TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

Similar documents
TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

TEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

TEST REPORT #68. Chiao M. Lee Paul Laurentius. Hussmann Corporation St. Charles Rock Road Bridgeton, MO United States of America

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

GWP Alternative Refrigerants

R4H4. Product Specifications

Low GWP Refrigerants for Air Conditioning Applications

R4H4. Product Specifications

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

N4H4. Product Specifications

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Low Global Warming Refrigerants For Commercial Refrigeration Systems

January 16 th, 2014 New York City

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

13 SEER CONDENSING UNITS & AIR HANDLERS

N4A6. Product Specifications

NH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT

Commercial High-Efficiency Condensing Units

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

4HP15L PRODUCT SPECIFICATIONS HIGH EFFICIENCY SPLIT HEAT PUMP SYSTEM UP TO 15 SEER & 9.0 HSPF COILS COMPONENTS COMPRESSOR WARRANTY CABINET DESIGN

Product Data. Fig. 1 - Unit 50VR -A

A/C Cooling Load calculation and measurement


TEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON

A 14 SEER Heat Pump with R---410A Refrigerant Series

R32 Compressor for Air conditioning and Refrigeration applications in China

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Low GWP Refrigerants for Air Conditioning and Chiller Applications

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Duct Free Systems Product Data Digest ¾ to 5 Nominal Tons

Product Data. Efficiency. S S Reliability

Product Data INDUSTRY LEADING FEATURES / BENEFITS. BH13NA SINGLE -STAGE HEAT PUMP WITH PURONr REFRIGERANT. Efficiency S S Reliability S

Product Data. 25HCB6 Performancet Stage Heat Pump with Puronr Refrigerant 2to5Tons INDUSTRY LEADING FEATURES / BENEFITS.

TEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines

INSTALLATION INSTRUCTIONS

WCH5**4. Product Specifications

RSG16**S1M. Split System Air Conditioner 16 SEER

1-1/2 THRU 2-1/2 TONS SPLIT SYSTEM FWM Series

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

Evaluation of HCFC Alternative Refrigerants

R-404A Alternative with Low Compressor Discharge Temperature

PAJ3. Product Specifications

Advance Product Data

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Steady and Cyclic Performance Testing of Packaged R-410A Units

Energy Use in Refrigeration Systems

CHAPTER 1 INTRODUCTION

Commercial High-Efficiency Condensing Units

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Advance Product Data

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration

SUBMITTAL DATA - OUTDOOR UNIT VEP075N432G VRF HEAT PUMP

Product Data. 224ANS PREFERREDt SERIES HEAT PUMP WITH PURONr REFRIGERANT 1-1/2 TO 5 NOMINAL TONS INDUSTRY LEADING FEATURES / BENEFITS

Product Data. 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons INDUSTRY LEADING FEATURES / BENEFITS

13HPD MERIT SERIES R 22 H E A T P U M P O U T D O O R U N I T S

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Product Data. Efficiency

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

PACKAGE AIR CONDITIONER

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning

Prepared by: (415) With. High. Prepared for: Final Report June 27, Contributors: Tom. Me!

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS

Application Engineering

Ruud Achiever Series Dedicated Horizontal Package Heat Pump

Ruud Achiever Series Dedicated Horizontal Package Heat Pump

INDUSTRY LEADING FEATURES 2 5 / BENEFITS

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

T-Class AC and HP Units Up to SEER and 9.0 HSPF. Commercial Air Conditioners and Heat Pumps. True performance and rugged durability

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

MAC N-407 Air-Cooled Chiller

1 TECHNICAL CHANGES. MUZ-A09NA MUZ-A09NA - 1 MUZ-A09NA - U1 MUZ-A09NA - U2 1. Refrigerant system diagram has been changed.

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

Product Data. 38EYX 50Hz Heat Pump With R---410a Refrigerant Single and Three Phase 2To5Tons FEATURES AND BENEFITS AVAILABLE SIZES:

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

T P A 120 S 4 S N 1 Y

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Product Data /4WCC3018A through 2/4WCC3060A Single Package Convertible Heat Pump 13 SEER 1½ - 5 Ton R-22/R-410A

Nominal Capacity /2Ton 024 2Tons /2Tons 036 3Tons /2Tons 048 4Ton 060 5Ton

Study of R161 Refrigerant for Residential Airconditioning

seer 4HP16LT Split System Enhanced Heat Pump Features and Benefits WARRANTY

Effects of Refrigerant-Lubricant Combinations on the Energy Efficiency of a Convertible Split-System Residential Air-Conditioner

Rooftop Units 60HZ. PACKAGED HEAT PUMPS 13HPP / rhp13 PRODUCT SPECIFICATIONS 13 HPP 36 A P - 1 A RHP 13 A 36 T - 1 A MODEL NUMBER IDENTIFICATION

R 410A Ducted Horizontal Air Conditioner

Product Data. S Sound level as low as 67 dba Comfort. S System supports Thermidistatt or standard thermostat controls Reliability

Product Data. S Up to 20.5 SEER / 15.5 EER S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound

Transcription:

Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #4 System Drop-in Test of Refrigerant R-32 in Split System Heat Pump (with Addendum) Travis Crawford Dutch Uselton Lennox Industries Inc. 1600 Metrocrest Drive Carrollton, TX 75006 December 19, 2012 Updated on April 24, 2013 This report has been made available to the public as part of the author company s participation in the AHRI s Low-GWP AREP.

1. Introduction: This document reports performance testing conducted on a 3.5 Ton split-system heat pump, designed for operation with R410A, but tested with both R410A and R32 (difluoromethane). This testing occurred during August 2012 at the Lennox Product Development and Research Center in Carrollton, TX. The motivation for this work was to investigate the suitability of lower Global Warming Potential (GWP) refrigerants as candidate replacements for the HFC refrigerant: R410A. These two refrigerants have GWPs (AR4, 2007 Assessment) of: R410A 2088 R32-675 2. Details of Test Setup: a. Description of System The out unit is designated as a 14HPX-042 (Lab Inventory Control # 29882). This R410A heat pump uses a scroll-type compressor and has a thermostatic expansion valve for refrigerant flow control in the heating mode. It uses POE oil. The calorimetered sample compressor was provided by Emerson Climate Technologies. The in unit is a multi-position coil-blower. The model number is CBX26UH- 042 (Lab Inventory Control #29880). This air handler uses a PSC-type direct drive blower and was tested in the upflow configuration. The air flow was set for nominal 1400 CFM (normal for a 3 ½ ton air conditioner). The AHRI 210/240 Directory ratings for this system are: AHRI #5184649 14HPX-042-230-18 + CBX26UH-042*+TDR Classification: HRCU-A-CB Cooling Capacity (Btuh): 42500 EER Rating (Cooling): 12.00 SEER Rating (Cooling): 14.00 Heating Capacity (Btuh) @ 47 F: 45500 Region IV HSPF Rating (Heating): 8.20 Heating Capacity (Btuh) @ 17 F: 28200 2

This system tested 98% of A capacity, 103% of A EER and 105% of SEER. b. Description of Modifications to System A refrigerant flow meter was placed in the liquid line. Pressure taps were placed at the liquid service valve, on the compressor suction and discharge lines and on the liquid line at the inlet to the in expansion valve. Thermocouples were placed on the outside of refrigerant piping. Adjustable stems were placed on the expansion valves to enable some superheat adjustment. c. Description of Tests Conducted The heat pump was evaluated using a pair of psychrometric test chambers. The in portion of the heat pump was connected to an AMCA 210 Code Tester. There are dry bulb/wet bulb temperature samplers on the inlet and outlet air streams. This enables measurement of air side capacity. A coriolis-type flow meter is used to determine refrigerant mass flow rate. With temperature and pressure sensors to establish refrigerant thermodynamic states, the refrigerant capacity can also be measured. An energy balance is determined between the two capacity measurements. The psychrometric test facility is operated as a certified satellite facility and is under an annual calibration system traceable to NIST standards. All instruments were determined to be within accuracy specifications at the conclusion of testing. The tests that have been conducted are the set of tests required to establish SEER and HSPF ratings according to AHRI 210/240. The test data from the steady-state tests are included in this report. The non-steady-state tests were also conducted but only the cyclic degradation values are included in the report. The compressor used was one that was furnished to us with calorimeter data for the 50F/100F and 45F/130F test points. We found that the performance improved after a run-in period. All data presented is post run-in. The approach taken was to charge the R410A system to achieve the subcooling and superheat values that matched production verification testing of this model s performance on the AHRI 210/240 B test (82F out temperature). When we switched to R32, we charged the unit to achieve approximately the same subcooling on the B test. We found it necessary to adjust the setting of in expansion valve to get a similar superheat. We did not have to adjust the out thermostatic expansion valve when we operated in heating mode. We did not exhaust the possible variations in charge and TXV settings to optimize performance. Some further efficiency gains might be possible. 3

Figure 1. Diagram of Split-System Heat Pump Legend: 60 Separation line between out and in components 132 Compressor 136 Reversing Valve 138 Out Heat Exchanger 140 Vapor Line to Out Heat Exchanger 142 Location of Liquid Service Valve 144 Liquid Line 148 Out Refrigerant Check Valve 150 - Out Thermostatic Expansion Valve 154 In Thermostatic Expansion Valve 156 In Refrigerant Check Valve 158 In Heat Exchanger 160 In Blower 161 In Blower Motor 164 Vapor Line to In Heat Exchanger 166 Compressor Discharge Line 170 Coriolis-Effect Refrigerant Flow Meter 171- Conditioned Air Delivered to Air Flow Measuring Equipment 180 Out Fan 182 Out Fan Motor 186 Low Voltage Control Panel 4

3. Results This page provides information that relates to the heat pump system. Subsequent pages provide information gathered from the cooling and heating mode tests. Basic Information Alternative Refrigerant Alternative Lubricant Baseline Refrigerant and Lubricant Make and Model of System Nominal Capacity and Type of System R32 3MAF-POE R410A + 3MAF-POE Lennox 14HPX-042 + CBX26UH-042 3.5 Ton Split Heat Pump Other System Changes in TXV superheat adjustment System Data Base. Alt. Ratio Degradation Coefficient (Cooling) Cd 0.044 0.028 0.64 Seasonal Energy Efficiency Ratio - SEER 14.68 14.60 0.99 Degradation Coefficient (Heating) Cd 0.109 0.071 0.65 Heating Seasonal Performance Factor HSPF (region IV, min DHR) 9.07 9.52 1.05 5

Test Data Form for Test: "A" Test Type of System: Split HP Alternate Refrigerant: R32 Air Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Condenser Flow Rate (air side) 39.84 39.96 m ^ 3/min 1407 1411 CFM 1.00 Inlet Temperature 26.67/19.44 26.67/19.5 C 80.0/67.0 80.0/67.1 F Outlet Temperature 15.33/14.28 15.56/14.22 C 59.6/57.7 60.0/57.6 F Flow Rate (air side) 123.1 123.1 m ^ 3/min 4347 4347 CFM 1.00 Inlet Temperature 35 35 C 95 95 F Outlet Temperature Net Air-Side Cooling Capacity not measured not measured C kw not measured not measured 41770 42738 F BTUH Refrigerant Side Data Baseline Alternative Baseline Alternative Temperatures & P P T (C) T (C) P [kpa] T [F] P [psia] T [F] Pressures [kpa] [psia] Compressor Suction 19.5 1067 22.8 1082 67.1 154.8 73.0 156.9 Compressor Discharge 69.4 2548 88.3 2653 157 369.6 191.0 384.8 Condenser Inlet 69.4 2548 88.3 2653 157 369.6 191.0 384.8 Condenser Outlet 38.7 2484 40.9 2616 101.7 360.2 105.6 379.4 Expansion Device Inlet 38.2 2444 40.2 2599 100.8 354.4 104.4 377 Subcooling, at expan. device 2.4 1.4 4.3 2.5 Evaporator Inlet Evaporator Outlet 15.3 1083 16.5 1088 59.6 157 61.7 157.8 Evaporator Superheat 5.3 7.1 9.6 12.7 Net Refrigerant-Side Cooling Capacity 42001 BTUH 42479 BTUH 6

Test Data Form for Test: "A" Test Type of System: Split HP Alternate Refrigerant: R32 Comparison Data Base. Alt. SI Units Base. Alt. IP UNits Ratio Mode (Heating/Cooling) Cooling Compressor Type scroll scroll Compressor Displacement 0.122 0.122 M^3/min 4.32 4.32 Nominal Motor Size hp Ft ^3/min Motor Speed 3500 3500 rpm 1.00 Expansion Device Type TXV TXV Lubricant Charge 1.242 1.242 liters 42 42 fl. oz. 1.00 Refrigerant Charge 6.35 4.863 kg 14 10.72 lb 0.77 Refrigerant Mass Flow Rate* 273.4 185.1 kg/hr 602.8 408.1 lb/hr 0.68 Composition, at compr. Inlet if applicable Ambient Temps. In - Out - db 26.67 26.67 C 80.0 80.0 F wb 19.44 19.5 C 67.0 67.1 F db 35 35 C 95.0 95.0 F wb C F Total Capacity 12242 12526 W 41770 42738 Btu/hr 1.02 Sensible Capacity 9059 8893 W 30910 30344 Btu/hr 0.98 Total System Power Input 3376 3661 W 3376 3661 W 1.08 Compressor Power Input 2685 2963 W 2685 2963 W 1.10 Energy Efficiency Ratio (EER) 12.35 11.67 W/W 12.35 11.67 Btuh/W 0.94 Coeff. Of Performance* (COP) 3.62 3.42 0.94 1.00 Data Source(s) for Refrigerant Properties NIST REFPROP Version 9 Submitted By: Uselton / Crawford 7

Test Data Form for Test: "B" Test Type of System: Split HP Alternate Refrigerant R32 Air Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Condenser Flow Rate (air side) 39.87 39.76 m ^ 3/min 1408 1404 CFM 1.00 Inlet Temperature 26.67/19.44 26.67/19.5 C 80.0/67.0 80.0/67.1 F Outlet Temperature 14.94/13.83 14.88/13.72 C 58.9/56.9 58.8/56.7 F Flow Rate (air side) 123.1 123.1 m ^ 3/min 4347 4347 CFM 1.00 Inlet Temperature 27.78 27.78 C 82.0 82.0 F Outlet Temperature C F Net Air-Side Cooling Capacity kw 44807 46210 BTUH Refrigerant Side Data Baseline Alternative Baseline Alternative Temperatures & P T (C) P [kpa] T (C) P [kpa] T [F] P [psia] T [F] Pressures [psia] Compressor Suction 18.2 1044 21.0 1071 64.8 151.4 69.8 155.3 Compressor Discharge 59.4 2118 73.8 2213 139 307.2 164.8 321.0 Condenser Inlet 59.4 2118 73.8 2213 139 307.2 164.8 321.0 Condenser Outlet 30.7 2060 33.1 2175 87.2 298.8 91.6 315.5 Expansion Device Inlet 30.6 2022 32.9 2157 87.1 293.3 91.2 312.8 Subcooling, at expan. device 2.3 1.6 4.1 2.9 Evaporator Inlet Evaporator Outlet 15.2 1059 16.7 1078 59.4 153.6 62 156.3 Evaporator Superheat 6.0 7.6 10.8 13.6 Net Refrigerant-Side Cooling Capacity 44996 BTUH 45892 BTUH 8

Test Data Form for Test: "B" Test Type of System: Split HP Alternate Refrigerant R32 Comparison Data Base. Alt. SI Units Base. Alt. IP Units Ratio Mode (Heating/Cooling) Cooling Compressor Type scroll scroll Compressor Displacement 0.122 0.122 M^3/min 4.32 4.32 Ft ^3/min 1.00 Nominal Motor Size hp Motor Speed 3500 3500 rpm 1.00 Expansion Device Type TXV TXV Lubricant Charge 1.242 1.242 liters 42 42 fl. oz. 1.00 Refrigerant Charge 6.35 4.863 kg 14 10.72 lb 0.77 Refrigerant Mass Flow Rate* 174.4 121.4 kg/hr 595.0 414.2 lb/hr 0.70 Composition, at compr. Inlet if applicable Ambient Temps. In - Out - db 26.67 26.67 C 80.0 80.0 F wb 19.44 19.5 C 67.0 67.1 F db 35 35 C 82.0 82.0 F wb C F Total Capacity 13132 13543 W 44807 46210 Btu/hr 1.03 Sensible Capacity 9468 9345 W 32306 31884 Btu/hr.99 Total System Power Input 2983 3119 W 2983 3119 W 1.05 Compressor Power Input 2287 2425 W 2287 2425 W 1.06 Energy Efficiency Ratio (EER) 15.02 14.82 W/W 15.02 14.82 Btuh/W.99 Coeff. Of Performance (COP) 4.40 4.34.99 Data Source(s) for Refrigerant Properties NIST REFPROP Version 9 Submitted By: Uselton/Crawford 9

Test Data Form for Test: "H1" Test Type of System: Split HP Alternate Refrigerant R32 Air Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Condenser Flow Rate (air side) 123.1 123.1 m ^ 3/min 4347 4347 CFM 1 Inlet Temperature 8.33/6.11 8.33/6.11 C 47.0/43.0 47.0/43.0 F Outlet Temperature C F Flow Rate (air side) 39.67 39.02 m ^ 3/min 1399 1378 CFM 0.98 Inlet Temperature 21.11 21.11 C 70.0 70.0 F Outlet Temperature 37.56 37.67 C 99.6 99.8 F Net Air-Side Heating Capacity 44625 44285 BTUH Baseline Alternative Baseline Alternative Refrigerant Side Data Temperatures & Pressures P T (C) T (C) P [kpa] T [F] P [psia] T [F] P [psia] [kpa] Compressor Suction 8.3 838 9.6 865 47.7 121.3 49.2 125.5 Compressor Discharge 77.3 2830 87.4 2670 170.8 407.5 189.4 387.3 Condenser Inlet 73.9 2822 81.4 2661 164.7 406.2 178.5 386.0 Condenser Outlet 25.0 2779 28.0 2639 77.4 400.1 82.4 382.8 Expansion Device Inlet 23.4 2750 26.1 2619 74.7 395.7 79 379.8 Subcooling, at expan. device 20.9 14.6 36.8 26.3 Evaporator Inlet Evaporator Outlet Evaporator Superheat 6.8 7.6 13.1 13.7 Net Refrigerant-Side Heating Capacity 46214 BTUH 47260 BTUH 10

Test Data Form for Test: "H1" Test Type of System: Split HP Alternate Refrigerant R32 Comparison Data Base. Alt. SI Units Base. Alt. Mode (Heating/Cooling) Heating Compressor Type scroll scroll Compressor Displacement 0.122 0.122 M^3/min 4.32 4.32 Nominal Motor Size hp IP UNits Ft ^3/min Motor Speed 3500 3500 rpm 1.00 Expansion Device Type TXV TXV Lubricant Charge 1.242 1.242 liters 42 42 fl. oz. 1.00 Refrigerant Charge 6.35 4.863 kg 14 10.72 lb 0.77 Refrigerant Mass Flow Rate* 210.2 151.1 kg/hr 463.6 333.2 lb/hr 0.72 Composition, at compr. Inlet if applicable Ambien t Temps. In - Out - db 21.11 21.11 C 70.0 70.0 F wb C F db 8.33 8.33 C 47.0 47.0 F wb 6.11 6.11 C 43.0 43.0 F Ratio Total Capacity 13079 12979 W 44625 44285 Btu/hr 0.99 Sensible Capacity 13079 12979 W 44625 44285 Btu/hr 0.99 Total System Power Input 3704 3633 W 3704 3633 W 0.98 Compressor Power Input 2978 2918 W 2978 2918 W 0.98 Energy Efficiency Ratio (EER) W/W Btuh/W Coeff. Of Performance (COP) 3.53 3.57 1.01 1.00 Data Source(s) for Refrigerant Properties NIST REFPROP Version 9 Submitted By: Uselton/Crawford 11

Test Data Form for Test: "H3" (17F Steady State Heating) Type of System: Split HP Alternate Refrigerant: R32 Air Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Flow Rate (air side) 123.1 123.1 m ^ 3/min 4347 4347 CFM 1.00 Inlet Temperature -8.4-8.4 C 17.0 17.0 F Outlet Temperature C F Condenser Flow Rate (air side) 39.5 40.35 m ^ 3/min 1395 1425 CFM 1.02 Inlet Temperature 21.11 21.11 C 70.0 70.0 F Outlet Temperature 32.22 32.00 C 90.0 89.6 F Net Air-Side Heating kw Capacity 30032 30177 BTUH Baseline Alternative Baseline Alternative Refrigerant Side Data Temperatures & Pressures P P T (C) T (C) P [kpa] T [F] P [psia] T [F] [kpa] [psia] Compressor Suction -8.6 524-5.7 542 16.5 76.1 21.7 78.7 Compressor Discharge 77.9 2416 90.8 2263 172.3 350.4 195.5 328.2 Condenser Inlet 70.6 2410 77.3 2259 159.0 349.5 171.2 327.6 Condenser Outlet 22.2 2398 23.4 2250 72.0 347.9 74.2 326.4 Expansion Device Inlet 18.9 2384 19.9 2241 66.0 345.8 67.9 325.0 Subcooling, at expan. device 17.6 12.7 31.7 22.8 Evaporator Inlet Evaporator Outlet Evaporator Superheat 3.8 6.3 6.9 11.4 Net Refrigerant-Side Heating Capacity 30013 BTUH 30492 BTUH 12

Test Data Form for Test: "H3" (17F Steady State Heating) Type of System: Split HP Alternate Refrigerant: R32 Comparison Data Base. Alt. SI Units Base. Alt. Mode (Heating/Cooling) Heating Compressor Type scroll scroll Compressor Displacement 0.122 0.122 M^3/min 4.32 4.32 Nominal Motor Size hp IP UNits Ft ^3/min Motor Speed 3500 3500 rpm 1.00 Expansion Device Type TXV TXV Lubricant Charge 1.242 1.242 liters 42 42 fl. oz. 1.00 Refrigerant Charge 6.35 4.863 kg 14 10.72 lb 0.77 Refrigerant Mass Flow Rate* 130.0 92.7 kg/hr 286.7 204.5 lb/hr 0.71 Composition, at compr. Inlet if applicable Ambient Temps. In - Out - db 21.11 21.11 C 70.0 70.0 F wb C F db -8.33-8.33 C 17.0 17.0 F wb -9.39-9.33 C 15.1 15.2 F Ratio Total Capacity 8802 8844 W 30032 30177 Btu/hr 1.00 Sensible Capacity 8802 8844 W 30032 30177 Btu/hr 1.00 Total System Power Input 3427 3314 W 3427 3314 W 1.00 Compressor Power Input 2698 2565 W 2698 2565 W.95 Energy Efficiency Ratio (EER) W/W Btuh/W Coeff. Of Performance (COP) 2.57 2.67 1.04 1.00 Data Source(s) for Refrigerant Properties NIST REFPROP Version 9 Submitted By: Uselton/Crawford 13

4. Conclusions The alternate refrigerant worked in this R410A system without significant equipment modifications. (Long-term reliability has not been established.) During testing, it was necessary to take precautions for protection of personnel and our facility since R32 is mildly flammable, having an ASHRAE A2L refrigerant designation. For R32 testing, steady-state cooling efficiencies dropped and the heating efficiencies went up. The SEERs were more comparable (due to a low Cd measured with R32). The HSPF was higher. The cooling capacity went up slightly and the heating capacity stayed about the same. 14

15

16

Mass flow rates are lower when using R32. We found that the setting on the in expansion valve needed adjustment to achieve superheat and subcooling similar to the R410A values. The compressor discharge temperature on the A test (95F out temperature) was 26F higher when using R32 refrigerant. The charge quantity for R-32 was 77% of the charge quantity for R-410A. The GWP of R-32 is 675, 32% of the GWP of R-410A which is 2088. In a TEWI calculation the direct warming contribution with R-32 will be reduced to 0.77 x 0.32 or 25% of the contribution from R- 410A for the tested system. 17

ADDENDUM Note: Participating companies have the option to perform additional tests at high ambient operating conditions, appropriately selected according to the equipment type. This data was collected for cooling operation at 115F (46.1C) out ambient. Type of System: Split HP Alternate Refrigerant: R32 Air Side Data Base. Alt. SI Units Base. Alt. IP Units Ratio Evaporator Flow Rate (air side) 39.84 39.96 m ^ 3/min 1407 1411 CFM 1.00 Inlet Temperature 26.7/19.4 26.7/ 19.5 C 80.0/67.0 80.0/67.1 F Outlet Temperature 16.0 / 14.8 16.3 / 14.72 C 60.8/58.7 61.3/58.5 F Condenser Flow Rate (air side) 123.1 123.1 m ^ 3/min 4347 4347 CFM 1.00 Inlet Temperature 46.1 46.2 C 115.0 115.1 F Outlet Temperature Net Air-Side Cooling Capacity not measured not measured C kw not measured not measured 37217 37889 F BTUH Refrigerant Side Data Baseline Alternative Baseline Alternative Temperatures & P P T (C) T (C) P [kpa] T [F] P [psia] T [F] Pressures [kpa] [psia] Compressor Suction 50.4 1103 26 1110 122.8 160 78.8 161 Compressor Discharge 85.8 3269 109 3400 186.4 474 229 493 Condenser Inlet 79.4 3269 97 3400 175 474 207 493 Condenser Outlet 49.9 3200 52 3358 121.8 464 125 487 Expansion Device Inlet 49.1 3158 50.6 3347 120.3 458 123 485 Subcooling, at expan. device 2.3 2.2 4.1 3.9 Evaporator Inlet Evaporator Outlet 16.2 1117 17.2 1117 61.2 162 62.9 162 Evaporator Superheat 5.2 6.9 9.4 12.4 Net Refrigerant-Side Cooling Capacity BTUH BTUH 18

Test Data Form for Test: 115F Test Type of System: Split HP Alternate Refrigerant: R32 Comparison Data Base. Alt. SI Units Base. Alt. IP UNits Ratio Mode (Heating/Cooling) Cooling Compressor Type scroll scroll Compressor Displacement 0.122 0.122 M^3/min 4.32 4.32 Ft ^3/min 1.00 Nominal Motor Size hp Motor Speed 3500 3500 rpm 1.00 Expansion Device Type TXV TXV Lubricant Charge 1.242 1.242 liters 42 42 fl. oz. 1.00 Refrigerant Charge 6.35 4.863 kg 14 10.72 lb 0.77 Refrigerant Mass Flow Rate* 27.6 184 kg/hr 607.4 405.6 lb/hr Composition, at compr. Inlet if applicable Ambient Temps. In - Out - db 26.67 26.67 C 80.0 80.0 F wb 19.44 19.44 C 67.0 67.0 F db 46.1 46.2 C 115.0 115.1 F wb C F Total Capacity 10908 11104 W 37217 37889 Btu/hr 1.02 Sensible Capacity 8521 8219 W 29075 28043 Btu/hr 0.96 Total System Power Input 4115 4418 W 4115 4418 W 1.07 Compressor Power Input 3429 3740 W 3429 3740 W 1.09 Energy Efficiency Ratio (EER) W/W 9.01 8.54 Btuh/W 0.95 Coeff. Of Performance* (COP) 2.64 2.50 0.95 Data Source(s) for Refrigerant Properties NIST REFPROP Version 9 Submitted By: Uselton / Crawford 19