ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

Similar documents
OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

User s Information and Installation Instructions

T-Series Air Conditioner T15 Model

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

Owners Manual Refrigerated Air Dryer MHT SERIES

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

MAC N-407 Air-Cooled Chiller

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

Owners Manual UA75 TO UA1200 SERIES Refrigerated Air Dryer

T-Series Air Conditioner T20 Model

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

MACH N-407 Heat Pump Air-Cooled Chiller

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

GENESIS Air Conditioners. All Models INSTRUCTION MANUAL nvent Rev. K P/N

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

WineZone Ceiling Mount Ductless Split 15

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

AIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO.

T-Series Air Conditioner T53 Model

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

User s Information and Installation Instructions

A/C-HEATER SYSTEM - MANUAL

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN.

User s Information and Installation Instructions

User s Information/Installation Instructions

Installation Instructions

Commercial High-Efficiency Condensing Units

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

Condensing Unit Installation and Operating Instructions

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Air-Cooled Condensing Units with Compact Screw Compressors

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

A910.8A Remote Water Chiller, 8 GPH A A / A A-220V TECHNICAL ASSISTANCE TOLL FREE TELEPHONE NUMBER:

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Hoshizaki America, Inc.

Installation Instructions

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

R.A.S.E.R.S System. Installation Guide

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

CD30 / CD30E INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

IMPORTANT. HOSHIZAKI provides this manual primarily to assist qualified service technicians in the service and maintenance of the icemaker.

WKS 2200 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

KM-630MAH KM-630MWH KM-630MRH

PDF Created with deskpdf PDF Writer - Trial ::

OPERATION AND MAINTENANCE INSTRUCTIONS FOR ROOF TOP HEAT PUMPS AND CEILING PLENUMS

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

Installation Instructions

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Trouble Shooting Guide RAA, 1-phase (D3627)

MAC-120HE-03 Air-Cooled Chiller

Trouble Shooting Guide PAA, 1-phase (D3731)

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

Polar Air Dryer. Instructions Manual PDRCF PDRCF R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513

NEWGATE TECHNOLOGIES, INC.

Fig. 1 - Unit PHD4 and WPH4

WCH5**4. Product Specifications

1998 Expedition/Navigator Workshop Manual

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS

Heat Pump Water Heater. Table of Contents

KR Electrical Defrost Unit Coolers (PN E108318_E)

Trouble Shooting Guide FAA, 3-phase (D3631)

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

R-410A AFFINITY SERIES DEX DEY Ton

Installation and Operation Guide For

Installation Instructions Owner s Manual

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999

Refrigerant Recovery Unit, Model RRU134

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

Installation Instruction

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

TFFR01 MANUAL PORTABAL 12/24 VOLTS DC REFRIGERATOR / FREEZER.

Trouble Shooting Guide PWA, 3-phase (D10571)

OPERATION AND MAINTENANCE INSTRUCTIONS FOR ROOF TOP HEAT PUMPS AND CEILING PLENUMS

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

SWIMMING POOL & SPA HEAT PUMPS OWNERS OPERATIONAL MANUAL

Owner s Information Manual

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Installation Instructions

Paragon. Induced Draft, Counter Flow Optional Accessories

Transcription:

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER 2001829 OPERATIONS AND MAINTENANCE MANUAL Prepared by: 860 Douglas Way PO Box 530 Natural Bridge Station, VA 24579

1.0 SCOPE: This Operations and Maintenance Manual provides for the safe installation, operation and maintenance of the 2001829, Environmental Control Unit (ECU). 2.0 EQUIPMENT DESCRIPTION: The ECU provides heating, cooling and ventilation of the enclosed space created by the deployed shelter. It is powered by the 208VAC, three-phase 60 Hz trailer mounted generator set. The ECU is designed to provide proper heating or cooling over the ambient temperature range of 17 degrees to 120 degrees Fahrenheit. A thermostatic control that monitors return airflow is used to set and regulate temperatures. Airflow is directed to the shelter by way of insulated supply air ducts (see Section 6.2). Air is returned to the ECU via insulated return air ducts (see Section 6.2). 3.0 SAFETY 3.1 QUALIFIED PERSONNEL For the purposes of this Manual, a qualified person is one who is familiar with the installation and operation of the specific equipment, and the hazards involved. 3.2 SIGNAL WORDS AND LABELS Signal Words and Labels are used within this Manual. The words and symbols convey the following advice: 3.2.1 Danger: Danger refers to immediate hazards that will result in severe personal injury or possible death. The word Danger is displayed within a box and highlighted in bold text and precedes the instruction in a procedure. 3.2.2 Warning: Warning refers to a hazard or unsafe method or practice that may result in a severe personal injury or possible death. The word Warning is displayed within a box and highlighted in bold text and precedes the instruction in a procedure. 3.2.3 Caution: Caution refers to a hazard or unsafe method or practice that may result in equipment damage or personal injury. The word Caution is displayed within a box and highlighted in bold text and precedes the instruction in a procedure. 3.2.4 Important: Important refers to a hazard or unsafe method or practice that can result in equipment damage or related equipment damage. The word Important! is displayed and highlighted in bold text and precedes the instruction in a procedure. 2

3.3 GENERAL PRECAUTIONS: The following general precautions should be followed when performing any maintenance or service work on the ECU: Danger: Placing the power switch to the OFF position does not completely deenergize the unit. Danger: Disconnect ECU from power source before performing any maintenance or service work. Danger: Do not work under a unit suspended by a sling device. Danger: Do not use a heating torch on any part that contains refrigerant. Danger: Do not work on ECU in confined spaces. R-407C is an asphyxiant. Warning: Do not operate ECU without covers, guards and panels in place. Warning: Do not inhale refrigerant gas. Warning: Avoid contact of refrigerant gas to skin and mucous membranes. Warning: Do not touch heater elements. Severe burns may result. Caution: Do not direct compressed air towards skin. Caution: Do not use any extreme source of heat to thaw a frozen coil. Use a hair dryer or a 60-watt maximum light bulb to thaw a frozen coil. Important: Do not exceed 20 psi when using compressed air for cleaning. Important: The ECU is charged with R-407C refrigerant. Compressor oil must be 3MA- P.O.E. or equivalent. Important: Do not block the discharge of the condenser fan. Allow three feet for discharge. Important: Do not operate ECU with return air ducts closed. Important: Do not operate ECU with supply air ducts closed. Important: Do not exceed 20 psi when using water for cleaning. 3

4.0 OPERATION 4.1 MAJOR COMPONENTS: a) Compressor: The compressor is a hermetically sealed unit with thermal overload protection. The compressor is equipped with a soft start current limiting device with a starting delay of 64 seconds after start of the evaporator fan motor. A hot gas bypass system is used to minimize power fluctuations with compressor cycling. b) Supply Fan: The evaporator fan motor is a 208-Volts AC, 3 Phase 60 Hz, TEFC, NEMA Frame with normally closed overload protection. c) Condenser Fan: The condenser fan motor is a 208-Volts AC, 3 Phase 60 Hz, TEFC, NEMA Frame with normally closed overload protection controlled by system pressure. NOTE: Based on the temperature outside, the condenser fan may run continuously. d) Filter: The return air filter is a metalized permanent type filter. The filter is located behind the panel containing the return air duct transition. e) Refrigerant: The ECU uses R-407C, A1/A1 Safety Group, Class III refrigerant. f) Heater: The heaters are resistive strip type elements located behind the panel containing the supply air duct transitions. A high temperature cut-out protects the heaters. g) Coils: Coils are copper tubed with aluminum fins. 4.2 INITIAL SET-UP: Remove the Return and Supply Ducts from the Duct Transport Bags. Remove the Return and Supply Duct Covers from the ECU by releasing the catches at each transition. The covers may be stored using the Velcro straps on the sides and top of the ECU. Secure the Return and Supply Ducts to the transition using the same catches used to hold the covers. IMPORTANT WAIT 3 MINUTES BEFORE RESTARTING ECU AFTER SHUTDOWN. START AND SHUTDOWN ECU IN VENT MODE ONLY. 4

4.3 START-UP (Cool Mode): The following steps should be taken each time the ECU is started. Turn ECU circuit breaker to the ON position. Set the ECU Mode Selector Switch (S2) to the VENT position. Place ECU Power switch (S1) to the ON position. The circulating fan motor will turn on delivering air to the supply ducts providing ventilation. To cool, place the Mode Selector Switch (S2) in COOL position. Turn the thermostat counter-clockwise in the cooler direction. The compressor will start after a 1 minute time delay. The condenser fan motor will cycle on and off based on system pressure. 4.4 START-UP (Heat Mode): The following steps should be taken each time the ECU is started. Turn ECU circuit breaker to the ON position. Set the ECU Mode Selector Switch (S2) to the VENT position. Place ECU Power switch (S1) to the ON position. The circulating fan motor will turn on delivering air to the supply ducts providing ventilation. To heat, place the Mode Selector Switch (S2) in HEAT position. Turn the thermostat clockwise in the warmer direction. The heater elements will start to warm the air stream. Allow a few minutes for the heater elements to warm-up to operating temperature. 4.5 SHUTDOWN: The following steps should be taken each time the ECU is shutdown: a) Place the unit Mode Selector switch (S2) to the VENT position. b) Allow the ECU to run for 3 minutes. c) Place the Power switch (S1) to the OFF position. 5

4.6 ECU CONTROLS: The DEG Instrument Panel is equipped with a power on/off switch (S1), a Mode Selector Switch (S2) to manually set the ECU operating mode and a thermostat to monitor return air. The three modes are: HEAT: In the HEAT position, power is supplied to the ECU thermostat and fan motor. The heater elements will be energized as determined by the setting of the thermostat. VENT: In the VENT position, power shall be applied to the ECU. The evaporator fan will be energized to provide ventilation. COOL: In the COOL position, power is supplied to the ECU thermostat and fan motor. The compressor will be energized as determined by the setting of the thermostat. 6

5.0 MAINTENANCE: All ECUs must be inspected on a regular basis and condenser coils and filters cleaned when needed. Local conditions or severe environment applications may require frequent inspections and cleaning to ensure the ECU operates at peak efficiency. It is important to note that accumulations of dirt and debris may, particularly in desert conditions, cause erratic operation. See Section 8.0 for replacement part numbers. WARNING REFER TO SECTION 3.0 SAFETY PRIOR TO PERFORMING MAINTENANCE WORK IMPORTANT REFER TO SECTION 6.2 DIMENSIONAL DATA AND COMPONENT LOCATION FOR COMPONENT LOCATIONS 5.1 MONTHLY MANITENANCE: Inspect the condenser coil(s) for dirt and debris. If excessive dirt or debris is present, clean the fins with either steam or a non-corrosive solvent to remove oil, pollen, dust, and soil. Do not use a direct high-pressure blast over 20 psi as damage to the coil may occur. IMPORTANT DO NOT USE A DIRECT HIGH PRESSURE BLAST OVER 20 PSI AS DAMAGE MAY OCCUR TO THE COILS Check filter. If dirty replace or wash as necessary. 5.1.1 Filter Access: The return air filter is located behind the Return Air Duct Connector Panel (see Section 6.2). The Panel is secured to the ECU with quarter-turn fasteners. Use a 5/32 hex head wrench to turn the fasteners counter-clockwise to release the Panel. 5.2 QUARTERLY MAINTENANCE: With power off, manually operate the condenser fans to ensure free movement and check the motor bearings for wear. Ensure that all fan mounting hardware and wiring terminations are tight. Inspect the compressor and condenser fan motor contactors. If the contacts appear severely burned or pitted, replace the contactors. Check the heater connections. Ensure that all heater element mounting hardware and wiring terminations are tight. 7

5.2.1 Electrical Component Access: The electrical components are located behind access panels. The panels are located on each side of the ECU (see Section 6.2). Panels are secured to the ECU with quarter-turn fasteners. Use a 5/32 hex head wrench to turn the fasteners counter-clockwise to release the panels. 5.3 YEARLY MAINTENANCE: Apply power to the ECU. With the ECU operating in the cool mode, check and record the ambient temperature, compressor oil level, and compressor suction and discharge pressures. In addition, if the operating pressures indicate a problem of any kind, determine the system superheat and subcooling, and refer to Section 7.0 TROUBLE SHOOTING. 5.3.1 Compressor, Condenser, and Test Port Access: The Compressor, Condenser, and Test Ports are located behind the Compressor/Condenser Access Panel. The Panel is located on condenser fan end of the ECU (see Section 6.2). The panel is secured to the ECU with 5/16 fasteners. Use a 5/16 SAE wrench to remove the fasteners and release the Panel. 8

5.4 REPAIR SERVICE In the event of a compressor burnout or filter clogging, it is imperative that the ECU piping system is thoroughly cleaned of all refrigerant and oil, and new filter-driers are installed. It is further recommended that the refrigerant not be reused. Whenever the refrigerant side of the ECU s piping has been exposed to atmospheric pressure for a period of time longer than that necessary to repair and charge the system, PSI recommends replacing the filter drier(s). 6.0 TECHNICAL DATA 6.1 PHYSICAL DATA: ECU Designation 2001829 Nominal Capacity, BTU/hr 96,000 Operating Charge, lbs. of R-407C 15.0 Compressor Data Number of Refrigeration Circuits 1 Quantity 1 Nominal Horsepower 8 Condenser Coil Data Quantity 2 Evaporator Coil Data Quantity 1 Condenser Fan Data Quantity 1 Nominal Horsepower 1.5 Supply Fan Data Quantity 1 9

Nominal Horsepower 2.0 ECU Designation Total Weight Without Refrigerant, pounds Length, inches Width, inches Height, inches 2001829 630 56 7/8 34 1/2 44 1/2 10

6.2 DIMENSIONAL DATA AND COMPONENT LOCATION: Duct connection dimensions are for reference only. 11

6.3 ELECTRICAL DATA 6.3.1 Horsepower and Run-Load Amps: ECU 2001829 Qty. Nominal Horsepower FLA (each) Compressor 1 8 31.8 Condenser Fan 1 1.5 5.3 Supply Fan 1 2.0 6.5 12

6.3.2 Electrical Schematic Power and Controls Wiring: 13

7.0 TROUBLE SHOOTING WARNING REFER TO SECTION 3.0 SAFETY PRIOR TO TROUBLE SHOOTING ECU IMPORTANT ECU IS EQUIPPED WITH A TIME DELAY TO PREVENT COMPRESSOR DAMAGE. IF UNIT IS TURNED OFF AND THEN ON WITHIN A FEW MINUTES THE COMPRESSOR WILL NOT START IMMEDIATELY. THE CONDENSING FAN IS CONTROLLED BY SYSTEM PRESSURE AND MAY OR MAY NOT TURN CONTINUOUSLY. Symptom Unit doesn t start ECU doesn t produce cold air Water does not drain from unit. Water is running out from the bottoms of the doors. Water is on fan. Coil is icy or frosty Compressor doesn t run Cause Power source is off. Power switch is in Off position. Selector switch is not in Cool position. Thermostat is not properly set. Refrigerant charge is low. Unit has a refrigerant leak. Return air is already cold. High Pressure Switch is tripped. Compressor is faulty. Drain is clogged. Drain hose is kinked. Suction pressure is low. Evaporator coil is dirty. Filter is dirty. Ducts are closed. Selector switch is not in Cool position. Thermostat is not properly set. Head pressure is high. Contactor is faulty. High Pressure Switch is tripped. Compressor is faulty. 14

Heater doesn t work Supply fan doesn t run Condensing fan doesn t run Selector switch is not in Heat position. Thermostat is not properly set. Return air is already hot. Power source is off. Power switch is in Off position. Contactor is faulty. ECU Circuit Breaker is tripped. Head pressure is low. Contactor is faulty. Compressor is not operating. Light load conditions exist and Condensing fan is not required. 15

8.0 PARTS LIST Reference Designator Description Part Number K1 Phase Monitor 3001445-001 K2 Contactor, Supply Fan 3001454-001 K3 Soft Start, Compressor 3001948-001 K4 Soft Start, Condenser Fan 3001450-001 K5 Contactor, Elec. Heat 3001455-001 S1 Switch, on/off 3001446-001 S2 Switch, Mode 3001447-001 S3 Thermostats 3001468-001, 3001469-001 S5 Freeze stat 3001463-002 S6 Switch, High Pressure 3001464-001 S7 Switch, Low Pressure 3001465-001 S9 Switch, Fan Cycle 3001467-002 S10 Thermal Overload, Heater 3001478-001 E3 Timer 3000062-001 HR Heater 3001522-001 PS DC Power Supply 3001452-002 HGV Solenoid, Hot Gas 3001477-001 SF B1 Motor, Supply Fan 3001949-001 COMP B2 Compressor 3001350-001 COND B3 Motor, Condenser Fan 3001671-001 Air Filter Air Filter 3001428-002 16

17