Rod probe 11961Z. Technical Information. Conductive level limit detection Partially insulated rod probe for use in conductive liquids

Similar documents
Ultrasonic Level Measurement nivopuls FDU 10 S

Liquiphant T FTL20H. Technical Information

Functional safety manual Liquiphant M/S with FEL57 and Nivotester FTL325P

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals

Vibracon LVL-A* Level limit switch for liquids, compact design

Liquiphant S, Nivotester FDL60/61, FTL670

PROFIBUS-PA Display RID 261 PROFIBUS-PA

Supplementary Installation and Operating Instructions. Category II2G

OPTIBAR P 1010/2010 C Supplementary instructions

Level Electrode NRG NRG Original Installation Instructions English

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version

Inductive slot sensor

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version

Immersion heaters for ATEX/IECEx hazardous areas or in non-atex version

DSF xx15.xx xhv Ex-Atex Ex-Atex Certified Two wire Hall Effect Speed Sensor

PEPPERL+FUCHS GmbH

Leakage detection sensor

Connection. e. g. Pt100. reference limit. yellow Output I. Composition

MSM400 Ultrasonic Suspended Solids Monitoring and Control System

OilSET-1000 (12 VDC)

Intrinsically Safe Pressure Transmitters for installation in hazardous locations Models IS-20-S, IS-21-S, IS-20-F, IS-21-F WIKA Datasheet IS-20

Pressure sensors. Ex ia I / IIC T6 acc. to ATEX. Features. Description. Measuring ranges. Applications

Level instruments. Point level measurement - Capacitance switches. Pointek CLS100 5/9. Overview. Configuration

NRG NRG NRG NRG

itemp RTD TMT 187 itemp TC TMT 188 Temperature head transmitter

Technical Data. General specifications Switching element function Rated operating distance s n 4 mm

Mobrey MSP900SH Level and MSP900FH Flow Ultrasonic Transmitters

Conductivity Electrode LRG Original Installation Instructions English

Flame detector. The QRA4.U is for use with the following types of burner control:

C Note! LGI16... Burner Controls. Building Technologies

Level Measurement. Point level measurement Capacitance switches. Pointek CLS100. Overview. Configuration

Capacitive leakage detectors of the Leckmaster range for installation in normally dry rooms

Rinse connection adapter CPR 40

Hygro and Hygrothermal Transducers (Capacitive) for Air Conditioning Applications

Inductive Conductivity Measurement. Simultaneous display of conductivity/ resistance/salinity and temperature; large measurement symbol.

Level Measurement. Point level measurement - Capacitance switches. Pointek CLS100. 5/10 Siemens FI Overview.

Magnetic-Inductive Flow Velocity Sensor PIT. Device Description

Differential Pressure Transmitter deltabar S PMD 230/235 deltabar S FMD 230/630/633 with ma output signal

OPERATING INSTRUCTIONS MAXIMAT LW CX COMPACT LEAKAGE SENSOR

for relative humidity and temperature

OPTIBAR DP 7060 Supplementary Instructions

Technical Data. Dimensions

RTK Instruments Limited St James Business Park, Knaresborough, North Yorkshire, England. HG5 8PJ

DB5 Intrinsically Safe Sounder Type DB-5

Alarm system For oil-water separator

Junction boxes control boxes THU 93.1 THU 93.6 THU 94.1 THU 94.9 PTB 98 ATEX March 1999

GAS DETECTOR ST400EC PART.NO

Technical Data. Dimensions

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

QFM21... Duct sensors. Symaro. for relative humidity and temperature

Technical Data. Dimensions

Oil Leak Detector NAR300 System

Differential Pressure and Flow Meter Media 5 Indicator 160 PN 40

Technical Data. General specifications. Rated operating distance s n 5 mm

Survey of electrical equipment installed in hazardous areas on tankers

Micro/Ultra Filtration System StamoClean CAT 430

Technical Information Liquiline To Go CYM290 and Liquiline To Go Ex CYM291

LAE10 LFE10. Use. Series 02

MEAS CAL ALARM CONF APT2000 CC ENCLOSURE TYPE 2

Mobrey MCU900 Series Universal Control Unit

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature

Magnetic-Inductive Flow Velocity Sensor PIT. Installation and Operating Instructions

Micro/Ultra Filtration System StamoClean CAT 430

Level Electrode NRG Original Installation Instructions English

UV Flame Supervision System

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

Flame detector. The QRA4.U is for use with the following types of burner control:

for relative humidity and temperature

Operating Instructions Condumax CLS15/16/21

COMPACT FLAME CONTROLLER CFC 1000

Technical Data. Dimensions

Rotameter series 250 metal tube variable area flowmeter

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-i.

Flame Safeguards LFE10. Building Technologies HVAC Products

Prosonic S FDU90/91/91F/92/93/95/96

CA 134. Piezoelectric accelerometer. IECEx NEPSI TIIS KGS. » From the Vibro-Meter product line» Vibration monitoring over a wide temperature

Dräger Polytron 5100 EC Detection of toxic gases and vapors

Conductive Leakage detectors of the Leckstar range

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

Manual Power relay SR853

Duct Air Quality Sensors

Hygro and Hygrothermo Transducers (capacitive) for climatic applications

COMPACT FLAME CONTROLLER CFC 200 (Formerly 8.XX)

Installation Guide. EXGP Oxygen Analyzer System (ATEX) Interface Electronics Unit

Industrial Cast-in Circulation Heaters for ATEX/IECEx hazardous areas or in non-atex version

Data Sheet 220 LEVEL MONITOR. Supplied by. .com. Call us on +44 (0)

COMPACT FLAME CONTROLLER CFC 2000

Technical Information OUSAF44

SECTION INDUCTIVE CONDUCTIVITY ANALYZERS

RADAR LEVEL GAUGE SPECIAL SAFETY INSTRUCTION

Cable Glands. Description Introduction to Cable Glands 399. EEXe Series EEXe Series. A2F, E1FX/E2FX, E1FW/E2FW and T3 Series

Rosemount 3100 Series Ultrasonic Level Transmitters

CE110I. Piezoelectric accelerometer with integrated electronics. IECEx

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products

Technical Information OUSAF21

SET-2000 Hi Level/Oil

Technical Information OUSAF22

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature

Dräger Polytron 5100 EC Detection of toxic gases and vapors

Transcription:

Technical Information Rod probe 11961Z Conductive level limit detection Partially insulated rod probe for use in conductive liquids Application Conductive level limit detection in process or storage tanks for all kinds of liquids: - for conductivity as of 0.02 ms/cm - for temperatures from 200 C to 250 C - for pressures from 1 to 160 bar As overfill protection with line monitoring even in Ex-area Zone 0 For minimum or maximum detection in tanks As pump protection in pipes As capacitive probe, e.g. for overfill protection Can be used for two-point control Your benefits For aggressive medium thanks to corrosion-resistant materials for rod and insulation Can be used in steam boilers thanks to ceramic insulation resistant to steam and hot water Can be deployed particularly with high pressure or vacuum Subsequent probe length shortening possible WHG (German Water Resources Act) + ATEX II 1/2 G approval Can be connected to separate switching units FTW325, FTW470Z, FTW570Z, FTC325, FTC625 Safety thanks to line monitoring Long operating life and reliable function without wear since no moving parts in the tank TI325F/00/EN/05.10 71115356

Table of contents Function and system design..................... 3 Measuring principle................................... 3 Measuring system..................................... 3 Input...................................... 4 Measured variable.................................... 4 Measuring range (detection range)........................ 4 Input signal......................................... 4 Documentation............................. 12 Technical Information................................ 12 Operating Instructions................................ 12 Certificates........................................ 12 Output..................................... 4 Switching units...................................... 4 Output signal........................................ 4 Line monitoring...................................... 4 Power supply................................ 5 Electrical connection.................................. 5 Cable entry......................................... 5 Cable specifications................................... 5 Operating conditions.......................... 6 Installation.................................. 6 Installation instructions................................. 6 Shortening probe rod.................................. 6 Mounting in piping.................................... 7 Environment................................ 7 Ambient temperature range............................. 7 Storage temperature................................... 7 Degree of protection................................... 7 Electromagnetic compatibility............................ 7 Process.................................... 8 Medium temperature range............................. 8 Medium temperature limits............................. 8 Conductivity........................................ 8 Limiting medium pressure range......................... 8 Mechanical construction....................... 9 Design, dimensions................................... 9 Weight............................................. 9 Wetted materials..................................... 9 Fitted electrodes..................................... 10 Certificates and approvals..................... 10 CE mark.......................................... 10 Overfill protection................................... 10 Type of protection (ATEX)............................. 10 Ordering information......................... 11 Rod probe 11961Z................................... 11 2 Endress+Hauser

FTW325 PFM FTC325 Rod probe 11961Z Function and system design Measuring principle Measuring system Alternating voltage is supplied to the probe by means of a transmitter (e.g. Nivotester FTW325). As soon as the conductive liquid forms a connection to the partition and the sensor, a measurable current flows which causes the sensor to switch. The use of alternating voltage prevents corrosion on the probe rod and electrolytic corrosion of the medium. 11961Z probe in the liquid tank, Nivotester FTW or FTC level limit switch in the control room The measuring device consists of: At least one 11961Z probe A switching unit (e.g. FTW325 or FTC625) Controllers, switch transmitters or signal transmitters, e.g. process control systems PLC, relays etc. FTW325 * Δs FTW470Z, FTW570Z ** Δs FTW470Z 1 2 1 2 FTC325, FTC625 HTC17Z EC17Z 1 2 3 4 5 6 * For two independent level limits or a two-point control (Δs) ** For two independent level limits or two two-point controls independent of one another (Δs) or one level limit and one two-point control (Δs) FTW470Z/570Z: Phase-out 2006 HTC17Z: Phase-out 2007 L00-11961Zxx-14-05-xx-xx-002 Endress+Hauser 3

Input Measured variable Measuring range (detection range) Input signal Change in resistance between tank wall and probe rod caused by presence/absence of conductive product (limit value, binary). The measuring range depends on the probe mounting location. The probes can be max. 2000 mm long. Probe covered => A measurable current flows between the probe rod and tank wall Probe not covered => A measurable current does not flow between the probe rod and tank wall Output Switching units Nivotester FTW325, FTW470Z*, FTW570Z*, FTC325, FTC625 * Phase-out: 2006 Output signal Line monitoring! Note! Relay output with floating change-over contacts for level alarms; For more information, see Nivotester FTW325, FTW470Z, FTW570Z, FTC325 or FTC625; Technical Information An additional printed circuit board for line monitoring is installed in the housing for probes with WHG approval. It is always switched or connected between the rod and housing wall. It has to be removed if using switching units (transmitters) that do not support line monitoring. With Nivotester FTC325 and FTC625, line monitoring only takes place via the PFM signal. 4 Endress+Hauser

Electrical connection Power supply Standard + ATEX: WHG (with line monitoring): 2 terminals for core cross-section to 2.5 mm 2 in housing 2 threaded connections for cable lug in housing with 2 m captive cable (brown*) FTW325 ** Δs CH2 CH1 * (blue*) 9 MAX 8 MIN 7 * (brown*) FTW470Z/570Z *** (brown*) Δs CH2 CH1 * (blue*) d2 MAX z2 b2 MIN b4 d4 * z4 CH1 * (blue*) CH2 Δs HTC27Z EC16Z EC17Z 1 2 3 4 5 6 FTC325 ** FTC625 ** 12 + 11 * With line monitoring ** For two independent level limits or a two-point control (Δs) *** For two independent level limits or two two-point controls independent of one another (Δs) or one level limit and one two-point control (Δs) FTW470Z/570Z: Phase-out 2006 HTC27Z: Phase-out 2007 L00-11961Zxx-04-05-xx-en-003 Cable entry The cable gland Pg16 is suitable for cable diameters from 7 to 12 mm 2. Connect cores preferably with insulated cable lugs to the connections in the probe housing: - central connection for the probe rod, - lateral connection for the earth. A 2 m captive twin-core cable is supplied for line monitoring. Cable specifications Use usual commercial cable (25 Ω per core). The connecting cable must comply with the requirements at the place of deployment. Use a screened cable in the event of strong electromagnetic radiation. Endress+Hauser 5

Operating conditions Installation Installation instructions Mounting location Preferably vertical from above. In the case of lateral mounting, mount the probes with the tip of the probe pointing slightly downwards. Orientation Level limit detection for standard applications in metal tanks. 1* 2* max. 200 3* L00-11961Zxx-11-05-xx-xx-002 1* Sufficient clearance provided outside the tank so the probe can be inserted without the application of force. 2* A short probe (maximum length 200 mm) can also be installed laterally, preferably with the tip of the probe pointing slightly downwards, so that the liquid can drain off better and conductive build-up does not form. 3* If used in agitated liquids, probes over 0.5 m in length must be laterally supported by insulated brackets. Shortening probe rod! Note! The probe can be shortened to any length. - Do not damage the insulation at any other point - After shortening, remove insulation over at least 20 mm at the tip of the probe - No mechanical strain may be put on the probe when shortening the probe rod 6 Endress+Hauser

Mounting in piping L00-11375Zxx-11-05-xx-xx-001 Environment Ambient temperature range Depends on the fluid temperature (limited through permitted interior temperatures of the connection housing) Permitted interior temperatures of the connection housing: Standard: ATEX: WHG: Storage temperature 200 C +250 C 20 C + 65 C (with line monitoring) Degree of protection IP55 as per EN 60529 200 C +250 C, depends on the connecting cable 200 C +200 C, depends on the connecting cable 20 C + 65 C in housing; take fluid temperature into account! Electromagnetic compatibility For interference emission and interference immunity, see connected Nivotester FTW or FTC limit switch EMC test procedures, see TI241F/00/EN Endress+Hauser 7

Process Medium temperature range Standard: ATEX: WHG: 200 C +250 C, depends on the connecting cable 200 C +200 C, depends on application (capacitive/conductive), see certificate 20 C + 65 C (with line monitoring) Connection between fluid temperature and interior temperature of the connection housing depending on ambient temperature: T 1 260 T 1 240 220 Standard 200 180 ATEX T 2 100 80 60 40 20 // // // 0 200 180 40 20 0 20 40 60 80 20 40 WHG* 100 // 120 200 220 240 260 T 2 180 200 * With line monitoring L00-11961Zxx-05-05-xx-xx-001 Medium temperature limits Conductivity Limiting medium pressure range As above Min. 0.02 ms/cm, see limit switch connected Standard: Line pressure pe 160 bar, see graphic ATEX + WHG: Note explosion protection directives and information in the certificates pe bar 200 150 100 200 150 100 50 50 100 150 200 250 0 50 T C L00-11961Zxx-05-05-xx-xx-002 8 Endress+Hauser

Mechanical construction! Note! All dimensions in mm Design, dimensions ø36 22 AF 36 AF L max. 2000 46 approx. 92 79 20 50 ø26 G½A ø approx. 13 Pg16 Gasket to DIN 7603 Ni Fe 42 or Ni 99.6 Ceramic, glazed Ni Fe 42 or Ni 99.6 Rod 1.4571 (SS 316Ti) ø6.5 L00-11961Zxx-06-05-xx-en-001! Note! Length of partial insulation min. 20 mm shorter than the probe length. Please indicate the desired probe length in mm when ordering. Weight Wetted materials Rod 1 m in length 500 g Probe rod Corrosion-resistant steel 316Ti (1.4571) Process connections Corrosion-resistant steel 316Ti (1.4571) Partial insulation Glazed ceramic Surround for partial insulation Ni Fe 42 or Ni 99.6 Endress+Hauser 9

Seal Corrosion-resistant steel Fitted electrodes Rod probe Diameter without insulation: 6.5 mm Maximum rod length: 2000 mm Minimum rod length: 100 mm Length of non-insulated area (tip of rod): min. 20 mm Certificates and approvals CE mark Overfill protection Type of protection (ATEX) The device is in conformity with the statutory requirements of the EC Directives. Endress+Hauser confirms that the device has been tested successfully by applying the CE mark. WHG (German Water Resources Act) Conductive EC type-examination certificate TÜV 02 ATEX 1951 X Capacitive EC type-examination certificate PBT 98 ATEX 2215 X 10 Endress+Hauser

Ordering information Rod probe 11961Z 10 Approval A ATEX II 1/2 G EEx ia IIC T6, WHG P ATEX II 1/2 G EEx ia IIC T6 R Non-hazardous area S Non-hazardous area, WHG Y Special version 2 ATEX II 1/2 G EEx ia IIB T6, WHG 3 ATEX II 1/2 G EEx ia IIB T6 20 Application * C FTC470Z, FTC471Z R FTW325 S FTC325, FTC625 X Non-specified switching unit Y Special version 30 Process connection, material G1 Thread ISO228 G ½ A, 316Ti Y9 Special version 40 Metal parts at ceramic A Ni Fe 42 B Ni 99.6 Y Special version 50 Rod material B Rod 316Ti Y Special version 60 Length of probe L 1... mm L, can be shortened 2 500 mm L, can be shortened 3 1000 mm L, can be shortened 5... inch L, can be shortened 6 20 inch L, can be shortened 7 39 inch L, can be shortened 9 Special version 995 Marking 1 Tagging (TAG) 11961Z complete product designation * The device designation is required to assign the suitable certificate (conductive or capacitive) to the application. Only the conductive certificate is supplied with version X. Due to space restrictions, the device names of the switching units are not illustrated on the nameplate. Endress+Hauser 11

Documentation Technical Information Operating Instructions Certificates Nivotester FTW325 TI373F/00/EN Nivotester FTC325 TI380F/00/EN Nivotester FTC625 TI370F/00/EN Rod probe 11961Z KA241F/00/A6 Nivotester FTW325 KA199F/00/A6 Nivotester FTC325PFM KA221F/00/A6 Nivotester FTC625 KA194F/00/A6 General construction supervision approval Conductive level limit detection ZE043F/00/DE Capacitive level measurement ZE210F/00/DE Capacitive level limit detection ZE211F/00/DE Safety instructions (ATEX) Conductive level limit detection XA197F/00/A3 Capacitive level limit detection + level measurement XA024F/00/A3 Instruments International Endress+Hauser Instruments International AG Kaegenstrasse 2 4153 Reinach Switzerland Tel. +41 61 715 81 00 Fax +41 61 715 25 00 www.endress.com info@ii.endress.com TI325F/00/EN/05.10 71115356 CCS/FM+SGML 6.0 71115356