SERVICE MANUAL MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-F.

Similar documents
SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

SERVICE MANUAL MUZ-D30NA / - MUZ-D36NA / - MUY-D30NA / - MUY-D36NA / - OUTDOOR UNIT. No. OBH502. Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA OUTDOOR UNIT. No. OBH543. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Models HFC

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Wireless type Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

SERVICE MANUAL MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA - U1 MSZ-GL18NA - U1 MSZ-GL24NA - U1

MSZ-GE06NA- 8, 9 MSZ-GE09NA- 8, 9 MSZ-GE12NA- 8, 9 MSZ-GE15NA- 8, 9 MSZ-GE18NA- 8, 9

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E

SERVICE MANUAL MSZ-HM09NA MSZ-HM12NA MSZ-HM15NA MSZ-HM18NA MSZ-HM24NA INDOOR UNIT. No. OBH746 REVISED EDITION-B. Models

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629.

SERVICE MANUAL MUZ-GE50VA - E1 MUZ-GE50VAH - E1 MUZ-GE60VA - E1 MUZ-GE71VA - E1

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

SERVICE MANUAL MUZ-GB50VA - MUZ-GB50VA - E2 OUTDOOR UNIT. No. OB455 REVISED EDITION-D. Wireless type Models HFC

SERVICE MANUAL MSZ-GE22VA - E1 MSZ-GE25VA - E1 MSZ-GE35VA - E1 MSZ-GE42VA - E1 MSZ-GE50VA - E1 MSZ-GE60VA - E1 MSZ-GE71VA - E1 INDOOR UNIT. No.

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL INDOOR UNIT

1 TECHNICAL CHANGES. MUZ-A09NA MUZ-A09NA - 1 MUZ-A09NA - U1 MUZ-A09NA - U2 1. Refrigerant system diagram has been changed.

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy

MUZ-EF25VE - E1 MUZ-EF25VEH - E1 MUZ-EF35VE - E1 MUZ-EF35VEH - E1 MUZ-EF42VE - E1 MUZ-EF50VE - E1 Indoor unit service manual MSZ-EF VE Series (OBH589)

SERVICE MANUAL MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA INDOOR UNIT. No. OBH501. Wireless type Models

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE INDOOR UNIT. No. OBH623. Models SPLIT-TYPE AIR CONDITIONERS

1. INDOOR UNITS... MSZ-FH-3 2. OUTDOOR UNITS... MSZ-FH-4 3. SYSTEM... MSZ-FH-5

SERVICE MANUAL INDOOR UNIT. No. OBH788

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE MSZ-FH25VE2 MSZ-FH35VE2 MSZ-FH50VE2 INDOOR UNIT. No. OBH623. Models

SERVICE MANUAL INDOOR UNIT MFZ-KA25VA - MFZ-KA50VA - MFZ-KA35VA - No. OB409. Models. Revision E: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-E

SERVICE MANUAL MSZ-DM25VA - E1, ER1 MSZ-DM35VA - E1, ER1 INDOOR UNIT. No. OBH750. Models

SERVICE MANUAL MSZ-HC25VA - E1 MSZ-HC35VA - E1 MSZ-HC35VA - E2 MSZ-HC35VAB - E1 MSZ-HC35VAB - E2 INDOOR UNIT. No. OBH466. Models

SERVICE MANUAL MS-GF20VA MS-GF25VA MS-GF35VA MS-GF50VA MS-GF60VA MS-GF80VA INDOOR UNIT. No. OBH621 REVISED EDITION-A. Models

SUZ-KA25VA2.TH SUZ-KA35VA2.TH SUZ-KA50VA2.TH SUZ-KA60VA2.TH SUZ-KA71VA2.TH

TECHNICAL & SERVICE MANUAL SUZ-SA71VA.TH. R410A Outdoor unit SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. May 2014 HFC. No.OCH561 R410A CONTENTS

SUZ-SA71VA3.TH SUZ-SA100VA2.TH

SERVICE MANUAL MFZ-KA25VA - MFZ-KA35VA - MFZ-KA35VA - E1. Wireless type Models FLOOR-TYPE, HEAT PUMP AIR CONDITIONERS. No.

SERVICE MANUAL MLZ-KA25VA - MLZ-KA35VA - MLZ-KA50VA - E1 INDOOR UNIT. No. OBH483. Ceiling cassette type Models

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy MUZ-GA35VAH - E1

SERVICE MANUAL MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG OUTDOOR UNIT. No. OBH767. Models HFC R32

SERVICE MANUAL OUTDOOR UNIT. No. OBH789

TECHNICAL & SERVICE MANUAL. Ceiling Concealed

SERVICE MANUAL MSC-A07YV - (WH) MSC-A09YV - (WH) MSC-A12YV - (WH) HFC. Wireless type Models

SERVICE MANUAL MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 INDOOR UNIT. No. OBH529. Models

SERVICE MANUAL MUCFH-GA35VB - MUCFH-GA50VB - MUCFH-GA60VB - E1. Wireless type Models HFC FLOOR AND CEILING TYPE AIR CONDITIONERS. No.

Submittal Data: LIVS09HP230V1B. Job Name Location Date. Submitted To. Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System

Submittal Data: VIR09HP115V1B Job Name Location Date. Submitted To. Innovative Ductless solutions 9,000 BTU/H (115V) Wall Mounted Heat Pump System

Submittal Data: VIR12HP230V1B. Job Name Location Date. Submitted To

Submittal Data: VIR24HP230V1B. Job Name Location Date. Submitted To

SERVICE MANUAL MUH-GA50VB - MUH-GA60VB - MUH-GA80VB - E1. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No. OB368 R410A CONTENTS

Part 3 Troubleshooting

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

SERVICE MANUAL MUCFH-GA35VB - MUCFH-GA50VB - MUCFH-GA60VB - E1 OUTDOOR UNIT. No. OB381. Models HFC

Power Input (Max) 1,500 W Dehumidification 1.7 pt/hr HSPF 10.5 COP 4.2 Compressor Type DC Inverter Driven 2-Stage Rotary Heating at 17 F FLA 8.

DESIGN & TECHNICAL MANUAL

SERVICE MANUAL MSC-GA20VB - (WH) MSC-GA25VB - (WH) MSC-GA35VB - (WH) Wireless type Models

DESIGN & TECHNICAL MANUAL

Revision C: Specification has been corrected. The value of "Moisture removal" for MSZ-GE24NA and MSY-GE24NA has been corrected. [2.7 pt.

DESIGN & TECHNICAL MANUAL

3.2 E1 Outdoor Unit PCB Abnormality E4 Actuation of Low Pressure Sensor E5 Compressor Motor Lock 3 52

MUH-24RV - MSH-30RV -

SERVICE MANUAL MLZ-KP25VF MLZ-KP35VF MLZ-KP50VF INDOOR UNIT. No. OBH801. Models

SERVICE MANUAL MUH-GA50VB- MUH-GA50VB - MUH-GA60VB - MUH-GA80VB - E1 OUTDOOR UNIT. No. OB368 REVISED EDITION-B. Wireless type Models HFC.

SERVICE MANUAL MUH-A18WV - MUH-A24WV - MUH-A30WV - E1. Wireless type Models HFC

SERVICE MANUAL MUX-A22WV - E1 HFC. Multi system type Model SPLIT-TYPE, AIR CONDITIONER. No. OB318 R410A CONTENTS. Revision A: MUX-A22WV -

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

SERVICE MANUAL. Wireless type Models MSZ-A09RV - (WH) MUZ-A09RV - MSZ-A12RV - (WH) MUZ-A12RV - E1 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

DESIGN & TECHNICAL MANUAL

TECHNICAL & SERVICE MANUAL

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

SERVICE MANUAL MXZ-2A40VA - MXZ-2A52VA - MXZ-3A54VA - MXZ-3A54VA - MXZ-4A71VA - MXZ-4A71VA - MXZ-4A80VA - E1 OUTDOOR UNIT. No. OB377 REVISED EDITION-A

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL

SERVICE MANUAL OUTDOOR UNIT MUZ-GA25VA - MUZ-GA25VA - MUZ-GA25VA - MUZ-GA25VA - MUZ-GA35VA - MUZ-GA35VA - MUZ-GA25VA(H)- MUZ-GA25VAH E4 MUZ-GA25VAH -

SUZ-A09VR.TH SUZ-A12VR.TH SUZ-A18VR.TH SUZ-A24VR.TH

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

13 SEER HEAT PUMPS. Featuring Earth-Friendly R-410A Refrigerant 13PJL SERIES. Features Coils constructed with copper tubing and enhanced aluminum

15A 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

TECHNICAL DATA & SERVICE MANUAL

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

Submittal Data: UMAT48HP230V1AF. Job Name Location Date. Submitted To

Product Data INDUSTRY LEADING FEATURES / BENEFITS

15A Operating Range Communication Wire Size 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA

13 SEER CONDENSING UNITS

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW1 AOU12RLFW1 ASU 9RLF1 ASU12RLF1 R410A

SERVICE MANUAL. Inverter Wall Mounted Single Split. MODELS Cooling Only. Heatpump SM-5WM-Y-NA-B1

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: CAF94R5 CAF124R5 CAF94R

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

SUBMITTAL DATA: MSZ-FH06NA & MUZ-FH06NA 6,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM. Electrical Power Requirements. Indoor / Outdoor A 1 / 11

DESIGN & TECHNICAL MANUAL

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338

EDUS Heat Pump - D-Series

Transcription:

Revision F: The descriptions of the expansion valve coil have been corrected. (10-4.) Some descriptions have been modified. Please void OBH543 REVISED EDITION-E. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 REVISED EDITION-F Models MUZ-FE09NA MUZ-FE09NA - 1 MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA Indoor unit service manual MSZ-FE NA Series (OBH542) CONTENTS MUZ-FE09NA MUZ-FE12NA MUZ-FE09NA - 1 MUZ-FE12NA1 MUZ-FE09NAH MUZ-FE12NAH NOTE: RoHS compliant products have <G> mark on the spec name plate. 1. TECHNICAL CHANGES 2 2. PART NAMES AND FUNCTIONS 3 3. SPECIFICATION 4 4. OUTLINES AND DIMENSIONS 6 5. WIRING DIAGRAM 7 6. REFRIGERANT SYSTEM DIAGRAM 9 7. DATA 11 8. ACTUATOR CONTROL 18 9. SERVICE FUNCTIONS 19 10. TROUBLESHOOTING 19 11. DISASSEMBLY INSTRUCTIONS 38 PARTS CATALOG (OBB543) TM

Use the specified refrigerant only Never use any refrigerant other than that specified. Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions. Revision A: MUZ-FE18NA has been added. Revision B: MUZ-FE09NA - 1 and MUZ-FE12NA1 have been added. Revision C: Specification has been corrected. [Capacity Rated Capacity Rated (Maximum), Power consumption Rated Power consumption Rated (Maximum)] Revision D: MUZ-FE09NAH and MUZ-FE12NAH have been added. Revision E: The formula for calculating the additional refrigerant charge has been corrected. Revision F: The descriptions of the expansion valve coil have been corrected. (10-4.) Some descriptions have been modified. 1 TECHNICAL CHANGES MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA 1. New model MUZ-FE09NA MUZ-FE09NA - 1 MUZ-FE12NA MUZ-FE12NA1 1. Compressor has been changed. 2. Inverter P.C. board has been changed. MUZ-FE09NA - 1 MUZ-FE12NA1 MUZ-FE09NAH MUZ-FE12NAH 1. Defrost heater has been added. 2. Inverter P.C. board has been changed. 2

2 PART NAMES AND FUNCTIONS MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH Air inlet (back and side) Piping Drain hose Air outlet Drain outlet MUZ-FE18NA Air inlet (back and side) Piping Drain hose Air outlet Drain outlet 3

3 SPECIFICATION Outdoor unit model MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA Capacity Cooling 1 Btu/h 9,000 (2,800~9,000) 12,000 (2,800~12,000) 18,000 (8,200~25,200) Rated (Minimum~Maximum) Heating 47 1 Btu/h 10,900 (3,000~18,000) 13,600 (3,000~21,000) 21,600 (7,500~29,700) Capacity 12NA 8,300(13,600) Heating 17 2 Btu/h 6,700 (12,500) Rated (Maximum) 12NA1 7,900(13,600) 11,700 (21,600) Power consumption Cooling 1 W 580 (160~650) 930 (160~960) 1,270 (570~2,280) Rated (Minimum~Maximum) Heating 47 1 W 710 (150~2,250) 950 (150~2,250) 1,540 (520~2,420) Power consumption 12NA 800(1,780) Heating 17 2 W 650 (1,730) Rated (Maximum) 12NA1 750(1,780) 1,240 (2,620) EER 1 [SEER] 3 Cooling 15.5 [26.0] 12.9 [23.0] 14.2 [20.2] 12NA 10.6 HSPF IV 4 Heating 10.0 12NA1 10.5 10.3 12NAH 10.1 COP Heating 1 4.50 4.20 4.11 Power supply V, phase, Hz 208/230, 1, 60 Max. fuse size (time delay) A 15 20 Min. circuit ampacity A 12 17.1 Fan motor F.L.A 0.56 0.93 09NA 12NA SNB130FQAH Model 09NA - 1, SNB172FQKMT Compressor 09NAH SNB130FQBHT 12NA1, 12NAH R.L.A 8.6 12.9 L.R.A 10.8 16.1 Refrigeration oil L (Model) 0.45 (NEO22) 0.40 (FV50S) Refrigerant control Linear expansion valve Sound level 1 Cooling db(a) 48 48 55 Heating db(a) 49 49 55 Defrost method Reverse cycle W in. 31-1/2 33-1/16 Dimensions D in. 11-1/4 13 H in. 21-5/8 34-5/8 Weight Ib. 80 119 External fi nish Munsell 3Y 7.8/1.1 Remote controller Wireless type Control voltage (by built-in transformer) VDC 12-24 Refrigerant piping t supplied Refrigerant pipe size Liquid in. 1/4 (0.0315) 3/8 (0.0315) (Min. wall thickness) Gas in. 3/8 (0.0315) 5/8 (0.0315) Connection method Indoor Flared Flared Outdoor Flared Flared Between the indoor Height difference ft. 40 50 & outdoor units Piping length ft. 65 100 Refrigerant charge (R410A) 2 lb. 9 oz. 4 lb. 3 oz. NOTE: Test conditions are based on AHRI 210/240. 1: Rating conditions (Cooling) Indoor: 80 FDB, 67 FWB, Outdoor: 95 FDB, (75 FWB) (Heating) Indoor: 70 FDB, 60 FWB, Outdoor: 47 FDB, 43 FWB 2: (Heating) Indoor: 70 FDB, 60 FWB, Outdoor: 17 FDB, 15 FWB 4

Test condition 3, 4 ARI Mode Test SEER (Cooling) HSPF (Heating) "A-2" Cooling Steady State at rated compressor Speed "B-2" Cooling Steady State at rated compressor Speed "B-1" Cooling Steady State at minimum compressor Speed "F-1" Cooling Steady State at minimum compressor Speed "E-V" Cooling Steady State at Intermediate compressor Speed 5 "H1-2" Heating Steady State at rated compressor Speed "H3-2" Heating at rated compressor Speed "H0-1" Heating Steady State at minimum compressor Speed "H1-1" Heating Steady State at minimum compressor Speed "H2-V" Heating at Intermediate compressor Speed 5 Indoor air condition ( F) Outdoor air condition ( F) Dry bulb Wet bulb Dry bulb Wet bulb 80 67 95 (75) 80 67 82 (65) 80 67 82 (65) 80 67 67 (53.5) 80 67 87 (69) 70 60 47 43 70 60 17 15 70 60 62 56.5 70 60 47 43 70 60 35 33 5: At Intermediate compressor Speed = ("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed". OPERATING RANGE (1) POWER SUPPLY Rated voltage Guaranteed voltage (V) Outdoor unit 208/230 V 1 phase 60 Hz Min. 187 208 230 Max. 253 (2) OPERATION Intake air temperature ( F) Mode Condition Indoor Outdoor DB WB DB WB Standard temperature 80 67 95 Cooling Maximum temperature 90 73 115 Minimum temperature 67 57 14 Maximum humidity 78 % Standard temperature 70 60 47 43 Heating Maximum temperature 80 67 75 65 Minimum temperature 70 60-13 -15 5

4 OUTLINES AND DIMENSIONS MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH 1-3/4 Air in 15-3/4 Air in Drain hole Drain hole 1-5/8 (FE09/12NA) 1-5/16 (FE09/12NAH) 11/16 12 ~ 12-3/4 13-9/16 REQUIRED SPACE 4 in. or more Unit: inch Basically open 4 inch or more without any obstruction in front and on both sides of the unit. 4 in. or more 7/8 Air out 1-9/16 2-3/8 13/16 Oval hole 29/32 11-1/4 8 in. or more 14 in. or more handle Open two sides of left, right, or rear side. 11-1/32 21-5/8 2 5-7/8 Liquid pipe :1/4 (flared) Gas pipe :3/8 (flared) 13/32 MUZ-FE18NA 11-29/32 5-15/16 19-11/16 31-1/2 2-23/32 6-23/32 REQUIRED SPACE 20 in. or more 16-7/16 Air in Drain hole 1-9/16 1-5/8 4 in. or more 4 in. or more 13 2 14-3/16 Air out 6-7/8 19-11/16 2-holes 13/32 13/16 20 in. or more 14 in. or more 33-1/16 4-5/16 3-3/16 Service panel 34-5/8 Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø 3/8 17-25/32 44 35 6-1/2 3-29/32 7-11/16 Gas refrigerant pipe joint Refrigerant pipe (flared) Ø 5/8 6

5 WIRING DIAGRAM MUZ-FE09NA MUZ-FE12NA MUZ-FE09NA - 1 MUZ-FE12NA1 7

MUZ-FE09NAH MUZ-FE12NAH MUZ-FE18NA 8

6 REFRIGERANT SYSTEM DIAGRAM MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH Unit: inch Refrigerant pipe ø3/8 (with heat insulator) Flared connection Flared connection Refrigerant pipe ø1/4 (with heat insulator) Muffler Stop valve (with service port) Stop valve (with strainer) 4-way valve Discharge temperature thermistor RT62 Service port Muffler Service port Compressor Defrost thermistor RT61 Capillary tube O.D. 0.118 I.D. 0.071 23-5/8 (ø3.0 ø1.8 600) Expansion valve Capillary tube O.D. 0.118 I.D. 0.079 9-7/16 (ø3.0 ø2.0 240) Outdoor heat exchanger Strainer #100 Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65 R.V. coil heating ON cooling OFF Refrigerant flow in cooling Refrigerant flow in heating MUZ-FE18NA Refrigerant pipe ø5/8 (with heat insulator) 4-way valve Muffler #100 Service port Flared connection Stop valve (with service port) Service port Discharge temperature thermistor RT62 Defrost thermistor RT61 Outdoor heat exchanger Ambient temperature thermistor RT65 Flared connection Refrigerant pipe ø3/8 (with heat insulator) Stop valve Strainer #100 Compressor LEV Strainer #100 Capillary tube O.D. 0.157 I.D. 0.094 3-15/16 (ø4.0 ø2.4 100) Outdoor heat exchanger temperature thermistor RT68 R.V. coil heating ON cooling OFF Refrigerant flow in cooling Refrigerant flow in heating 9

MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE Model MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH Max. Length A Refrigerant piping: ft. Max. Height difference B Gas Piping size O.D: in. Liquid 65 40 3/8 1/4 MUZ-FE18NA 100 50 5/8 3/8 Indoor unit Max. Height difference B Max. Length A Outdoor unit ADDITIONAL REFRIGERANT CHARGE (R410A: oz.) NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation. Model MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH Outdoor unit precharged Refrigerant piping length (one way): ft. 25 30 40 50 60 65 2 lb. 9 oz. 0 1.62 4.86 8.10 11.34 12.96 Calculation: X oz. = 1.62/5 oz./ft. (Refrigerant piping length (ft.) - 25) NOTE: Refrigerant piping exceeding 33 ft. requires additional refrigerant charge according to the calculation. Model Outdoor unit precharged Refrigerant piping length (one way): ft. 33 40 50 60 70 80 90 100 MUZ-FE18NA 4 lb. 3 oz. 0 4.14 10.06 15.98 21.90 27.82 33.74 39.66 Calculation: X oz. = 2.96/5 oz./ft. (Refrigerant piping length (ft.) - 33) 10

7 DATA MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA 7-1. PERFORMANCE DATA 1) COOLING CAPACITY Indoor air Model IWB ( F) MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA Outdoor intake air DB temperature ( F) 75 85 95 105 115 TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC 71 11.0 6.9 0.58 10.3 6.5 0.63 9.7 6.1 0.68 9.0 5.6 0.72 8.3 5.2 0.75 67 10.4 7.9 0.55 9.7 7.4 0.60 9.0 6.8 0.65 8.4 6.4 0.69 7.7 5.8 0.72 63 9.8 8.8 0.52 9.1 8.1 0.58 8.5 7.6 0.62 7.7 6.9 0.66 7.0 6.3 0.69 71 14.7 8.8 0.85 13.7 8.2 0.94 12.9 7.7 1.01 12.0 7.2 1.06 11.0 6.6 1.10 67 13.9 10.2 0.81 13.0 9.5 0.89 12.0 8.8 0.96 11.2 8.1 1.02 10.3 7.5 1.07 63 13.1 11.3 0.77 12.1 10.5 0.85 11.3 9.7 0.92 10.3 8.9 0.98 9.4 8.1 1.02 71 22.1 15.6 1.13 20.6 14.6 1.24 19.4 13.7 1.33 18.0 12.7 1.40 16.6 11.7 1.46 67 20.9 17.5 1.07 19.4 16.3 1.17 18.0 15.1 1.27 16.7 14.1 1.35 15.4 12.9 1.41 63 19.6 19.1 1.02 18.2 17.7 1.12 16.9 16.5 1.21 15.4 15.0 1.30 14.0 13.7 1.35 NOTE: 1. IWB : Intake air wet-bulb temperature TC : Total Capacity (x10 3 Btu/h) SHC : Sensible Heat Capacity (x10 3 Btu/h) TPC : Total Power Consumption (kw) 2. SHC is based on 80 F of indoor Intake air DB temperature. 2) COOLING CAPACITY CORRECTIONS Refrigerant piping length (one way: ft.) 25 (std.) 40 65 100 MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA 1.0 0.954 0.878 - MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA 1.0 0.954 0.878 0.771 3) HEATING CAPACITY Indoor air Outdoor intake air WB temperature ( F) Model 5 15 25 35 43 45 55 IDB ( F) TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC 75 4.8 0.44 6.3 0.56 7.9 0.66 9.4 0.73 10.6 0.77 11.0 0.78 12.4 0.81 MUZ-FE09NA 70 5.2 0.42 6.7 0.54 8.2 0.64 9.6 0.71 10.9 0.75 11.2 0.77 12.7 0.80 65 5.5 0.41 6.9 0.52 8.6 0.62 10.0 0.69 11.2 0.73 11.6 0.74 13.0 0.78 75 4.8 0.57 6.3 0.69 7.9 0.79 9.4 0.73 10.6 0.77 11.0 0.78 12.4 0.81 MUZ-FE09NAH 70 5.2 0.55 6.7 0.67 8.2 0.77 9.6 0.71 10.9 0.75 11.2 0.77 12.7 0.80 65 5.5 0.54 6.9 0.65 8.6 0.75 10.0 0.69 11.2 0.73 11.6 0.74 13.0 0.78 MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA 75 6.0 0.58 7.9 0.73 9.9 0.86 11.8 0.96 13.3 1.00 13.7 1.02 15.5 1.06 70 6.5 0.55 8.4 0.71 10.2 0.84 12.0 0.93 13.6 0.98 14.0 1.00 15.8 1.04 65 6.8 0.53 8.6 0.68 10.7 0.81 12.4 0.91 14.0 0.96 14.4 0.97 16.2 1.02 75 6.0 0.71 7.9 0.86 9.9 0.99 11.8 0.96 13.3 1.00 13.7 1.02 15.5 1.06 70 6.5 0.68 8.4 0.84 10.2 0.97 12.0 0.93 13.6 0.98 14.0 1.00 15.8 1.04 65 6.8 0.66 8.6 0.81 10.7 0.94 12.4 0.91 14.0 0.96 14.4 0.97 16.2 1.02 75 9.5 0.91 12.5 1.15 15.7 1.35 18.7 1.50 21.1 1.58 21.7 1.60 24.6 1.66 70 10.3 0.87 13.3 1.11 16.2 1.32 19.1 1.46 21.6 1.54 22.2 1.57 25.2 1.63 65 10.8 0.83 13.6 1.06 17.0 1.27 19.8 1.42 22.2 1.50 22.9 1.52 25.7 1.60 NOTE: 1. IDB : Intake air dry-bulb temperature TC : Total Capacity (x10 3 Btu/h) TPC : Total Power Consumption (kw) 2. Above data is for heating operation without any frost. How to operate with fixed operational frequency of the compressor. 1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL mode or EMERGENCY HEAT mode before starting to operate the air conditioner. 2. The compressor starts with operational frequency. 3. The fan speed of the indoor unit is High. 4. This operation continues for 30 minutes. 5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on the remote controller. 11

7-2. PERFORMANCE CURVE Cooling Cooling capacity (at Rated frequency) Indoor air Wet-bulb temperature difference ( F) Total power consumption (kw) Capacity correction factors 0.8 0.7 0.6 1.5 1.4 1.3 1.2 1.1 1.0 0.9 72 68 64 14 23 32 41 50 59 68 77 86 95 104 113 MUZ-FE09NA MUZ-FE09NAH Outdoor intake air DB temperature( F) SHF at rating condition = 0.76 Airflow = 307 CFM Indoor intake air WB temperature ( F) 71 67 63 0.5 65 75 85 95 105 115 Outdoor intake air DB temperature ( F) Indoor intake air Wet-bulb temperature( F) 76 75 MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH Total power consumption (kw) 1.3 1.2 1.1 1.0 0.9 0.8 0.7 SHF at rating condition = 0.73 Airflow = 350 CFM Indoor intake air WB temperature ( F) 65 75 85 95 105 115 Outdoor intake air DB temperature ( F) 71 67 63 MUZ-FE18NA Total power consumption (kw) 1.5 1.4 1.3 SHF at rating condition = 0.84 Airflow = 634 CFM 1.2 1.1 1.0 0.9 65 70 75 80 85 90 95 100 105 110 115 Indoor intake air WB temperature ( F) Outdoor intake air DB temperature ( F) 71 67 63 This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity. 12

Heating Indoor air Dry-bulb temperature difference ( F) Capacity correction factor 1.3 1.2 1.1 1.0 0.9 0.8 0.7 0.6 0.5 0.4 Heating capacity (at Rated frequency) Indoor intake air Dry-bulb temperature ( F) 59 68 79-4 5 14 23 32 41 50 59 Outdoor intake air WB temperature ( F) MUZ-FE09NA Total power consumption (kw) 1.0 0.8 0.6 0.4 0.2 Indoor intake air DB temperature ( F) Airflow = 381 CFM 0-15 -5 5 15 25 35 45 55 65 Outdoor intake air WB temperature ( F) 75 70 65 MUZ-FE12NA MUZ-FE12NA1 Total power consumption (kw) 1.2 1.0 0.8 0.6 0.4 Indoor intake air DB temperature ( F) Airflow = 420 CFM 75 70 65 0.2-15 -5 5 15 25 35 45 55 65 Outdoor intake air WB temperature ( F) MUZ-FE09NAH Total power consumption (kw) 1.0 0.8 0.6 0.4 0.2 Indoor intake air DB temperature ( F) Airflow = 381 CFM 0-15 -5 5 15 25 35 45 55 65 Outdoor intake air WB temperature ( F) 75 70 65 MUZ-FE12NAH Total power consumption (kw) 1.2 1.0 0.8 0.6 0.4 Indoor intake air DB temperature ( F) Airflow = 420 CFM 75 70 65 0.2-15 -5 5 15 25 35 45 55 65 Outdoor intake air WB temperature ( F) MUZ-FE18NA Total power consumption (kw) 1.8 1.4 1.0 0.6 Indoor intake air DB temperature ( F) Airflow = 738 CFM 0.2-15 -5 5 15 25 35 45 55 65 Outdoor intake air WB temperature ( F) 75 70 65 This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity. 13

7-3. CONDENSING PRESSURE Cooling Data is based on the condition of indoor humidity 50 %. Air flow should be set to High speed. MUZ-FE09NA MUZ-FE09NAH (PSIG) 580 Condensing pressure 540 500 460 420 380 340 300 Indoor DB temperature ( F) 86 80 75 70 260 68 70 75 80 85 90 95 100 105( F) Outdoor ambient temperature (PSIG) 180 175 170 86 165 160 155 80 150 145 75 140 135 70 130 125 120 68 70 75 80 85 90 95 100 105( F) Outdoor ambient temperature Suction pressure Indoor DB temperature ( F) MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH (PSIG) 580 Condensing pressure 540 500 460 420 380 340 300 Indoor DB temperature ( F) 86 80 75 70 260 68 70 75 80 85 90 95 100 105( F) Outdoor ambient temperature (PSIG) 180 175 170 165 86 160 155 150 80 145 140 75 135 130 70 125 120 68 70 75 80 85 90 95 100 105( F) Outdoor ambient temperature Suction pressure Indoor DB temperature ( F) MUZ-FE18NA Condensing pressure (PSIG) 480 440 400 360 320 280 Indoor DB temperature ( F) 86 80 75 70 240 68 70 75 80 85 90 95 100 105( F) Outdoor ambient temperature Suction pressure (PSIG) 190 86 180 80 170 160 75 150 70 140 130 Indoor DB temperature ( F) 120 110 68 70 75 80 85 90 95 100 105( F) Outdoor ambient temperature 14

Heating Data is based on the condition of outdoor humidity 75%. Air flow should be set to High speed. Data is for heating operation without any frost. MUZ-FE09NA MUZ-FE09NAH (PSIG) (PSIG) 400 170 75 70 380 160 65 360 75 150 340 70 65 140 320 130 300 120 280 110 260 100 240 90 220 58Hz 80 200 58Hz 180 70 160 60 140 50 120-15 -10 5 10 15 20 25 30 35 40 45 50 55 60 6570( F) 40-15 -10 5 10 15 20 25 30 35 40 45 50 55 60 6570( F) Condensing pressure Indoor DB temperature ( F) Outdoor ambient temperature Suction pressure Indoor DB temperature ( F) Outdoor ambient temperature MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH (PSIG) 400 Condensing pressure 380 360 340 320 300 280 260 240 220 200 180 160 140 Indoor DB temperature ( F) Outdoor ambient temperature 58Hz 75 70 65 (PSIG) 170 120 40-15 -10 5 10 15 20 25 30 35 40 45 50 55 60 6570( F) -15-10 Suction pressure 160 150 140 130 120 110 100 90 80 70 60 50 Indoor DB temperature ( F) Outdoor ambient temperature 58Hz 75 70 65 5 10 15 20 25 30 35 40 45 50 55 60 6570( F) MUZ-FE18NA (PSIG) (PSIG) 480 240 460 220 440 75 200 420 70 180 400 65 160 380 140 360 120 340 100 320 80 300 60 58Hz 280 40 260 20 240-15 -10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75( F) Outdoor ambient temperature Condensing pressure Indoor DB temperature ( F) Suction pressure Indoor DB temperature ( F) 58Hz 75 70 65 0-15 -10-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75( F) Outdoor ambient temperature 15

7-4. STANDARD OPERATION DATA Total Electrical circuit Refrigerant circuit Indoor unit Outdoor unit Model MSZ-FE09NA MSZ-FE12NA MSZ-FE18NA Item Unit Cooling Heating Cooling Heating Cooling Heating Capacity Btu/h 9,000 10,900 12,000 13,600 18,000 21,600 SHF 0.76 0.73 0.84 Input kw 0.580 0.710 0.930 0.950 1.800 2.200 Rated frequency Hz 34 42 51 52.5 50.5 62.5 Indoor unit MSZ-FE09NA MSZ-FE12NA MSZ-FE18NA Power supply V, phase, Hz 208/230, 1, 60 Input kw 0.018 0.024 0.024 0.030 0.058 Fan motor current A 0.19/0.17 0.25/0.23 0.25/0.23 0.32/0.29 0.56/0.51 Outdoor unit MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA Power supply V, phase, Hz 208/230, 1, 60 Input kw 0.562 0.686 0.906 0.920 1.212 1.482 Comp. current A 2.38/2.15 2.98/2.70 4.05/3.66 4.12/3.72 4.47/4.04 5.72/5.17 Fan motor current A 0.35/0.32 1.16/1.05 1.13/1.02 Condensing pressure PSIG 376 355 402 392 373 357 Suction pressure PSIG 154 108 148 104 151 107 Discharge temperature F 142 145 160 158 150 159 Condensing temperature F 112 108 117 115 111 105 Suction temperature F 53 36 53 34 58 41 Comp. shell bottom temperature F 144 128 146 129 132 136 Ref. pipe length ft. 25 Refrigerant charge (R410A) 2 lb. 9 oz. 4 lb 3 oz. Intake air temperature DB F 80 70 80 70 80 70 WB F 67 60 67 60 67 60 Discharge air temperature DB F 59 99 58 101 59 102 WB F 56 55 56 Fan speed (High) rpm 1,020 1,120 1,120 1,220 1,300 Airfl ow (High) CFM 307 (Wet) 381 350 (Wet) 420 634 (Wet) 738 Intake air temperature DB F 95 47 95 47 95 47 WB F 43 43 43 Fan speed rpm 810 870 810 870 840 810 Airfl ow CFM 1,102 1,187 1,102 1,187 1,769 1,701 16

7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY MUZ-FE09NA MUZ-FE09NAH Correction of Cooling capacity Correction of Cooling total input Correction of Heating capacity 1.5 1.5 2.0 Correction of Heating total input Capacity correction factors 1.0 0.5 Input correction factors 1.0 0.5 Capacity correction factors 1.5 1.0 0.5 Input correction factors 3.0 2.0 1.0 0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz) The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH 1.5 Correction of Cooling capacity Correction of Cooling total input 1.5 1.5 Correction of Heating capacity Correction of Heating total input 2.5 Capacity correction factors 1.0 0.5 Input correction factors 1.0 0.5 Capacity correction factors 1.0 0.5 Input correction factors 2.0 1.5 1.0 0.5 0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz) The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor MUZ-FE18NA 1.5 Correction of Cooling capacity Correction of Cooling total input 2.0 1.5 Correction of Heating capacity 2.0 Correction of Heating total input Capacity correction factors 1.0 0.5 Input correction factors 1.5 1.0 0.5 Capacity correction factors 1.0 0.5 Input correction factors 1.5 1.0 0.5 0 50 100 150 (Hz) 0 50 100 150 (Hz) 0 50 100 150 (Hz) The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor 0 50 100 150 (Hz) The operational frequency of compressor 7-6. HOW TO OPERATE FIXED-FREQUENCY OPERATION (Test run operation) 1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice). 2. Test run operation starts and continues to operate for 30 minutes. 3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode. 4. Indoor fan operates at High speed. 5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies). 6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller. 17

8 ACTUATOR CONTROL MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA 8-1. OUTDOOR FAN MOTOR CONTROL The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running. Compressor ON OFF 5 seconds 15 seconds Outdoor fan motor ON OFF 8-2. R.V. COIL CONTROL Heating................. ON Cooling................. OFF Dry.................... OFF NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor. <COOL> <HEAT> 5 seconds 5 seconds ON Compressor OFF R.V.coil ON OFF Outdoor fan ON motor OFF 8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR Sensor Purpose Compressor LEV Actuator Outdoor fan motor R.V. coil Indoor fan motor Discharge temperature thermistor Protection Cooling: Coil frost prevention Indoor coil temperature thermistor Heating: High pressure protection Cooling: High pressure protection Defrost thermistor Heating: Defrosting Fin temperature thermistor Protection Outdoor heat exchanger temperature thermistor High pressure protection Ambient temperature thermistor Low ambient temperature operation 18

9 SERVICE FUNCTIONS MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA 9-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature <JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board (Refer to 10-6.1.). Defrost finish temperature Jumper MUZ-FE09/12NA MUZ-FE12NA1 MUZ-FE09/12NAH MUZ-FE18NA Soldered (Initial setting) 41 F (5 C) 50 F (10 C) JS ne (Cut) 50 F (10 C) 64 F (18 C) 9-2. PRE-HEAT CONTROL SETTING PRE-HEAT CONTROL When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when outside temperature is 68 F (20 C) or below. When pre-heat control is turned ON, compressor is energized. (About 50 W) <JK> To activate the pre-heat control, cut the JK wire of the inverter P.C. board (Refer to 10-6.1.). NOTE: When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary. 10 TROUBLESHOOTING MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA 10-1. CAUTIONS ON TROUBLESHOOTING 1. Before troubleshooting, check the following 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for miswiring. 2. Take care of the following during servicing 1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after confirming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug. 2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board. 3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor. 4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components. 5) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires. <Incorrect> <Correct> Lead wiring Connector housing 3. Troubleshooting procedure 1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service work. 2) Before servicing, check that the connector and terminal are connected properly. 3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration. 4) Refer to 10-2 and 10-3. 19

10-2. FAILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled. MSZ-FE09NA MSZ-FE18NA 1. Flow chart of failure mode recall function for the indoor/outdoor unit MSZ-FE12NA Operational procedure The cause of abnormality cannot be found because the abnormality does not recur. Setting up the failure mode recall function Turn ON the power supply. <Preparation of the remote controller> While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. First, release RESET button. Hold down the other two buttons for another 3 seconds. Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then release the buttons. Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1 Does POWER lamp (MSZ-FE09/12NA)/the upper lamp of OPERATION INDICATOR lamp (MSZ-FE18NA) on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of POWER lamp (MSZ-FE09/12NA)/the upper lamp of OPERATION INDICATOR lamp (MSZ- FE18NA). 2 Judgment of indoor/outdoor abnormality (Blinks) Before blinking, does POWER lamp (MSZ-FE09/12NA)/the upper lamp of OPERATION INDICATOR lamp (MSZ-FE18NA) stay ON for 3 seconds? When it stays ON for 3 seconds (without beep): The outdoor unit is abnormal. (OFF) Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnormalities that cannot be recalled with this way. Check if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 10-2.2) 1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received. The indoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the indoor unit failure mode table. (Refer to indoor unit service manual.) Make sure to check at least two consecutive blinking cycles. 2 The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the outdoor unit failure mode table. (Refer to 10-2.3) Make sure to check at least two consecutive blinking cycles. 3 Releasing the failure mode recall function Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller. Repair the failure parts. Deleting the memorized abnormal condition After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above. Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above. NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized. 2. Blinking pattern when the indoor unit is abnormal: 2.5-second OFF Blinking at 0.5- second interval 2.5-second OFF Blinking at 0.5- second interval ON OFF Beeps Repeated cycle Beeps Repeated cycle Beeps Repeated cycle 3.Blinking pattern when the outdoor unit is abnormal: Blinking at 0.5-2.5-second OFF 3-second ON second interval 2.5-second OFF 3-second ON Blinking at 0.5- second interval ON OFF beep Repeated cycle Beeps 20 beep Repeated cycle Beeps Repeated cycle

2. Flow chart of the detailed outdoor unit failure mode recall function Operational procedure The outdoor unit might be abnormal. Check if outdoor unit is abnormal according to the following procedures. Make sure that the remote controller is set to the failure mode recall function. With the remote controller headed towards the indoor unit, press TOO COOL or TOO WARM button to adjust the set temperature to 77 F (25 C). 1 1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received. Does POWER lamp(msz-fe09/12na)/the upper lamp of OPERATION INDICATOR lamp(msz- FE18NA) on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of POWER lamp (MSZ-FE09/12NA)/the upper lamp of OPERATION INDICATOR lamp (MSZ-FE- 18NA). 2 (Blinks) (OFF) The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the outdoor unit failure mode table (10-2.3.). Make sure to check at least two consecutive blinking cycles. 2 The outdoor unit is normal. Releasing the failure mode recall function Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller. Release the failure mode recall function according to the left mentioned procedure. Repair the failure parts. Deleting the memorized abnormal condition After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" (10-2.1.). Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above. NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized. 2.Blinking pattern when outdoor unit is abnormal: 2.5-second OFF 3-second ON Blinking at 0.5- second interval 2.5-second OFF 3-second ON Blinking at 0.5- second interval ON OFF beep Repeated cycle Beeps beep Repeated cycle Beeps Repeated cycle 21

3. Outdoor unit failure mode table OPERATION INDICATOR POWER lamp Upper lamp (Indoor unit) Abnormal point (Failure mode/protection) LED indication (Outdoor P.C. board) Condition Remedy Indoor/ outdoor unit failure mode recall function Outdoor unit failure mode recall function OFF ne (rmal) 2-time fl ash Outdoor power system Overcurrent cut-out operates 3 Reconnect connectors. 2.5 seconds consecutive times within 1 minute after Refer to 10-5. "How OFF the compressor gets started. to check inverter/ compressor". Check stop valve. 3-time fl ash Discharge temperature 1-time fl ash every Thermistor shorts or opens during Refer to 10-5. "Check 2.5 seconds thermistor 2.5 seconds compressor running. OFF 4-time fl ash 2.5 seconds OFF 5-time fl ash 2.5 seconds OFF 6-time fl ash 2.5 seconds OFF 7-time fl ash 2.5 seconds OFF 8-time fl ash 2.5 seconds OFF 9-time fl ash 2.5 seconds OFF 10-time fl ash 2.5 seconds OFF 11-time fl ash 2.5 seconds OFF 12-time fl ash 2.5 seconds OFF 14-time fl ash 2.5 seconds OFF Defrost thermistor Fin temperature thermistor P.C. board temperature thermistor Ambient temperature thermistor Overcurrent 3-time fl ash 4-time fl ash 2-time fl ash 11-time fl ash Compressor synchronous 12-time fl ash abnormality (Compressor startup failure protection) Discharge temperature High pressure Fin temperature/ P.C. board temperature Outdoor fan motor nvolatile memory data MUZ-FE18NA Power module Discharge temperature DC voltage Each phase current of compressor 7-time fl ash 5-time fl ash 6-time fl ash 8-time fl ash 9-time fl ash Overcurrent Compressor openphase 2.5 seconds 10-time fl ash OFF Stop valve (Closed valve) 14-time fl ash Large current fl ows into intelligent power module. Waveform of compressor current is distorted. Temperature of discharge temperature thermistor exceeds 241 F (116 C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212 F (100 C) or less 3 minutes later. Temperature of indoor coil thermistor exceeds 158 F (70 C) in HEAT mode. Temperature of defrost thermistor exceeds 158 F (70 C) in COOL mode. Temperature of fi n temperature thermistor on the inverter P.C. board exceeds 167 ~ 176 F (75 ~ 80 C), or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 158 ~ 167 F (70 ~ 75 C). Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up. nvolatile memory data cannot be read properly. The interphase short circuit occurs in the output of the intelligent power module (IPM). The compressor winding shorts circuit. Temperature of discharge temperature thermistor has been 122 F (50 C) or less for 20 minutes. DC voltage of inverter cannot be detected normally. Each phase current of compressor cannot be detected normally. Large current fl ows into intelligent power module (IPM). The open-phase operation of compressor is detected. The interphase short circuit occurs in the output of the intelligent power module (IPM). The compressor winding shorts circuit. Closed valve is detected by compressor current. of outdoor thermistors". Defective outdoor thermistors can be identifi ed by checking the blinking pattern of LED. Reconnect compressor connector. Refer to 10-5. "How to check inverter/ compressor". Check stop valve. Reconnect compressor connector. Refer to 10-5. "How to check inverter/ compressor". Check refrigerant circuit and refrigerant amount. Refer to 10-5. "Check of LEV". Check refrigerant circuit and refrigerant amount. Check stop valve. Check around outdoor unit. Check outdoor unit air passage. Refer to 10-5. "Check of outdoor fan motor". Refer to 10-5. "Check of outdoor fan motor". Refer to 10-5. "Check of inverter P.C. board". Replace the inverter P.C. board. Refer to 10-5. "How to check inverter/ compressor". Refer to 10-5. "Check of LEV". Check refrigerant circuit and refrigerant amount. Refer to 10-5. "How to check inverter/ compressor". Reconnect compressor connector. Refer to 10-5. "How to check inverter/ compressor". Check stop valve NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.). OPERATION INDICATOR POWER lamp: MSZ-FE09/12NA Upper lamp: MSZ-FE18NA 22

10-3. TROUBLESHOOTING CHECK TABLE. Symptom LED indication 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Outdoor unit 1-time fl ash every does not operate. 2.5 seconds 6-time flash 11-time fl ash 14-time fl ash 'Outdoor unit 2-time fl ash stops and restarts 3 minutes later' is repeated. 3-time flash Outdoor unit operates. 4-time flash 5-time fl ash 8-time fl ash 10-time fl ash 12-time fl ash 13-time fl ash 1-time fl ash 3-time fl ash 4-time fl ash Abnormal point/ Condition Outdoor power system Condition Remedy Overcurrent cut-out operates 3 consecutive times within 1 Reconnect connector of compressor. minute after the compressor gets started, or failure of restart of compressor has repeated 24 times. Refer to 10-5. "How to check inverter/compressor". Check stop valve. Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor, defrost thermistor, outdoor heat exchanger temperature thermistor, P.C. board temperature thermistor or ambient temperature thermistor shorts or opens during compressor running. Outdoor control system Serial signal Stop valve/ Closed valve Outdoor unit (Other abnormality) Overcurrent protection nvolatile memory data cannot be read properly. [POWER lamp (MSZ-FE09/12NA)/the upper lamp of OPERA- TION INDICATOR lamp (MSZ-FE18NA) of the indoor unit lights up or fl ashes 7 times.] The communication fails between the indoor and outdoor unit for 3 minutes. Closed valve is detected by compressor current. Outdoor unit is defective. Large current fl ows into intelligent power module. MUZ-FE09/12NA, MUZ-FE12NA1, MUZ-FE09/12NAH When overcurrent protection occurs within 10 seconds after compressor starts, compressor restarts after 15 seconds. Refer to 10-5. "Check of outdoor thermistors". Replace inverter P.C. board. Refer to 10-5. "How to check miswiring and serial signal error. Check stop valve. Refer to 10-2.2. "Flow chart of the detailed outdoor unit failure mode recall function". Reconnect connector of compressor. Refer to 10-5. "How to check inverter/compressor". Check stop valve. Discharge temperature overheat protec- (116 C), compressor stops. Compressor can restart if discharge erant amount. Temperature of discharge temperature thermistor exceeds 241 F Check refrigerant circuit and refrigtion temperature thermistor reads 212 F (100 C) or less 3 minutes Refer to 10-5. "Check of LEV". later. Fin temperature /P.C. board temperature thermistor overheat protection High pressure protection Compressor synchronous abnormality Outdoor fan motor Each phase current of compressor Temperature of fi n temperature thermistor on the heat sink Check around outdoor unit. exceeds 167 ~ 176 F (75 ~ 80 C) or temperature of P.C. board Check outdoor unit air passage. temperature thermistor on the inverter P.C. board exceeds 158 Refer to 10-5. "Check of outdoor ~ 167 F (70 ~ 75 C). fan motor". Temperature of indoor coil thermistor exceeds 158 F (70 C) in Check refrigerant circuit and refrigerant HEAT mode. Temperature of outdoor heat exchanger temperature amount. thermistor exceeds 158 F (70 C) in COOL mode. Check stop valve. The waveform of compressor current is distorted. Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up. Each phase current of compressor cannot be detected normally. Reconnect connector of compressor. Refer to 10-5. "How to check inverter/compressor". Refer to 10-5. "Check of outdoor fan motor. Refer to 10-5. "Check of inverter P.C. board. Refer to 10-5. "How to check inverter/compressor". DC voltage DC voltage of inverter cannot be detected normally. Refer to 10-5. "How to check inverter/compressor". Frequency drop by current protection Frequency drop by high pressure protection Frequency drop by defrosting in COOL mode Frequency drop by discharge temperature protection Current from power outlet is nearing Max. fuse size. Temperature of indoor coil thermistor exceeds 131 F (55 C) in HEAT mode, compressor frequency lowers. Indoor coil thermistor reads 46 F (8 C) or less in COOL mode, compressor frequency lowers. Temperature of discharge temperature thermistor exceeds 232 F (111 C), compressor frequency lowers. NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1. 2. LED is lighted during normal operation. The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. Flashing (Example) When the fl ashing frequency is 2. The unit is normal, but check the following. Check if indoor fi lters are clogged. Check if refrigerant is short. Check if indoor/outdoor unit air circulation is short cycled. Check refrigerant circuit and refrigerant amount. Refer to 10-5. "Check of LEV". Refer to 10-5. "Check of outdoor thermistors". Inverter P.C. board (Parts side) LED Flashing MUZ-FE09/12NA MUZ-FE12NA1 MUZ-FE09/12NAH 0.5-second ON 0.5-second ON MUZ-FE18NA ON OFF 2.5-second OFF 2.5-second OFF LED 23

. Symptom LED indication 18 19 20 Outdoor unit operates. 7-time fl ash 8-time fl ash 9-time fl ash Abnormal point/ Condition Low discharge temperature protection MUZ-FE09/12NA MUZ-FE12NA1 MUZ-FE09/12NAH PAM protection PAM: Pulse Amplitude Modulation MUZ-FE18NA Zero cross detecting circuit Condition Temperature of discharge temperature thermistor has been 122 F (50 C) or less for 20 minutes. The overcurrent fl ows into IGBT (Insulated Gate Bipolar transistor: TR821) or the bus-bar voltage reaches 320 V or more, PAM stops and restarts. Zero cross signal for PAM control cannot be detected. Inverter check mode The connector of compressor is disconnected, inverter check mode starts. Remedy Refer to 10-5. "Check of LEV". Check refrigerant circuit and refrigerant amount. This is not malfunction. PAM protection will be activated in the following cases: 1 Instantaneous power voltage drop (Short time power failure) 2 When the power supply voltage is high. Check if the connector of the compressor is correctly connected. Refer to 10-5. "How to check inverter/compressor". 10-4. TROUBLE CRITERION OF MAIN PARTS MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA Part name Check method and criterion Figure Defrost thermistor (RT61) Ambient temperature thermistor (RT65) Outdoor heat exchanger temperature thermistor (RT68) Discharge temperature thermistor (RT62) Fin temperature thermistor (RT64) Compressor Measure the resistance with a tester. Refer to 10-6. Test point diagram and voltage, 1. Inverter P.C. board, for the chart of thermistor. Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up. Refer to 10-6. Test point diagram and voltage, 1. Inverter P.C. board, for the chart of thermistor. Measure the resistance between terminals using a tester. (Winding temperature: -4 ~ 104 F (-20 ~ 40 C)) rmal MUZ-FE09NA - 1 U-V MUZ-FE09/12NA MUZ-FE12NA1 MUZ-FE18NA U-W MUZ-FE09/12NAH V-W 1.52 ~ 2.17 Ω 0.78 ~ 1.11 Ω 0.83 ~ 1.18 Ω WHT 2 3 1 W V RED BLK U Outdoor fan motor Measure the resistance between lead wires using a tester. (Part temperature: -4 ~ 104 F (-20 ~ 40 C)) Color of lead wire RED BLK BLK WHT WHT RED rmal 11 ~ 16 Ω WHT RED BLK 2 3 1 W V U 24

Part name Check method and criterion Figure R. V. coil (21S4) Measure the resistance using a tester. (Part temperature: 14 ~ 104 F (-10 ~ 40 C)) rmal 0.97 ~ 1.38 kω Expansion valve coil (LEV) Measure the resistance using a tester. (Part temperature: 14 ~ 104 F (-10 ~ 40 C)) MUZ-FE09/12NA MUZ-FE09/12NAH MUZ-FE12NA1 Color of lead wire rmal WHT RED RED ORN 37 ~ 54 Ω YLW BRN BRN BLU Measure the resistance using a tester. (Part temperature: 14 ~ 104 F (-10 ~ 40 C)) MUZ-FE18NA Color of lead wire rmal RED ORN RED WHT 37 ~ 54 Ω RED BLU RED YLW WHT RED ORN WHT ORN RED (+12V) LEV YLW BRN BLU LEV YLW BLU Defrost heater MUZ-FE NAH Measure the resistance using a tester. (Part temperature: 14 ~ 104 F (-10 ~ 40 C)) rmal (Ω) 349 ~ 428 25

10-5. TROUBLESHOOTING FLOW A How to check inverter/compressor Disconnect the connector between compressor and the intelligent power module (IPM). Check the voltage between terminals. See 10-5. Check of open phase. Are the voltages balanced? Replace the inverter P.C. board. Check the compressor. See 10-5. Check of compressor. B Check of open phase With the connector between the compressor and the intelligent power module disconnected, activate the inverter and check if the inverter is normal by measuring the voltage balance between the terminals. Output voltage is 50-130 V. (The voltage may differ according to the tester.) << Operation method>> Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA- TION: Refer to 7-6.) <<Measurement point>> at 3 points BLK (U) - WHT (V) Measure AC voltage between the lead wires at 3 points. BLK (U) - RED (W) WHT(V) - RED (W) NOTE: 1. Output voltage varies according to power supply voltage. 2. Measure the voltage by analog type tester. 3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 10-6.1.) C Check of compressor Refer to 10-5. Check of compressor winding. Is the compressor normal? Refer to 10-5. Check of compressor operation time. Does the compressor operate continuously? OK Replace the compressor. Refer to 10-5. Check of compressor start failure. 26

D Check of compressor winding Disconnect the connector between the compressor and intelligent power module, and measure the resistance between the compressor terminals. <<Measurement point>> At 3 points BLK - WHT BLK - RED Measure the resistance between the lead wires at 3 points. WHT - RED <<Judgement>> Refer to 10-4. 0[Ω] Abnormal [short] Infinite [Ω] Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement. E Check of compressor operation time Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to over current. <<Operation method>> Start heating or cooling operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION: Refer to 7-6.) <<Measurement>> Measure the time from the start of compressor to the stop of compressor due to overcurrent. F Check of compressor start failure <<Judgement>> 0 second 1 second 2 seconds 10 seconds 10 minutes Compressor starts Abnormal (IPM failure) (Compressor winding short) Abnormal (Compressor lock out) (Starting defect) Abnormal (Poor contact,) (Outdoor P.C. board defect) (Disconnected connector) Abnormal (Refrigerant circuit defect) (Closed valve) rmal Confi rm that 1~4 is normal. Electrical circuit check 1. Contact of the compressor connector 2. Output voltage of inverter P.C. board and balance of them (See 10-5. ) 3. Direct current voltage between DB61(+) and (-) (MUZ-FE09/12NA, MUZ- FE12NA1, MUZ-FE09/12NAH)/JP715(+) and JP30(-) (MUZ-FE18NA) on the inverter P.C. board 4. Voltage between outdoor terminal block S1-S2 Does the compressor run for 10 seconds or more after it starts? Check the refrigerant circuit. Check the stop valve. After the compressor is heated with a drier, does the compressor start? 1 Compressor start failure. Activate pre-heat control. (Refer to 9-2. "PRE-HEAT CONTROL SETTING") Replace the compressor. 1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating. 27 Heating part

G Check of outdoor thermistors Disconnect the connector of thermistor in the outdoor P.C. board (see below table), and measure the resistance of thermistor. Is the thermistor normal? (Refer to 10-6.1.) Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board. Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch. Does the unit operate for 10 minutes or more without showing thermistor abnormality? OK (Cause is poor contact.) Replace the inverter P.C. board. MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH Thermistor Symbol Connector, Pin. Board Defrost RT61 Between CN641 pin1 and pin2 Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2 Inverter P.C. board Ambient temperature RT65 Between CN643 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3 MUZ-FE18NA Thermistor Symbol Connector, Pin. Board Defrost RT61 Between CN671 pin1 and pin2 Discharge temperature RT62 Between CN671 pin3 and pin4 Fin temperature RT64 Between CN673 pin1 and pin2 Inverter P.C. board Ambient temperature RT65 Between CN672 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN671 pin5 and pin6 H Check of R.V. coil First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4. In case CN721 (MUZ-FE09/12NA, MUZ-FE12NA1, MUZ-FE09/12NAH)/CN602 (MUZ-FE18NA) is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector although no signal is being transmitted to R.V. coil. Check if CN721 (MUZ-FE09/12NA, MUZ-FE12NA1, MUZ-FE09/12NAH)/CN602 (MUZ-FE18NA) is connected. Unit operates COOL mode even if it is set to HEAT mode. Disconnect connector between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode). Is there 208/230 VAC between CN721 (MUZ- FE09/12NA, MUZ-FE12NA1, MUZ-FE09/ 12NAH)/CN602 (MUZ-FE18NA) and on the inverter P.C. board 3 minutes after the power supply is turned ON? Replace the 4-way valve. Replace the inverter P.C. board. Unit operates HEAT mode even if it is set to COOL mode. Disconnect connector between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode). Is there 208/230 VAC between CN721 (MUZ- FE09/12NA, MUZ-FE12NA1, MUZ-FE09/ 12NAH)/CN602 (MUZ-FE18NA) and on the inverter P.C. board 3 minutes after the power supply is turned ON? Replace the inverter P.C. board. Replace the 4-way valve. 28

I Check of outdoor fan motor MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH Disconnect CN932 from the inverter P.C. board, and measure the resistance of the outdoor fan motor. Is the outdoor fan motor normal? (Refer to 10-4.) Replace the inverter P.C. board. Replace the outdoor fan motor. MUZ-FE18NA Disconnect the connectors CN931 and CN932 from the inverter P.C. board. Check the connection between the connector CN931 and CN932. Is the resistance between each terminal of outdoor fan motor normal? (Refer to 10-4.) Disconnect CN932 from the inverter P.C. board, and turn on the power supply. Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-) Replace the outdoor fan motor. (Fixed to either 5 or 0 VDC) Does the voltage between each terminal become 5 and 0 VDC repeatedly? Does the outdoor fan motor rotate smoothly? Replace the inverter P.C. board. 29

J Check of power supply MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH Disconnect the connector (CN61) between compressor and intelligent power module. Turn ON power supply and press EMERGENCY OPERATION switch. Rectify indoor/outdoor connecting wire. Does POWER lamp on the indoor unit light up? Is there voltage 208/230 VAC between the indoor terminal block S1 and S2? Replace the indoor electronic control P.C. board. Is there bus-bar voltage 260-325 VDC between DB61 (+) and DB61 ( ) on the inverter P.C. board? (Refer to 10-6.1.) Does LED on the inverter P.C. board light up or fl ash? (Refer to 10-6.1.) Replace the inverter P.C. board. 260-325VDC Check the electric parts in main circuit. If light up, OK. If fl ash, refer to 10-3. DB61 Inverter P.C. board (Solder side) 30

MUZ-FE18NA Disconnect the connector between compressor and intelligent power module. Turn ON power supply and press EMERGENCY OPERATION switch. Rectify indoor/outdoor connecting wire. Does the upper lamp of OPERATION INDICATOR on the indoor unit light up? Is there voltage 208/230 VAC between the indoor terminal block S1 and S2? Replace the indoor electronic control P.C. board. Is there bus-bar voltage 294-370 VDC between JP715 (+) and JP30 ( ) on the inverter P.C. board? (Refer to 10-6.1.) Does LED on the inverter P.C. board light up or fl ash? (Refer to 10-6.1.) Replace the inverter P.C. board. Check the electric parts in main circuit. If LED lights up, it is OK. If LED flashes, refer to 10-3. JP30 JP715 294-370 VDC 31

K Check of LEV (Expansion valve) Turn ON the power supply. <Preparation of the remote controller> While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. First, release RESET button. Hold down the other two buttons for another 3 seconds. Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then release the buttons. MSZ-FE09NA MSZ-FE12NA MSZ-FE18NA Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1 Expansion valve operates in full-opening direction. 1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received. Do you hear the expansion valve "click, click "? Do you feel the expansion valve vibrate on touching it? OK Is LEV coil properly fi xed to the expansion valve? Does the resistance of LEV coil have the characteristics? (Refer to 10-4.) Replace the LEV coil. Properly fi x the LEV coil to the expansion valve. Measure each voltage between connector pins of CN724 on the inverter P.C. board. 1. Pin (-) Pin (+) 2. Pin (-) Pin (+) 3. Pin (-) Pin (+) 4. Pin (-) Pin (+) Is there about 3 ~ 5 VAC between each? NOTE: Measure the voltage by an analog tester. Replace the inverter P.C. board. Replace the expansion valve. NOTE: After check of LEV, do the undermentioned operations. 1. Turn OFF the power supply and turn ON it again. 2. Press RESET button on the remote controller. 32

L Check of inverter P.C. board Check the outdoor fan motor. (Refer to 10-5..) Is the fuse (F901) blown on the inverter P.C. board? Check the connection of the connectors (CN931, CN932) of the outdoor fan motor. If the connection is poor, make it correct. Only for MUZ-FE18NA Operate the outdoor unit by starting EMERGENCY OPERATION. Check the LED indication on the inverter P.C. board. Does the LED fl ash 10 times? (10-time fl ash) Check the remedy following LED indication. (Refer to 10-3.) Replace the inverter P.C. board. 33

M How to check miswiring and serial signal error Turn OFF the power supply. Is there rated voltage in the power supply? Turn ON the power supply. Check the power supply. Is there rated voltage between outdoor terminal block S1 and S2? Press EMERGENCY OPERATION switch once. Check the wiring. Does the OPERATION INDICATOR lamp light up? <Confi rmation of the power to the indoor unit> Is serial signal error indicated 6 minutes later? Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire? Correct them. B A Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not miswiring. Bridge the outdoor terminal block S2 and S3. 1 1. Miswiring may damage indoor electronic control P.C. board during the operation. Be sure to confirm the wiring is correct before the operation starts. 3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes. Turn ON the power supply. Is the bus-bar voltage of the inverter P.C. board normal (Refer to "TEST POINT DIAGRAM AND VOLTAGE" in this manual.)? Does the LED on the inverter P.C. board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"? 3 (Lighted or not lighted) Replace the inverter P.C. board. 2 2. Be careful of the residual voltage of smoothing capacitor. Turn OFF the power supply. Remove the bridge between outdoor terminal block S2 and S3. Turn OFF inverter-controlled lighting equipment. Turn OFF the power supply and then turn ON again. Press EMERGENCY OPERATION switch. A Replace the indoor electronic control P.C. board. Is serial signal error indicated 6 minutes later? B Reinstall either the unit or the light away from each other. Attach a fi lter on remote control receiving section of the indoor unit. 34

N Electromagnetic noise enters into TV sets or radios Is the unit grounded? Ground the unit. Is the distance between the antennas and the indoor unit within 9.91 ft., or is the distance between the antennas and the outdoor unit within 9.91 ft.? Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit. Is the distance between the TV sets or radios and the indoor unit within 3.28 ft., or is the distance between the TV sets or radios and the outdoor unit within 9.91 ft.? Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit. Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the antenna wiring? Replace or repair the antenna. Replace or repair the coaxial cable. Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close? Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas. Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the followings before asking for service. 1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave) 2. Channel, frequency, broadcast station affected by the electromagnetic noise 3. Channel, frequency, broadcast station unaffected by the electromagnetic noise 4. Layout of: indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver 5. Electric field intensity of the broadcast station affected by the electromagnetic noise 6. Presence or absence of amplifi er such as booster 7. Operation condition of air conditioner when the electromagnetic noise enters in 1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise. 2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise. 3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise. 4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise. 35

10-6. TEST POINT DIAGRAM AND VOLTAGE 1. Inverter P.C. board MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH Bus-bar voltage Smoothing Smoothing Smoothing Heater connector DB61 capacitor capacitor capacitor Back side of unit Fuse (F701) (CN722) 260-325 VDC (C63) (C62) (C61) T3.15AL250V MUZ-FE NAH 208/230 VAC (-) (+) Fuse (F801) T3.15AL250V R.V. coil (CN721) 208/230 VAC Fuse (F901) T3.15AL250V Output to drive compressor (LDU, LDV, LDW) 208/230 VAC Front side of unit Output to drive outdoor fan motor (CN932) Fin temperature thermistor /RT64 (CN642) Outdoor heat exchanger temperature thermistor /RT68(CN644) Ambient temperature thermistor /RT65 (CN643) Defrost thermistor /RT61(CN641) Discharge temperature thermistor /RT62 (CN641) LED LEV connector (CN724) Jumper wire for changing defrost setting (JS) Jumper wire for pre-heat control setting (JK) Defrost thermistor(rt61) Ambient temperature thermistor(rt65) Outdoor heat exchanger temperature thermistor(rt68) 100 90 80 70 60 50 40 30 20 10 0-4 14 32 50 68 86 104 Temperature( F) Discharge temperature thermistor (RT62) 800 700 600 500 400 300 200 100 0 32 60 68 86 104 122 140 158 176 194 212 230 248 Temperature ( F) 36 Fin temperature thermistor(rt64) 200 180 160 140 120 100 80 60 40 20 0 32 50 68 86 104 122 140 158 176 Temperature( F)

MUZ-FE18NA Fuse (F62) T2.0AL250V Fuse (F601) T3.15AL250V R.V. coil (CN602) 208/230 VAC Jumper wire for changing defrost setting (JS) Jumper wire for pre-heat control setting (JK) Signal of outdoor fan motor (CN931) LED Output to drive outdoor fan motor (CN932) Fuse (F901) T3.15AL250V Defrost thermistor /RT61 (CN671) Discharge temperature thermistor/rt62 (CN671) Outdoor heat exchanger temperature thermistor /RT68 (CN671) Ambient temperature thermistor/rt65 (CN672) Fin temperature thermistor/rt64 (CN673) Fuse (F880) T3.15AL250V LEV connector (CN724) Defrost thermistor(rt61) Ambient temperature thermistor(rt65) Outdoor heat exchanger temperature thermistor(rt68) 100 90 80 70 60 50 40 30 20 10 0-4 14 32 50 68 86 104 Temperature( F) Discharge temperature thermistor (RT62) 800 700 600 500 400 300 200 100 0 32 60 68 86 104 122 140 158 176 194 212 230 248 Temperature ( F) 37 JP715 (+) Bus-bar voltage 294-370 VDC JP30 (-) Fin temperature thermistor(rt64) 200 180 160 140 120 100 80 60 40 20 0 32 50 68 86 104 122 140 158 176 Temperature( F)

11 DISASSEMBLY INSTRUCTIONS <"Terminal with locking mechanism" Detaching points> The terminal which has the locking mechanism can be detached as shown below. There are two types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching. (1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the locking mechanism. Sleeve Locking lever 11-1. MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH NOTE: Turn OFF power supply before disassembly. OPERATING PROCEDURE Slide the sleeve. Pull the terminal while pushing the locking lever. 1. Removing the cabinet (1) Remove the screw fixing the service panel. (2) Pull down the service panel and remove it. (3) Remove the screws fixing the conduit cover. (4) Remove the conduit cover. (5) Disconnect the power supply wire and indoor/outdoor connecting wire. (6) Remove the screws fixing the top panel. (7) Remove the top panel. (8) Remove the screws fixing the cabinet. (9) Remove the cabinet. (10) Remove the screws fixing the back panel. (11) Remove the back panel. Photo 1 Screws of the top panel Connector Hold the sleeve, and pull out the terminal slowly. PHOTOS Screws of the top panel Back panel Screws of the back panel Photo 2 Screw of the cabinet Screws of the terminal block support and the back panel Screws of the cabinet Service panel Screw of the service panel Photo 3 Direction to remove Screws of the conduit cover Conduit cover Conduit plate Screws of the cabinet Hooks 38

OPERATING PROCEDURE 2. Removing the inverter assembly, inverter P.C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN641 (Defrost thermistor and discharge temperature thermistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN721 (R.V.coil) CN724 (LEV) CN932 (Fan motor) (3) Remove the compressor connector (CN61). (4) Remove the screws fixing the heat sink support and the separator. (5) Remove the fixing screws of the terminal block support and the back panel. (6) Remove the inverter assembly. (7) Remove the screw of the ground wire and screw of the terminal block support. (8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and remove the inverter P.C. board from the P.C. board support. Photo 4 PHOTOS Screws of the heat sink support and the separator Photo 5 (Inverter assembly) Heat sink Hook of the P.C. board support Inverter P.C. board P.C. board support Screws of the terminal block support and the back panel Screw of the terminal block support Terminal block support Heat sink support Screw of the ground wire 3. Removing R.V. coil (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board> CN721 (R.V. coil) (3) Remove the R.V. coil. Hook of the P.C. board support Photo 6 Screw of the P.C. board fixture R.V. coil Discharge temperature thermistor 39

OPERATING PROCEDURE 4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor. (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN641 (Defrost thermistor and discharge temperature thermistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) (3) Pull out the discharge temperature thermistor from its holder. (Photo 6) (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor from its holder. (6) Pull out the ambient temperature thermistor from its holder. Photo 7 Photo 8 PHOTOS Outdoor heat exchanger temperature thermistor Defrost thermistor Screws of the outdoor fan motor 5. Removing outdoor fan motor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the connectors for outdoor fan motor. (3) Remove the propeller nut. (4) Remove the propeller. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor. 6. Removing the compressor and 4-way valve (1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the inverter assembly. (Refer to 2.) (3) Recover gas from the refrigerant circuit. NOTE: Recover gas from the pipes until the pressure gauge shows 0 PSIG. (4) Detach the brazed part of the suction and the discharge pipes connected with compressor. (5) Remove the nuts of compressor legs. (6) Remove the compressor. (7) Detach the brazed part of pipes connected with 4-way valve. Propeller Photo 9 Propeller nut Brazed parts of 4-way valve 40

11-2. MUZ-FE18NA OPERATING PROCEDURE 1. Removing the cabinet (1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the screws fixing the conduit cover. (6) Remove the conduit cover. (7) Remove the top panel. (8) Remove the valve cover. (9) Disconnect the power supply and indoor/outdoor connecting wire. (10) Remove the screws of the cabinet. (11) Remove the cabinet. (12) Remove the screws of the back panel. (13) Remove the back panel. Photo 2 Screws of the back panel Screws of the top panel Screws of the back panel Screws of the back panel NOTE: Turn OFF power supply before disassembly. PHOTOS Photo 1 Screws of the top panel Screws of the cabinet Screws of the cabinet Photo 3 Screws of the conduit cover Screws of the cabinet Screws of the back panel Screws of the back panel Screws of the service panel Screw of the valve cover Conduit plate 41

OPERATING PROCEDURE 2. Removing the inverter assembly, inverter P.C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN602 (R.V. coil) CN671 (Defrost thermistor, discharge temperature thermistor and outdoor heat exchanger temperature thermistor) CN672 (Ambient temperature thermistor) CN724 (LEV) CN931, CN932 (Fan motor) (3) Remove the compressor connector. (4) Remove the screws fixing the relay panel. (5) Remove the relay panel. (6) Remove the earth wires and the lead wires of the inverter P.C. board. (7) Remove the screws of the PB support. (8) Remove the inverter P.C. board from the relay panel. Photo 4 Inverter P.C board Screws of the PB support PHOTOS Screw of the relay panel Earth wires Screws of the PB support 3. Removing R.V. coil (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connector: <Inverter P.C. board> CN602 (R.V. coil) (3) Remove the R.V. coil. Photo 5 Screws of the relay panel Screw of the R.V. coil Brazed parts of 4-way valve 42

OPERATING PROCEDURE 4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN671 (Defrost thermistor, discharge temperature thermistor and outdoor heart exchanger temperature thermistor) CN672 (Ambient temperature thermistor) (3) Pull out the discharge temperature thermistor from its holder. (Photo 8) (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor from its holder. (6) Pull out the ambient temperature thermistor from its holder. Photo 6 Outdoor heat exchanger temperature thermistor PHOTOS Ambient temperature thermistor 5. Removing outdoor fan motor (1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board> CN931 and CN932 (Fan motor) (3) Remove the propeller. (4) Remove the screws fixing the fan motor. (5) Remove the fan motor. Photo 7 Defrost thermistor 6. Removing the compressor and 4-way valve (1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Recover gas from the refrigerant circuit. NOTE: Recover gas from the pipes until the pressure gauge shows 0 kg/cm 2 (0 MPa). (5) Detach the brazed part of the suction and the discharge pipes connected with compressor. (6) Remove the compressor nuts. (7) Remove the compressor. (8) Detach the brazed parts of 4-way valve and pipes. (Photo 5) Photo 8 Brazed part of the discharge pipe Screws of the outdoor fan motor Discharge temperature thermistor 43 Brazed part of the suction pipe