Use this addendum with the LP Installer s Guide to install a. GRAFIK RP System

Similar documents
2800 Series Control Units

Application Note #603 Revision A June 2016 Lighting Control for Noise-Sensitive Applications

Application Note #109 Revision D December A Guide to Using Dimmable Receptacles. Overview. FAQs. 1 Technical Support

Application Note #451 Revision B June 2012

Meeting RF Performance Criteria...7 Background...7 Expectations...7 End-of-Line Testing...7 Fixture Control Self-Test...7 Basic Functionality...

Application Note #407 Revision F March 2019

Phase-Adaptive Power Module

GPF Dimming Panels. GRAFIK Systems SPECIFICATION SUBMITTAL

ACONT600AF11MA/ACONT602AF22MA Programmable Comfort Control

design guide for wireless l i g h t i n g c o n t r o l

MODEL RLY-DIM-D INSTALLATION INSTRUCTIONS

Venetian blindstm with Intelligent Tilt Alignment

centralised lighting control LCP128TM systems

5+2 DAY. OWNER S MANUAL Venstar Inc. 05/08

Humidity Module OWNER S MANUAL. Complete Control from

Owner s Manual. 5+2 Day Programmable Digital Thermostat

Owner s Manual. Digital Thermostat. Heat/Cool & Heat Pump 7-Day Programmable S1-THEM22P7S COMMERCIAL. Model HVAC SERVICE PARTS

Programmable 5-2 Day Digital Thermostat

Fluorescent Dimming Ballast Selection Guide Where to go next: Fluorescent Lighting Controls Selection Guide, pg.196

AddressPro Digital Dimming Technical Product Information

MODEL TSTATBBPB101 PROGRAMMABLE DIGITAL THERMOSTAT. Heat Pump & Heat Cool. Meets California Title 24 Residential USERS INFORMATION MANUAL

Thermostats. Digital Non-Programmable. GEAppliances.com. Owner s Manual & Installation Instructions RAK148D2 RAK164D2

Operating Manual. PRO 1000 Series EFS-01. Non-Programmable Thermostat

AIM TECHNICAL MANUAL PATENT PENDING STOP REMEMBER TO ACTIVATE UNIT BEFORE TESTING. See page 9 for Activation Instructions

VENSTAR T1070 FAN COIL THERMOSTAT PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

Digital Non-Programmable

Thermostat Remote Control & Receiver

Owner s Manual. Digital. Heat Pump. 5+2 Day Programmable. Model S1-THEH21P5S HVAC SERVICE PARTS TM

5+2 DAY PROGRAMMABLE DIGITAL THERMOSTAT

SC Installation, Operation & Application Guide

Carrier NON-PROGRAMMABLE DIGITAL THERMOSTAT. Dual Setpoint Thermoglow Backlight No Batteries Required Auto Changeover Locking Keypad

7-Day. Digital Thermostat. residential. & 2-cool

5+2 Day. up to HEAT COOL

Digital Refrigerator/Freezer Thermometer model 00986

Thermostats. Digital Programmable. GEAppliances.com

installation instructions Fan Tray System FTA-3/FTA-6

Owner s Manual. Digital Thermostat. Heat/Cool & Heat Pump 7-Day Programmable S1-THEU22P7S RESIDENTIAL. Model HVAC SERVICE PARTS

Maestro 0 10 V Dimmer Sensor

Remote Relay Module (RRM)

Thermometer model 02059

LUMA-NET 804CP / 808CP REMOTE CONTROL PANEL

Owner s Manual. Digital Thermostat

The Vanguard System TM VM-2900 Air Seeder Monitor. Operator s Manual

T6 Pro Hydronic. User Guide. Thermostat controls. Customer assistance. Programmable Thermostat

- User Brochure tekmarnet 4 Setpoint Control 161

centralised lighting control LCP128TM systems

IMPORTANT INSTRUCTIONS FOR FAN-FORCED HEATER USE

VX SERIES Wireless Thermostat with Occupancy Sensor

Unpacking Your Fan 2.

MODEL EPC-D-F-ATS INSTALLATION INSTRUCTIONS ! IMPORTANT SAFEGUARDS!

CT500 Electronic Thermostat

VENSTAR T1075 FAN COIL THERMOSTAT 7 DAY PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

2-Port alarmcharge Hub - Manual

Installation and Owner Man u al

1 For All Programmable or Non-Programmable. Digital Thermostat. Meets Residential California Title 24

! "! # Please read these installation and operating instructions completely and carefully before starting.

Owner's Manual. Voltage Converter. Reverse. 110V to 220V STEP UP. For International Power Connectivity Converts U.S. 110V to Foreign 220V

Thermometer with Wired Sensor

GRAFIK T Controls GRAFIK T

ELECTRONIC COMMUNICATING THERMOSTAT COOL AUTO. Hold Prog Mode Fan. Owner's Manual. RC-120 Two Stage Heat/Cool 2 Stage Heat / 2 Stage Cool

- User Brochure Programmable Thermostat 510

I2:00 Mo MODEL TSTATBBPB501 PROGRAMMABLE DIGITAL THERMOSTAT. Heat Pump & Heat Cool. Meets California Title 24 Residential USERS INFORMATION MANUAL

1 For All Programmable Digital Thermostat

Installation/Operation Instructions COMP-COOL50/COMP-COOL50P 50 CFM COMPONENT COOLERS

Installation, Operation & Service Manual

Application Note #106 Revision D June Emergency Lighting. Overview

MaxLite LED High Bay Fixtures

Introduction... 1 System Overview... 1 System Diagram... 2

2 - Wire Programmable Digital Thermostat

Module de relais Relay Module. Manuel de l utilisateur 301RW. User Manual ERP /07

IMPORTANT SAFETY INFORMATION:

SC Installation, Operation & Application Guide

MaxLite LED Round Pendant Highbay Series

Technical Bulletin April Opticom Infrared System. Optical Preemption Detector Identification Guide

EclipseDryer Guide. Effective 10/09

INSTRUCTIONS PARTS LIST For President, Monark, Standard, and Fast-Flo Pumps, and Agitator

Programmable Digital Thermostat

Radiant Thermostat 519

myroomtm Operations and Maintenance MANUAL

Universal Fan and Light Remote Control

HotPoly Tote Tank / IBC Heaters (TTH Series)

Introduction... 1 System Overview... 1 System Diagram... 2

MaxLite LED MICRO-T PANEL

CA 120 Owners Manual of 10

Owner s Manual. Digital Thermostat. Non-Programmable

Humidity Monitor model 01080

OWNER'S MANUAL. RSL-2701U (for CANADA MODEL) RSL-2701S (for USA MODEL ) Royal Sovereign International Inc.

READ AND SAVE THESE INSTRUCTIONS DRANE-KOOLER. Water Tempering Device. Installation, Operation, and Maintenance Manual

programmable control model installation and setup guide M /11/ Hunter Fan Company

Thermometer with Probe model 00891A

OWNER'S MANUAL RSL MyBinding.com 5500 NE Moore Court Hillsboro, OR Toll Free: Local:

Remote Vehicle Control System

Operation Manual Vortex mixer unitexer 1

Door/Window Sensor Installation Instructions

INSTRUCTIONS FOR YOUR NEW REMOTE FAN CONTROL SYSTEM CAUTION: THIS REMOTE ONLY WORKS WITH SOME FANS IN SLOPED CEILING

INSTALLATION AND OPERATION MANUAL

1 For All Programmable Digital Thermostat. Meets Residential California Title 24

Horizontal Bottle Cooler Installation and Operation Manual

WALL MOUNT ELECTRIC FIREPLACE OWNERS MANUAL

USER MANUAL MODEL READ ALL INSTRUCTIONS BEFORE PROCEEDING. 5-2 Day Programmable Multi-Stage 2 Heat/1 Cool Heat Pump Digital Thermostat

Transcription:

Attention Installer: Use this addendum with the LP Installer s Guide to install a GRAFIK RP System Wallstation GRAFIK RP A GRAFIK RP System is a combination of up to four Grafik RP Dimming Panels and up to four EGRX-, NTGRX-, and SG- series Wallstations. GRAFIK RP Dimming System Addendum 1

Panel Overview TVM Module (optional) Terminal Blocks for Load Wiring 4 Output Dimming Module Circuit Breakers (optional) RP Panel Programmer Isolation Switch (optional) 2 GRAFIK RP Dimming System Addendum

STEP 1: Mount Panels Refer to the LP Installer s Guide steps 1 and 2 on pages 2, 3 and 4 for mounting wallboxes and GRAFIK RP panels. STEP 2: Control Wiring In GRAFIK RP- dimming panels are wired directly to wallstations. Refer to the LP Installer s Guide on pages 5 and 6. Note that GRX-4000 and GRX-3000 Control Units will not work with GRAFIK RP. STEP 3: Feed and Load Wiring Refer to the LP Installer s Guide step 4 on pages 8 and 9. STEP 4: Install Wallstations and Activate Loads Refer to page 12 (steps 7 and 8) of the LP Installer s Guide. No DIP switch changes are required. STEP 5: Activate Panel Programmer and Wallstations Activate the RP Panel Programmer and Wallstations by turning on breaker 1. The RP Panel Programmer s Power OK LED will light, indicating that the control system is powered. Note: If the panel is feed-through style, turn on the breaker dedicated to system controls. This will activate the GRAFIK RP Panel Programmer as well as any Wallstations. 1 2 3 4 D 5 Power OK LED DataA OK Power GRAFIK RP Dimming System Addendum 3

STEP 6: Assign Load Types Note the factory default load type is L 1 Non-Dim. Refer below for setting the load type for each output. Panel Programmer L 1 Non-Dim L 2 Incandescent L 3 Magnetic Low L 4 Lutron TuWire Voltage L 5 Electronic Low Voltage L 6 Neon L 7 0-10 V L 8 Tridonic DSI L 9 DALI Stromkreis Circuit Circuito Fade B C A, D Note: If the correct load type for a particular circuit is unknown, set load type to L 1 until the correct load type is determined. A. Enter Load Type Setup Mode. Press and hold buttons 2 and 5 simultaneously until all LEDs blink. (Note: Pressing and holding buttons 2 and 5 simultaneously at any point in the following process will cause the Panel Programmer to exit from the Load Type Setup Mode.) B. Select a Circuit for Load Type Setup. Use buttons 1 and 2 to select a circuit. (e.g. Circuit #1 shown in picture) C. Select Load Type. Use buttons 3 and 4 to set the load type for the selected circuit. (e.g. Load Type L 1 shown in picture) D. Repeat steps B and C for all circuits in the panel. Verify that all circuits have been assigned the correct load type. E. Exit Load Type Setup. Press and hold buttons 2 and 5 simultaneously until LEDs stop flashing to exit. Load Type setup is now complete and all settings are saved. 1 2 3 4 Off Caution! Failure to correctly assign Load Type may damage loads especially certain Electronic Transformers and Electronic Ballasts. Verify with transformer or ballast manufacturer that product can be dimmed with phase control dimming before setting to any Load Type other than Non-Dim. STEP 7: Remove Bypass Jumpers Refer to page 16 (step 12) of the LP Installer s Guide. 4 GRAFIK RP Dimming System Addendum

STEP 8: Setup Scenes A scene consists of a light level for each circuit and one fade time. GRAFIK RP allows setup and storage of 4 Scenes, plus Off. A. Enter Scene Setup Mode. Press and hold buttons 1 and 5 simultaneously until Light Level LED blinks. (Note: Pressing and holding buttons 1 and 5 simultaneously in the following process will exit from Scene Setup Mode.) B. Select Scene 1. Scene 1 is selected each time Scene Setup Mode is entered. (Scene 1 LED is lit and Light Level LED is blinking) To select a different Scene, press button 5 until the correct Scene LED is lit. C. Select Circuit. Use buttons 1 and 2 to select a circuit. (e.g. Circuit #1 shown in picture) D. Set each Circuit s Light Level. Use buttons 3 and 4 to set the light level for the displayed circuit in Scene 1. The light level is displayed, and the lights will respond accordingly. (e.g. Circuit #1 is set to 100% in scene 1 shown in picture) Repeat steps C and D for all circuits in the panel. Light level setup is complete for Scene 1. Panel Programmer Stromkreis Circuit Circuito Fade 1 2 3 4 Off Stromkreis Circuit Circuito Fade C D A, H 1 2 3 4 Off B GRAFIK RP Dimming System Addendum 5

E. Fade Time Setup for Scene 1. Press button 5: the Fade Time LED will blink orange and F 1 will be displayed in the Circuit window. Scene 1 is still selected (Scene 1 LED is lit). (e.g. Fade time for scene 1 is 3 seconds) F. Set Fade Time for Scene 1. Use buttons 3 and 4 to set the Fade Time from 0-59 seconds or 1-60 minutes. To set Fade Time in minutes, press button 3 to scroll through 0-59 seconds, a green LED will light next to the M showing the Fade Time is now expressed in minutes. Scene 1 setup is now complete. G. Scenes 2, 3, and 4. Press button 5 until the correct Scene LED is lit, and follow Steps C through F. H. Exit Scene Setup Mode. Press and hold buttons 1 and 5 simultaneously until LEDs stop flashing to exit. Panel Programmer Stromkreis Circuit Circuito Fade 1 2 3 4 Off F E, G STEP 9: Use System Pressing buttons on a wallstation that is connected to the GRAFIK RP Panel will select a scene and fade time. If the Wallstation is equipped with a master raise lower function, pressing either button will raise or lower all of the lights in the system. 6 GRAFIK RP Dimming System Addendum

Congratulations: Your GRAFIK RP Dimming System is now programmed! For further support refer to the LP Installer s Guide pages 32, 33, 36, and 37. GRAFIK RP Dimming System Addendum 7

Internet: www.lutron.com E-mail: product@lutron.com WORLD HEADQUARTERS Lutron Electronics Co. Inc., TOLL FREE: (800) 523-9466 (U.S.A., Canada, Caribbean) Tel: (610) 282-3800; International 1-610-282-3800 Fax: (610) 282-3090; International 1-610-282-3090 GREAT BRITAIN Lutron EA Ltd., Tel: (171) 702-0657; International 44-207-702-0657 Fax: (171) 480-6899; International 44-207-480-6899 GERMANY Lutron Electronics GmbH Tel: (309) 710-4590; International 49 309 710-4590 Fax: (309) 710-4591; International 49 309 710-4591 ASIAN HEADQUARTERS Lutron Asuka Co., Ltd. (Japan) Tel: (03) 5575-8411; International ++81-3-5575-8411 Fax: (03) 5575-8420; International ++81-3-5575-8420 HONG KONG SALES OFFICE Lutron GL (Hong Kong) Tel: 2104-7733; International 852-2104-7733 Fax: 2104-7633; International 852-2104-7633 SINGAPORE Lutron GL (Singapore) Tel: 65 220 4666 Fax: 65 220 4333 LIMITED WARRANTY Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid. This warranty is in lieu of all other express warranties, and the implied warranty of merchantability is limited to one year from purchase. This warranty does not cover the cost of installation, removal, or reinstallation, or damage resulting from misuse, abuse, or improper or incorrect repair, or damage from improper wiring or installation. This warranty does not cover incidental or consequential damages. Lutron s liability on any claim for damages arising out of or in connection with the manufacture, sale, installation, delivery, or use of the unit shall never exceed the purchase price of the unit. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. These products may be covered by one or more of the following United States patents: 4,797,500; 4,835,343; 4,924,349; 5,038,081; 5,309,068; 5,430,356; 5,633,540; 5,990,635; 6,046,550; 6,091,205; 6,188,181; 6,380,692; D422,567; D436,930; D453,742; D456,783; D461,782; D465,460; D465,770; D466,090; D466,091; D466,484; and corresponding foreign patents. U.S. and foreign patents pending. Lutron, Tu-Wire, and Hi-lume are registered trademarks of Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Inc., Quincy, Massachusetts. 2003 Lutron Electronics Co., Inc. Lutron Electronics Co., Inc. Made and printed in U.S.A. P/N 032-125 Rev. A 4/03