UL LISTED. SPRINKLER HEADS IN STOCK: Pendent Upright Horizontal sidewall Concealed. RESPONSE Quick response Standard response

Similar documents
Automatic Sprinklers

Automatic Sprinklers

MODEL: FA003U FA004U FA005P FA006P STANDARD SPRAY, STANDARD QUICK RESPONSE, 5 3 mm BULB TYPE, K5.6, 1/2" CONNECTING THREAD

MODEL: FA007C FA008C STANDARD SPRAY, STANDARD QUICK RESPONSE, 5 3 mm BULB TYPE, K5.6, 1/2" CONNECTING THREAD WRENCH FLAT

Sprinkler Identification Numbers. TY3351 Horizontal TY3451 Vertical. Technical Data

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Horizontal Sidewall Wet Pipe and Dry Pipe Systems General Description

WRENCH FLATS 1/2" NPT. 7/16" (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE

Sprinkler Identification Number. Page 1 of 6 AUGUST 2018 TFP288. Worldwide Contacts.

Sprinkler Identification Numbers

RAPID RESPONSE Series LFII Residential Sprinklers 5.6 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

Series TY-FRB 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General Description

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

WRENCH FLATS NPT 1/2" 7/16" (11,1 mm) NOMINAL MAKE-IN. 1-1/2" (38,1 mm) 2-3/16" (55,6 mm) WRENCH NPT. (12,7 mm) NOMINAL MAKE-IN.

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response)

WRENCH FLATS 1/2" NPT. 7/16" (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE

* Temperature rating is FIGURE K-FACTOR QUICK RESPONSE SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLERS

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description

Series DS-1 Stainless Steel Dry-Type Sprinklers 5.6K Pendent, HSW, and Extended Coverage HSW Standard and Quick Response General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

ESCUTCHEON PLATE SEATING 3/4" NPT SURFACE. 1-1/2" (38,1 mm) CROSS SECTION PENDENT RECESSED PENDENT

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

special request FACTORY ASSEMBLED UPRIGHT WITH SCREW FIELD ASSEMBLED MODEL S2 SHIELD (SEE INSTALLATION SECTION) WRENCH FLATS *

Page 1 of 8 DECEMBER 2018 TFP408. Worldwide Contacts.

Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description

Sprinkler Identification Number (SIN)

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

Sprinkler Identification Numbers

O-RING UPRIGHT SHIELD WRENCH FLATS WRENCH FLATS FIGURE 1 SERIES TY-B UPRIGHT (TY3153) AND PENDENT (TY3251) SPRINKLERS

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16" (42,7 mm) CROSS SECTION

Series TY-B & TY-FRB, 10 mm Orifice, ISO 7/1-R3/8 Upright, Pendent, and Recessed Pendent Sprinklers Standard and Quick Response General Description

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

Sprinkler Identification Number TY ECLH HSW, 8.0K, 3/4"NPT

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Model/Sprinkler Identification Numbers

Model/Sprinkler Identification Number JULY, 2011 WARNINGS

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description

Submittal Packages Detailed with Items and Reviewers

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description

Series DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage General Description

Model CHEC 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers General Description

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard)

FIGURE 1 MODEL RFIII ECLH CONCEALED HSW SPRINKLER ASSEMBLY AND FEATURES. 5/16" (7,9 mm) MIN. 9/16" (14,3 mm) MAX.

RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description

Residential Flush Horizontal Side-Wall Sprinkler Model HF-RES,K=4.2 (SIN / SS4423) (PTFE gasketed orifice seal design)

SENJU SPRINKLER CO.,LTD. Residential Flush Pendent Sprinkler Model ZN-RES,K=4.2 (SIN / SS4421) (PTFE gasketed orifice seal design) General Description

Series LFII Residential Pendent Sprinklers 4.9 K-factor General Description

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

Series TY-FRL 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Exaggerated for Clarity. Residential Pendent, Recessed Pendent. System No. Submitted By Spec Sect Para Location Date Approved Date

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

SENJU SPRINKLER CO., LTD.

40.49 V27, K5.6 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS. Residential Horizontal Sidewall, Recessed Horizontal Sidewall V2744 QUICK RESPONSE

MICROFAST SR/QR EXTENDED COVERAGE HSW SPRINKLER VK605 (K5.6) TECHNICAL DATA

Model WS TM 5.6 K-factor Specific Application Window Sprinklers, Horizontal and Pendent Vertical Sidewall General Description

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description

The Series LFII (TY3596) Residential

Model TY-FRFS, TY-FS Special, and TY-FS 57, 80, and 115 K-factor Upright and Pendent Flat Spray Sprinklers General Description

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK486 (K4.0) TECHNICAL DATA

Sprinkler Identification Number (SIN) TY4234. Page 1 of 8 APRIL 2012 TFP Technical Services

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-Factor General Description

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE LIGHT HAZARD ELO PENDENT SPRINKLER VK608

PACKAGED SOLUTIONS FOR FIRE PROTECTION, PLUMBING AND BUILDINGS

TECHNICAL DATA. Refer to Approval Chart 1 and Design Criteria for culus Listing requirements that must be followed.

DISCONTINUED PRODUCT

Model TY-FRFS, TY-FS Special, and TY-FS Flat Spray Sprinklers, Upright and Pendent 57, 80, and 115 K-factor General Description

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK494 (K4.9) TECHNICAL DATA

40.10 V27, K5.6. Standard Spray; Upright, Pendent and Recessed Pendent. System No. Submitted By Spec Sect Para Location Date Approved Date

TECHNICAL DATA 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA

Special Features: For Light Hazard Occupancies Only Designed for Corridor Applications 28 Maximum Width Spacing. 3. technical data

micromatic Standard response Horizontal Sidewall sprinkler

SPRINKLER HEAD. Upright, Pendent & Recessed Pendent Sprinklers MODEL: SD1010, SD1015, SD1030, SD1032 DESCRIPTION TECHNICAL SPECIFICATION

SENJU SPRINKLER CO.,LTD. Residential Flush Pendent Sprinkler Model ZN-RES,K=4.2 (SIN / SS4421) (PTFE gasketed orifice seal design) General Description

Norminal Sprinkler Temperature Rating

40.50 V38, K5.6. Adjustable Concealed Standard Spray Pendent Standard and Quick Response

mirage standard response concealed pendent sprinkler vk492 (K5.6)

STANDARD/quick. Sprinkler 42o. August 8, 2011

Series LFII Residential Horizontal Sidewall Sprinklers 4.4 K-factor General Description

Microfast quick response Fusible element hsw sprinkler

Series LFII Residential Horizontal Sidewall Sprinklers 4.2 K-factor General Description

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed.

MicrofastHP QUICK RESPONSE HORIZONTAL SIDEWALL HIGH PRESSURE SPRINKLER VK319 (K5.6) TECHNICAL DATA

Transcription:

SPRINKLER HEADS SMOOTHFLOW AUSTRALIA SPRINKLER HEADS IN STOCK: Pendent Upright Horizontal sidewall Concealed RESPONSE Quick response Standard response COLOURS Natural brass Chromed Power coated white TEMPERATURE 68 o C 79 o C 93 o C BULBS & SPRING SEALS: Manufactured by German company - The JOB GmBH: Their web is www.job-bulbs.com UL LISTED TWO PIECE ESCUTCHEONS Two piece slip-on style Recessed Escutcheons Depth of Outer Cup: 27 mm Outside Diameter of Outer Cup: 76 mm Depth of Center Adapter Ring: 9 mm +/- 0.8 mm Adjustment Range: Flush to 18 mm recessed www.smoothflow.com.au Tel: 02-9605 2288 info@smoothflow.com.au Page 34

TD01516 PIN: NX003-NX006 UPRIGHT SPRINKLERS AND PENDENT SPRINKLERS MODEL: NX003 / NX004 / NX005 / NX006 STANDARD SPRAY, STANDARD / QUICK RESPONSE, 5 / 3 mm BULB TYPE, K5.6, 1/2" CONNECTING THREAD GENERAL DESCRIPTION The NX003/NX004 Standard/Quick Response Upright and NX005/NX006 Standard/Quick Response Pendent Sprinklers (Ref. Figure A) are automatic sprinklers of the frangible bulb type. They are standard/quick response standard orifice spray sprinkler intended for use in fire sprinkler systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on NFPA 13 requirements). The Upright, Pendent Sprinklers all produce a hemispherical water distribution pattern below the deflector. 1-13/32" ( 35.5mm ) WRENCH FLAT SPRINKLER OPERATION During a fire conditions, the thermal-sensitive liquid in the glass bulb expands, causing the bulb to shatter, releasing the button and spring seal assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. COVERAGE For coverage area and sprinkler placement, refer to NFPA13 standards. ESCUTCHEON RING SEATING SURFACE 1/2" PIPE THREAD 1-19/32" ( 40.9mm ) 2-1/4" ( 56.9mm ) 1 2 3 4 5 6 CENTERLINE OF WATERWAY 7 1-11/16" ( 42.5mm ) 2-5/16" ( 58.2mm ) 8 UPRIGHT 1/2" PIPE THREAD 27/32" ( 21.8mm ) CROSS SECTION 1-1/4" ( 31.5mm ) PENDENT 2-15/16" (75mm ) TYPICAL INSTALLATION 1.SSU DEFLECTOR 2.SET SCREW 3.GLASS BULB 4.FRAME 5.BUTTON 6.SPRING SEAL 7.SSP DEFLECTOR 8.STANDARD ESCUTCHON FIGURE A : MODEL NX003/NX004 UPRIGHT & MODEL NX005/NX006 PENDENT SPRINKLERS TECHNICAL SPECIFICATIONS Model & Sprinkler I.D. No. NX003 NX004 NX005 NX006 Style Upright Pendent Bulb Nominal Dia. & Response Ø5mm, Standard Ø3mm, Quick Ø5mm, Standard Ø3mm, Quick Response Response Response Response Thread Size [Optional] NPT1/2 or R12 Nominal Orifice Size 1/2 Inch Nominal K-Factor 5.6 (U.S.) 80 (metric) Max. Working Pressure 175 psig 1.2 MPa (12 bar) Factory Hydrostatic Test 100% @ 500psig (3.4 MPa) Min. Operating Pressure 7 psig 0.048 MPa (0.48 bar) Sprinkler Finish [Optional] Natural Brass Chrome Plated White Color Coated SMOOTHFLOW AUSTRALIA PTY LTD TEL: 02-9605 2288 SHEET TD01516 13 HEALD ROAD, INGLEBURN, NSW 2565 info@smoothflow.com.au www.smoothflow.com.au

TD01516 PIN: NX003-NX006 Escutcheon Finish Listings and Approvals AVAILABLE TEMPERATURE RATING Chrome Plated or Color Coated In Any Color UL(United States) ULC(Canada) Temp. Classification Ordinary Ordinary Intermediate Intermediate Nominal Temp. Rating 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C Max. Ambient Temp. Allowed 5 115 F 46 C 135 F 57 C 155 F 68 C 180 F 82 C Max. Recommended Ambient Temp. 6 100 F 38 C 100 F 38 C 150 F 65 C 150 F 65 C Glass Bulb Color 7 Orange Red Yellow Green Footnotes: 1 Sprinkler I.D. Nos. and nominal U.S. K-factors provided in accordance with the 2002 edition of NFPA 13. 2 The pipe thread connections accord with ISO7/1. 3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. 4 UL and ULC Listed for both Light-Hazard and Ordinary-Hazard occupancies. 5 Based on National Fire Prevention and Control Administration Contract No. 7-34860. 6 Based on NFPA 13. Other limits may apply depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 7 The temperature rating is stamped on the deflector or adjacent to orifice seat on frame. SPRINKLER MATERIALS Bronze Forging UNS-C87400 Frame or Casting DZR Deflector Brass UNS-28000 Glass with Glycerin Solution, JOB G5 or Day-Impex-937 for Glass Bulb NX003/ NX005 JOB F3 0r Day-Impex-941 for NX004/ NX006 Set Screw Brass UNS-28000 Button Brass UNS-28000 Spring Stainless Steel Seal Teflon Tape Standard Escutcheon Cold Rolled Steel (Type E-1) ACCESSORIES Standard Escutcheon Type E-1 Installation Wrench Type T-1 DISCHARGE COEFFICIENT Model NX003/NX004 Upright and Model NX005/NX006 Pendent Sprinklers are rated for use at a maximum service pressure of 175 psig (12 bar). The nominal discharge curve plotted in Figure B represents the flow Q in GPM (LPM) as determined by the following formula: Q=K(P) 0.5 Where: DISCHARGE IN U.S. GALLONS PER MINUTE (GPM) 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 PRESSURE IN POUNDS PER SQUARE INCH (PSIG) 10 30 50 70 90 110 130 150 170 280 PARTIAL CURVE ONLY MAX. PRESSURE 175 PSIG 260 240 220 200 180 160 140 120 100 80 60 40 PARTIAL CURVE ONLY 20 MAX. PRESSURE 1.2 MPA 0.2 NOMINAL K=5.6 NOMINAL K=80 0.4 0.6 0.8 1.0 1.2 PRESSURE IN MPA FIGURE B : NOMINAL DISCHARGE CURVE Q Flow, GPM (LPM) K Discharge Coefficient, K=5.6 (80) P Discharge Pressure, psig (bar) Listing standards permit the actual value of K to vary from 5.3 to 5.8 (76,4 to 83,6); however, for hydraulic calculations, a K-factor of 5.6 (80,7) is to be applied. DISCHARGE IN LITERS PER MINUTE (LPM) SMOOTHFLOW AUSTRALIA PTY LTD TEL: 02-9605 2288 SHEET TD01516 13 HEALD ROAD, INGLEVURN, NSW 2565, info@smoothflow.com.au www.smoothflow.com.au

TD01516 PIN: NX003-NX006 WARNING The Model NX003/NX004 Upright Sprinklers and Model NX005/NX006 Pendent Sprinklers described herein must be installed and maintained in compliance with this document, as well as applicable standards of the National Fire Protection Association, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the integrity of these devices. impairment of the sprinkler. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or manufacturer should be contacted relative to any questions. INSTALLATION NOTES Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontal, a small air bubble should be present. The Model NX003/NX004 Upright Sprinklers and Model NX005/NX006 Pendent Sprinklers must be installed in accordance with the following instructions. 1. Prior to installing the sprinklers, if applicable, verify that the face of the sprinkler fitting is within the proper range of distance, which can be accommodated by the type of escutcheon being used. 2. With pipe thread sealant applied to the pipe threads and after installing standard escutcheon, over the sprinkler threads, hand tighten the sprinkler into the sprinkler fitting. 3. Refer to Figure D and select the appropriate Sprinkler Wrench for tightening the sprinkler into the sprinkler fitting. NOTES A leak tight 1/2 pipe thread sprinkler joint should be obtained with a torque of 7 to 14 ft.lbs. (9.5 to 19.0 Nm). A maximum of 21 ft.lbs. (28.5 Nm) of torque is to be used to install the sprinkler. Higher levels of torque may distort the sprinkler inlet with consequent leakage or TYPICAL INSTALLATION FIGURE C : MODEL NX005/NX006 PENDENT SPRINKLER INSTALLED WITH A STANDARD ESCUTCHEON SPRINKLER WRENCH T-1 FIGURE D : SPRINKLER WRENCH SELECTION & USE Push on the Sprinkler Wrench, while it is being turned, to ensure that the Wrench recess stays fully engaged with the sprinkler wrench flats. Carefully remove the Sprinkler Wrench by disengaging it from the sprinkler wrench flats, and then lowering it down over the sprinkler deflector. CARE AND MAINTENANCE Automatic sprinklers must never be shipped or stored where their temperatures will exceed SMOOTHFLOW AUSTRALIA PTY LTD TEL: 02-9605 2288 SHEET TD01516 13 HEALD ROAD, INGLEBURN, NSW 2565 info@smoothflow.com.au www.smoothflow.com.au

TD01516 PIN: NX003-NX006 100 F/38 C and they must never be painted, plated, coated or otherwise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers both before and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb (ref. Installation Section Note). NOTES Absence of an escutcheon, which is used to cover a clearance hole, may delay the time to sprinkler operation in a fire situation. Before closing a fire protection system control valve for maintenance work on the fire protection system, which it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. It is recommended that automatic sprinkler systems be inspected quarterly by a qualified Inspection Service. ORDERING PROCEDURE A Product Symbol Number (PSN) shall be specified when ordering sprinklers. And it is suggested that a color chip be provided when ordering special color coated Escutcheons. Otherwise, responsibility for duplication cannot be accepted. Contact your local distributor for availability. Sprinkler Assemblies: Specify: 1/2" orifice, (specify temperature rating), Model NX003/NX004 Upright Sprinklers with (specify type of finish), PSN (specify as follows). NX003/NX004 Standard/Quick Response Upright Sprinklers : PSN 012 X 1 13 X 2 X 3 X 1 Response Frame 1 Standard Response UNS-C87400 2 Quick Response,UNS-C87400 3 Standard Response DZR 4 Quick Response DZR X 2 Class Bulb and Nominal Temperature Rating 1 Job,135 F 57 C 2 Job,155 F 68 C 3 Job,175 F 79 C 4 Job,200 F 93 C 5 Day-Impex,135 F 57 C 6 Day-Impex,155 F 68 C 7 Day-Impex,175 F 79 C 8 Day-Impex,200 F 93 C X 3 Thread Size and Sprinkler Finish 1 NPT1/2 Natural Brass 2 NPT1/2 Chrome Plated 3 R12 per ISO 7/1 Natural Brass 4 R12 per ISO 7/1 Chrome Plated 5 NPT1/2 White Color Coated 6 R12 White Color Coated NX005/NX006 Standard/Quick Response Pendent Sprinklers : PSN 012 X 1 23 X 2 X 3 X 1 Response and Frame 1 Standard Response UNS-C87400 2 Quick Response,UNS-C87400 3 Standard Response DZR 4 Quick Response DZR X 2 Class Bulb and Nominal Temperature Rating 1 Job,135 F 57 C 2 Job,155 F 68 C 3 Job, 175 F 79 C 4 Job, 200 F 93 C 5 Day-Impex, 135 F 57 C 6 Day-Impex, 155 F 68 C 7 Day-Impex, 75 F 79 C 8 Day-Impex, 200 F 93 C X 3 Thread Size and Sprinkler Finish 1 NPT1/2 Natural Brass 2 NPT1/2 Chrome Plated 3 R12 per ISO 7/1 Natural Brass 4 R12 per ISO 7/1 Chrome Plated 5 NPT1/2 White Color Coated 6 R12 White Color Coated Accessories: SMOOTHFLOW AUSTRALIA PTY LTD TEL: 02-9605 2288 SHEET TD01516 13 HEALD ROAD, INGLEBURN, NSW 2565 info@smoothflow.com.au www.smoothflow.com.au

TD01516 PIN: NX003-NX006 Order the following accessories, as applicable: Type E-1 1/2" Standard Escutcheon with chromate finishes: PSN 0608 111 Type E-1 1/2" Standard Escutcheon with white painted finish: PSN 0608 112 Type T-1 Wrench: PSN0109 WEIGHT The nominal weights are as follows. 1/2" Orifice Model NX003/ NX004 Upright 2.8 ozs. (80 g) 1/2" Orifice Model NX005/ NX006 Pendent 2.8 ozs. (80 g) E-1 Standard Escutcheon 0.6 ozs. (18 g) T-1 Sprinkler Wrench 18 ozs. (510 g) CONVERSION TABLE Name of Unit Unit Conversion Symbol Factor Millimeter mm 1 in.=25.4 mm Square meter m 2 1 ft 2 =0.0929 m 2 Liter L 1 gal=3.785 L Cubic decimeter dm 3 1 gal=3.785 dm 3 Cubic meter m 3 1 ft 3 =0.0283 m 3 Kilogram kg 1 lb=16 ozs.=0.4536 kg Kilograms per cubic meter Kg/m 3 1 lb/ft 3 =16.0183kg/m 3 Pascal Pa 1 psi=6895 Pa Bar bar 1 psi=0.0689 bar Newton meter N m 1 ft lbs=1.355 N m This! WARNING product must be installed by an experienced, trained installer, in accordance with the instructions provided with each valve. These instructions contain important information. Failure to follow these instructions may result in serious personal injury, property damage, or valve leakage. We reserve the right to change product specifications, designs and standard equipment without notice and without incurring obligations. If you have any questions about the safe installation and use of this device, contact Smoothflow Australia. SMOOTHFLOW AUSTRALIA PTY LTD TEL: 02-9605 2288 SHEET TD01516 13 HEALD ROAD, INGLEBURN, NSW 2565 info@smoothflow.com.au www.smoothflow.com.au

TD01518 PIN: NX017/NX018 HORIZONTAL SIDEWALL SPRINKLERS MODEL: NX017 / NX018 STANDARD SPRAY, STANDARD / QUICK RESPONSE, 5 / 3 mm BULB TYPE, K5.6, 1/2" CONNECTING THREAD GENERAL DESCRIPTION Horizontal sidewall sprinklers are generally used in lieu of pendent and upright sprinklers because of building construction or installation economy considerations. They are designed for installation along a wall or the side of a beam and just beneath a smooth ceiling. Installed with their centerline of waterway horizontal, these sprinklers produce a quarter-spherical water discharge pattern that is predominately directed downward and outward from the deflector; however, a portion of the spray is also directed towards the back wall. Model NX017 / NX018, Standard / Quick Response Horizontal Sidewall Sprinklers (Ref. Figure A), are automatic sprinklers of the frangible bulb type, and standard spray, 1/2 orifice, 5 / 3 mm bulb. They are standard / quick response - standard orifice sidewall sprinklers intended for use in fire sprinkler systems designed in accordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on NFPA 13 requirements). SPRINKLER OPERATION During a fire conditions, the thermal-sensitive liquid in the glass bulb expands, causing the 1 2 3 4 5 6 9/16"(14mm) CENTERLINE OF WATERWAY 2-1/8" (54mm) 2-3/4" (70mm) 1/2" PIPE THREAD 1.DEFLECTOR 2.SET SCREW 3.GLASS BULB 4.SPRING SEAL 7/8"(22mm) WRENCH FLAT 5.BUTTON 6.FRAME FIGURE A : MODEL NX017/NX018 HORIZONTAL SIDEWALL SPRINKLERS bulb to shatter, releasing the button and spring seal assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. COVERAGE For coverage area and sprinkler placement, refer to NFPA13 standards. TECHNICAL SPECIFICATIONS Model & Sprinkler I.D. No. NX017 NX018 Style Horizontal Sidewall Response & Bulb Nominal Dia. Standard Response, Ø5 mm Quick Response, Ø3 mm Thread Size [Optional] NPT1/2 or R12 Nominal Orifice Size 1/2 Inch Nominal K-Factor 1 5.6 (U.S.) 80 (metric) Max. Working Pressure 175 psig 1.2 MPa (12 bar) Factory Hydrostatic Test 100% @ 500psig (3.4 MPa) Min. Operating Pressure 7 psig 0.048 MPa (0.48 bar) Sprinkler Finish [Optional] Natural Brass or Chrome Plated White Color Coated Listings and Approvals UL(United States) ULC(Canada) SMOOTHFLOW AUSTRALIA PTY LTD Tel: 02-9605 2288 Technical Data Sheet TD01518 13 Heald Road, Ingleburn NSW 2565 info@smoothflow.com.au www.smoothflow.com.au

TD01518 PIN: NX017/NX018 AVAILABLE TEMPERATURE RATING Temp. Classification Ordinary Ordinary Intermediate Intermediate Nominal Temp. Rating 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C Max. Ambient Temp. Allowed 5 115 F 46 C 135 F 57 C 155 F 68 C 180 F 82 C Max. Recommended Ambient Temp. 6 100 F 38 C 100 F 38 C 150 F 65 C 150 F 65 C Glass Bulb Color 7 Orange Red Yellow Green Footnotes: 1 Sprinkler I.D. Nos. and nominal U.S. K-factors provided in accordance with the 2002 edition of NFPA 13. 2 The pipe threads connections accord with ISO7/1. 3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. 4 UL and ULC Listed for both Light-Hazard and Ordinary-Hazard occupancies. 5 Based on National Fire Prevention and Control Administration Contract No. 7-34860. 6 Based on NFPA 13. Other limits may apply depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 7 The temperature rating is stamped on the deflector or adjacent to orifice seat on frame. Note: Locate with deflectors 4 to 6 (100mm to 150mm) from walls. Align horizontal sidewall sprinklers with top of deflectors parallel to the ceiling or roof. SPRINKLER MATERIALS Frame Deflector Glass Bulb Set Screw Button Spring Seal Standard Escutcheon (Type E-1) ACCESSORIES Bronze Casting DZR Brass UNS-28000 Glass with Glycerin Solution, JOB G5 or Day-Impex-937 for NX017 JOB F3 0r Day-Impex-941 for NX018 Brass UNS-28000 Brass UNS-28000 Stainless Steel Teflon Tape Cold Rolled Steel Standard Escutcheon Type E-1 Installation Wrench Type T-1 DISCHARGE COEFFICIENT Model NX017/NX018 Horizontal Sidewall Sprinklers are rated for use at a maximum service pressure of 175 psig (12 bar). The nominal discharge curve plotted in Figure B represents the flow Q in GPM (LPM) as determined by the following formula: Q=K(P) 0.5 Where: Q Flow, GPM (LPM) K Discharge Coefficient, K=5.6 (80) P Discharge Pressure, psig (bar) DISCHARGE IN U.S. GALLONS PER MINUTE (GPM) 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 PRESSURE IN POUNDS PER SQUARE INCH (PSIG) 10 30 50 70 90 110 130 150 170 280 PARTIAL CURVE ONLY MAX. PRESSURE 175 PSIG 260 240 220 200 180 160 140 120 100 80 60 40 PARTIAL CURVE ONLY 20 MAX. PRESSURE 1.2 MPA 0.2 NOMINAL K=5.6 NOMINAL K=80 0.4 0.6 0.8 1.0 1.2 PRESSURE IN MPA FIGURE B : NOMINAL DISCHARGE CURVE Listing standards permit the actual value of K to vary from 5.3 to 5.8 (76.4 to 83.6); however, for hydraulic calculations, a K-factor of 5.6 (80.7) is to be applied. DISCHARGE IN LITERS PER MINUTE (LPM) SMOOTHFLOW AUSTRALIA PTY LTD Tel: 02-9605 2288 Techanical Data Sheet TD01518 13 Heald Road, Ingleburn, NSW 2565 info@smoothflow.com.au www.smoothflow.com.au

WARNING Automatic Sprinklers SPRINKLER FITTING TD01518 PIN: NX017/NX018 SPIRIT LEVEL The Model NX017/NX018 Horizontal Sidewall Sprinklers described herein must be installed and maintained in compliance with this document, as well as applicable standards of the National Fire Protection Association, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the integrity of these devices. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or manufacturer should be contacted relative to any questions. INSTALLATION NOTES Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontal, a small air bubble should be present. The diameter of the air bubble is approximately 1/16" (1.6mm) for the 135 F/57 C to 3/32" (2.4mm) for the 286 F/141 C rating. (At higher ambient temperatures, the bubble may be barely perceptible for the lower temperature ratings.) The Model NX017/NX018 Horizontal Sidewall Sprinklers must be installed in accordance with the following instructions. 1. Prior to installing the sprinklers, if applicable, verify that the face of the sprinkler fitting is within the proper range of distance, which can be accommodated by the type of escutcheon being used. 2. The Model NX017/NX018 Horizontal Sidewall Sprinklers must be installed with the centerline of waterway horizontal and perpendicular to a back wall surface. It is recommended that a lightweight spirit level (less than 1 pound), be used to level the sprinkler fitting, as shown in Figure D and that a square be used to check perpendicularity of the waterway centerline to the mounting surface. CENTERLINE OF WATERWAY 6" (150mm) OR LONGER NIPPLE DEFLECTOR FIGURE C: LEVELING OF SPRINKLER FITTING AND DEFLECTOR 3. With pipe thread sealant applied to the pipe threads and after installing standard escutcheon, over the sprinkler threads, hand tighten the sprinkler into the sprinkler fitting. 4. Refer to Figure E and select the appropriate Sprinkler Wrench for tightening the sprinkler into the sprinkler fitting. The word TOP on the Deflector must face upwards towards the ceiling. The Type T-1 Sprinkler Wrench must be used for installing Model NX017/NX018 sprinklers. When using T-1 type wrench, the wrench is to be applied to the sprinkler wrench flats only (Ref. Figure A). NOTES A leak tight 1/2 pipe thread sprinkler joint should be obtained with a torque of 7 to 14 ft.lbs. (9.5 to 19.0 Nm). The maximum installing torque shall not excess 21 ft.lbs. (28.5 Nm). Higher levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler. SMOOTHFLOW AUSTRALIA PTY LTD Tel: 02-9605 2288 Technical Data Sheet TD01518 13 Heald Road, Ingleburn, NSW 2565 info@smoothflow.com.au www.smoothflow.com.au

TD01518 PIN: NX017/NX018 SPRINKLER WRENCH T-1 valve for maintenance work on the fire protection system, which it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. It is recommended that automatic sprinkler systems be inspected quarterly by a qualified Inspection Service. ORDERING PROCEDURE FIGURE D : SPRINKLER WRENCH SELECTION & USE Push on the Sprinkler Wrench, while it is being turned, to ensure that the Wrench recess stays fully engaged with the sprinkler wrench flats. Carefully remove the Sprinkler Wrench by disengaging it from the sprinkler wrench flats, and then lowering it down over the sprinkler deflector. It is recommended that a spirit level be used to level the Deflector, as shown in Figure D. CARE AND MAINTENANCE Automatic sprinklers must never be shipped or stored where their temperatures will exceed 100 F/38 C and they must never be painted, plated, coated or otherwise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers both before and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb (ref. Installation Section Note). NOTES Absence of an escutcheon, which is used to cover a clearance hole, may delay the time to sprinkler operation in a fire situation. Before closing a fire protection system control A Product Symbol Number (PSN) shall be specified when ordering sprinklers. And it is suggested that a color chip be provided when ordering special color coated Escutcheons. Otherwise, responsibility for duplication cannot be accepted. Contact your local distributor for availability. Sprinkler Assemblies: Specify: 1/2" orifice, (specify temperature rating), Model NX017/NX018 Standard/Quick Response Horizontal Sidewall Sprinkler with (specify type of finish), PSN (specify as follows). NX017/NX018 Standard/Quick Response Horizontal Sprinklers : PSN 012 X 1 33 X 2 X 3 X 1 Response 3 Standard Response 4 Quick Response X 2 Class Bulb and Nominal Temperature Rating 1 Job,135 F 57 C 2 Job,155 F 68 C 3 Job,175 F 79 C 4 Job,200 F 93 C 5 Day-Impex,135 F 57 C 6 Day-Impex,155 F 68 C 7 Day-Impex,175 F 79 C 8 Day-Impex,200 F 93 C X 3 Thread Size and Sprinkler Finish 1 NPT1/2 Natural Brass 2 NPT1/2 Chrome Plated 3 R12 per ISO 7/1 Natural Brass 4 R12 per ISO 7/1 Chrome Plated 5 NPT1/2 White Color Coated 6 R12 White Color Coated SMOOTHFLOW AUSTRALIA PTY LTD Tel: 02-9605 2288 Technical Data Sheet TD01518 13 Heald Road, Ingleburn, NSW 2565 info@smoothflow.com.au www.smoothflow.com.au

TD01518 PIN: NX017/NX018 Accessories: Order the following accessories, as applicable: Type E-1 1/2" Standard Escutcheon with chromate finishes: PSN 0608 111 Type E-1 1/2" Standard Escutcheon with white painted finish: PSN 0608 112 Type T-1 Wrench: PSN0109 WEIGHT The nominal weights are as follows. 1/2" Orifice Model NX017/ NX018 Horizontal Sidewall 2.8 ozs. (80 g) E-1 Standard Escutcheon 0.6 ozs. (18 g) T-1 Sprinkler Wrench 18 ozs. (510 g) CONVERSION TABLE Name of Unit Unit Conversion Symbol Factor Millimeter mm 1 in.=25.4 mm Square meter m 2 1 ft 2 =0.0929 m 2 Liter L 1 gal=3.785 L Cubic decimeter dm 3 1 gal=3.785 dm 3 Cubic meter m 3 1 ft 3 =0.0283 m 3 Kilogram kg 1 lb=16 ozs.=0.4536 kg Kilograms per cubic meter Kg/m 3 1 lb/ft 3 =16.0183kg/m 3 Pascal Pa 1 psi=6895 Pa Bar bar 1 psi=0.0689 bar Newton meter N m 1 ft lbs=1.355 N m This! WARNING product must be installed by an experienced, trained installer, in accordance with the instructions provided with each valve. These instructions contain important information. Failure to follow these instructions may result in serious personal injury, property damage, or valve leakage. We reserve the right to change product specifications, designs and standard equipment without notice and without incurring obligations. If you have any questions about the safe installation and use of this device, contact Smoothflow Australia SMOOTHFLOW AUSTRALIA PTY LTD Tel: 02-9605 2288 Technical Data Sheet TD01518 13 Heald Road, Ingleburn, NSW 2565 info@smoothflow.com.au www.smoothflow.com.au