Modbus TCP/IP Version 4.0 and Modbus RTU Gateway Version 2.4

Similar documents
Modbus TCP Register List GreenManager for GreenMaster C-F Valid for firmware version 2.0 or later

Manual for the integration in BMS/GTC

Installation Instructions for the TBLZ-2-66 control box. for controlling two air handling units (Twin Function) GOLD RX

FUNCTION MANUAL, INSTALLATION GOLD RX/PX/CX/SD Generation F. Applicable to Program Version 1.27 and newer versions

Modbus RTU RS485 Manual

FUNCTIONAL PROFILE: Gateway Lonworks FTT-10, TBLZ , Version 1.00 COMPACT Sizes 02-03, Program Version 1.00

Description of the functions, IQlogic

Modbus Point Map. for the. Data Aire DAP-II

Operation and Maintenance Instructions GOLD LP

DAP III Zone Master User s Guide

1/8. Field settings table [6.8.2] =... ID66F3. Applicable indoor units *HYHBH05AAV3 *HYHBH08AAV3 *HYHBX08AAV3. Notes - 4P E

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

1/8. Field settings table. Applicable indoor units. *GSQH10S18AA9W ThermaliaC12* Notes - *GSQH10S18AA9W / ThermaliaC12* 4P C

Field settings table [6.8.2] =... ID66F2. Applicable units *BLQ05CAV3 *DLQ05CAV3 *BLQ07CAV3 *DLQ07CAV3. Notes (*1) *B* (*2) *D* 1/8

1/8. Field settings table. Applicable indoor units *HYHBH05AAV3 *HYHBH08AAV3 *HYHBX08AAV3. Notes - 4P C

Systemair UAB Linų st. 101, LT Ukmergė, LITHUANIA Phone: Fax:

Reference Guide for Microprocessor Controller

ECL Comfort 210 / 296 / 310

Model 8682-KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control

Operating your heating system with the Prefect PRE5701 Programable Thermostat

REMOTE CONTROL FOR CHILLER MYCHILLER

Q-SMART MODBUS KIT. Modbus Protocol & Parameters. Cod EN rev.a ed.08/2018. Q-SMART Software Version AE17

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

User manual. CTS 602 by Nilan VPL 15 VPL 15 TOP. Version: 9.02, Software-version: 2.21

SEQUENCE OF OPERATIONS

Product Manual SZ1009

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

Digital Precise Air Control - DPAC

Reference Guide for Microprocessor Controller

Installation Guide. ECL Comfort 210, application A Table of Contents

Operation and Maintenance Instructions GOLD RX/PX/CX/SD, Generation D

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502*

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.

SAUTER flexotron800 V2 Ventilation V3.3. manual P P

- Brochure D 542. Introduction. Features. tekmarnet 4 Thermostat /05. 5 Data Brochure Control settings wiring instructions

INSTALLATION MANUAL. * If using remote sensors the thermostat must be hardwired. Need Help?

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Operation and Maintenance Instructions

SAUTER flexotron 800 Ventilation application User Guide

INSTALLATION AND OPERATION MANUAL

ggg Air Handling Unit RT 700/1000S-EC-RS INSTALLATION OPERATION & CONTROL PANEL MAINTENANCE & SERVICE

Corrigo E - User Manual Ventilation

Metasys Integrator TITUS Application

USER MANUAL. OPTIMA 312 ES960C circuit board

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING 2 INSTALLATION

Topvex SX/C, Topvex TX/C Air Handling Unit

For Raychem ACS-30 Controls Systems

VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual

SERVICE & SETUP MANUAL WATER HEATER ELECTRONIC CONTROLLER

C-series Controllers for air handling systems

User s Manual

INSTALLATION AND OPERATION MANUAL

Installation Instructions / User s Manual TSTAT0406 and TSTAT0408

Rotex Underfloor Heating User Guide

XC1008D -XC1011D- XC1015D and VGC810

VERSO DOMEKT. Residential ventilation units m³/h. Non residential ventilation units m³/h

Sauter flexotron 800 ventilation Manual

Swegon Home Solutions CASA. R2 Smart. Installation, commissioning and maintenance instruction. R2_a_EN-t

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Climatix Basic reference addresses for eq Fläkt application v1.x

- Data Brochure tekmarnet 4 Thermostat 542e

1.0 Digital Controller

CEM-24 Series. Owner's Manual - Installation and Operating Instructions

Air handling unit. REC Temovex 400S-EC-RS. Experts on indoor climate in low-energy houses

eco TOP INSTALLATION AND MAINTENANCE MANUAL

Operation manual. Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3

Reference Guide for Microprocessor Controller

Lennox Climatic 50 and BMS Modbus, Trend or BACnet.

Product Manual SZ1022/SZ1031/SZ1035/

Plug-n-Play Humidity Controller. IHC-200 User Manual. Version 1.3s. Inkbird Tech. Co., Ltd.

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

WATER HEATER ELECTRONIC CONTROLLER USER MANUAL

Parts Diagram. Up button. Down button. Right (fan) button. Left (system) button. RC/RH Jumper. Field programming pins

1.0 Digital Controller

ATC32U03 igate Communicating, Programmable Thermostat

1F97-51 OPERATION GUIDE WHITE-RODGERS. Operator: Save this booklet for future use! 7-Day Programmable Electronic Digital Thermostat

OPERATING MANUAL. Need Help? This manual covers: T955WH Wireless Thermostat System. Table of Contents

1F91W-71 OPERATION GUIDE WHITE-RODGERS. Operator: Save this booklet for future use! Multi-stage Electronic Digital Thermostat

TSI Model 8630 PRESSURA Room Pressure Monitor Modbus Communications Application Note LC-106

Technical manual MARK WTW AIRSTREAM _R01

EMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

4 Wiring Brochure Wiring and

BLAUAIR AUTOMATIC CONTROL SYSTEM

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR COMPACT AIR & COMPACT HEAT

E8 Controller and BCM for Modulex EXT GF-136-C USER MANUAL. Installation, Operation & Maintenance

Topvex SR 09, 11, Topvex TR Compact Air Handling Units

Power and Energy Management Solutions

Operating instructions

User manual. User manual. CTS 600 by Nilan. Comfort Comfort Version: 10.00, Software-version: 2.30

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

DC 60 & DM 60 displays

AdaptAire. Digital Control System. User Manual. Expert Systems

TELLUS. Complete HVAC substation for air handling, cooling, heating and hot tap water. Main advantages. General

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

User Manual Ichill 200 L/D (Firmware version 1.7)

SC Installation, Operation & Application Guide

Transcription:

Modbus TCP/IP Version 4.0 and Modbus RTU Gateway Version 2.4 Overview ModBus can access single addresses or multiple addresses simultaneously; either reading or writing single bit values or 16-bit values. A ModBus address contains either a 1-bit discrete value or a 16-bit integer value. Modbus Data formats Modbus data types are 1-bit values and 16-bit values. Modbus Type Description Reference Coil Status Discrete Output 0x Input Status Discrete Input 1x Holding Register 16 bit Output Register 4x Input Register 16 bit Input Register 3x Supported ModBus commands. The Gateway module supports these ModBus commands. Function Code Description. 01 Read Coil Status 02 Read Input Status 03 Read Holding Registers 04 Read Input Registers 05 Force Single Coil 06 Preset Single Register 08 Diagnostics. Sub-function 00 Only - Return Query Data (loop back). 15 Force multiple coils 16 Preset Multiple Registers www.swegon.se 1

Coil Status. 1 bit (R/W). Modbus Name Min/Max vera Min/Max verb 0x0001 Highspeed operation. 0-1 0-1 Controls the AHU from S-CL stop or lowspeed to highspeed operation. 0x0002 Lowspeed operation. 0-1 0-1 Controls the AHU from S-CL stop to lowspeed operation. 0x0003 Stop. 0-1 0-1 Controls the AHU to stop. 0x0004 Switch-clock func. 0-1 0-1 0=Lowspeed-Highspeed. VerA 1=Stop-Lowspeed. VerB 1=Stop-Lowspeed-Highspeed. 0x0005 Outdoor temp compensation. 0-1 0-1 Used to enable the function. 0x0006 Summer night cooling. 0-1 0-1 Used to enable the function. 0x0007 Alarm reset. 0-1 0-1 Reset for active alarms. 0x0008 Reserve 1. 0 0 0x0009 Reserve 2. 0 0 0x0010 Reserve 3. 0 0 0x0011 Reserve 4. 0 0 0x0012 Reserve 5. 0 0 0x0013 Reserve 6. 0 0 0x0014 Reserve 7. 0 0 0x0015 Reserve 8. 0 0 0x0016 Reserve 9. 0 0 2 www.swegon.se

Input status 1 bit (RO). Modbus Name Min/Max vera Min/Max verb 1x0001 Cool energy recovery. 0-1 0-1 Indicates if the function is active. 1x0002 Summer night cooling. 0-1 0-1 Indicates if the function is active. 1x0003 Group alarm-a. 0-1 0-1 Indicates if the alarm relay output-a is active. 1x0004 Group alarm-b. 0-1 0-1 Indicates if the alarm relay output-b is active. 1x0005 Highspeed operation. 0-1 0-1 Indicates all operating cases. 1x0006 Lowspeed operation. 0-1 0-1 Indicates all operating cases. 1x0007 Stop. 0-1 0-1 Indicates all operating cases. 1x0008 Heating indication relay. Not used 0-1 Indicates if the heating function is active. 1x0009 Cooling relay, stage 1. 0-1 0-1 Indicates if the cooling function stage 1 is active. 1x0010 Cooling relay, stage 2. Not used 0-1 Indicates if the cooling function stage 2 is active. 1x0011 Cooling compressor 1. Not used 0-1 Indicates if the compressor 1, in Cooler is active. 1x0012 Cooling compressor 2. Not used 0-1 Indicates if the compressor 2, in Cooler is active. 1x0013 Reserve 1. 0 0 1x0014 Reserve 2. 0 0 1x0015 Digital In 1 (Only Ethernet). 0-1 0-1 Indicates if input 1, on Ethernet module is active. 1x0016 Digital In 2 (Only Ethernet). 0-1 0-1 Indicates if input 2, on Ethernet module is active. www.swegon.se 3

1x0017 Alarm no. 1. 0-1 0-1 1x0018 Alarm no. 2. 0-1 0-1 1x0019 Alarm no. 3. 0-1 0-1 1x0020 Alarm no. 4. 0-1 0-1 1x0021 Alarm no. 5. 0-1 0-1 1x0022 Alarm no. 6. 0-1 0-1 1x0023 Alarm no. 7. 0-1 0-1 1x0024 Alarm no. 8. 0-1 0-1 1x0025 Alarm no. 9. 0-1 0-1 1x0026 Alarm no. 10. 0-1 0-1 1x0027 Alarm no. 11. 0-1 0-1 1x0028 Alarm no. 12. 0-1 0-1 1x0029 Alarm no. 13. 0-1 0-1 1x0030 Alarm no. 14. 0-1 0-1 1x0031 Alarm no. 15. 0-1 0-1 1x0032 Alarm no. 16. 0-1 0-1 1x0033 Alarm no. 17. 0-1 0-1 1x0034 Alarm no. 18. 0-1 0-1 1x0035 Alarm no. 19. 0-1 0-1 1x0036 Alarm no. 20. 0-1 0-1 4 www.swegon.se

1x0037 Alarm no. 21. 0-1 0-1 1x0038 Alarm no. 22. 0-1 0-1 1x0039 Alarm no. 23. 0-1 0-1 1x0040 Alarm no. 24. 0-1 0-1 1x0041 Alarm no. 25. 0-1 0-1 1x0042 Alarm no. 26. 0-1 0-1 1x0043 Alarm no. 27. 0-1 0-1 1x0044 Alarm no. 28. 0-1 0-1 1x0045 Alarm no. 29. 0-1 0-1 1x0046 Alarm no. 30. 0-1 0-1 1x0047 Alarm no. 31. 0-1 0-1 1x0048 Alarm no. 32. 0-1 0-1 1x0049 Alarm no. 33. 0-1 0-1 1x0050 Alarm no. 34. 0-1 0-1 1x0051 Alarm no. 35. 0-1 0-1 1x0052 Alarm no. 36. 0-1 0-1 1x0053 Alarm no. 37. 0-1 0-1 1x0054 Alarm no. 38. 0-1 0-1 1x0055 Alarm no. 39. 0-1 0-1 1x0056 Alarm no. 40. 0-1 0-1 1x0057 Alarm no. 41. 0-1 0-1 www.swegon.se 5

1x0058 Alarm no. 42. 0-1 0-1 1x0059 Alarm no. 43. 0-1 0-1 1x0060 Alarm no. 44. 0-1 0-1 1x0061 Alarm no. 45. 0-1 0-1 1x0062 Alarm no. 46. 0-1 0-1 1x0063 Alarm no. 47. 0-1 0-1 1x0064 Alarm no. 48. 0-1 0-1 1x0065 Alarm no. 49. Not used 0-1 1x0066 Alarm no. 50. Not used 0-1 1x0067 Alarm no. 51. Not used 0-1 1x0068 Alarm no. 52. Not used 0-1 1x0069 Alarm no. 53. Not used 0-1 1x0070 Alarm no. 54. Not used 0-1 1x0071 Alarm no. 55. Not used 0-1 1x0072 Alarm no. 56. Not used 0-1 1x0073 Alarm no. 57. Not used 0-1 1x0074 Alarm no. 58. Not used 0-1 1x0075 Alarm no. 59. Not used 0-1 1x0076 Alarm no. 60. Not used 0-1 1x0077 Alarm no. 61. Not used 0-1 6 www.swegon.se

Input Registers. 16-bit integer value (RO). Modbus Name Min/Max vera Min/Max verb 3x0001 Operation mode. 1-200 0-255 VerA indicates the AHU handterminal menu. VerB operationstatus for the AHU. 00=Stop alarm, 01=Manual stop, 02=Ext.stop, 03=RS232 stop, 04=S-CL stop, 10=Manual LS, 11=S-CL LS, 12=Ext.LS, 13=RS232 LS, 14=Prolonged LS, 20=Manual HS, 21=Ext.HS, 22=RS232 HS, 23=S-CL HS, 24=Prolonged HS, 30=SN-Cool, 31=Reecooling, 40=Manual test OP, 41=Duct airflow adj, 42=Filtercalibration. 3x0002 Delayed ext. HS_min. 0-59 0-59 Remaining time for prolonged highspeed. 3x0003 Delayed ext. HS_hour. 0-23 0-23 Remaining time for prolonged highspeed. 3x0004 Delayed ext. LS_min. Not used 0-59 Remaining time for prolonged lowspeed. 3x0005 Delayed ext. LS_hour. Not used 0-23 Remaining time for prolonged lowspeed. 3x0006 SF flow. 0-4000l/s 0-8000l/s Current supply air fan flow. 3x0007 EF flow. 0-4000l/s 0-8000l/s Current exhaust air fan flow. 3x0008 SF VAV level. 0-100.0% 0-100.0% Current level of the supply air input signal for the VAV/Forcing function. 3x0009 EF VAV level. 0-100.0% 0-100.0% Current level of the exhaust air input signal for the VAV/Forcing function. 3x0010 SF level. 0-100.0% 0-100.0% Current running level for the supply air fan. 3x0011 EF level. 0-100.0% 0-100.0% Current running level for the exhaust air fan. 3x0012 Heat exch. Level. 0-100.0% 0-100.0% Current level for the heat exchanger. www.swegon.se 7

3x0013 SA temp. 0-40.00 C -55.00-125.00 C Current supply air temperature. 3x0014 OUT-D temp. -20.00-40.00 C -55.00-125.00 C Current outdoor air temperature. 3x0015 EA temp. 0-40.00 C -55.00-125.00 C Current exhaust air temperature. 3x0016 SA temp regulation. 0-40.00 C -55.00-125.00 C Current supply air regulator temperature setpoint. 3x0017 FP temp. 0-40.00 C -55.00-125.00 C Current frost protection temperature. 3x0018 Reheat level. 0-100.0% 0-100.0% Current level for the reheater coil. 3x0019 Cooling level. 0-100.0% 0-100.0% Current level for cooling. 3x0020 SA filter level. 0-100.0% 0-2000Pa Current level for the supply air filter. 3x0021 EA filter level. 0-100.0% 0-2000Pa Current level for the exhaust air filter. 3x0022 SF filter alarm level. Not used 0-2000Pa Current alarm level for the supply air filter. 3x0023 EF filter alarm level. Not used 0-2000Pa Current alarm level for the exhaust air filter. 3x0024 Alarm No. 0-48 0-49 Active alarm No. 3x0025 Air handling unit. 0-1 0,2 0=No communication. 1=Version 4 or A. 2=Version B. 8 www.swegon.se

3x0026 Copy of Input Status 1-16. 0-65535 0-65535 Bit 0 = 1x0001 Bit 1 = 1x0002 Bit 15 = 1x0016 3x0027 Copy of Input Status 17-32. 0-65535 0-65535 Bit 0 = 1x0017 Bit 1 = 1x0018 Bit 15 = 1x0032 3x0028 Copy of Input Status 33-48. 0-65535 0-65535 Bit 0 = 1x0033 Bit 1 = 1x0034 Bit 15 = 1x0048 3x0029 Copy of Input Status 49-64. 0-65535 0-65535 Bit 0 = 1x0049 Bit 1 = 1x0050 Bit 15 = 1x0064 3x0030 Copy of Input Status 65-77. 0-65535 0-65535 Bit 0 = 1x0065 Bit 1 = 1x0066 Bit 12 = 1x0077 3x0031 SF flow regulation. 0-4000l/s 0-8000l/s Current supply fan regulator flow setpoint. 3x0032 EF flow regulation. 0-4000l/s 0-8000l/s Current exhaust fan regulator flow setpoint. 3x0033 EA temp regulation. 0-40.00 C 0-40.00 C Current exhaust air regulator temperature setpoint. 3x0034 SF VAV regulation. Not used 0-100.0% Current level for the supply fan VAV regulator. 3x0035 EF VAV regulation. Not used 0-100.0% Current level for the exhaust fan VAV regulator. 3x0036 Operating time. 0-9999 0-9999 Shows how many 24-hour days the unit operated. 3x0037 Program version. Not used 0-65535 Program version in GOLD AHU. 3x0038 Coolforcing level. 0-100.0% 0-100.0% Current level for coolforcing. www.swegon.se 9

Holding Registers. 16-bit integer value (R/W). Modbus Name Min/Max vera Min/Max verb 4x0001 Second. 0-59 0-59 The AHU internal time. 4x0002 Minute. 0-59 0-59 The AHU internal time. 4x0003 Hour. 0-23 0-23 The AHU internal time. 4x0004 Date. 0-31 0-31 The AHU internal time. 4x0005 Weekday. 1-7 1-7 The AHU internal time. 4x0006 Month. 1-12 1-12 The AHU internal time. 4x0007 Year. 2000-2099 2000-2099 The AHU internal time. 4x0008 Switch clock Channel1 start-minut. 0-59 0-59 4x0009 Switch clock Channel1 start-hour. 0-23 0-23 4x0010 Switch clock Channel1 stop-minut. 0-59 0-59 4x0011 Switch clock Channel1 stop-hour. 0-23 0-23 4x0012 Switch clock Channel1 period. 0-9 0-10,128-138 VerA 0=Not active. 1=Monday. 2=Tuesday. 3=Wednesday. 4=Thursday. 5=Friday. 6=Saturday. 7=Sunday. 8=Monday..Friday. 9=Monday..Sunday. VerB 0=HS 128=LS Not active. 1=HS 129=LS Monday. 2=HS 130=LS Tuesday. 3=HS 131=LS Wednesday. 4=HS 132=LS Thursday. 5=HS 133=LS Friday. 6=HS 134=LS Saturday. 7=HS 135=LS Sunday. 8=HS 136=LS Monday..Friday. 9=HS 137=LS Monday..Sunday. 10=HS 138=LS Saturday..Sunday. 10 www.swegon.se

4x0013 Switch clock Channel2 start-minut. 0-59 0-59 4x0014 Switch clock Channel2 start-hour. 0-23 0-23 4x0015 Switch clock Channel2 stop-minut. 0-59 0-59 4x0016 Switch clock Channel2 stop-hour. 0-23 0-23 4x0017 Switch clock Channel2 period. 0-9 0-10,128-138 4x0018 Switch clock Channel3 start-minut. 0-59 0-59 4x0019 Switch clock Channel3 start-hour. 0-23 0-23 4x0020 Switch clock Channel3 stop-minut. 0-59 0-59 4x0021 Switch clock Channel3 stop-hour. 0-23 0-23 4x0022 Switch clock Channel3 period. 0-9 0-10,128-138 4x0023 Switch clock Channel4 start-minut. 0-59 0-59 4x0024 Switch clock Channel4 start-hour. 0-23 0-23 4x0025 Switch clock Channel4 stop-minut. 0-59 0-59 4x0026 Switch clock Channel4 stop-hour. 0-23 0-23 4x0027 Switch clock Channel4 period. 0-9 0-10,128-138 4x0028 Switch clock Channel5 start-minut. 0-59 0-59 4x0029 Switch clock Channel5 start-hour. 0-23 0-23 4x0030 Switch clock Channel5 stop-minut. 0-59 0-59 4x0031 Switch clock Channel5 stop-hour. 0-23 0-23 4x0032 Switch clock Channel5 period. 0-9 0-10,128-138 4x0033 Switch clock Channel6 start-minut. 0-59 0-59 4x0034 Switch clock Channel6 start-hour. 0-23 0-23 4x0035 Switch clock Channel6 stop-minut. 0-59 0-59 4x0036 Switch clock Channel6 stop-hour. 0-23 0-23 4x0037 Switch clock Channel6 period. 0-9 0-10,128-138 4x0038 Switch clock Channel7 start-minut. 0-59 0-59 4x0039 Switch clock Channel7 start-hour. 0-23 0-23 4x0040 Switch clock Channel7 stop-minut. 0-59 0-59 4x0041 Switch clock Channel7 stop-hour. 0-23 0-23 4x0042 Switch clock Channel7 period. 0-9 0-10,128-138 4x0043 Switch clock Channel8 start-minut. 0-59 0-59 4x0044 Switch clock Channel8 start-hour. 0-23 0-23 4x0045 Switch clock Channel8 stop-minut. 0-59 0-59 4x0046 Switch clock Channel8 stop-hour. 0-23 0-23 4x0047 Switch clock Channel8 period. 0-9 0-10,128-138 4x0048 Delayed ext. HS_hour Set. 0-3 0-23 Setting for prolonged highspeed. 4x0049 Delayed ext. HS_min Set. 0-59 0-59 Setting for prolonged highspeed. 4x0050 Delayed ext. LS_hour Set. Not used 0-23 Setting for prolonged lowspeed. www.swegon.se 11

4x0051 Delayed ext. LS_min Set. Not used 0-59 Setting for prolonged lowspeed. 4x0052 SF lowspeed. 0-4000 l/s 0-8000 l/s Air flow setpoint of the supply air fan running at lowspeed. 4x0053 EF lowspeed. 0-4000 l/s 0-8000 l/s Air flow setpoint of the exhaust air fan running at lowspeed. 4x0054 SF highspeed. 0-4000 l/s 0-8000 l/s Air flow setpoint of the supply air fan running at highspeed. 4x0055 EF highspeed. 0-4000 l/s 0-8000 l/s Air flow setpoint of the exhaust air fan running at highspeed. 4x0056 SF maxspeed. 0-4000 l/s 0-8000 l/s Air flow max. limit of the supply air fan. 4x0057 EF maxspeed. 0-4000 l/s 0-8000 l/s Air flow max. limit of the supply air fan. 4x0058 SF VAV higspeed set. 0-100.0% 0-100.0% Duct pressure setpoint of the supply air fan running at highspeed. 4x0059 EF VAV highspeed set. 0-100.0% 0-100.0% Duct pressure setpoint of the exhaust air fan running at highspeed. 4x0060 SF VAV lowspeed set. Not used 0-100.0% Duct pressure setpoint of the supply air fan running at lowspeed. 4x0061 EF VAV lowspeed set. Not used 0-100.0% Duct pressure setpoint of the exhaust air fan running at lowspeed. 4x0062 Flow regulation. 1-3 0-3 VerA setting of flow/fan regulation type. 1=Flow, 2=VAV, 3=Boost/forcing. VerB setting of flow/fan regulation type. 0=Flow, 1=VAV-pressure, 2=VAV-demand 3=Boost/forcing. 4x0063 Reg.speed VAV SA. Not used 0-9 Setting for VAV regulation speed. 4x0064 Reg.speed VAV EA. Not used 0-9 Setting for VAV regulation speed. 12 www.swegon.se

4x0065 SF downreg. NZ. Not used 0-9.90 C Neutralzone before dowregulation of the supply air fan gains. 4x0066 Temperature regulation. 1-3 1-3 Setting of temperature regulation type. 1=ERS, 2= SA, 3=EA. 4x0067 SA temp set. 10.00-30.00 C 10-40.00 C Supply air temperature setpoint. 4x0068 EA temp set. 10.00-30.00 C 10.00-40.00 C Exhaust air temperature setpoint. 4x0069 Min SA temp. 0-18.00 C 10.00-18.00 C Min. supply air temperature setpoint in conjunction with EA-regulation. 4x0070 Max SA temp. 19.00-60.00 C 20.00-50.00 C Max. supply air temperature setpoint in conjunction with EA-regulation. 4x0071 ERS DIFF. 0-7.00 C 1.00-10.00 C Differential temperature at ERS-reg. 4x0072 ERS Brakepoint. 12.00-30.00 C 10.00-30.00 C Brakepoint temperature at ERS-reg. 4x0073 ERS-step. 1-4 1-4 Setting for step at ERS temperature regulation. 4x0074 Reg.speed temp SA. Not used 0-9 Setting for temperature regulation speed. 4x0075 Reg.speed temp EA. Not used 0-9 Setting for temperature regulation speed. 4x0076 Filtertest time hour. 0-23 Not used 4x0077 Filtertest time min. 0-59 Not used 4x0078 Alarmlimit SF filter. 0-99.0% 0-99.0% Alarmlimit setpoint of the supply air filter. 4x0079 Alarmlimit EF filter. 0-99.0% 0-99.0% Alarmlimit setpoint of the exhaust air filter. 4x0080 SN-COOL EA temp Start. 17.00-27.00 C 20.00-30.00 C Temperature limit for the summernight cooling function. 4x0081 SN-COOL EA temp Stop. 12.00-22.00 C 10.00-18.00 C Temperature limit for the summernight cooling function. 4x0082 SN-COOL OUT temp Start. 5.00-15.00 C 10.00-15.00 C Temperature limit for the summernight cooling function. www.swegon.se 13

4x0083 ServicePeriod. 0-99 0-99 AHU setting for Service period month. 4x0084 Copy of Coil Status. 0-65535 0-65535 Bit 0 = 0x0001 Bit 1 = 0x0002 Bit 15 = 0x0016 4x0085 Outdoor temp comp. X1. Not used -30.00-(-10.00) C Indicate where the winter comp. curve ends. 4x0086 Outdoor temp comp. X2. Not used -10.00-15.00 C Indicate where the winter comp. curve begins. 4x0087 Outdoor temp comp. X3. Not used 15.00-25.00 C Indicate where the summer comp. curve begins. 4x0088 Outdoor temp comp. X4. Not used 25.00-40.00 C Indicate where the summer comp. curve ends. 4x0089 Outdoor temp comp. Y1. 0-10.00 C 0-10.00 C Indicate the maximum level of winter comp. 4x0090 Outdoor temp comp. Y2. -10.00-10.00 C -10.00-10.00 C Indicate the maximum level of summer comp. 4x0091 Outdoor flow comp. X1. Not used -30.00-(-10.00) C Indicate where the winter comp. curve ends. 4x0092 Outdoor flow comp. X2. Not used -10.00-20.00 C Indicate where the winter comp. curve begins. 4x0093 Outdoor flow comp. Y1. Not used 0-50.0% Indicate the maximum level of winter comp. 4x0094 Coolforcing. 0-2 0-2 Setting of coolforcing. 0=Not active. 1=Comfort. 2=Economy. 4x0095 Neutral zone. 0.50-5.00 C 0.50-10.00 C Setting of neutral zone size. Min/max for Par. 67,68,69,70,71,72 are limitet from the AHU handterminal. 14 www.swegon.se