Experimental Study on Fractionation of R-407C and Recharge Operations

Similar documents
Low Global Warming Refrigerants For Commercial Refrigeration Systems

PRACTICAL EXPERIENCE WITH AN ALTERNATIVE TO R-22 BASED ON R-32lR /R a. R E Low, B E Gilbert, T W Dekleva.

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Study of R161 Refrigerant for Residential Airconditioning

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Air-Cooled Heat Exchanger Performance for R410A

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Efficiency of Non-Azeotropic Refrigerant Cycle

Low GWP Refrigerants for Air Conditioning Applications

Purdue e-pubs. Purdue University

Sub-Critical Operation of the CO2 Expander/ Compressor

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Comparison of Energy Efficiencies of Commercial Refrigeration Direct and Indirect Systems

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Comparison of Thermophysical Properties of HFC 125, 32 and 143a

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

The Development of the Energy-Saving Technology by the Composition Control of R407C

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

An Experimental and Theoretical Study on System Performance of Refrigeration Cycle Using Alternative Refrigerants

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

R32 Compressor for Air conditioning and Refrigeration applications in China

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

A Performance-Enhancing Additive for Vapor- Compression Heat Pumps: Additional Test Results

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Evaluation of HCFC Alternative Refrigerants

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

High Efficiency Heat Pump for Domestic Hot Water Generation

System Using Exhaust Heat from Residential GHPs

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Compressor Capacity Control

Purdue e-pubs. Purdue University. T. Hamada Mitsubishi Heavy Industries Ltd. N. Nishiura Mitsubishi Heavy Industries Ltd.

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Experimental Investigation Of A New Low- Approach Evaporator With Reduced Refrigerant Charge

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Heat Transfer of R-22 and Alternatives in a Plate- Type Evaporator

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Alternative Refrigerants For Household Refrigerators

Refrigerant Glide and Effect on Performances Declaration

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

Wide-Boiling Refrigerant Mixtures - Technical and Commercial Challenges

The Circulation Composition Characteristic of the Zeotropic Mixture R1234ze(E)/R32 in a Heat Pump Cycle

Experimental Study on the Performance of Twisted Capillary Tube

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Investigation of Evaporator Performance with and without Liquid Overfeeding

Energy Efficiency of Air-to-Air Mini Heat Pump

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Development of HFC-134a Compressor for Domestic Refrigerator

Investigation, Analysis and Solution of Higher Noise of Heat Pump Water Heater

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Simscape Refrigerant Loop Product

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Evaluation of Mechanical Dehumidification Concepts (Part 2)

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Perspectives of Aluminum As A Construction Material for Stationary Refrigeration and Air Conditioning Systems

HSPF Calculation of a System Allowing Switching Between a Single-Stage to a Two-Stage Compression System

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1998 Experimental Study on Fractionation of R-407C and Recharge Operations M. Paulus-Lanckriet Solvay Research & Technology O. Buyle Solvay Research & Technology Follow this and additional works at: http://docs.lib.purdue.edu/iracc Paulus-Lanckriet, M. and Buyle, O., "Experimental Study on Fractionation of R-407C and Recharge Operations" (1998). International Refrigeration and Air Conditioning Conference. Paper 394. http://docs.lib.purdue.edu/iracc/394 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

EXPERIMENTAL STUDY ON FRACTIONATION OF R~407C AND RECHARGE OPERATIONS M. Paulus~Lanckriet, 0. Buyle SOLVAY RESEARCH & TECHNOLOGY Business Unit Fluorochemicals ABSTRACT This paper provides an update on our knowledge in the field ofr-407c fractionation and evaluates its impact while the system is in operation. Furthermore, the impact of leakages has been evaluated in terms of performance changes and fractionation ofr-407c. Concentration shifts also result from common practice in the servicing of refrigeration installations. All these potential problems with R-407C have been quantified in an existing experimental refrigeration system, including recharge operations. The paper gives a summary of our latest results on fractionation and recharge tests leading to practical recommendations for the use ofr-407c. INTRODUCTION In the context of the R-22 phase-out starting in Europe in the year 2000, HFCs are developed as efficient substitutes in refrigeration and air conditioning systems. These refrigerants are already used in new equipments for applications where R-22 would have been chosen in the past. R-22 will not be replaced by only one single substitute, but by a range of products. Depending on the application, pure HFCs or mixtures ofhfcs are taken into account. In particular, R-407C and R-41 OA are recognized worldwide as promising substitutes for R-22. R-407C (HFC-32/ HFC-125/HFC-134a 23/25/52 %) is a zeotropic mixture with a significant temperature glide (7K). Up to now, the use of zeotropic refrigerants was limited to special cases. IfR-407C becomes widely used in usual R-22 applications, there is a need to investigate the practical implications arising from its zeotropic character. The fractionation ofr-407c has already been studied experimentally by the authors under typical refrigeration conditions and first data have been published [1). The present paper provides an update on our knowledge in this field and evaluates the impact of the fractionation while the system is in operation. STATE OF KNOWLEDGE ON FRACTIONATION- A QUICK OVERVIEW Introduction Several studies have already been published about the effect of the zeotropic character of mixtures, most of them based on leakage tests, with possibly recharge processes. Some of these 93

publications are based on experimental detenninations, others on computer simulations, but most of them give mainly the consequences on performance parameters (COP and volumetric capacity) in case of a leak. An overview has already been given by Chen., Kruse and Wischollek ([2], [3], [4]), which include in the last case the influence of fractionation and partial miscibility of components in oils. Fractionation of R-407C in a Refrigeration Systems Apart from the reference [1], only two other publications are related to the fractionation of R-407C in the refrigeration installation without any leak. Goth (5], with the simulation of an installation equipped with an important accumulator; estimates the circulating composition is enriched in HFC-134a (increase between 5 and 10 %in the circulating composition). Surprisingly, he finds that the phenomenon is opposite, with a decrease in the HFC-134a concentration, when the installation is not equipped with a liquid accumulator. Corr and Murphy (6], by simulation, give the same results as the previous one without accumulator, for the circulating composition. They found concentrations ofhfc-32/ HFC-125/HFC-134a 25/27.3/47.7 %). They confirm [1) with the concentrations of the components in a vapor phase in contact with a liquid one : they are roughly equal to each other (;:::=: 33 weight%). However, the location of the detennination is different (in the condenser for the work reported in [6], instead of at the entrance of the evaporator for the work reported in [1]). R-407C Fractionation during Leak Scenarios It is quite difficult to compare the results between the different tests and calculations published in the literature. As recognized above, the results depend on the type of equipment. Also important are the operating conditions, temperatures in the heat exchangers and leak. scenario, for example. The general criterion for the recharge of refrigerant is also different in each case : the apparition of first bubbles in the sight glass, or the supposition made that a critical lack of refrigerant is reached (in all the cases, between 90% and 60% ofthe initial R-407C charge). However, general tendencies can be drawn. The leak is generally in vapor phase, located after the expansion valve. Only Stanbouly [7) has investigated other locations, but it is evident that a leak in vapor phase after the expansion valve leads to the higher effects on R-407C compositions and performances. In reference [7], no refrigerant analysis was performed, but both COP and cooling capacities decreased of a few percents after five leak/recharges. The simulation of an evaporator vapor leak by Bresnahan and Low [8) gives quite optimistic results: only a few percent enrichment ofhfc-134a in the leak when no liquid remains in the condenser, the system must then be recharged. The sole effect on performances is a decrease by a few percents of the refrigeration capacity ofr-407c after a few leak/recharge cycles. Tests in a supermarket cabinet described by Kruse and Chen (9] have also shown that after 8 % and 50 % ofloss of charge, the circulating composition is quite different :from the R-407C nominal composition, HFC-32/HFC-125/HFC-134a 21/24/55% and 18/21/61% respectively for a leak of8% and 50%. 94

When only performances are estimated by calculations based on static leak tests in the vapor phase (Preisegger and Bivens, [10] [11]), the volumetric capacity is recognized to decrease by a few percents. An increase in COP is even noted in [10).because of the higher HFC-134a content. In order to complete our knowledge in that field, we have thus combined both GC analysis for the fractionation study and experimental performances determination of a specially designed refrigeration equipment. The results are described in the following part of the paper. EXPE~ENTALRECBARGESCENARIOS Introduction The effect of successive leak and recharge processes has been investigated in an experimental system, fully equipped with measuring devices allowing the measurement of pressure, temperature and flow rate ofthe refrigerant at different points ofthe cycle. The equipment allows also the sampling of refrigerant in different locations, for further GC analysis. Description of the Refrigeration Equipment The experimental refrigeration installation (Figure 1) was designed for R-22 and used as such for R-407C. It is equipped with a semi-hennetic compressor. The refrigerant flow rate is measured with a Coriolis massflow meter. The condenser is water-cooled and the evaporator is a liquid/glycol dry heat exchanger. The inlet temperatures of water and glycol are maintained constant; the flow-rates are regulated by a three-way valve and the temperature is fixed with thermocryostats before the inlet in the heat exchangers. The flows are also measured with volumetric flowmeters. Six locations have been taken for the sampling of the refrigerant : before and after the condenser, the receiver and the evaporator (see figure 2). Among all locations, only the sample at the entrance of the evaporator is a "two-phase" sample in the refrigeration device. The valve connection is realized on the upper side of the tubing, in such a way as to provide the vapor phase at this location. It is also used for the simulation of the leak at this point. Each sample has been analyzed by gas chromatography, in order to show the possible segregation between HFC-32, HFC-125, and HFC-134a. Experimental Conditions The running conditions were -20 oc at the evaporator (bubble temperature) and 40 oc at the condenser (dew temperature), with a constant superheat of 2 K in the evaporator. As previously mentioned, the location of the leak has been chosen in order to provide the worst effect on the composition: in vapor phase at the entrance of the evaporator. The refrigerant was recovered in a bottle placed on a scale. The weight of each sample was close to 0.300 kg for an initial charge of8 kg. 95

The composition of the refrigerant recovered from the installation, initially charged with R-407C, has been determined during each leak process before recharge. The latter sampling was made when a total of 1 kg refrigerant had leaked. This quantity corresponds to the apparition of the first bubbles in the sight glass, previously determined with an emptying simulation of the refrigeration equipment. Performances parameters were calculated at this stage, together with an analysis of the refrigerant in the bottle and of samples taken at the six location of the installation. This leak/recharge cycle was realized four times. Results Fractionation effect The analysis of the leaked refrigerant was used to calculate the global composition ofthe refrigerant R-407C (initially HFC-32/HFC-125/HFC-134a 23/25/52 %) remaining in the refiigeration equipment. The variation is presented in figure 3. Taking into account the ASHRAE specifications which fix the concentration ofthe mixtures with a tolerance of± 2% by weight, the HFC-134a concentration reaches nearly the boundary after the first leak and exceeds 54% during the second leak. The level of21% for HFC-32 and 23% for HFC-125 is reached during the third leak process. There is no significant effect by recharge ofr-407c. The concentrations at the different locations of the installation are presented in table 1, at the initial stage and after the four leak/recharge processes. They follow the same general trend as the global composition of the refrigerant as shown in figure 3. Evolution of the Performances The reduction in refrigeration capacity, electrical COP and volumetric capacity after the four leaking cycles are presented in table 2. They have been based on temperature, pressure and power measurements and taking into account the nominal R-407C thermodynamic properties or the thermodynamic properties of the real composition of the refrigerant remaining in the installation. This is done with REFPROP 5. 0 from NIST. The variations are hardly significant if the nominal composition ofr-407c is taken for the calculations. However, a better estimation can be made with the real composition in which case a clear decrease is observed, respectively of 11 %, 4 %, and 8 % for the refrigeration capacity the electrical COP and the volumetric capacity. This is also in reasonable agreement with the literature discussed above. CONCLUSION AND PRACTICAL IMPLICATIONS Leak and recharge processes on a refrigeration installation with the zeotropic R-407C refiigerant show a quite important variation of the refrigerant composition in the equipment, leading to a refrigerant which can be significantly different from the nominal composition. The 96

recharge with the nominal R-407C composition does not correct the shift of concentrations. It will thus be necessary to take care of this fact when R-407C must be recovered, reclaimed and/or recycled after use. The effect ofleak and recharge processes are in accordance with the previously published literature and show that the refrigeration capacity is the most affected parameter. It has to be noted that only four leaking processes have been realized, which is quite few in comparison with a real refrigeration equipment. The reduction of the performance parameters is not revealed if they are calculated with the R-407C nominal composition. However, this decrease is quite real because ofthe change of composition due to the leak process, which is not corrected by a recharge with the R-407C nominal composition. Even if it is quite difficult to evaluate the remaining composition in the equipment without any leak analysis, it would be necessary to adapt the recharge composition in order to recover the initial R-407C performances. REFERENCES [1] : M. Paulus-Lanckriet, 0. Buyle, "R-407C!R.-410A: an analysis ofthe two prominent candidates for the replacement ofr-22 in refrigeration applications", IIFIIIR Conference Heat Pump Systems, Energy Efficiency, And Global Warming, Linz, Austria, 28.09/01.10.97 [2) : J. Chen, H. Kruse, "Kaltemittelgemische als Substitute fur R22, R502 und Rl3B I", AIF Forschungsvorhaben Nr 9841, Forschungsrat Kaltetechnik, Frankfurt 1995 [3] : H. Kruse, F. Wischollek; E. Wobst; G. Ahnefeld, U. Hesse, "Konzentrationsverschiebung in Kreisprozessen bei Verwendung von Kaltemittelgemischen", F orschungsrat Kaltetechnik, Frankfurt 1996 (4] :F. Wischollek; H. Kruse, "Erprobung von Kaltemittelgemischen im Verdichterkreislauf, Teilforschungsvorhaben A: Eigenschaften vonausgewahlten 01/Ka.ltemittelgemischen", Forschungsrat Kaltetechnik Frankfurt 1998 (5] : Y. Goth, "Ecart entre les compositions de charge et circulation dans une installation frigori:fique", Joumee "Fluide Frigorigenes de demain", Paris, France, 07.02.97 [6] : Stuart Carr, F. Thomas Murphy, Stuart Wilkinson, "Composition shifts of zeotropic HFC refrigerants in service", ASHRAE Transactions, US 1994, V.IOO, n 2, pp. 538-548 [7] : Stanbouly, "Serviceability issues associated with R-407C refrigerant", 1996 International Conference at Purdue University, July 1996 [8] : J.D. Bresnahan, R.E. Low, "Zeotropic refrigerants in the real world : performance testing of R22 andr502 alternatives based onr32/r125/r134a'', 1995 AIRAH Conference, Melbourne [9) : H. Kruse, J. Chen, "Cycle performance of alternative refrigerant mixtures", International seminar ofheat Transfer and Thermophysical Properties, Japan, 1993 97

[10] :E. Preisegger, "Aspects concerning the composition shifts in refrigerant blends", Fifth European Seminar for the Future of Refrigeration and Air Conditioning, Italy, 1995 [11] :D.A Bivens and al.,"hcfc-22 alternative for air conditioners and heat pumps", ASHRAE Transactions, V. 1 00 n 2, 1994 Figure l : Experimental refrigeration device Receiver 2 3 Condenser Expansion Valve Compressor 6 Figure 2 :Localization of the sampling points for the refrigerant fractionation determination 98

., l: ~ 40!!! c GJ 30 Variation of R407C concentrations in the equipment during the leak/recharge scenarios (initial charge of 8 kg, leak of 1 kg) Recharge 1 Recharge 2 Reehi!irge 3 R~c:hargll!l 4 "1 -- ----- -- --- -------- ------- --- -------- --------- -- --------- " :-~:-~ : _:_ : =-_- :-..: ;-_ :~ : _:_ : : ~: -..::-..::-~-:-~ -=:-..: :-..:: ~-:-: ~ --R134o u - ----- - l: 0 (J Leak 1 Leak 2 Leak 3 Leak 4 :: [_~_:.~---~ : ~---- ------------- -- ---- -...a--r1:25 - ~--- -Nornlnal concenlratiol"'s = ::-: ::::~ : :===::: :1 - -- Sp!!!ci(Jc:atio~ Figure 3 :Variation of the refrigerant composition during the four cycles Location Receiver inlet Receiver outlet Evaporator inlet Evaporator outlet Condenser inlet Condenser outlet -- lifc-32/hfc~125/hfc... l34a Weight%. - -- -- Initi~l - ---- -- - _ --...... _ ;\fter f'otjr. - _- -.- - Jeakfiecharg~ steps 23.2/25.5/51.3 20.1/22.6/57.3 22.9/25.3/51.8 20.0/22.6/57.4 29.7/30.8/39.5 26.8/28.4/44.8 22.1/24.9/53.0 19.9/22.5/57.6 25.0/26.6/48.4 21.6/23.6/54.9 24.2/26.1/49.7 21.4/23.5/55.0 Table 1 : hritial and final concentrations at the different locations of the refrigeration device. :.... :. ~arat11eter : - ltedtctio~- ~- - -- _ -. : _._--_ c.: a 1-.c~--- 1 _ a _ : t:e.:d -. w- - r t_-_h -- R-4!>_ o _7. c-- R _-_._duc_ ti ;on_ % w ->calculated 'Yith - - - - concentrations - real concentrations - Refrigeration capacity 2.7 11.0 Electrical COP 1.0 3.9 Volumetric capacity 3.0 8.0 Table 2 ; Reduction of initial perfonnances after the fourth recharge 99