CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

Similar documents
PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

CWX 6 - CWX 8 - CWX 10 CASSETTE TYPE TERMINAL UNIT

CWX 3 - CWX 5 CASSETTE TYPE TERMINAL UNIT. Cooling

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

CIATCOOLER LJA. Chilled water production units USE. Attractive design, Compact and quiet

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

KPSW CONSOLE TERMINAL UNIT

High temperature air-to-water heat pumps

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

HT V2 HT Split

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

AQUACIAT. Water chillers. Free cooling modules for AQUACIAT2 700V to 1100V AQUACIAT POWER 1200V to 1800V USE RANGE FREE COOLING

BRAN Residential chillers and heat pumps. Reversible unit, air source for outdoor installation 4,81-27,2 kw <<< BACK INDEX.

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

AGEO CALEO. Water-to-water high temperature heat pumps USE RANGE DESCRIPTION. Designed to replace a conventional boiler and produce domestic hot water

Roof top SPACE RPC 450Z R407C M011

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

Modular Air-cooled Chillers

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS

ECOCIAT. Domestic hot water heat recovery unit. Use. Range

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

DYNACIAT POWER. High energy efficiency Compact and quiet

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

VEXTRA. acoustic comfort Saves up to. 40% floor space. Use. Range. Description. Drycoolers. Slim design and. Capacity up to kw.

Galletti Water chillers and heat pumps catalogue

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw. Scroll Compressors SCAEY-FC DE 98

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw

Roof top SPACE RPC 315Z R407C MA00

Aquaflair TRAC-TRAF-TRAH

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

SyScroll 40 to 75 Air NEW

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

CSAGV 27 / 80. GROUPE FRIGORIFIQUE A CONDENSATION PAR AIR HELICOÏDE Fluide réfrigérant R 407 C

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB

PHRT 9 / 18 PHRT 12 PHRT 16 PHRT 18. Pompe à chaleur avec équipement hydraulique - Fluide réfrigérant R 410 A

TCHE-THHE TCEE

Chiller units and air-water heat pumps RANGE OPERATING LIMITS

Water chillers water/water type SIGMA Technical information manual

RMA AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

44,9 202,0 kw. technicalcatalogue

MAGISTER. Compact and attractive design Energy savings with EC motor and self-regulating control. Easy to install. Use. Chilled water operation

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

TCHE-THHE TCEE

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Be sustainable while protecting your business

GeoCIAT Modular. Components. Heat pump Heating only, Glycol/water mix/water. Refrigerant and hydraulic module diagram. HomeConnect control.

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

BRH. Climaveneta Technical Bulletin. Water-cooled liquid chillers ,5-35,1 kw. Versatile High efficiency Maximum silent-running

OPERA MORE. Use. Range. Drycoolers Air-cooled condensers. for LESS. Capacity: up to 1100 kw. Water misting. Free cooling

Split inverter air-to-water heat pump CERTIFIED BY CERTITA. option 30/35-40/45

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

RTA TECHNICAL MANUAL AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION O L S E A F RA N

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

EXPAIR. Use. Precision air handling cabinets. Reducted footprint Dual-wall construction

LEP kw. Indoor monobloc water-water unit. Total heat recovery multi-purpose units LEP PLUS

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

kw COOLING kw HEATING

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw

CONDENCIAT CD. Condensing units. Quiet operation Low speed fans All year round operation USE. Cooling capacity : 25 to 165 kw.

HYDRONIC RESIDENTIAL

O L R E RGA ST RA N AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION TECHNICAL MANUAL

Air Cooled Chillers & Heat Pumps WinPACK HE-A

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

ERAH MC Ka. Range kw. AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS FOR OUTDOOR INSTALLATION (Standard line)

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

LDK LDK. Air to water chillers and heat pumps VERSIONS ACCESSORIES

i-chiller 181 to 210 kw ic770 to ic780 ABOUT THE i-chiller RANGE RELIABILITY: ENERGY & PROCESS EFFICIENCY: EASE OF OPERATION & MAINTENANCE:

MAC N-407 Air-Cooled Chiller

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

PURESTREAM CHILL-CUBE TM BY FRIULAIR

kw. technicalcatalogue

HIWARM COMPACT kw

Compact and silent Scroll compressors All-season operation

environmental climate control equipment & solutions AQUACOOL Water-to-water heat pump with passive energy recovery

Multi-pipe Units with Scroll Compressors. Model CMAA Cooling capacity kw Heating capacity kw

AQUACIAT. Inverter Heat pump USE RANGE GRAND INVERTER

ULTIMATE ENERGY SAVING TECHNOLOGY

SyScroll Air EVO NEW

LZT High efficiency air to water heat pumps with E.V.I. compressors

Transcription:

TECHNICAL INSTRUCTIONS CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw CHG 1 CHG 1 8. kw. kw.7 kw 1. kw April 7 19 - GB - 2

MARKING This product marked conforms to the essential requirements of the Directives: - Low voltage no. /9/EC. - Electromagnetic Compatibility no. 89/ EEC, modified 92/1 and 9/8 EEC. SUMMARY 1 - Application - Use...................................... 2 2 - Presentation......................................... - Technical characteristics................................ - Physical characteristics................................. - Description.......................................... - Cooling performances.................................. 7 - Corrections to be made when using anti-freeze..............7 8 - Curves of available pressures............................7 9 - Sound levels.........................................8 - Accessories..........................................8 - "ECH" electronic control.................................8 APPLIANCES FILLED WITH R A R A R A is a high-pressure refrigerant (+ % in relation to R 22 and R 7 C). The compressors approved for operation with this fluid are filled beforehand with polyalcohol oil. Contrary to mineral oil, it is very hygroscopic: it absorbs the humidity of the ambient air very quickly. This can modify its lubricant properties and lead in time to the destruction of the compressor. MAINTENANCE INSTRUCTIONS 1 - Never add oil to the appliance; the compressor is filled with polyalcohol oil, a special oil which cannot tolerate the presence of other oils. 2 - The instruments used for: - filling, - pressure measurements, - emptying under vacuum, - recovering the fluid, must be compatible and only used for the R A fluid. Note: the pressure taps of the refrigerating circuit are /1 SAE (1/2 - - UNF) - In the case of a new charge: - the charge must be undertaken in liquid phase, - use a balance and a dip pipe type R A cylinder, - charge the weight of R A as per the value indicated on the unit s identification plate (for split systems, refer to the installation instructions as the charge must consider the length of the connecting lines). - In case of leakage, do not complete the charge: recover the remaining refrigerant for recycling and perform a total charge. Recovery, recycling or the destruction of the fluid must be done in compliance with the laws in force in the country concerned. - If the refrigerant circuit is opened, you must: - avoid the entry of air into the circuit as much as possible, - replace or install a drier, - perform the vacuum operation at a minimum level of. mbar (static). 1 - APPLICATION - USE This appliance generates chilled water for the air-conditioning of premises, using terminal units. 2

2 - PRESENTATION 2.1 - DESCRIPTION 1 - Sound-proofed hermetic compressor. 2 - Plate water heat exchanger. - "Plate-Fin" air heat exchanger. - Fan motor. - Fan protection grille. - Electrical box. 7 - Microprocessor control unit display keyboard. 8 - Circulating pump. 9 - Expansion tank. - Safety valve. - Pressure gauge. - Water inlet connector. - Water outlet connector. 1 - Filling / drainage of the water circuit. 1 - Air vent. 1 - Hole for connecting cables. Materials: - Copper piping. - Painted sheet metal cabinet. - Copper/aluminium air heat exchanger. - Stainless steel water heat exchanger. - Plastic grille. 7 9 1 8 1 1 1 2 CHG 1 1 7 9 1 8 1 1 2 NOTE: The units are supplied with a water filter which is to be installed on the water intake. 2.2 - ELECTRICAL EQUIPMENT Per EN -2-. "ECH" electronic control with fan speed control Pressure safety cutout. Water flow detector.

- TECHNICAL CHARACTERISTICS Model CHG 1 GHG 17 Cooling capacity kw 8...7 1. Nominal power consumption* kw. /..2.2.2 EER* 2.2 / 2.28 2.9 2. 2.2 Total Max. 1-phase kw. _ power consumption -phase kw.. 7. 8.7 Total Max. 1-phase A 2 _ current consumption -phase A 9 1 17 Nominal water flow m /h 1. 1.91 2. 2.81 - m /s.9.. 7. Available pressure kpa 2 8 7 (*) Gross value (without circulator) Single-phase / Three-phase NOMINAL OPERATING CONDITIONS Outside air temperature (dry): + C Water outlet temperature: + 7 C NOTE: Water system pressure: 1. to bar. OPERATING LIMITS (pure water) (*) Max. outside air temperature (dry): + C Min. outside air temperature (dry): - C ( and CHG 1); - 7 C (); - C () Max. water outlet temperature for C external: + 1 C Max. water outlet temperature for C external: + 18 C Min. water outlet temperature: + C (*) The limits indicated are those of the machine. - PHYSICAL CHARACTERISTICS Model CHG 1 Dimensions L mm 1,19 1,19 1,19 1,19 H mm 7 1,2 1,2 1,2 P mm Weight kg 87 1 Dimensions L mm 1,27 1,27 1,27 1,27 packaged H mm 9 1, 1, 1, P mm Weight kg 99 L P H H 7 8 Fastening L P 1 Water inlet connection (male) 2 Water outlet connection (male) with air vent valve Water circuit fill/drain Holes for electric cables CHG 1 2 9 18 1 2 Rear view 18 1 Rear view

- DESCRIPTION Model CHG 1 Hermetic "SCROLL" compressor with thermal protection Sound insulation cover Power supply 2V/1/Hz _ V/N/Hz Start-up current 1-phase A 97 _ -phase A 8 7 1 Start-up current with kit single-phase start-up (accessory) Direct drive propeller fan motor with thermal protection, horizontal blowing Total air flow m /h,,,, m /s.8 1.7 1.7 1.7 Propellor diameter mm Power supply 2V/1/Hz Rotation speed rpm 77 77 77 77 Current A.7 1. 1. 1. Power input kw..2.2.2 Water capacity litres.7.8 1. 1. Expansion system expansion valve Air exchanger with louver fins Water exchanger Plate-type stainless steel water treatment section Charged internal cooling system with HP and LP switch R A refrigerant Total charge A _ kg 1.8.. 2.8 Current A.8 1 1. 1. Power input kw.1.2.28.2 Power supply 2V/1/Hz Circulating pump Capacity litres 2 2 2 2 Expansion tank (charge pressure 1. bar) Safety valve (pressure bar) Pressure gauge ( to bar) Air vent valve Hydraulic system 1 2 2 1 1 Male connections inlet /" 1" 1" 1" outlet /" 1" 1" 1" Water capacity of the unit litres 2.2 2. 2.8.2 Water flow rate detection pressure differential cut-out Water filter supplied, uninstalled Water volume in system Minimum water volume (*) litres Maximum water volume (**) litres Mains power supply Power supply 2V/1/Hz _ Equipment protection index V/N/Hz IP 2 IP 2 IP 2 IP 2 (*) If the water volume of the system is below the minimum, a buffer tank must be installed. (**) If the water volume of the system is above the maximum, an additional expansion tank is required. 2 1 1

- COOLING PERFORMANCES COOLING CAPACITY INPUT POWER Cooling capacity (kw) 9 8 Total input power (kw).. 7 2. 2 Cooling capacity (kw) 18 17 1 1 1 Total input power (kw)... 9 CHG 1 Cooling capacity (kw) 19 18 17 1 1 Total input power (kw) 7.. 1. Cooling capacity (kw) 2 22 22 21 19 18 17 1 1 1 Total input power (kw) 8 7. 7..

7 - CORRECTIONS TO BE MADE WHEN USING ANTI-FREEZE (Cooling mode) IMPORTANT : Use monopropylene glycol. A minium rate of 1% to % is needed to avoid any risk of corrosion. Correction factors 1. 1. 1.19 Pressure drop 7.1 - PRINCIPLE OF USING THE CURVES Choose the percentage of monopropylene glycol according to the minimum temperature to protect the hydraulic circuit against frost and determine the coefficients to be applied to the power, the water flow rate and the pressure drop. 1.1 1. Water flow 7.2 - EXAMPLE Protection at an external temperature of -1 C, which gives % glycol ("Freezing points" curve). The "Reduction of cooling capacity" curve gives the coefficient to be applied to the refrigerating capacity (.9). The "Water flow" curve gives the coefficient to be applied to the water flow rate (1.1). The "Pressure drop" curve gives the coefficient to be applied to the pressure drop (1.19). Curves valid for temperature control on the water intake. Outdoor temperature C Reduction of cooling capacity 1..9-2 - Freezing points -1 - - % in weight of Monopropylene Glycol 8 - CURVES OF AVAILABLE PRESSURES (on unit's outlet) Available pressure (kpa) 9 7 Available pressure (kpa) 1 1 9 7 Speed Speed Speed 1 Speed 2 Speed 1 Speed 2. 1 1. 2 Water flow rate (m /h).2...8 1 1.2 1. 1. 1.8 2 2.2 2. Water flow rate (m /h) 7

CHG 1 Available pressure (kpa) 1 1 9 7 Available pressure (kpa) 1 1 9 7 Speed Speed 2 Speed 1. 1 1. 2 2. Water flow rate (m /h) Speed 1 Speed 2. 1 1. 2 2... Water flow rate (m /h) 9 - SOUND LEVELS Model Power level Sound-pressure level Lw (dba) Lp (dba) 7 7 9 CHG 1 7 9 7 9 Sound-pressure level: Unit installed outdoors (free field) on a reflective surface. Measurement carried out at a distance of m. db to be deducted from the sound power level 2 1 2 Distance in metres - ACCESSORIES CHG 1 Set of 2 flexible hoses length 1 m Ø /" _ Insulated tank liters Single start-up kit (for single-phase model) Remote control RS 8 communication interface length 1 m Ø 1" _ _ (MODBUS protocol) - "ECH" ELECTRONIC CONTROL Microprocessor control module, including: - chilled water temperature control (water return), - control of operating parameters, - self-adapting algorithm for water volume reduction, - circulating pump control (frost protection and anti-sticking function), - dynamic setpoints are possible according to the outside temperature (to be activated at the time of installation by means of special parameterization), - anti-short cycle system, - hour counter compressor and circulating pump, - alarm management, - anti-freeze security (water exchanger), - digital display of :. water temperature,. set-point,. alarm code (HP, LP, water output, probes, anti-freeze...). - remote alarm reporting is possible via a potential-free contact, - integrated condensation pressure control, - remote control with display unit (accessory), - serial communications port (RS 8 interface, accessory). Due to our policy of continuous development, our products are liable to modification without notice. R.D. 28 Reyrieux BP 1 Trévoux CEDEX France Phone 7 92 92 - Fax 7 2 R.C.S. Bourg-en-Bresse B 79 728