat Pump OD (heating) 1. R-Y contacts close on the comfort control sending 24VAC to Y terminal on TDR and the YI (Y In) terminal on the EVC 2. R-G contacts also close on the comfort control sending 24VAC to the G terminal on the TDR. (The combination of 24VAC on terminals Y and G on the TDR will close the high speed contacts of the TDR) The blower motor will now run on high speed. 3. The combination of 24VAC on the Y terminal and zero volts on the O terminal signals the EVC that the unit is in heat-pump heating mode. 4. Normally closed contacts on the EVC will pass 24VAC to the YO terminal providing power to the outdoor unit control circuit 5. The blower motor will now run on high speed Cooling OD 1. R-Y contacts close on the comfort control sending 24VAC to Y terminal on TDR and the YI (Y In) terminal on the EVC 2. R-G contacts also close on the comfort control sending 24VAC to the G terminal on the TDR. (The combination of 24VAC on terminals Y and G on the TDR will close the high speed contacts of the TDR) 3. R-O jumper on the TDR sends 24VAC to the O terminal on the EVC. This signals the EVC that the unit is in cooling mode. The EVC will control the EEV to maintain the correct superheat. 4. Normally closed contacts on the EVC will pass 24VAC to the YO terminal providing power to the outdoor unit control circuit 5. The blower motor will now run on high speed Electric Heating 1. R-W contacts close on the comfort control sending 24VAC to the W terminal on the TDR. 24VAC is also sent to EHC to energize the heat relay. 2. R-G contacts close on the comfort control sending 24VAC to the G terminal on the TDR. (The combination of 24VAC on terminals W and G on the TDR will close the high speed contacts of the TDR) 3. WJ contacts on the TDR close providing an interlock circuit to allow the electric heat relays to operate. The comfort control must be setup to control R-G contacts with a call for electric heat. This closes the interlock circuit and allows the heat relay circuit to be energized. Optional Condensate Switch 1. An optional OEM condensate switch can be installed within the unit. This switch is only available through the National Distribution Center or Global Parts. 2. Switch contacts are normally open and close when water level rises. The closed switch will interrupt current flow to the YO terminal and de-energize the OD unit. 3. Switch is only operational during cooling mode. Condensate overflow is not operational during heating or defrost modes. Standard aftermarket condensate switches cannot be used within the unit but can be installed exterior of the unit. The 3rd party condensate overflow switch must be wired between Y of the thermostat and YI of the EEV control. 15 GAM5-SF-1D

SW1 410 22 1 2 3 Freeze Protection 1. The EVC control has the ability to sense when the coil is beginning to ice. When this event occurs, the contacts to the YO circuit will open and de-energize the OD unit. 2. The indoor blower motor will continue to run to aid in defrosting the coil. After the coil has sufficiently defrosted, the YO contacts will close and cooling operation will begin again. Fan Off Delay 1. The TDR has a dip switch that can enable a 90 second fan off delay anytime a fan call is made from the comfort control. The factory default is ON. To disable the delay, turn power off to the unit, turn the dip switch to the off position and turn power back on to the unit. DIP SWITCH SETTING - Refrigeration Switch Wire Ties Note: Ensure that the system refrigerant is set to match your application, either R-410A or R-22. using the Refrigerant Switch located on the Expansion Valve Control board (EVC) in the Control Pocket. Factory default is R-410A. Note: A power cycle is needed for the EVC to recognize the change. SW1 410 22 GAM5-SF-1D 16

SW1 410 22 1 2 3 CONFIGURATION DIP SWITCH SETTINGS SW2 Switch Settings (Configuration) DS1 DS2 DS3 OFF ON OFF ON ON OFF OFF OFF ON ON OFF ON Model Number GAM5A0A18M11SA GAM5A0A24M21SA GAM5A0B30M21SA GAM5A0B36M31SA GAM5A0C42M31SA GAM5A0C48M41SA GAM5A0C60M51SA DS1 DS2 DS3 EVC STATUS EVC STATUS LED (Non Heat Pump Systems) Flash 1 Cool mode / No active call 3 Active call for cooling EVC STATUS LED (Heat Pump Systems) Flash 1 Cool mode / No active call 3 Active call for cooling or defrost 4 Heat mode selected or Thermostat system switch off 6 Active call for heating NOTE: Status LED is for determining EVC control state only. Auxiliary heat status is not reported. EVC FAULT CODES LED Color RED EVC Fault LED Description Possible Causes OFF Standby 1 Stepper Motor coil has an open circuit or intermittent short Faulty EEV motor / wiring harness 2 Control has detected an internal failure Verify EEV motor resistance. EEV motor drive, motor feedback, or 12v failure. Verify EEV motor resistance 3 Evaporator Temperature Sensor (ET) input out of range (Verify resistance, 5VDC output from control) (1) Sensor open / shorted, unplugged, wiring harness problem 4 Gas Temperature Sensor (GT) input out of range (Verify resistance, 5VDC output from control) (1) Sensor open / shorted, unplugged, wiring harness problem 5 Stepper Motor Coil is shorted (2) Faulty EEV motor / wiring harness 6 Valve is not responding to a change in position Possible stuck valve, ET/GT sensor calibration 7 High superheat System low on charge, liquid line restriction, ET/GT sensor calibration 10 Low superheat (3) Stuck valve, ET/GT sensor calibration, restricted distributor line that ET is connected to, check valve leaking 11 Internal condensate drain switch activated for 100 seconds (2) Condensate line clogged 13 Indoor frost protection activated (4) Low / incorrect airflow, low refirgerant charge, ET sensor calibration. Normal for low ambient cooling NOTES: 1) EEV will try to go to a safe position, cooling attempt allowed 2) EVC disables YO 3) Cooling attempt allowed, 5 consecutive Y calls with same condition disables YO 4) EVC disables YO for 5 minutes NOTE: Faults 6, 7, & 10 may require jumper from "Test - Close" for 10 seconds to clear fault LED 17 GAM5-SF-1D

THERMAL RESISTANCE AND VOLTAGE TABLE TEMP F TEMP C THERMISTOR RESISTANCE (OHMS) * Volts DC at plug J3 EVAP TEMP (ET) - Orange to Orange GAS TEMP (GT) - Black to Black TEMP F TEMP C THERMISTOR RESISTANCE (OHMS) * Volts DC at plug J3 EVAP TEMP (ET) - Orange to Orange GAS TEMP (GT) - Black to Black 20 6.7 45076 3.20 72 22.2 11024 1.54 21 6.1 43764 3.17 74 23.3 10492 1.49 22 5.6 42494 3.14 76 24.4 9990 1.44 23 5.0 41266 3.10 78 25.6 9515 1.39 24 4.4 40077 3.07 80 26.7 9065 1.34 25 3.9 38927 3.04 82 27.8 8639 1.29 26 3.3 37813 3.00 84 28.9 8236 1.25 27 2.8 36736 2.97 86 30.0 7855 1.20 28 2.2 35692 2.93 88 31.1 7493 1.16 29 1.7 34681 2.90 90 32.2 7150 1.12 30 1.1 33703 2.86 92 33.3 6825 1.08 31 0.6 32755 2.83 94 34.4 6516 1.04 32 0.0 31838 2.80 96 35.6 6224 1.01 33 0.6 30949 2.76 98 36.7 5946 0.97 34 1.1 30087 2.73 100 37.8 5682 0.93 35 1.7 29253 2.69 102 38.9 5432 0.90 36 2.2 28445 2.66 104 40.0 5194 0.87 37 2.8 27661 2.62 106 41.1 4968 0.84 38 3.3 26902 2.59 108 42.2 4753 0.81 39 3.9 26166 2.56 110 43.3 4548 0.78 40 4.4 25452 2.52 112 44.4 4354 0.75 41 5.0 24761 2.49 114 45.6 4169 0.72 42 5.6 24090 2.45 116 46.7 3992 0.70 43 6.1 23440 2.42 118 47.8 3825 0.67 44 6.7 22810 2.39 120 48.9 3665 0.65 45 7.2 22198 2.35 122 50.0 3513 0.62 46 7.8 21605 2.32 124 51.1 3368 0.60 47 8.3 21030 2.29 126 52.2 3230 0.58 48 8.9 20472 2.25 128 53.3 3098 0.56 49 9.4 19931 2.22 130 54.4 2972 0.54 50 10.0 19405 2.19 132 55.6 2853 0.52 51 10.6 18896 2.16 134 56.7 2738 0.50 52 11.1 18401 2.12 136 57.8 2629 0.48 53 11.7 17921 2.09 138 58.9 2525 0.46 54 12.2 17455 2.06 140 60.0 2425 0.45 55 12.8 17002 2.03 142 61.1 2330 0.43 56 13.3 16563 2.00 144 62.2 2239 0.42 57 13.9 16137 1.97 146 63.3 2153 0.40 58 14.4 15723 1.94 148 64.4 2070 0.39 59 15.0 15320 1.91 150 65.6 1990 0.37 60 15.6 14930 1.88 61 16.1 14550 1.85 62 16.7 14182 1.82 * Values should be within +/ 5% 63 17.2 13824 1.79 64 17.8 13476 1.76 65 18.3 13138 1.73 66 18.9 12810 1.70 67 19.4 12491 1.67 68 20.0 12181 1.65 69 20.6 11879 1.62 70 21.1 11586 1.59 STATUS LED FAULT LED J7 Liteport SW1 R410A / R22 SW2 Configuration See Table J4 OPEN TEST CLOSE GAM5-SF-1D 18 STATUS D14 MH4 R18 D27 D15 R1 D18 D3 R9 R58 D28 + R33 MOV1 J7 R61 C21 D30 R4 - SW1 OFF ON R54 410 22 R8 OFF ON D17 R45 SW2 D16 R17 R39 1 1 C26 R57 R60 R25 2 2 C25 R29 C15 3 3 R62 C19 J4 R63 R74R70 C24 C20 L4 C14 OPEN D21 R64 R75 U4 TEST R55 CLOSE R53 R81 D22 R52 R76 C28 R51 FAULT D19 J2 MH1 J2 C27 Y1 R23 C35 O B YO R R71 D23 R31 C22 C31 R79 D25 EXPANSION VALVE CONTROL BOARD (EVC) D26 R80 PGC PGD VSS VDD CLR D24 J5 K1 C11 R11 R56 R82 R32 R37 C18 C34 R41 Q9 R42 R10 R47 X1 C12 C17 R66 D29 R46 + + R84 C7 Q10 C13R24R13 R69 L3 D6 C4 C10 U1 D4 D7 D11 C5 R85 D9 U2 C6 P/N LABEL D2 R6R34Q5 R16R35 R21 Q6 Q7 C2 R36 Q8 R38 D13 R28 R2 R86 R30 C9 1- R49 C8 Q1 Q2 Q3 Q4 R7 R48 C23 R22 D10 L2 C36 TRANE U.S. INC. R5 R40 R3 D1 R15 R14 D5 R20 R19 D8 R27 R26 D12 C38 C3 C37 +12V R83 R59 C16 D20 R73 C30 R72 C33 R77 R78 R12 C32 +VDD C29 R43 R44 L1 GND MH2 C1 MH3 J1 J6 J3 J1 To EEV Stator J6 To Internal Condensate Switch (Optional) ET Sensor GT Sensor J3 See Table

Sensor Locations Gas Temperature Sensor (GT) - located on copper section of manifold (black wires) Evaporator Temperature Sensor (ET) - located on 3/8" Aluminum distributor tube (orange wires) EEV Stepper Motor Stepper Motor Tables - For use with Low and High Superheat Troubleshooting Table 1 - For use with FIG 1 Common Terminal to Terminal Measurement Gray Orange 46 ohms Gray Red 46 ohms Gray Yellow 46 ohms Gray Black 46 ohms Table 2 - For use with FIG 2 Common Terminal to Terminal Measurement Brown Blue 46 ohms Brown Yellow 46 ohms Red Orange 46 ohms Red White 46 ohms FIG 1 FIG 2 1 ORANGE 2 RED 3 YELLOW 4 BLACK 1 WHITE 2 YELLOW 3 ORANGE 4 BLUE 5 GRAY (common) 5 BROWN (common) 8 RED (common) 19 GAM5-SF-1D

Electronic Expansion Valve Test Note: Close Valve and Open Valve Tests are active in any mode of operation Test Pins: OPEN, CLOSE, TEST (See J4 on EVC Board) Close Valve Test - Touch CLOSE pin to TEST pin. EEV drives closed (5 seconds max) and stays closed for 1.5 minutes (90 seconds). 1) Status LED will be flashing. 2) Gauges should indicate suction pressure dropping. Valve is working. LPCO may trip. Note: The Close Valve Test will exit after 1.5 minutes (90 seconds) and will not reinitiate (requires a break and make to initialize). To clear faults stored in memory, apply a jumper between Close and Test pins for 10 seconds. Open Valve Test - Touch OPEN pin to TEST pin. EEV drives open (5 sec max) and stays open for 30 seconds. 1) Status LED will be flashing. 2) Temperature probe should indicate superheat falling. Valve is working. Note: If jumper is left on pins, the OPEN VALVE TEST will be cleared after 30 seconds and will not reinitiate (requires a break and make to reinitialize). Exit Test Mode - The Open Valve Test or Closed Valve Test can be cancelled by jumping to the opposite mode Test pin. The system will return to normal super heat control. SUBCOOLING ADJUSTMENT The following combinations should be charged to 8 degrees sub-cooling to maintain ratings. Indoor Unit Model No. GAM5A0A18M11SA GAM5A0A24M21SA GAM5A0B30M21SA GAM5A0B36M31SA GAM5A0C42M31SA GAM5A0C48M41SA GAM5A0C60M51SA Outdoor Unit Model No. 4A6B4018E1 4A6H5018E1 4A6B4024E1 4A6H5024E1 4A6B4030E1 4A6H5030E1 4A6B4036E1 4A6H5036E1 4A6B4042E1 4A6H5042E1 4A6B4048E1 4A6H5048E1 4A6B4049E1 4A6H5049E1 4A6B4060E1 4A6H5060E1 4A6B4061E1 4A6H5061E1 All other matches must be charged per the nameplate charging instructions. GAM5-SF-1D 20 The following combinations should be charged to 8 degrees sub-cooling to maintain ratings. Indoor Unit Model No. GAM5A0A18M11SA GAM5A0A24M21SA GAM5A0B30M21SA GAM5A0B36M31SA GAM5A0C42M31SA GAM5A0C48M41SA GAM5A0C60M51SA Outdoor Unit Model No. 4TWB4018E1 4TWR5018E1 4TWB4024E1 4TWR5024E1 4TWB4030E1 4TWR5030E1 4TWB4036E1 4TWR5036E1 4TWB4042E1 4TWR5042E1 4TWB4048E1 4TWR5048E1 4TWB4049E1 4TWR5049E1 4TWX5049E1 4TWB4060E1 4TWR5060E1 4TWB4061E1 4TWR5061E1 4TWX5061E1 All other matches must be charged per the nameplate charging instructions.

21 GAM5-SF-1D

HIGH SUPERHEAT Superheat above 30F at OD unit Start Here Verify that OD condenser coils are clean Verify line set is properly sized for application NO Is subcooling at the outdoor unit between 8-12F? YES Perform temperature sensor check Add refrigerant until subcooling reaches ~10F Is liquid line temperature at the indoor unit within 8F of outdoor liquid line temperature? NO Verify line set size and charge is correct Recheck superheat EEV and coil are working. Replace EVC Check operation YES Perform OPEN VALVE test at EVC. The system is running at maximum capacity and this may be causing the high superheat. Wait until the indoor temperature is less than 80F and check the superheat again. YES YES Does suction pressure go down? Perform CLOSE VALVE test at EVC. YES Does superheat drop below 30F? NO Is indoor temperature >85F? NO NO Ohm coil per Stepper Motor Tables Replace coil NO Is ohm reading correct? YES Replace EEV. Check operation GAM5-SF-1D 22

23 GAM5-SF-1D

GAM5-SF-1D 24

25 GAM5-SF-1D

NOTE: The fan control has a 90 second OFF delay that is factory set on. To turn this feature off, turn dip switch to 0 and cycle power to the unit. Turn comfort to FAN ON mode Constant Torque Motor Troubleshooting This terminal block is located on the motor. Look for labels below on the motor side of the connection. Motor does not run FIGURE 1 Turn off power. Check set screw position and motor bearings. Correct or replace as needed. Check operation NO Does blower wheel turn freely? YES High voltage should always be present. Correct high voltage wiring. NO Is ~230 VAC measured between terminals L & N on the motor? See Figure 1 FIGURE 2 Correct wiring. Check operation YES NO Is 24VAC measured from terminal 8(G) to terminal 9(BL) on the fan control? NO Is ~24 VAC measured between the wire connected to C on the motor and the wire connected to terminal 1 thru 5 on the motor? See Figure 2 YES Replace fan control. Check operation YES Replace motor. Check operation GAM5-SF-1D 26

27 GAM5-SF-1D

10/12 Trane 6200 Troup Highway Tyler, TX 75707 www.trane.com For more information contact your local dealer (distributor) The manufacturer has a policy of continuous product and product data improvement, and it reserves the right to change design and specifications without notice.