Appliance and Controller Electrical Installation Guide.

Similar documents
Installation and Operating Manual for the ProCon 16, 27, 47, 75 & 77 Wall Mounted Condensing Boiler Range.

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

ProCon Boiler Controller Commissioning Quick Reference Guide

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

Installation and Operating Manual for the ProCon HT 150 & 225 Floor Standing Condensing Boiler Range.

Installation and Operating Manual for the ProCon 47, 75 & 77 Wall Mounted Condensing Boiler Range

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

Installation and Operating Manual for the ProCon HT & HTP 150 & 225 Floor Standing Condensing Boiler Range. **RVS Controlled**

Contents. 1 General Appliance Type Single Units Cascade Manager Units Cascade Slave Units...

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating

RVL481. Heating Controller. including d.h.w. heating

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

Ultramax PB. Floor standing premix gas fired condensing boilers with outputs at 65, 85, 100 & 120kW BOILERS

Hamworthy. Wessex Modumax. High Efficiency, Fully Modulating Boilers Condensing & Non Condensing, Pre-mix, Gas Fired. Outputs 100kW to 750kW

RVA Cascade Controller for modulating gas-fired Boilers Basic Documentation

RVL470. Heating Controller. Use. Functions. Series B

Room Units and Sensors for Use in Heating Plants. Siemens Building Technologies HVAC Products SIGMAGYR. Type summary

Hamworthy. Purewell VariHeat

Sirius FS. Working towards a cleaner future

Installation and Operating Manual for the EcoStar 500 Oil Condensing Floor Standing Range Output Range kw

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controllers User manual. Building Technologies HVAC Products

RVL480. Heating Controller

RVP310. Heating Controller. Building Technologies HVAC Products

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit

Heating and D.h.w. Controller RVL482 Basic Documentation

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

PRELIMINARY EDITION

95% Hamworthy Fully Modulating, Low NOx, Stainless Steel, Condensing Modular Boilers. Wessex ModuMax mk3. New. Restyled with latest Siemens controls

Sirius WH. Working towards a cleaner future

Sirius FS Working towards a cleaner future. Floor Standing Condensing Gas Boilers. Installation, Operation & Maintenance Manual

Control Products & Systems OEM

RMG MK. II RMG Mk.II RS Mk.II RMG Mk.II RS Mk.II

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controller User Manual. Building Technologies HVAC Products

Boiler Sequence Controller

Hamworthy. Varmax. New. Fully modulating, low NOx, stainless steel, condensing boilers Natural Gas or LPG Outputs 120kW to 900kW

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation

Local Process Bus LPB

Stokvis R40 Boiler Gas-Fired Wall Hung Condensing

RVS46.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros 2 Zone controller User Manual. Building Technologies HVAC Products

Control Products & Systems OEM

Thision L. Wall mounted gas fired condensing boilers with individual unit outputs from 48kW to 145kW and multi-boiler cascade sets up to 1140kW

Floor standing boilers. RMG Mk.II RS Mk.II

GENERAL DESCRIPTION AND INSTRUCTIONS FOR KFG CONTROL

District heating controller for two heating circuits and d.h.w. according to Siemens specifications:

R40 (Evolution Range) Gas-Fired, Wall Hung Condensing Boiler Boiler Options & Systems Planner Manual

Use. Functions. Key function. Other functions

RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation

RVL479. Heating Controller. for use with a partner unit

Planner Documentation THISION L

Type summary Albatros 2

Quickheat 30 weather compensated boiler control

Installation and Operating Manual for the ProCon E 26 Wall Mounted Condensing Boiler Range

up to Seasonal efficienc (gross) y ErP Nat Gas 5:1 Part L LPG

DESIGN DATA THRs 2013

District heating controller

IMAX XTRA EL. 715kW FLOOR STANDING CONDENSING FEATURES AND BENEFITS

Boiler systems Upsilon Cascade. Innovation has a name.

Heating controller Lago

District heating controller

RVA Heating Circuit or Primary Controller Basic Documentation. Siemens Building Technologies Landis & Staefa Division

M116 / M450 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS. Type : B23 ATLANTIC 2000

Heating Controller. Building Technologies HVAC Products. Synco 700

PERTRONIC INDUSTRIES LTD F4-RMAX Installation Note

RVS13... RVS53... AVS75... AVS37... QAA75... QAA78... QAA55... Albatros2 Boiler controllers User Manual. Building Technologies HVAC Products

Linkam Scientific Instruments USER GUIDE PE120-AFM. Temperature Controlled Peltier Stage

District Heating Controller

STREBEL S-CB + Cascade Kits

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning

FEATURES AND BENEFITS. Up to 109.8% part load efficiency

Euron. Compact Wall Mounted Gas Fired Condensing Boilers and Combis with Outputs 24kW - 30kW BOILERS

FM458/CMC 930. Strategy module. Service instructions. For contractors. Read carefully prior to commissioning or service.

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

WALL-MOUNTED CONDENSING BOILERS WH 46 WH 65 INSTALLATION, OPERATION AND MAINTENANCE MANUAL

CPM, CPMSP Cascade header kits Installation, Commissioning and Maintenance Instructions

Hamworthy Fleet Vertical Floor Standing. Condensing Boilers Natural Gas Outputs 80kW to 1050kW 5 YEAR HEAT EXCHANGER WARRANTY

Hamworthy. Stratton Wall Hung. Stainless Steel Condensing Boilers Natural Gas or LPG Outputs 45kW to 100kW

Suggested Schematics with Control and Power Wiring details

Ca 6s and BCa 6s kw INSTALLATION AND OPERATING INSTRUCTIONS. Page 1 31/07/00

Hamworthy Fleet Horizontal Floor Standing. Condensing Boilers Natural Gas Outputs 40kW to 350kW 5 YEAR HEAT EXCHANGER WARRANTY

VARMAX TWIN. Instructions for installation, use and maintenance. GAS CONDENSING BOILER 550 to 900 kw with modulating burner for natural gas

FireNET Plus Wiring Instructions

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

ORENA BRAND CONVENTIONAL (ORENA Brand) CE

Installation Manual RINS1211-4

Cascade Sequencer. Control Installation and Operation Instructions. Infinite Energy Boiler Manual. Also read and follow: CS-IOM-1

Hamworthy. Stratton Wall Hung. Stainless Steel Condensing Boilers Natural Gas or LPG Outputs 45kW to 100kW

QAA Room Unit for Boiler Control with OpenTherm Interface Basic Documentation. Siemens Building Technologies Landis & Staefa Division

Aluminium range of condensing boilers. Works every time. Designed to meet carbon reduction targets. Lifetime service and support

BOSCH CONDENS 5000W ZSB18-2A

Stainless steel range of condensing boilers. Designed to meet carbon reduction targets. Lifetime service and support. Outputs from 50kW to 660kW

Wall Hung Condensing Boilers. Working towards a cleaner future. heating specialists

Mixer module VR 61. Operating and Installation Manual. Mixer module for VRC 430 / VRC 430f

Luna Platinum. Solutions for centralized heating systems installations P

Instruction Manual WARNINGS

RVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation

RVL47. Heating Controller. Installations Instructions. Installation

Planner Documentation R600 EVO

ADI CD CONDENSING BOILER

Transcription:

Appliance and Controller Electrical Installation Guide. MHG Heating Ltd Unit 4 Epsom Downs Metro Centre Waterfield Tadworth Surrey KT20 5LR Telephone 0845 6448802 Fax 0845 6448803 Email Info@mhgheating.co.uk www.mhgheating.co.uk

Page Intentionally Blank 2

Content Appliances Page ProCon 16 77 Wall Mounted Condensing Boilers (LMU64) 4 ProCon 75 & 77 Wall Mounted Condensing Boilers Cascade Manager (LMU64) 6 ProCon HT 150-225 Floor Standing Condensing Boilers (LMU64) 8 Boiler Controller Mounted Options AGU2.511 BMS Run & Fault Output & 0-10V or 0-20mA Input Clip 10 AGU2.500 Heating Zone 2 Pump & Mixing Valve Clip 11 OCI420 LPB Cascade & System Controller Communication Clip 13 Cascade, System & Room Controls RVA47 Cascade Manager Without Optional Housing 14 RVA47 Cascade Manager With Optional Housing 15 RVA63 Boiler and Zone Controller Without Optional Housing 17 RVA63 Boiler and Zone Controller With Optional Housing 19 RVA46 Zone Controller Without Optional Housing 22 RVA46 Zone Controller With Optional Housing 23 QAA73 Single Boiler Opentherm Room Unit 24 QAA70/50/10 PPS Cascade or System Controller Room Unit 25 Please note that this document is intended as a quick reference guide. Further detailed guidance should be sought from the respective boiler/controller technical manuals. 3

ProCon 16 77 Wall Mounted Condensing Boilers. Boiler Wiring Terminals Boiler Controller Mounted Terminals Tag Terminal Designation Terminal #s Voltage Screened Cable (Earthed Screening) RU 1 & 2 < 25V Yes QAA73 Opentherm Room Unit or Link to enable second heating zone time switch. (AGU2.500 Communication Clip required to control second heating zone pump/valve.) RT 3 & 4 < 25V Yes Heating Volt Free Enable. (Via Time Switch/Room Thermostat/BMS) AT 5 & 6 < 25V Yes BW 7 & 8 < 25V Yes Outside Air Sensor. (QAC34) (Mounted on North Facing Wall) (Parameter alteration required if outside air sensor not connected) Hot Water Sensor (QAZ36) or Volt Free Enable. (Via Time Switch/Calorifier Thermostat/BMS) (Parameter alteration required if Volt free enable used) BW/K3 10 Perm Live 11 Neutral 12 Switched Live 230V - Hot Water Charging Pump or 3 way Valve Output. (Max 1 Amp) (Parameter alteration required if charging pump used with 16 & 31 and if 3 way valve used with 47 & 75.) K2 13 Switched Live 14 Neutral 230V - Models 16 & 31 External Heating Pump. (Max 1 Amp) Models 47 & 75 Internal Boiler Pump. (Max 1 Amp) K1 16 Neutral 17 Switched Live 230V - Models 16 & 31 Internal Boiler Pump. (Max 1 Amp) Models 47 & 75 External Heating Pump. (Max 1 Amp) E 9, 15 & 18 - - Common Permanent Earth N 19 230V - Permanent Neutral L 20 230V - Permanent Live (Max 5 Amp) X10-03 - <25V Yes Safety Interlock Volt Free Enable (For use with ventilation interlocks/gas pressure switch etc.) For cascade control via a RVA47 cascade manager each boiler must be fitted with an OCI420 Clip. Refer to Page 13/14 for additional guidance. 4

Generic Single Boiler Hydraulic Configuration For BMS Run and Fault indication terminal allocation refer to the section titled, Boiler Controller Mounted Options. 5

ProCon 75 & 77 Wall Mounted Condensing Boilers Cascade Manager. Additional Wiring Terminals (This terminal rail is in addition to the standard rail.) Terminal Designation Tag Voltage Screened Cable (Earthed Screening) BW 230V - Hot Water Charging Pump Output. (Max 2 Amp) HK / ZB 230V - Heating Circuit Pump Output. (Max 2 Amp) H1 < 25V Yes RL < 25V Yes VL < 25V Yes BW < 25V Yes AF < 25V Yes RU < 25V Yes Enabling Input Volt Free Enable or 0-10Volt or Operation Changeover (M = Ground & H1 = Positive) Return Sensor (QAD21) (M = Ground & B70/B4 Positive) Flow Sensor (QAD21) (M = Ground & B10 Positive) Hot Water Sensor (QAZ21) or Volt Free Enable. (Via Time Switch/Calorifier Thermostat/BMS) (Parameter alteration required if Volt free enable used) (M = Ground & B3 Positive) Outside Air Sensor. (QAC34) (Mounted on North Facing Wall) (Parameter alteration required if outside air sensor not connected) (M = Ground & B9 Positive) Room Unit QAA70/50/10 (M = Ground & A6 Positive) Each boiler within the cascade including the master will have an OCI420 Communication Clip fitted. The LPB communication wiring must be wired (X41) between each OCI420 Communication Clip in parallel. 6

Generic Multiple Boiler Hydraulic Configuration For BMS Run and Fault indication terminal allocation refer to the section titled, Boiler Controller Mounted Options. 7

ProCon HT 150-225 Floor Standing Condensing Boilers. Boiler Wiring Terminals External Flow and return sensors (QAD21) are required for Cascade Manager Units only. The sensors must be wired to the terminal detailed below. These terminals are located on the top left of the boiler frame when viewed from the front. (These terminals are pre-wired on Standalone FS units.) Module Controller Mounted Safety Interlock Terminals (X10:03)(Low Voltage<25V) If required each module can be connected to an external safety device. A relay must be used to ensure separation of the voltages generated by each module controller. (X10:03) Tag RU H1 BW AF BUS Terminal Designation Terminal Screened Voltage #s Cable (Earthed Screening) A6 & MD < 25V Yes QAA70/50/10 PPS Room Unit H1 & M 0-10 Volt Input via BMS/Volt Free Enable via Room <25V Yes (Polarity Sensitive) Thermostat/BMS B3 & M Hot Water Sensor (QAZ21) or Volt Free Enable. < 25V Yes (Via Time Switch/Calorifier Thermostat/BMS) (Parameter alteration required if Volt free enable used) B9 & M < 25V Yes Outside Air Sensor. (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall)(Parameter alteration required if outside air sensor not connected) DB & MB (Polarity Sensitive) < 25V Yes Boiler Communication to Slave Boilers. (LPB DB Data & MB Ground) BW HK N Neutral Q3 Switched Live 11 Switched Live N Neutral 230V - Hot Water Charging Pump or 3 way Valve Output. (Max 2 Amp) 230V - Heating Pump Output (Max 2 Amp) 230V N Perm Neutral L Perm Live 230V - Permanent 240 Volt Supply (Max 10 Amp) VL B10 & M < 25V Yes System Flow Sensor (QAZ21/QAD21) (Standalone boilers have an internal sensor. Cascade manager boilers required an externally mounted sensor) RL M & B70 < 25V Yes System Return Sensor (QAZ21/QAD21) (Standalone boilers have an internal sensor. Cascade manager boilers required an externally mounted sensor) X10-03 - <25V Yes Safety Interlock Volt Free Enable (For use with ventilation interlocks/gas pressure switch etc.) 8

Generic Single HT Boiler Hydraulic Configuration Generic Multiple HT Boiler Hydraulic Configuration (Indicting the location of the system mounted Flow and Return Sensors) For Module BMS Run and Fault indication terminal allocation refer to the section titled, Boiler Controller Mounted Option. 9

Boiler Controller Mounted Options. AGU2.511 BMS Run & Fault 230V Outputs & 0-10Volt/0-20mA Input Clip. Terminal Designation Tag Switched Output Power Input X52-01 Output 1R X52-02 Output 2R X52-03 Output 3R X52-03 Control Input X51-01 Terminal #s 1 Live 2 Neutral 1 Live 2 Neutral 1 Live 2 Neutral Voltage 230V (Max) 230V (Max) 230V (Max) 3 Live 230V (Max) 1 Control Input 2 Ground 0-10V Or 0-20mA Power Supply from X01-02 for switched live outputs. Power Supply from BMS can replace power supply from X01-02 (<230V/0.5Amp) Programmable Output Available Options Boiler Fault Output. Or Boiler Operating Output or SSOV.(Safety Shut Off Valve) (Max 1 Amp) (Parameter amendment required) Programmable Output Available Options Boiler Fault Output. Or Boiler Operating Output or SSOV (Max 1 Amp) (Parameter amendment required) Programmable Output Available Options Boiler Fault Output. Or Boiler Operating Output or SSOV (Max 1 Amp) (Parameter amendment required) Programmable Control Input 0-10 Volt or 0-20mA Flow Temperature or % Power Control (Parameter amendment required) 10

Boiler Controller Mounted Options. AGU2.500 Heating Zone 2 Pump/Mixing Valve/Sensor Clip. Terminal Designation Tag Switched Output Power Input X52-01 Pump Output X52-02 Mixing Valve X52-03 Flow Sensor Input X51-01 Terminal #s 1 Live 2 Neutral 1 Live 2 Neutral 1 Close 2 Neutral 3 Open Voltage 230V 230V 230V Power Supply from X01-02 for switched live outputs. Heating Zone 2 Pump Outputs (Max 1 Amp) Heating Zone 2 Mixing Valve Outputs (Valve control is possible only when a zone flow sensor is connected) (Max 1 Amp) 1 & 2 <25V Heating Zone 2 Flow Sensor Inputs. (QAD36) 11

Generic Single Boiler (AGU2.500 Zoned) Hydraulic Configuration 12

Boiler Controller Mounted Options. OCI420 LPB Cascade Communication Clip. For use when control is provided via a RVA47 Cascade Manager or RVA63 Controller. Terminal Designation Tag Terminal #s LPB X41-01 1, DB LPB Data 2, MB LPB Ground (Polarity Sensitive) Screened Cable Yes LPB Control Communication From RVA47 Cascade Manager or RVA63 Boiler and zone controller. (Parameter amendment required) 13

RVA47 Cascade Manager. Manager Wiring Terminals.(Rear of controller)(housing available) Tag Terminal Designation Terminal #s Voltage Screened Cable (Earthed Screening) H1 6 (Polarity Sensitive) <25V Yes B70/ B4 0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS (M terminal used to create circuit) 5 <25V Yes System Return Sensor (QAD21) (To be positioned on boiler side of system Low Loss Header) Hot Water Sensor (QAZ21)/Volt Free Enable via Calorifier Thermostat/BMS (Parameter alteration required if Volt Free Enable Used) M M <25V Yes Ground Connection for all Sensors/Inputs B3 4 <25V Yes B10 2 <25V Yes System Flow Sensor (QAD21) (To be positioned on system side of system Low Loss Header) B9 1 <25V Yes Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall) MD M <25V Yes QAA70/50/10 Room Unit (PPS Ground) A6 - <25V Yes QAA70/50/10 Room Unit (PPS Data) MB M (Polarity Sensitive) <25V Yes Boiler Communication (LPB Ground connected in parallel to boiler mounted OCI420 Clips) DB - (Polarity Sensitive) <25V Yes Boiler Communication (LPB Data connected in parallel to boiler mounted OCI420 Clips)) Q3 3 230V - Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp) Q1 2 230V - Heating Pump Output (Max 2 Amp) F1 F 230V - Power Input for Heating and Hot Water Pump Outputs (To be linked to Live Input) L L 230V - Permanent Live (Max 6 Amp) N N 230V - Permanent Neutral For cascade control via a RVA47 cascade manager each boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance. 14

RVA47 Cascade Manager. Manager Wiring Terminals.(Housing) (Housing designed for use with additional RVA46 Zone controller) (RVA 46 Zone Controller wiring Information detailed later in document.) Terminal Designation Tag Voltage Screened Cable (Earthed Screening) DB <25V Yes Boiler Communication (LPB Data connected in parallel to boiler mounted OCI420 Clips)) MB <25V Yes Boiler Communication (LPB Ground connected in parallel to boiler mounted OCI420 Clips) A6 <25V Yes QAA70/50/10 Room Unit (PPS Data) MD <25V Yes QAA70/50/10 Room Unit (PPS Ground) B9 <25V Yes Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall) M <25V Yes Ground Connection for all Sensors/Inputs B10 <25V Yes System Flow Sensor (QAD21) (To be positioned on system side of system Low Loss Header) B3 <25V Yes B70/ B4 Hot Water Sensor (QAZ21)/Volt Free Enable via Calorifier Thermostat/BMS (Parameter alteration required if Volt Free Enable Used) <25V Yes System Return Sensor (QAD21) (To be positioned on boiler side of system Low Loss Header) H1 <25V Yes 0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS Q1 230V - Heating Pump Output (Max 2 Amp) Q3 230V - Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp) N 230V - Permanent Neutral PE - - Permanent Earth L 230V - Permanent Live (Max 6 Amp) (All M Terminals are Internally Linked) For cascade control via a RVA47 cascade manager each boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance. 15

Generic Multiple Boiler RVA47 Controlled Hydraulic Configuration Outside Air Sensor QAC32 Up to 12 ProCon Boilers In Cascade RVA47 Cascade Controller QAA70/50/10 Heating Zone LPB Communication to each boiler via an OCI clip module. Zone Pump Hot Water Primary Pump Flow Sensor QAD21 Return Sensor QAD21 Hot Water Sensor QAZ21 Component Control Capability of RVA47 16

RVA63 Boiler and Zone Controller. Manager Wiring Terminals.(Rear of controller)(housing available) Tag Terminal Designation (Low Voltage Terminals) Terminal #s Voltage Screened Cable (Earthed Screening) MD - <25V Yes Zone 2 QAA70/50/10 Room Unit (PPS Ground) A7 - <25V Yes Zone 2 QAA70/50/10 Room Unit (PPS Data) B12 3 <25V Yes Zone 2 Flow Sensor (QAD21/26) (To be positioned on Zone side of 3 way mixing valve) M M <25V Yes Ground Connection for all Sensors/Inputs B8 1 <25V Yes Flue Gas Sensor (Not Used) B31/ H2/ B41 4 (Polarity Sensitive) <25V Yes Volt Free Enable via Room Thermostat/BMS B1 3 <25V Yes Zone 1 Flow Sensor (QAD21/26) (To be positioned on Zone side of 3 way mixing valve) H1 6 (Polarity Sensitive) <25V Yes 0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS B2 5 <25V Yes Boiler Sensor (Not Used) B3 4 <25V Yes Hot Water Sensor (QAZ21)/Volt Free Enable via Calorifier Thermostat/BMS (Parameter alteration required if Volt Free Enable Used) B9 1 <25V Yes Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall) MD M <25V Yes Zone 1 QAA70/50/10 Room Unit (PPS Ground) A6 - <25V Yes Zone 1 QAA70/50/10 Room Unit (PPS Data) MB M (Polarity Sensitive) <25V Yes Boiler Communication (LPB Ground connected in parallel to boiler mounted OCI420 Clip or RVA47 Manager) DB - (Polarity Sensitive) <25V Yes Boiler Communication (LPB Data connected in parallel to boiler mounted OCI420 Clip or RVA47 Manager) For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance. 230 Volt Terminals shown on following page. 17

RVA63 Boiler and Zone Controller. Manager Wiring Terminals.(Rear of controller)(housing available) Terminal Designation (230 Volt Terminals) Tag Terminal #s Voltage Y6-230V Zone 2 Mixing Valve Closing Output (Max 2 Amp) Y5-230V Zone 2 Mixing Valve Opening Output (Max 2 Amp) F3-230V Power Input for Zone 2 Valve Outputs (To be linked to Live Input) Q6 3 230V Zone 2 Pump Output (Max 2 Amp) Q2 2 230V Zone 1 Pump Output (Max 2 Amp) F6 F 230V Power Input for Zone Pumps Output (To be linked to Live Input) Y2 3 230V Zone 1 Mixing Valve Closing Output (Max 2 Amp) Y1 2 230V Zone 1 Mixing Valve Opening Output (Max 2 Amp) F2 F 230V Power Input for Zone 1 Valve Outputs (To be linked to Live Input) Q3/Y 3 3 230V Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp) F1 F 230V Power Input for Hot Water Pump/Valve Output (To be linked to Live Input) K5 4 230V Burner Enable Output Stage 2 (Not Used) F5 F 230V Power Input Burner Enable Stage 2 (Not Used) K4 2 230V Burner Enable Stage 1 (Not Used) F4 F 230V Power Input Burner Enable Stage 1 (Not Used) L L 230V Permanent Live (Max 6 Amp) N N 230V Permanent Neutral For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance. 18

RVA63 Boiler and Zone Controller. Manager Wiring Terminals. (Housing) Tag Terminal Designation (Low Voltage Terminals) Voltage Screened Cable (Earthed Screening) DB <25V Yes Boiler Communication (LPB Ground connected in parallel to boiler mounted OCI420 Clip or RVA47 Manager) M <25V Yes Boiler Communication (LPB Data connected in parallel to boiler mounted OCI420 Clip or RVA47 Manager) A6 <25V Yes Zone 1 QAA70/50/10 Room Unit (PPS Data) M <25V Yes Zone 1 QAA70/50/10 Room Unit (PPS Ground) B9 <25V Yes Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall) M <25V Yes Ground Connection for all Sensors/Inputs B3 <25V Yes Hot Water Sensor (QAZ21)/Volt Free Enable via Calorifier Thermostat/BMS (Parameter alteration required if Volt Free Enable Used) B2 <25V Yes Boiler Sensor (Not Used) H1 <25V Yes 0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS B7 - - Not Used with RVA63 B1 <25V Yes Zone 1 Flow Sensor (QAD21) (To be positioned on Zone side of 3 way mixing valve) B31/ H2/ B41 <25V Yes Volt Free Enable via Room Thermostat/BMS B8 <25V Yes Flue Gas Sensor (Not Used) B12 <25V Yes Zone 2 Flow Sensor (QAD21) (To be positioned on Zone side of 3 way mixing valve) B4 - - Not Used with RVA63 M <25V Yes Ground Connection for all Sensors/Inputs M <25V Yes Zone 2 QAA70/50/10 Room Unit (PPS Ground) A7 <25V Yes Zone 2 QAA70/50/10 Room Unit (PPS Data) (All M Terminals are Internally Linked) For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance. 230 Volt Terminals shown on following page. 19

RVA63 Boiler and Zone Controller. Manager Wiring Terminals. (Housing) Terminal Designation (230 Volt Terminals) Tag Voltage K6 - Not Used with RVA63 Y6 230V Zone 2 Mixing Valve Closing Output (Max 2 Amp) Y5 230V Zone 2 Mixing Valve Opening Output (Max 2 Amp) N 230V Permanent Neutral Q6 230V Zone 2 Pump Output (Max 2 Amp) Q2 230V Zone 1 Pump Output (Max 2 Amp) N 230V Permanent Neutral Y2 230V Zone 1 Mixing Valve Closing Output (Max 2 Amp) Y1 230V Zone 1 Mixing Valve Opening Output (Max 2 Amp) Q3/Y 3 230V Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp) PE - Permanent Earth N 230V Permanent Neutral L1 230V Permanent Live (Max 6 Amp) K5 230V Burner Enable Output Stage 2 (Not Used) F5 230V Power Input Burner Enable Stage 2 (Not Used) K4 230V Burner Enable Stage 1 (Not Used) For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance. 20

Generic Single Boiler RVA63 Controlled Hydraulic Configuration RVA47 Cascade Controller Outside Air Sensor QAC32 RVA63 Controller LPB Communication to each boiler via OCI Clip Modules LPB Single Boiler Control with OCI420 Clip Heating Zone 1 Heating Zone 2 QAA70/50/10 QAA70/50/10 Zone 1 Pump Hot Water Primary Pump Zone 2 Pump Mixing Valve Hot Water Sensor QAZ21 Mixing Valve Zone 1 Flow Sensor QAD26 Zone 2 Flow Sensor QAD26 Component Control Capability of RVA63 21

RVA46 Zone Controller. Controller Wiring Terminals.(Rear of controller)(housing available) Tag Terminal Designation Terminal #s Voltage Screened Cable (Earthed Screening) H1 6 <25V Yes Volt Free Enable via Room Thermostat/BMS M M <25V Yes Ground Connection for all Sensors/Inputs B1 2 <25V Yes Zone Flow Sensor (QAD21) (To be positioned on Zone side of 3 way mixing valve) B9 1 <25V Yes Zone Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall) (Not required if using RVA47 O/S Sensor) MD M <25V Yes Zone QAA70/50/10 Room Unit (PPS Ground) A6 - <25V Yes Zone QAA70/50/10 Room Unit (PPS Data) MB M (Polarity Sensitive) <25V Yes DB - (Polarity Sensitive) <25V Yes RVA47/63 Communication (LPB Ground connected in parallel to RVA47 Manager or RVA63 Zone controller) RVA47/63 Communication (LPB Data connected in parallel to RVA47 Manager or RVA63 Zone controller) Y2 3 230V - Mixing Valve Closing Output (Max 2 Amp) Y1 2 230V - Mixing Valve Opening Output (Max 2 Amp) F2 1 230V - Power Input for Zone Valve Outputs (To be linked to Live Input) Q2 2 230V - Zone Pump Output (Max 2 Amp) F6 F 230V - Power Input for Zone Pump Output (To be linked to Live Input) L L 230V - Permanent Live (Max 6 Amp) N N 230V - Permanent Neutral 22

RVA46 Zone Controller. Controller Wiring Terminals.(Housing) (Housing designed for use with primary RVA47 Cascade Manager.) (RVA 47 Cascade Manager wiring Information detailed earlier in document.) Terminal Designation Tag Voltage Screened Cable (Earthed Screening) A6 <25V Yes Zone QAA70/50/10 Room Unit (PPS Data) MD <25V Yes Zone QAA70/50/10 Room Unit (PPS Ground) B9 <25V Yes Zone Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall)(Not required if using RVA47 O/S Sensor) M <25V Yes Ground Connection for all Sensors/Inputs B1 <25V Yes Zone Flow Sensor (QAD21) (To be positioned on Zone side of 3 way mixing valve) H1 <25V Yes Volt Free Enable via Room Thermostat/BMS Q2 240V - Zone Pump Output (Max 2 Amp) Y1 240V - Mixing Valve Opening Output (Max 2 Amp) Y2 240V - Mixing Valve Closing Output (Max 2 Amp) (All M Terminals are Internally Linked) 23

QAA73 Single Boiler Opentherm Room Units Room Unit Mounting Plate Wiring Terminals Terminal Designation Terminal #s Voltage Screened Cable (Earthed Screening) 1 & 2 <25V Yes Opentherm communication to Single Boiler Installation 3 & 4 - - Not Used 5 & 6 - - Not Used 24

QAA70/50/10 PPS Cascade or System Controller Room Units Room Unit Mounting Plate Wiring Terminals Terminal Designation Terminal #s Voltage Screened Cable (Earthed Screening) D1 & D2 PPS communication to RVA47/46/63 <25V Yes Controlled Installation D 3 & D4 Tamperproof QAW44 Remote Sensor or Volt <25V Yes Free Enable D5 & D6 - - Not Used 25

NOTES 26