Fire Dynamics During the Channel Tunnel Fires

Similar documents
The investigation of accidents and incidents in complex railway tunnel systems

CERBERUS: A NEW MODEL TO ESTIMATE SIZE AND SPREAD FOR FIRES IN TUNNELS WITH LONGITUDINAL VENTILATION

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen

VENTILATION AND SUPPRESSION SYSTEMS IN ROAD TUNNELS: SOME ISSUES REGARDING THEIR APPROPRIATE USE IN A FIRE EMERGENCY

TUNPROTEC. Active Tunnel Fire Protection

SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM

Hot Issues in Fire Engineering 12 March 2013

An experimental study of the impact of tunnel suppression on tunnel ventilation

Fire Safety in the Channel Tunnel

THE IMPACT OF FIXED FIRE FIGHTING SYSTEMS ON TUNNEL SAFETY THE BURNLEY INCIDENT IN A CURRENT THEORETICAL PERSPECTIVE

The first tunnel fire. Benefits of fire

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS

Sprinklers Modeling for Tunnel Road Fire Fighting

Innovative Solutions for Active Fire Protection in Road/Rail Tunnels and Underground Facilities

Ventilation for Smoke Control, Fire Control & Life Safety in Tunnels. Dr. Ricky Carvel BRE Centre for Fire Safety Engineering University of Edinburgh

IMPROVING VENTILATION AND PASSIVE PROTECTION WITH FFFS

AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION

EARLY FIRE DETECTION IN SWISS ROAD TUNNELS WITH MORE THAN FIREGUARD SENSORS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

Effective Firefighting Operations in Road Tunnels

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

Impact of quick incident detection on safety in terms of ventilation response

Ventilation Effects on Fire Patterns during Post Flashover Burning

Test One: The Uncontrolled Compartment Fire

A brief presentation of the second fire in the Gudvanga tunnel

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363)

Fire Protection and Safety in Tunnels Conference Opening Remarks. Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee

State of the Road Tunnel Safety Technology in Japan. Hideto Mashimo 1

Modeling a real backdraft incident fire

PHASED CONSTRUCTION AND SAFETY IN MALA KAPELA TUNNEL

Increasing Fire Safety of Cologne Main Station by High Pressure Water Mist

Edinburgh Research Explorer

Full-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater Tunnel

Appendix SPAIN Madrid M30-Río-TUNNEL

Emergency Ventilation System Design - Preliminary Report Shishir Gupta

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Impact of Tunnel Ventilation on Tunnel Fixed Fire Suppression System

Tunnel Fire Dynamics

COMPENSATORY EFFECTY OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS

OVERCOMING EVACUATION LIMITATIONS OF THE UČKA TUNNEL BY IMPROVEMENT OF FIRE SAFETY MEASURES

Road tunnel safety rules in Italy: the tunnel country

Essentials of Fire Fighting 6 th Edition Firefighter I

OBSERVATION ON THE TWO RECENT BUS FIRES AND PRELIMINARY RECOMMENDATIONS TO PROVIDE FIRE SAFETY

COMMISSION REGULATION (EU)

Large scale fire tests with fixed fire fighting system in Runehamar tunnel

CFD ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

Chapter 17 Test. Directions: Write the correct letter on the blank before each question.

RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA. Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018

Overview of the PRISME project Technical Description and Main Outcomes

Laboratory fire experiments with a 1/3 train carriage mockup

SIMPLE AND RELIABLE FIRE DETECTION IN ROAD TUNNELS

and Sprinkler System in Resalat Tunnel of Tehran

Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition

Development of a test method for fire detection in road tunnels

Evolution in the knowledge about interior firefighting

CFD-AIDED TENABILITY ASSESSMENT OF RAILWAY TUNNEL TRAIN FIRE SCENARIOS

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks

1 Aviation English Vocabulary Level 4 to 5

Research on Mobile Water Spray Device Reducing the Temperature of Metro Fire

Aspirating Gas Detection CFD Modelling Predicts Application Performance

MistMax Pro; A WaterMist fire skid designed for your UTV or smaller fire fighting vehicle.

IMO DEVELOPMENT OF MODEL PROCEDURE FOR EXECUTING SHIPBOARD EMERGENCY MEASURES. Fire-fighting drills. Submitted by the Republic of Korea

Fire Protection. A Health and Safety Guideline for Your Workplace. Introduction. Fire Prevention and Control. Workplace Assessment

Hazardous Material Safety Program

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

Appendix AUSTRIA Vienna Kaisermühlentunnel

F.R.A.M.E. EVENT NETWORKS used in "FRAME".

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

AUTOMATIC FIREFIGHTING SYSTEMS IN PAINT BOOTHS

Risk Management of Fire using Video Based Detection

SAFE CABLING SYSTEMS IN TUNNELS UNDER FIRE

Inquiry into the fire on Heavy Goods Vehicle shuttle 7539 on 18 November 1996

( )

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

Heat pump supplemental heating system for motor vehicles

Tokyo-wan Aqualine - Experience of Traffic and Safety

Prevention of Fires and Explosions in Wood Pellet Facilities. Allen Wagoner, FLAMEX, Inc.

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring.

Yunyong P. Utiskul, Ph.D., P.E., CFEI

CFD STUDY OF FIRE PROTECTION SYSTEMS IN TUNNEL FIRES

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China

Guidance on Video Smoke Detection Technology (VSD)

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

PRELIMINARY ANALYSIS OF THE NUMBER OF OCCUPANTS, FIRE GROWTH, DETECTION TIMES AND PRE-MOVEMENT TIMES FOR PROBABILISTIC RISK ASSESSMENT

Fire in the Heinenoordtunnel, Lessons learned.

FIRE STOP 200/30. High technology system for first attack of fire with high pressure nebulized water (Water mist) FD 907. Ed.

The Mont Blanc tunnel project. Eric CESMAT, Sylvain DESANGHERE

Structural Firefighting Policy

AUTOMATIC FIRE EXTINGUISHING SYSTEM for TUNNEL PROTECTION with SPREAD REMOTE CONTROLLED MONITORS (TUDEM-LEGIO)

NECESSITY OF CARRYING OUT FULL-SCALE BURNING TESTS FOR POST-FLASHOVER RETAIL SHOP FIRES

Road Tunnel Classification System for Fire Brigades Prof. Haukur Ingason SP

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

automatic FiReFighTing SYSTeMS in PainT booths

Crossrail. Clare Hebden; September 2012

Delhi Metro System. Emergency and Fire Safety Measures in. - by Sanjeev Kumar & Kailash Chandra Joshi. Fire Protection & Safety

This document is a preview generated by EVS

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

Transcription:

Fire Dynamics During the Channel Tunnel Fires Ricky Carvel BRE Centre for Fire Safety Engineering University of Edinburgh ABSTRACT Three major fire incidents have occurred in the Channel Tunnel since it opened in the early 90s. The fires on the 18 th of November 1996 and the 11 th of September 2008 grew to involve many heavy goods vehicles (HGV) on carrier wagons and caused major damage to the tunnel structure. The fire on the 21 st of August 2006 involved only a single HGV and did not spread, although the adjacent HGV was damaged by heat. Each of these incidents is described and the incidents are compared. The official inquiry into the 2008 fire has not yet been published, so information has been collected from press reports. It is clear that the fire development in 1996 and 2008 was broadly similar, while the fire in 2006 was very different. These differences may be due to the cargo and construction of the vehicles involved, but also may be due to the differences in ventilation during the incidents. The conventional model of fire dynamics in multiple vehicle fires is discussed with reference to the Channel Tunnel fires. It is observed that the primary difference between the 2006 fire and the other two was that in the 1996 and 2008 fires, the initial fire would have experienced a reversal in airflow direction and an increase in ventilation flow after the fire was established. In the 2006 fire there was no reversal or increase in flow. It is proposed that these ventilation changes may be able to explain the differences in fire dynamics. Recommendations based on these proposals are made. KEYWORDS: fire dynamics, channel tunnel, ventilation INTRODUCTION The Channel Tunnel forms the rail link between the UK and France. It consists of three parallel tunnels; two running tunnels, each with a single rail track, on either side of a service tunnel, see Figure 1. The tunnels are approximately 50 km long (37 km of which is under the English Channel). The tunnel runs north-west to south-east, the northernmost tunnel is referred to as Running Tunnel North (RTN) and generally handles traffic from the UK to France, with the traffic coming from France generally using Running Tunnel South (RTS). The service tunnel has three main safety functions: to provide normal ventilation for the running tunnels, to provide a safe haven for passengers and crew in the event of an evacuation and to facilitate the speedy arrival of the emergency services. Figure 1 Layout of the Channel Tunnel 463

Four types of trains use the tunnel: 1. Tourist shuttles, consisting of single and double-decker wagons, carrying coaches and cars 2. Heavy Goods Vehicle (HGV) shuttles carrying lorries and trucks on semi-open wagons 3. Passenger trains (Eurostar) 4. Freight trains There have been three significant fire incidents in the Channel Tunnel to date: on the 18 th of November 1996, the 21 st of August 2006 and the 11 th of September 2008. Each of these incidents has occurred on a HGV shuttle. In the 1996 fire the train was travelling from France to the UK in RTS, in the other two incidents, the train was travelling from the UK to France in RTN. The HGV shuttle trains (see schematic in Figure 2) are generally composed of: 1. A locomotive at the front of the train, staffed by a driver 2. An amenity coach, carrying all passengers (vehicle drivers), staffed by the Chef de Train and a steward. (This is generally at the front of the train; occasionally it is between the rear loader and rear locomotive. In all three fire incidents to date, the amenity coach was at the front.) 3. Front loader wagon 4. Front rake of fifteen semi-open HGV carrier wagons (each 20m long) 5. Middle loader wagon 6. Rear rake of fifteen semi-open HGV carrier wagons 7. Rear loader wagon 8. Rear locomotive, no crew. In total, the train is about 740 m long. Figure 2 Schematic of the HGV shuttle trains (direction of travel indicated) During normal operation of the tunnel, there is a minimal supply of fresh air into the tunnel, this is designated the Normal Ventilation System (NVS). Under NVS conditions, the prevailing airflow is due to the piston effect of the trains, thus runs in the same direction as the trains themselves. The speed of the airflow relative to the train is approximately half the speed of the train relative to the tunnel. Thus, before any emergency ventilation conditions are implemented, any fire on the train (travelling at 140 km/h) will experience the relative airflow as having a velocity of about 20 ms -1 towards the rear of the train. Once a fire incident is declared, the Supplementary Ventilation System (SVS) is activated. This generates a flow of about 2.9 ms -1 (relative to the tunnel) in the opposite direction to the direction of train travel. THE INCIDENTS 18 th November 1996 The 1996 fire occurred on HGV Shuttle Mission 7539, which departed the French terminal at 21:42 hrs on the 18 th of November. The main events relating to ventilation conditions and fire behaviour are summarised in Table 1. The fire ultimately involved the rearmost ten HGV carriers and destructively damaged the rear loader wagon and locomotive. The distribution of cargoes and damage on the rear rake is given in Table 2. 464

Time Event Comment 21:42 Train departs station Fire visible on 2nd rake. On wagon 7 or 10 (witnesses) 21:48 Train enters tunnel 21:51 Onboard fire alarm On rear locomotive 21:58 Train stopped Driver initially tried to keep going. Decision to stop on basis of a faulty system warning light. Once stopped, driver unable to see tunnel walls to identify location. 22:13 SVS activated Fan blades set incorrectly. No longitudinal flow 22:22 SVS fully established Evacuation carried out Ventilation flow now about 2.9 ms -1 22:53 Fire brigade assess fire ~ 5 wagons on fire at the rear 23:39 Fire fighting begins Takes about 6 hours. Table 1 Timeline of the 1996 fire. Loader wagon Plastic bags Reels of paper Plastic racks Catalogues Pineapples Pineapples Cornflakes Frozen fat Frozen chips Reels of paper Clothes Machinery Cheese Titanium scraps 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Salvageable Serious damage Irreparable damage to all carrier wagons. All vehicles destroyed. Serious damage to tunnel lining Loader wagon Rear locomotive Table 2 Distribution of cargo and damage in the 1996 fire. Time Event Comment 13:25 Train departs station Fire not in evidence 13:26 Train enters tunnel Smoke emanating from incident vehicle. (Caught on CCTV) 13:30:31 1st smoke detector triggered Train had passed three earlier smoke detectors which did not activate 13:30:45 Onboard fire detection triggered Detector on rear loader wagon 13:31 All trains ordered to reduce to 100 km/h Driver acted on this instruction 13:32:39 2nd smoke detector triggered 13:34 Train instructed to stop Train had to clear the go zone before stopping 13:37 SVS started but dampers closed No SVS in running tunnel 13:39 SVS now operational in both running tunnels Ventilation assumed to be about 2.5 ms -1 13:40 Train stops SVS already established, fire never experiences an inversion of flow 13:49 Evacuation complete Smoke / visibility not an issue 15:45 Fire fighting begins 2 hours after train stopped 16:05 Fire extinguished One HGV destroyed. Carrier wagon damaged. Downstream HGV suffered significant heat damage, but did not ignite. Upstream HGV suffered minor heat damage. Table 3 Timeline of the 2006 fire 465

21 st August 2006 The 2006 fire occurred on HGV Shuttle Mission 7370, from the UK to France, which departed the Folkestone terminal at 13:23 hrs on the 21 st of August. The main events relating to ventilation conditions and fire behaviour are summarised in Table 3. 11 th September 2008 At the time of writing (December 2009), the official report on the investigation into this fire has not been published. The French Bureau d'enquêtes sur les Accidents de Transport Terrestre (BEA-TT) and the UK Rail Accident Investigation Branch (RAIB) are carrying out a joint investigation into the fire. As the official investigation is not yet public, the precise details of the incident cannot be listed here. A few facts can be gleaned from the RAIB web pages [1], press reports on the BBC web pages [2], The Guardian newspaper [3], New Civil Engineer (NCE) magazine [4] and elsewhere, including: No fire was visible as the train entered the tunnel The train was stopped, beside a cross-passage, immediately following identification of the fire The train stopped 39km into the tunnel (11.5 km from the French Portal) The fire was larger and more destructive than the 1996 fire The passengers could see flames from the amenity coach and heard an explosion The passengers felt the heat from the fire before they evacuated the amenity coach 29 passengers and 3 crew were evacuated, 14 required hospital attention Graphics on the BBC web pages imply that the initial fire was on the first HGV carrier wagon The fire may have started on a lorry carrying chemicals, which is understood to have overturned [this is not mentioned in later press articles, so may be spurious] The concrete tunnel lining required repairs along 650m of its length There was severe damage to the concrete (spalling to a depth of 400mm; the full depth of the tunnel lining) over a 20m long section of the tunnel The train was not carrying a full complement of HGV; some carrier wagons were empty Some of the HGV were not carrying any cargo The incident evolved in a similar manner to the 1996 fire, except that the SVS was operated sooner The fire was extinguished by mid-morning the following day. From these facts we can deduce the following: The fire started near the front of the train (it was visible by the passengers) The fire extended along most of the length of the train (the damage to the tunnel was 170m i.e. approx 8 wagons longer than in the 1996 fire, which involved almost half the train) COMPARISON OF THE INCIDENTS Obviously, the most striking difference between the three incidents is that in the 1996 and 2008 fires, the fire would appear to have spread very rapidly to involve multiple HGV and carrier wagons by the time the fire brigade arrived at the scene and made their initial assessment, whereas in the 2006 incident, the fire had not spread to either of the adjacent vehicles by the time the fire brigade arrived. There are a number of possible reasons for this discrepancy, including: The construction and cargo of the initial vehicle on fire The construction and cargoes of the adjacent vehicles The differences in ventilation flow experienced by the fire in its development 466

In this paper it is proposed that the differences in ventilation conditions experienced by the fires in these instances are the primary factor responsible for the different outcomes of the events. The 2006 fire differs significantly from the other two incidents in that the fire, while it did experience some changes in the velocity of the airflow, did not experience any reversal of the flow or periods of low flow. This is due to the fact that the fire was detected while the train was in the go zone (a section of the tunnel where Eurotunnel policy states that no trains should be stopped) and, hence, the SVS airflow was established before the train came to a halt. Thus (very approximately) the airflow experienced by the train would have been: ~ 20 ms -1 before detection / ~ 15 ms -1 after detection / ~ 3 ms -1 after train stopped In the 1996 fire, the sequence would have been more like this: ~ 20 ms -1 before / ~15 ms -1 after / reversal of flow when stopped / minimal flow for 20 min / ~ 3 ms -1 In the 2008 fire, the pattern is believed to have been much like in 1996, except that the minimal flow period would only have been of the order of a few minutes. This paper proposes that the reversal of flow and the velocity increases following periods of minimal flow are directly linked to periods of rapid fire spread along the train. FIRE DYNAMICS IN A MULTIPLE VEHICLE FIRE The generally accepted model of fire development in multiple vehicle tunnel fire incidents was described in 2003 by Ingason [5]. The process, divided into zones, is discussed using a schematic picture similar to the one in Figure 3. Figure 3 The conventional model of catastrophic tunnel fires, based on Ingason The basic concept is that there is a fire travelling along a line of vehicles in the direction of ventilation flow. The fire consumes fuel as it progresses, but the extent of the combustion zone is limited by the amount of fresh air supplied by the (forced) ventilation system. A large fire in a tunnel will consume a large amount of oxygen. It is well established [6,7] that most fuel types release about 13 MJ of energy per kg of oxygen consumed (approximately equivalent to about 3 MJ/m 3 of air consumed ; although this value is temperature dependent). Thus, the maximum sustainable heat release rate of a large fire in a tunnel is constrained by the airflow to the fire. 467

The Channel Tunnel tubes may be taken to be 40 m 2 in cross-section, thus, the volumetric flow of air to the fire is approximately 40v m 3 s -1, where v is the longitudinal airflow velocity (in ms -1 ). Thus the maximum sustainable heat release rate of a fire in the tunnel is approximately 120v MW. Thus, when the train was moving (and the flow was over 15 ms -1 ), the theoretical maximum HRR of the fire would have been over 1.8 GW (an unrealistically high number), whereas while the SVS was active and the train stopped, the maximum sustainable HRR would have been about 350 MW which is equivalent to only two or three HGV fires simultaneously (based on the HGV fire tests from Runehamar; up to 200 MW [8] and Hammerfest; up to 120 MW [9]). When the flow was lower than SVS flow, the maximum HRR would also have been lower. It is only during the periods of relatively low flow (i.e. after the train had stopped) that the fire behaviour would follow Ingason s pattern. Under these circumstances, a zone of hot, unburned, gaseous fuel would be produced downstream of the fire location. If, after this zone of hot fuel developed, the ventilation conditions in the tunnel were changed either by reversing or increasing the flow these hot flammable gases would mix with fresh air and this would lead to very rapid burning, perhaps even an explosive event analogous to backdraught in compartment fires. It is proposed that these rapid burning events in the 1996 and 2008 Channel Tunnel fires lead to rapid fire spread between wagons, possibly across several wagons at a time. It may be that the 2006 fire did not spread in the same way because there were no reversals of flow or increases in flow during the incident. FIRE GROWTH AND SPREAD IN THE 1996 AND 2008 FIRES In both the very large fire incidents in the Channel Tunnel, the fire was detected by a fixed flame detector while the train was moving at high speed in the tunnel. Given the nature of the detection systems, it is assumed that the fire was at least a few MW in size and external to the initial incident vehicle by the time it was detected. 25 20 Fire growth (MW/min) 15 10 5 0 0 1 2 3 4 5 6 Ventilation Velocity (m/s) Figure 4 The apparent relationship between fire growth rate and ventilation velocity [11]. It has previously been observed that the rate of growth of a fire in a tunnel is dependent on the ventilation rate [10,11]. While no experimental fire tests have been carried out in tunnels with ventilation flow rates above about 6 ms -1, such information as is available suggests that there is a decline in growth rate with increasing velocity, for ventilation velocities above about 4 ms -1, see 468

Figure 4. Thus it is likely that the fire would not have grown very large while the train was moving at high velocity. As the train progressed, the fire may have spread to the vehicle immediately following the initial incident vehicle, or this vehicle could have simply been pre-heated by the initial fire. It is likely that at the least some small fires may have been ignited on this vehicle by firebrands. Once the train came to a stop, the resulting reversal of flow would have given these small fires (on a pre-heated fuel load) a plentiful supply of fresh air at a velocity likely to lead to rapid fire growth [10], thus the adjacent vehicle (previously downstream) vehicle would be likely to become fully involved at this time. Concurrently with this, the flames from the initial fire would be directed towards the (previously upstream) other adjacent vehicle, so it is quite likely that the fire would spread in that direction too. As the flow reduced to natural ventilation conditions, the fires on these vehicles would become established but, due to the lack of available fresh air, may not have burned fully, producing a hot, fuel rich atmosphere. In the 1996 fire this phase may have lasted as much as 20 minutes, in 2008 it was shorter. Despite the lack of oxygen at the initial burning vehicle, the hot flammable gases would burn whenever and wherever they mixed with fresh air. This burning zone could have migrated several vehicle lengths away from the initial fire location, igniting small fires on every vehicle in the zone. Once the SVS was established (introducing another reversal in flow direction), there would be sufficient fresh air to enflame these small fires, so the fire would grow and spread very rapidly; perhaps even explosively if the conditions were suitable. This process is able to explain the rapid spread to a very large fire observed by the fire brigade on entrance to the tunnel in both incidents. RECOMMENDATIONS At present this analysis is largely speculation. Further research is required and is intended. However, if this scenario is demonstrated to be valid, the following recommendations can be made for train fires in tunnels: 1. If it is necessary to stop the train in the tunnel, the emergency ventilation system should be activated and allowed to become fully established before the train is signalled to stop. This would mean that the fire would never experience a reversal in flow direction or a period of very low flow. 2. If a train on fire is stopped in the tunnel and is subject to a longitudinal airflow, the airflow velocity should not be increased after the fire has become well established. 3. Given that fire growth and spread appears to be slower on a fast moving train, compared to one that is stopped, consideration should be given to drive the train out of the tunnel before stopping. REFERENCES 1 RAIB website: www.raib.gov.uk 2 BBC website: news.bbc.co.uk 3 The Guardian newspaper: www.guardian.co.uk 4 New Civil Engineer: www.nce.co.uk 5 H. Ingason Fire Development in Catastrophic Tunnel Fires (CTF) Proc. Int. Symp. Catastrophic Tunnel Fires (CTF), Borås, Sweden, Nov 20-21, 2003. pp. 31-47 6 Babrauskas, V. From Bunsen burner to heat release rate calorimeter in Heat Release in Fires (eds Babrauskas, V. & Grayson, S.J.), pp. 7-29. Elsevier Applied Science, Barking (1992). 469

7 Drysdale, D.D. Introduction to Fire Dynamics John Wiley and Sons. (1st Edition 1985, 2nd Edition 1999) 8 H. Ingason, A. Lönnermark Heat release rates from heavy goods vehicle trailer fires in tunnels Fire Safety Journal, Volume 40, Issue 7, 2005, pp 646-668, DOI: 10.1016/j.firesaf.2005.06.002. 9 Studiensgesellschaft Stahlanwendung e. V., editor. Fires in transport tunnels: report on full-scale tests. EUREKA-Project EU499: FIRETUN, Dusseldorf, Germany, 1995. 10 R. Carvel Design fires for tunnel water mist suppression systems 3rd Int. Symp. on Tunnel Safety and Security, Stockholm, Sweden, March 12-14, 2008. Published by SP, Report 2008:11, ISBN 978-91-85829-25-5 pp. 141-148. 11 R. Carvel, G. Rein & J.L. Torero Ventilation and suppression systems in road tunnels: Some issues regarding their appropriate use in a fire emergency Proc. 2 nd Int. Tunnel Safety Forum for Road and Rail, Lyon, France, April 2009. ISBN: 1 901808 27 0. pp. 375-382 470