PSN-1000 & PSN 1000(E) Installation Manual

Similar documents
AFC-1000 Fire Alarm Installation Manual

PFC-4064 Conventional Fire Alarm Panel

FireNET Plus Wiring Instructions

Booster Power Supply Manual

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

30.45 Electric Release PDRP-2001

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

MR-2602 Two Zone Fire Alarm Control Panel

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

Installation Guide for models:

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

FireNET Fire Alarm Control Panel Installation Manual

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

TECHNICAL DATA OBSOLETE

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

Model 17A00 Expansion Enclosure

Remote NAC Power Supply D7038

Installation Guide for models:

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Specification/ Data Sheet

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

AL800ULADA. NAC Power Extender. Installation Guide

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

SIGA-CC1 Single Input Signal Module Installation Sheet

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULX Series. Power Supply/Charger. Installation Guide

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

Series. Access Power Controllers. Installation Guide

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

/5121/5122 TrueAlert Power Supply Installation Instructions

LifeAlarm Fire Alarm Control Panels

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Installation, Operating and Maintenance Manual

Conventional Releasing Control Panel

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

Notification Appliance Circuit Module

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

Addressable NAC Output Module D327A

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Harrington Signal HS-3100/3200 Fire Alarm Control Unit

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

June 10, 2002 DF C S2424

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

LifeAlarm Fire Alarm Controls

MANUAL RESET ALARM RELEASE

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Operation and Installation Guide. Fire Alarm Control Panel

SILENT KNIGHT. Model SK-2/E & SK-4/E. Installation and Operations Manual. Fire Alarm Control Panel. Part Number Rev. A ECN /08/05

Electric Release Panel Wiring Tips

4100U City and Relay Cards Installation Instructions

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

Print Specification. Publication. Instructions. Specific requirements. General requirements

TrueAlert Addressable Notification

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

Release Control Fire Alarm Systems

FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

FireNET Series - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL

IFP-2000 F r a en e h n y h t y PH P D

SP-1000X. Panic Device Power Controller Installation Guide. Rev

Public Safety DAS Annunciator Panel

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

Multiple Input and Output Modules

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

good things in small packages

ORENA BRAND CONVENTIONAL (ORENA Brand) CE

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

MS-2410BC. Conventional Fire Alarm Control Panel. Programming, Installation, Maintenance and Operating Instruction Manual

MANUAL RESET ALARM RELEASE BOX

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

PN: 51883:D ECN Field Charger/Power Supply FCPS-24FS6 FCPS-24FS8. Document # /14/05 Revision: D

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

TrueAlert Addressable Notification Appliances

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

July 14, 1999 DF C-100.

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

SAFEPATH SP40/2 D10 D35 AMP P/N P/N Installation, Testing, TONE SW Operation, and W4 Maintenance D54 SHORT

Fire Alarm Wiring. Circuit types, styles and limitations

Conventional Fire Alarm Control Panel

Field Charger/Power Supply FCPS-24S6 FCPS-24S8. Document # /06/03 Revision: C1 PN: 51977:C1 ECN

Signature Series Auto-Sync Output Module (CC1S)

SENTROL ZX440F. Security System Control. Installation/ Programming

These instructions detail procedures to follow in order to avoid damage to equipment.

Transcription:

PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com Document 5403599-Rev. C.-04/17

1. Installation Wiring Document 120VAC 50Hz~60Hz 240VAC 50Hz~60Hz Connect to separate unswitched AC circuit BLACK WHITE GROUND PSN-1000 POWER SUPPLY 120 240 FUSE BULK COMM 120/240 VAC Jumper Position Primary AC 120VAC 50Hz~60Hz, 5.1 AMP Min Low AC Detect 98VAC 240VAC 50Hz~60Hz, 2 AMP Min Low AC Detect 194VAC Common Relays 3A @ 125VAC (Resistive) 3A @ 30VDC (Resistive) Battery Charging 27.3VDC @ 1A Low Battery Detect @20.4VDC Earth Fault to Any Terminal 0 Ohms Fuse Specification 8A-250VAC Time-Lag P/N 5409083-B (12/21/2016) LOW AC NC COM NO TROUBLE NC COM NO Common relays are non-power limited. BATTERY - BATTERY + Battery connection (non-power limited). Use two (2) 12V batteries connected in series. - I2 + - I1 + E.O.L. - NAC2 + - NAC4 + - NAC6 + - NAC1 + - NAC3 + - NAC5 + - + IN A B P-LINK - + OUT A B P-LINK REPEATER RPTR COMM P-LINK FROM CONTROL PANEL E.O.L. F.C.C. This device has been verified to comply with FCC Rules Part 15, Class A Operation is subject to the following conditions: 1. This device may not cause radio interference. 2. This device must accept any interference received including any that may cause undesired operation. Requirements System must be fully tested after installation. Intended for indoor use in dry locations only. Separation of power limited wiring from non-power limited wiring must be at least 1/4". Install in accordance with installation manual Part Number 5403599 Rev, NFPA 70, 72, 12, 12A, 13, 15, 16, 17, 17A, 750, 2001 MAIN COMM P-LINK - + A B CAUTION: De-Energize Unit Prior to Servicing Type of Circuit Voltage Type Power Type AC Connection High Voltage Non-Power Limited Battery Connection Low Voltage Non-Power Limited Trouble Relay Low Voltage Non-Power Limited Low AC Relay Low Voltage Non-Power Limited Notification Device Circuits (NACs) Low Voltage Power Limited Input Circuits Low Voltage Power Limited Plink RS-485 Connections Low Voltage Power Limited 2

Main Supply Circuit PSN-1000 POWER EXPANDER-5403599-REV C-04/17 The AC terminals are located on the power supply board. The power supply board supervises the main AC power and provides indication that the AC power is absent. 120VAC 50/60 Hz 240VAC 50/60 Hz Connect to separate Unswitched AC circuit Black White Ground B W G Figure 1 The terminals are rated at 120 VAC/240 VAC 50/60 Hertz and are marked so accordingly on the board. The earth ground connection is marked as G and is the furthest connection from the line voltage connection. The AC input power ratings: Maximum of 5.1A at the nominal 120 VAC rating. Maximum of 3A at the nominal 240 VAC rating. AC POWER AC120V /AC230V,50/60Hz Rechargeable Battery Circuit The battery charging circuit is provided on the power supply board. Terminal connections are provided to connect wire leads for battery connection. The battery must be a recognized or listed sealed lead acid battery or equivalent. The battery charging voltage is approximately 27.3 VDC and the circuit is supervised. The battery circuit is protected with a non-replaceable 7 amp poly switch located on the main circuit board. The maximum battery charging circuit is 1.0 amp DC. The battery circuit is rated for 8 to 55 AH batteries and the cabinet will house up to two 18 AH batteries. The batteries will operate the panel for at least 24 hours and 5 minutes of alarm. In order to determine the minimum size batteries for standby and alarm times desired, the installer must complete a battery calculation work sheet in order to determine the minimum battery size for a particular application. For reference, the battery calculation work sheet is attached as Appendix A. Complete standby battery calculations must be completed to ensure adequate battery sizes are provided. 3

BATTERY - + - + 12 V Battery - + 12 V Battery Figure 2 Separation of Circuits - Power Limited, Non-Power Limited, High Voltage Wiring The main AC power connection is considered high-voltage and non-power limited. Battery conductors, and the alarm, supervisory, and trouble relays are non-power limited. All remaining circuits are low-voltage, power limited connections. Proper separation must be maintained between the circuits listed above. All separations in the different wiring must be maintained by at least 0.25 inches and the wire insulation must be for the higher voltage. In the enclosure there are sufficient knock outs located around the periphery of the cabinet to allow the installer to maintain separation between power limited and non-power limited connections. The main AC power connection should be made on the left side or top left of the cabinet. Notification Appliance Circuits (NACs) The PSN-1000 is equipped with six NAC circuits. Each of the circuits is rated for a continuous 3 amps at 24 VDC. The outputs are supervised and regulated. The NACs reverse polarity upon activation and the board and illustrations are marked accordingly. The NAC circuits can be configured for Class A operation. Class-A operation is accomplished by using a pair of NAC circuits. Therefore, the PSN-1000 can provide 3 Class A circuits, each rated for a continuous 3 amps at 24 VDC. The outputs are supervised and regulated. NAC circuits are power limited and the type of output is selectable. The NACs may be configured for strobe synchronization with Potter/AMSECO, Wheelock, Gentex, or System Sensor strobe devices as shown compatible in this document and the installation instructions. The maximum impedance is a function of the load being applied to the circuit. In order to calculate the maximum impedance as follows (Alarm Current of Notification Appliances) X (Wire Resistance) < 3 volts. The NAC circuits may be configured for Class A, Style Z or Class B, Style Y. The panel has ground fault detection on the NAC circuits. The impedance to ground for ground fault detection is 0 ohms. 4

I2 + - NAC 2 + - NAC 4 + - NAC I1 + - NAC 1 + - NAC 5 + - NAC Notification Appliance 5.1k EOL Potter Part #3005013 Figure 3 (Class B NAC) The end of line resistor is a 5.1K ohm resistor. The resistor assembly has been evaluated in past projects and is a standard in the Potter panel product line. The Potter part number for the listed end of line assembly is 3005013 EOL Resistor Assembly. 5

I2 + - NAC 2 + - NAC 4 + - NAC I1 + - NAC 1 + - NAC 5 + - NAC Notification Appliance Figure 4 (Class A NAC) Class A operation requires that two NAC circuits be utilized as shown in Figure 4. Up to 3 Class A circuits can be configured by pairing NAC 1&2, NAC 3&4 and NAC 5&6. 6

Input Circuits PSN-1000 POWER EXPANDER-5403599-REV C-04/17 The panel is equipped with two input circuits, I1 and I2. These circuits are dry-contact monitoring inputs, and can be used in class B mode only. I1 and I2 are low voltage, power limited, and supervised. Maximum wiring resistance = 100 ohms. Maximum wiring capacitance = 1 uf. Maximum wire length = 10,000 feet. Maximum IDC voltage = 24 VDC Maximum IDC current = 15 ma The panel has ground fault detection on the input circuits. The impedance to ground for ground fault detection is 0 ohms. - I2 + - NAC 2 + - NAC 4 + - NAC - I1 + - NAC 1 + - NAC 5 + - NAC Normally Open Dry Contact 5.1k EOL Potter Part #3005013 Figure 5 (Input Circuit as Class B Dry Contact Input) The end of line resistor is a 5.1K ohm resistor. The resistor assembly has been evaluated in past projects and is a standard in the Potter panel product line. The Potter part number for the listed end of line assembly is 3005013 EOL Resistor Assembly. 7

P-Link from Control Panel The control panel communicates with the PSN-1000 via the main P-Link circuit. This connection is electrically isolated from the rest of the PSN-1000. All supervision of the PSN-1000 is conducted through this connection. - + A B P-LINK Wiring from Control Panel P-Link Repeater Figure 6 The P-Link repeater output allows for system expansion by reconditioning and repeating all P-Link communications. The PSN-1000 repeater output provides an additional 1 amp at 24 VDC which can be used to power additional P-Link devices such as LCD Annunciators and/or SLC Loop expanders. Wiring is fully supervised and power limited. Any connection to ground of 0 ohms will be annunciated as a ground fault. P-Link Current = 1 Amp Each P-Link Voltage = 24 VDC Maximum wire length = 6,500 feet. Maximum wire resistance = Maximum wiring resistance is based on load. Calculate using the following equation (Total P-Link Alarm Current) x (Wire Resistance) < 6 volts. To the next device - NAC 6 + - + A B P-LINK - NAC 3 + - + A B - + A B Expansion Device - + A B Expansion Device Figure 7 (P-Link Class B Wiring Example) 8

- + A B Expansion Device - NAC 6 + - + A B P-LINK - NAC 3 + - + A B Figure 8 (P-Link Class A Wiring Example) - + A B Expansion Device Releasing Device Circuit The releasing circuit is fully supervised and power limited. The releasing device circuit is a NAC that is programmed to control a releasing device such as a solenoid or squib. The output is a constant 24 VDC, regulated output. When connected to a releasing device, the circuit is a special application circuit and listed with the devices as outlined in Section 6 of this ULLD document. The maximum current is 3 amps. The maximum line impedance is calculated using the following formula. Rmax (ohm) = (24V-Vmin-0.95V)/I total Vmin is the lowest voltage operation of the connected devices. I total is the total current of the connected devices. When a NAC is used as a releasing circuit, the End of Line Diode (EOLD) assembly must be installed. The EOLD is Potter part number 3005012 and must be installed in accordance with the installation manual. 9

- NAC 2 + - NAC 4 + - NAC 6 + - + A P-LINK - NAC 1 + - NAC 5 + - NAC 3 + - + A End of line device 5.1k ohm 1/2W Part #3005012 Releasing Device Note: EOL Device shall be installed in the same electrical enclosure as the releasing device. Figure 9 Municipal Box Connection When programmed as a municipal box connection, the circuit is power limited, is supervised for open and short circuit conditions and provides a local energy connection. Trip current = NAC1-NAC6 = 3 Amps Max Voltage = 24 VDC The panel has ground fault detection on municipal box connection circuits. The impedance to ground for ground fault detection is 0 ohms. - NAC 2 + - NAC 4 + - NAC 6 + - + A B P-LINK - NAC 1 + - NAC 5 + - NAC 3 + - + A B End of line device 5.1k ohm 1/2W Part #3005012 + - Municipal Box Notes: The EOL device shall be installed in the same electrical enclosure as the Municipal Box. Figure 10 10

Relay Outputs PSN-1000 POWER EXPANDER-5403599-REV C-04/17 The panel has a dedicated trouble relay and low AC relay. The dedicated trouble relay is a failsafe trouble relay that changes position anytime a trouble condition occurs. The contact rating is 24VDC / 3.0A, 125VAC / 3A, Power Factor: 1.0. These outputs are non-power limited and not supervised. However, they are power-limited if the power supply to the connected devices is powerlimited. LOW AC NC COM NO TROUBLE NC COM NO Figure 11 General Wiring Information The cabinet has various conduit knockouts located around the cabinet for ease of wire installation. In addition, this method provides a means to separate different types of circuit to reduce electrical interference, transient voltage or voltage ratings. The enclosure requires the use of power limited and non-power limited wiring on the main board as well as within the enclosure. Power limited wiring is to remain separated from non-power limited by a minimum or 0.25 inches and all cabling should be insulated to the higher voltage. When the panel is installed, the National Electrical Code (NEC, NFPA 70) should be followed for the proper installation and separation of power limited and non-power limited circuits. The mixing of power limited and non-power limited should be avoided. 3. Functionality The PSN-1000 & PSN-1000E provide power and communication expansion capability to the PFC-6000 series control panels. The PSN-1000 provides an electrically isolated Plink repeater output, providing additional power and communications distance. The larger cabinet of the PSN-1000E provides locations for mounting additional SLCE-127 SLC expanders. The 6 NAC circuits are configured and controlled by the main control panel. The PSN-1000 transfers from AC to battery instantly upon AC failure or brownout. The trouble relay will indicate the low AC condition after the Low AC Report Delay has elapsed. 11

LED behavior (Power Supply Board) AC Power: ON = AC Present, OFF = AC not Present Low Battery: OFF = No Fault. Flashing = Low battery Condition. ON = Battery Charger Failure Earth Fault: Flashing = Earth Fault detected. Comm: 1 second flash indicates normal communications with NAC control board LED Behavior (NAC Control Board) Bulk Comm: 1 second flash indicates normal communications with NAC control board RPTR Comm: Flashes when P-Link repeater communications occur Main Comm: Flashes when P-Link commands are received from the control panel 5 Position DIP Switch A 5 position dip switch is provided for setting the ID of the PSN-1000/E. An ID in the range of 1-31 can be specified according to the table below. PSN-1000/E Dip Switch Settings ID SW-1 SW-2 SW-3 SW-4 SW-5 1 On Off Off Off Off 2 Off On Off Off Off 3 On On Off Off Off 4 Off Off On Off Off 5 On Off On Off Off 6 Off On On Off Off 7 On On On Off Off 8 Off Off Off On Off 9 On Off Off On Off 10 Off On Off On Off 11 On On Off On Off 12 Off Off On On Off 13 On Off On On Off 14 Off On On On Off 15 On On On On Off 16 Off Off Off Off On 17 On Off Off Off On 18 Off On Off Off On 19 On On Off Off On 20 Off Off On Off On 21 On Off On Off On 22 Off On On Off On 23 On On On Off On 24 Off Off Off On On 25 On Off Off On On 26 Off On Off On On 27 On On Off On On 28 Off Off On On On 29 On Off On On On 30 Off On On On On 31 On On On On On 12

5. Testing/Maintenance PSN-1000 POWER EXPANDER-5403599-REV C-04/17 The power supply board has one fuse on the board for the AC power over current protection. The AC fuse is rated at 8A 250VAC Time-Lag and screened onto the main board as F1. The batteries are to be replaced at least once every four years. The batteries are required to be UL recognized batteries with a date of manufacture permanently marked on the battery. The battery is to be tested at least annually and if the battery is showing signs of failure, it is to be replaced. The battery is to remain in the cabinet with nothing on or around the batteries. Only properly sized sealed lead acid batteries are to be used with the control panel. Use of another battery or not providing the proper clearance may result in a fire or an explosions. The PSN-1000 is required to be installed in accordance with local and state building codes and NFPA 72 (National Fire Alarm Code). The PSN-1000 and related system is required to be inspected and tested in accordance with NFPA 72. 6. Compatibilities NAC Appliances Please refer to Potter document 5403592-C NAC Compatibility Document Releasing Circuit Devices (All 24 VDC Devices, only one device per circuit) Nohmi - Koatsu R85M14, R85M10-N Skinner 73218BN4UNLVNOC111C2 Skinner 73212BN4TNLVN0C322C2 Victaulic 753-E Series Viking 11591, 11601, 11602, 13843 and 13844. Fireaway - Stat-X Models 30E, 60E, 100E, 250E, 500E, 1000E, and 2500E Aero-K Models G30, G60, G100, G250, G500, G1000, G1500 and G2500 (Maximum of 10 per circuit) Note: A Fireaway transient protection device (Part # 3005014) must be installed with each releasing device 13

Appendix A, Battery Calculation Work Sheets (Include for all P-Link devices being powered by the PSN-1000) Description Quantity Standby (ma) Total Standby (ma) Alarm (ma) Total Alarm (ma) Main board ( PSN-1000/1000E) 1 60 60 200 200 LCD Remote (RA-6075R or RA-6075) 20 25 LCD Remote (RA-6500R or RA-6500) 20 50 Other PSN-1000/E Power Expanders 15 15 NAC 1 NAC 2 NAC 3 NAC 4 NAC 5 NAC 6 Total (ma) (*Refer to maximum allowable standby current) Total A Total (ma) Convert to Amps x 0.001 Convert to Amps x 0.001 60 Minutes per Hour Alarm time (minutes) Total A Multiply by standby hours Total Standby AH Example: 5 minute alarm - Enter 12 10 minute alarm- Enter 6 Total Alarm AH +Total Standby AH Total AH Efficiency Factor 0.80 Required AH *Maximum Allowable Standby Current (UL 24-Hour standby time) 7 AH.230 A 18 AH.619 A 33 AH 1.151 A 55 AH 1.930 A Important Notes: 1) PSN-1000/E enclosure can house up to (2) 18 AH batteries. Larger batteries require accessory enclosure, Space Age Electronics part #SSU00500. 2) NFPA 72-2002 require 24 hours of standby power followed by 5 minutes alarm activation. 3) NFPA 12, 12A require 24 hours and five minutes of alarm activation. 4) Door holder circuits configured to disconnect upon AC loss need not be included in the battery standby calculation since they will not draw power during that time. Door holders will contribute to standby current draw when AC is present. 5) Total current must not exceed power supply rating (10 A) 14

SLC# Current Draw Worksheet (Repeat for each SLCE-127 being powered by the PSN-1000) Description Qty Standby (ma) Total Standby (ma) Alarm (ma) Total Alarm (ma) SLCE-127 Main Board 1 60 60 60 60 Analog photo smoke detector (PSA) 0.325 0.325 Analog photo DUCT smoke detector (DSA) 0.325 0.325 Analog photo smoke / fixed heat detector (PSHA) 0.325 0.325 Analog fixed heat detector (FHA) 0.325 0.325 Analog combo heat detector (RHA) 0.325 0.325 Conventional initiating zone module - 4 inch mount (CIZM-4) *Note 1 0.325 1.0 Miniature contact module (MCM) 0.325 0.325 Single contact module - 4 inch mount (SCM-4) 0.325 1.0 Dual contact module - 4 inch mount (DCM-4) 0.325 1.0 Monitored output module - 4 inch mount (MOM-4) *Note 2 0.325 1.0 Twin relay module - 4 inch mount (TRM-4) 0.325 1.0 Short circuit isolator (SCI) *Note 3 0.325 2.34 Analog sounder base (ASB) 0.325 0.325 Analog relay base (ARB) 0.325 0.325 Isolator base (AIB) *Note 3 0.325 2.34 SLC alarm LED Current n/a n/a n/a 27.0 SLC Standby Current SLC Alarm Current * Note 1: CIZM requires 24VDC power source. Standby current Style D = 4.90 ma, Style B (8.5 ma). Alarm Current = 50.0 ma * Note 2: MOM requires 24VDC power source. Standby current = 1.6 ma. Alarm Current = 1.60 ma * Note 3: In Class B (Style 4) installations the following rule must be observed: Number of SLC Devices + Number of Isolated branches * 8 Must be <= 127 * Note 4: In Class A (Style 7) installations the following rule must be observed: Number of SLC Devices + Number of Isolators used Must be <= 127 15