Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Similar documents
Manual Supplement. Product/System Title: Static Pressure Controller. Contents of this manual supplement include:

Model 8682-KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control

Manual Supplement. Product/System Title: Premium Clean Room Monitor. Contents of this manual supplement include:

SUREFLOW ADAPTIVE OFFSET CONTROLLER MODELS BAC

TSI Model 8630 PRESSURA Room Pressure Monitor Modbus Communications Application Note LC-106

RPM1600 Series Room Pressure Monitors

PRESSURA ROOM PRESSURE CONTROLLER MODELS 8630-SC 8630-PC

SUREFLOW ROOM PRESSURE CONTROLLER MODELS BAC

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

Critical Environments. Model FHC50/FHM10. Fume Hood Controller/Monitor. Operation and Service Manual. P/N , Revision B October 2010

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

PRESSURA ROOM PRESSURE CONTROLLER MODEL RPC30

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

PRESSURA ROOM PRESSURE MONITOR MODELS 8630-SM 8630-PM

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

Digital Precise Air Control - DPAC

Metasys Integrator TITUS Application

Verasys System Operation Overview Technical Bulletin

CONTENTS. Installation Guide. VT7200 Series

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.


SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

EVERWATCH FACE VELOCITY MONITOR MODEL 8610

Installer Manual KNX Touchscreen Thermostat

L SERIES UNITS 505,191M. 4/2006 Supersedes 504,908M

Table of Contents. W2W Open

L SERIES UNITS 504,908M. 10/2004 Supersedes 9/2004

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

VT8300 Series Installation Guide 24 Vac Low Voltage

Rev UltraSite User s Guide BCU Supplement

Selected Laboratory Energy Efficiency Measures

BACnet Points List for Single Compressor Water to Water PROSSWWE-01

BACnet Programmable TEC (PTEC) VAV Chilled Beam with Demand Control Ventilation (CO2) and Floating or Analog Output Owner s Manual

TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers

York 25-Ton VAV Rooftop Unit

HVAC Controls Laboratory. Model EVERWATCH Face Velocity Monitor. Operation and Service Manual. P/N , Revision E October 2002

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

VENSTAR T1070 FAN COIL THERMOSTAT PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

Reference Guide for Microprocessor Controller

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers

Installation & Calibration Guide

- Data Brochure Boiler Control 274

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1

VCB-X Modular Service Tool Technical Guide. VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2.

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

1.0 Digital Controller

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide

Reference Guide for Microprocessor Controller

MicroTech Rooftop/RMC

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

TEC Networked Multi-Stage Economizer Thermostat

Meridian wiredhart. HART Field Device Specification Goldmine Rd. Monroe, NC USA

I/O ZONE 560/583 USERS GUIDE

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

- Data Brochure Universal Reset Module 423

Metasys Integrator Airflow Application

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

Introduction. What is the W2W Open controller?

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

JADE Economizer Module (MODEL W7220)

OVEN INDUSTRIES, INC.

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

Document # R00

Modbus TCP Register List GreenManager for GreenMaster C-F Valid for firmware version 2.0 or later

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

VENSTAR T1075 FAN COIL THERMOSTAT 7 DAY PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

AirTrak. Digital Control System. User Manual. Touchscreen Systems

2704 Controller Melt Pressure Controller

Installation & Operation Manual

Fan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

Contents. Glossary

Pioneer Gold Controller Technical Guide

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

OPERATION & MAINTENANCE MANUAL GUARDIAN SPACE PRESSURE MONITOR WITH REMOTE AUXILLARY ALARM

Product Manual SZ2161. Description The SZ2161 is a microprocessor-based controller designed for water source heat pump plant control applications.

COCB_ Circuit Breaker (2 state inputs/ 2 control inputs)

Fire Alarm Control Panels FPD-7024

DACC - NMDA BUILDINGS

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

Advanced Installation and Configuration Instructions

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Manual for the integration in BMS/GTC

Reciprocating Chiller

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

Product Manual SZ1145

T600MEP-2 Programmable Economizer Thermostat

2604 Controller Melt Pressure Controller

LUFKIN WELL MANAGER MODBUS MAP

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment

Electric Coils. Blower Coils. Product Information

Transcription:

Model Number: 8680-N2 Product/System Title: Room Pressure AOC Controller with N2 Communications Protocol Contents of this manual supplement include: 1) Sequence of Operation 2) Variable map 3) Description of software items added 4) Software items deleted 5) Description of variables 6) Wiring Diagram N2 communications are installed on the Model 8680-N2 room pressure controllers. This document provides the technical information needed for the host DDC system to communicate with 8680-N2 units. This document assumes the programmer is familiar with the N2 protocol. Further technical assistance is available from TSI if your question is related to TSI interfacing to a DDC system. If you need further information regarding N2 programming in general, please contact Johnson Controls. Page 1 of 11 Released 2/13/02

Sequence of Operation The Model 8680-N2 measures the room pressure differential and receives temperature information from the thermostat. The 8680-N2 control algorithm modulates the supply and general exhaust air to provide adequate supply air while maintaining the room pressure differential and temperature control. Temperature control is provided by a thermostat that provides temperature information to the Model 8680-N2 controller and controls the reheat coil. The thermostat will provide a 0-10V signal, corresponding to a 50-85 F temperature. Alternatively, the temperature can be sent to the controller over the N2 bus (Analog Input #3) In occupied mode, the Model 8680-N2 has two supply flow set points: ventilation and temperature. The ventilation setpoint is the minimum supply flow for the space, used when the heating and cooling loads are met. The temperature supply set point is a higher flow, required to meet an increased cooling load in the lab. Laboratory temperature is continuously transmitted to the Model 8680-N2. When the laboratory temperature is satisfied, the ventilation set point is maintained, unless additional supply air is required for the room pressure balance. When the space temperature is more than 1 F above the temperature setpoint, the 8680-N2 slowly will increase the supply air volume, to a maximum of the temperature minimum supply flow, until the space temperature returns to setpoint. When the space temperature is more than 1 F below the temperature setpoint, the 8680-N2 slowly will decrease the supply air volume, to a minimum of the ventilation minimum supply flow, until the space temperature returns to setpoint. If the supply volume is at the ventilation minimum supply flow, the thermostat will modulate the reheat valve to provide the necessary heating. In unoccupied mode, the supply flow will remain at the unoccupied supply flow rate. Supply air volumes will rise above the minimum setpoints, under all conditions, as required to maintain space pressurization. Temperature control and occupied/unoccupied modes will only affect the minimum supply flows, which are used, for example, when fume hood sashes are lowered. NOTE: The 8680-N2 will not allow the temperature minimum supply volume to be less than the ventilation minimum supply volume Page 2 of 11 Released 2/13/02

Description of New Software Items The Model 8680-N2 has new/different software items which optimize the unit for N2. The new software items are located in various menus as shown in the attached Menu Structure drawing. Item TEMP SETP TEMP CAL XDCR OUT Description The TEMP SETP item is the setpoint temperature of the space. If the actual temperature is more than 1 F below the setpoint, the 8680- N2 will slowly decrease the minimum supply flow setpoint until it is at the ventilation minimum, at which point the reheat coil will have to be energized (by others). If the temperature is more than 1 F above the temperature setpoint, then the 8680-N2 will slowly increase the minimum supply flow setpoint, until the supply flow is at the temperature minimum setpoint. The TEMP CAL item is used to calibrate the temperature signal from the thermostat to the proper temperature. To calibrate the temperature signal, enter the TEMP CAL menu item, and use the and keys to adjust the displayed temperature until it matches the actual temperature. Then, press the SELECT key to save the new calibration. The XDCR OUT menu item allows the user to select the maximum range of the pressure transducer. The values are 0.1, 0.2, 0.3, 0.4, and 0.5 inches H2O (25, 50, 75, 100, 125 pascals). The default value is 0.5 inches H2O (125 pascals). This menu item is found in the HOOD FLOW, EXHAUST FLOW, and SUPPLY FLOW menus. Page 3 of 11 Released 2/13/02

Menu Configuration SETPOINTS ALARM CONFIGURE CALIBRATION SETPOINT VENT MIN SET TEMP MIN SET UNOCCUPY SET TEMP SETP MIN OFFSET MAX OFFSET LOW ALARM HIGH ALARM MIN SUP ALM ALARM RESET AUDIBLE ALM ALARM DELAY ALARM RELAY MUTE TIMEOUT DISPLAY AVG UNITS EXH CONFIG SENSOR ZERO SENSOR SPAN ELEVATION TEMP CAL CONTROL SYSTEM FLOW FLOW CHECK DIAGNOSTICS SPEED SENSITIVITY CONTROL SIG Kc VALUE Ti VALUE Kc OFFSET TOT SUP FLOW TOT EXH FLOW OFFSET VALUE SUP SETPOINT EXH SETPOINT HD1 FLOW IN EX1 FLOW IN SP1 FLOW IN CONTROL SUP CONTROL EXH SENSOR INPUT SENSOR STAT SWITCH INPUT SUP FLOW IN TEMP INPUT LOW ALM REL HIGH ALM REL INTERFACE HOOD FLOW EXHAUST FLOW SUPPLY FLOW NET ADDRESS HD1 DCT AREA HD1 FLO ZERO FLO STA TYPE XDCR OUT TOP VELOCITY EX1 DCT AREA EX1 FLO ZERO FLO STA TYPE XDCR OUT TOP VELOCITY SP1 DCT AREA SP1 FLO ZERO FLO STA TYPE XDCR OUT TOP VELOCITY Page 4 of 11 Released 2/13/02

Software Items Deleted The following software items have been deleted from the 8680-N2: Menu SETPOINTS ALARM CONFIGURE SYSTEM FLOW INTERFACE Item MAX SUPPLY SET TEMP LOW TEMP HIGH MIN EXH ALARM ROOM VOLUME ACPH NET PROTOCOL Page 5 of 11 Released 2/13/02

Variable Map Manual Supplement NPT NPA UNITS 1 DESCRIPTION AI 1 ft/min, m/s, Room Pressure Value in. H 2 O, Pa, mm H 2 O AI 2 CFM, l/s Current Offset Value AI 3 F, C Temperature AI 4 CFM, l/s Minimum Supply Setpoint AI 5 CFM, l/s Hood Exhaust Flow Value AI 6 CFM, l/s Auxiliary Exhaust Flow Value AI 7 CFM, l/s Supply Flow Value AI 8 CFM, l/s Total Exhaust Flow Value AI 9 # Supply Control Output AI 10 # Exhaust Control Output BI 1 Low Room Pressure Alarm 0=Normal 1=Low Alarm BI 2 High Room Pressure Alarm 0=Normal 1=High Alarm BI 3 Min. Supply Flow Alarm 0=Normal 1=Low Flow Alarm BI 4 Emergency Mode 0=Normal 1=Emergency Mode BI 5 Occupied/Unoccupied Mode 0=Occupied 1=Unoccupied BI 6 Data Error 0=Normal 1=Data Error AO 1 ft/min, m/s, Room Pressure Setpoint in. H 2 O, Pa, mm H 2 O AO 2 ft/min, m/s, Low Alarm Setpoint in. H 2 O, Pa, mm H 2 O AO 3 ft/min, m/s, High Alarm Setpoint in. H 2 O, Pa, mm H 2 O AO 4 CFM, l/s Min. Supply Alarm Flow Alarm Setpoint AO 5 CFM, l/s Minimum Ventilation Rate Supply Flow Setpoint AO 6 CFM, l/s Minimum Temperature Supply Flow Setpoint AO 7 CFM, l/s Unoccupied Mode Minimum Supply Flow Setpoint AO 8 CFM, l/s Minimum Offset Setpoint AO 9 CFM, l/s Maximum Offset Setpoint Page 6 of 11 Released 2/13/02

NPT NPA UNITS 1 DESCRIPTION AO 10 CFM, l/s Minimum Exhaust Flow Setpoint AO 11 F, C Temperature Setpoint AO 12 # Units 0=Feet per minute 1=Meters per second 2=Inches of H 2 O 3=Pascals 4=millimeters of H 2 O 1 Units will correspond with choice in UNITS variable (AO #12). Flow rates will either be CFM or l/s, based on whether UNITS variable is set for an english or metric unit type. Page 7 of 11 Released 2/13/02

Description of Variables NPT - Network Point Type Variables are defined as analog inputs, binary inputs, and analog outputs. Analog inputs are current control parameters and items that the controller is measuring. Binary inputs represent controller states. Analog outputs are the programmable setpoints for the isolation room pressure controller and monitor. These setpoints can be changed through the keypad or by overriding the current setpoint. NPA - Network Point Address Address of the desired point. Change of Status (COS) - Room Pressure Analog Input The 8680-N2 has the ability to change control setpoints locally. The alarm setpoints need to be based on the controller s control setpoint (AO #1). For example the setpoint could go from - 0.002 H 2 O to +0.001 H 2 O. If the COS alarm setpoints are not changed to accommodate you could get low alarm or low warning messages when the unit is working correctly. If these alarm points are set outside of the setpoint values, incorrect alarm messages can be prevented. Override Analog Input Command Analog Input values can be set using the override command. These values will be reset to the correct items when the Override is released. There is not a time-out on the override command. Override Binary Input Command Overriding a 1 to Emergency binary inputs enables that mode. To release the controller from emergency state, override a 0 to the Emergency input or press either the emergency or reset key. Releasing the override will return the controller to the Normal state. If the 8680-N2 had been put into Emergency mode from the keypad, then it cannot be cleared remotely. Overriding a 1 to the Occupied/Unoccupied Mode binary inputs enables the unoccupied mode. To release the controller from the unoccupied state, override a 0 to the Occupied/Unoccupied Mode. Pressing the AUX key will also toggle the unit between Occupied and Unoccupied Modes. The alarm and data error variables can be overridden, but this will not affect the controller. Overriding the low alarm variable will result in a change of status, but will not put the controller into low alarm mode. The local alarm modes can only be controlled locally. Only override these variables for diagnostic purposes, and release them for normal operation. Binary Input Data Error Data Error binary inputs are used to indicate if something has gone wrong with the controller. Data Error indicates when some of the data stored on the device has been corrupted. The calibration and setpoint values should be checked on the controller. Page 8 of 11 Released 2/13/02

Override Analog Output Command The analog output variables can be overridden to change their values. The overridden value will be checked for validity. If invalid, the override command will be ignored, and the value will not change. The override flag will not be set when the value is ignored. The override command will be cleared when the variable is reset in the menus. The variable will not reset with the release command. Supported Commands Command Request Device ID Synchronize Time Command Poll Without/With Ack Message Read Analog Input Command Read Binary Input Command Read Analog Output Command Write Analog Input Write Binary Input Write Analog Output Override Analog Input Command Override Binary Input Command Override Analog Output Command Override Release Request Identify Device Type Command Response Returns 0x10 d. There Is No Internal Clock To Synchronize. Any Change Of Status Is Returned Variable Value Variable Value Variable Value Returns 0x10h Note: Poll Without/With Ack Message will need to be sent twice in order to receive all of the possible change of status variables. Page 9 of 11 Released 2/13/02

Wiring Diagram Manual Supplement MODEL 8680-N2 -N2A WIRING DIAGRAM -ELECTRIC - 21 22 23 24 25 26 Page 10 of 11 Released 2/13/02

MODEL 8680-N2 -N2A WIRING DIAGRAM --PNEUM PNEUMATIC 21 22 23 24 25 26 Page 11 of 11 Released 2/13/02