Corp L9 Revised HS27 SERIES UNITS SPECIFICATIONS. Model No. HS HS HS HS27-042

Similar documents
HS25 SERVICE UNIT INFORMATION

HSXA15 HSXB15. IMPORTANT Operating pressures of this R410A unit are higher than pressures in R22 units. Always use service equipment rated for R410A.

13ACX. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R 410A.

XC13. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R410A.

HP13 WARNING WARNING. Service Literature HP13 SERIES UNITS

TSA WARNING. Service Literature TSA SERIES UNITS. 6, 7.5, 10, 12.5, 15 & 20 ton

13ACX. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R 410A.

UNIT INFORMATION Corp L10 Replaces Corp L4 10HP SERIES UNITS

HSXA16 WARNING. WARNING R 410A refrigerant can be harmful if it is inhaled. R 410A refrigerant must be used and recovered responsibly.

XC16. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R410A.

HPXA15 HPXB15 WARNING

SPB*H4 Commercial Heat Pump

INSTALLATION INSTRUCTIONS

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION

MERIT Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,500 to 59,000 Btuh AIR CONDITIONERS 13ACXN PRODUCT SPECIFICATIONS

INSTALLATION INSTRUCTIONS

LENNDX INSTALLATION INSTRUCTIONS. IIlIIIIIIIIIIIIIIIIIIIIIIIHI A, WARNING A, WARNING WARNING RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE

3 to 5 Tons. AIR CONDITIONERS 2scu13. Dry Charge Split System - 60 HZ PRODUCT SPECIFICATIONS. 2 scu 13 lc 1 36 t - 1 a MODEL NUMBER IDENTIFICATION

2 shp 13 lc 1 36 t - 1 a

DRY CHARGE UNITS. 1.5 to 5 Tons. HEAT PUMP OUTDOOR UNITS lps13dc PRODUCT SPECIFICATIONS L P S 13 DC MODEL NUMBER IDENTIFICATION

ELITE Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,800 to 60,000 Btuh AIR CONDITIONERS EL16XC1 PRODUCT SPECIFICATIONS

INSTALLATION INSTRUCTIONS

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

IMPORTANT CB26UH CBX26UH. Service Literature. CB26UH and CBX26UH Series Table of Contents. Model Number Information... 2

INSTALLATION INSTRUCTIONS HS40 SERIES UNITS

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

T-SERIES SPLIT SYSTEM UNITS R-410A - 60 HZ. EER up to to 20 Tons Cooling Capacity - 71,000 to 236,000 Btuh AIR CONDITIONERS TS

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SCU16LT Series Split System Air Conditioner WARNING

UNIT INFORMATION. Corp L7. Gauge Manifold Attachment... Page 30 Parts Arrangement... Page 8

HPXA19. IMPORTANT Operating pressures of this R410A unit are higher than pressures in R22 units. Always use service equipment rated for R410A.

INSTALLATION INSTRUCTIONS

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!

Commercial High-Efficiency Condensing Units

Corp L2 Revised

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SHP13LE Series Split System Heat Pump

INSTALLATION INSTRUCTIONS

INSTALLATION AND MAINTENANCE INSTRUCTIONS 2SCU13 Series Split System Air Conditioner WARNING

072, 090, 120, 180 & 240 MODELS C SERIES CONDENSING UNITS P SERIES HEAT PUMPS

Specially Designed. SilentComfort Fan Guard. Visit us at For the latest technical information,

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

14 AC x

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

PACKAGE AIR CONDITIONER

T P A 048 S 4 N 4 1 T

INSTALLATION INSTRUCTIONS

4TTB3060D1000B 208/230/1/60 35 SCROLL /230/1/ /8

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4SHP16LT Series Split System Heat Pump

Commercial High-Efficiency Condensing Units

XC16. ELITE SERIES R 410A Two Stage Compressor SilentComfort Technology A I R C O N D I T I O N E R S

14HPX MERIT SERIES R 410A H E A T P U M P O U T D O O R U N I T S

4TTB3030D1000B 208/230/1/60 4TTB3036D1000B 208/230/1/ RECIP /230/1/ RECIP YES YES

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

INSTALLATION AND OPERATING INSTRUCTIONS

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTR6024-SF-1B. Split System Cooling 4TTR6024A1000B CAUTION CAUTION WARNING

MERIT Series R-410A. SEER up to HSPF up to to 5 Tons Cooling Capacity - 18,000 to 61,000 Btuh Heating Capacity - 17,500 to 58,500 Btuh

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

Service Literature GCS/CHA16 15 and 20 Ton (52.8 and 70.3 kw)

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

4A6H5042G1000A 208/230/1/ DURATION - SCROLL 3/4 208/230/1/ NO (Use BAYKSKT263) YES YES PROPELLER DIRECT

T P A 120 S 4 S N 1 Y

T S A 048 S 4 N 4 1 T

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTB6-SF-3. Split System Cooling 4TTB6048A1000A, 4TTB6049A1000A CAUTION

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

7/8 NO NO NO PROPELLER DIRECT / /230/1/ SPINE FIN /8 8 LBS., 0 OZ. YES 7/8 3/8

208/230/1/ CLIMATUFF /230/1/ YES NO NO PROPELLER 23-1 DIRECT / /230/1/ SPINE FIN

MERIT Series R-410A. SEER up to to 5 Tons Cooling Capacity - 18,000 to 60,000 Btuh AIR CONDITIONERS ML14XC1 PRODUCT SPECIFICATIONS

INSTALLATION AND MAINTENANCE INSTRUCTIONS 2SHP13 Series Split System Heat Pump WARNING

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTR6048-SF-1A. Split System Cooling 4TTR6048A1000A CAUTION CAUTION WARNING

Service Literature GCS/CHA16 6, 7.5, 10 and 12.5 Ton (21, 26.4, 35.2 and 44.0 kw)

INSTALLATION INSTRUCTIONS

Service Facts. Split System Cooling 3.0 Ton 4A7A6036J-SF-1B-EN. January A7A6036J1000A

XC17. DAVE LENNOX SIGNATURE COLLECTION R-410A - SilentComfort Technology. SEER up to to 5 Tons Cooling Capacity - 21,800 to 59,000 Btuh

4TTR6036B1000A 208/230/1/ CLIMATUFF - SCROLL 3/4 3/4 3/4 3/4 3/4 208/230/1/ NO YES NO PROPELLER DIRECT

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

INSTALLATION INSTRUCTIONS

4SHP13 & 14 Series Split System Heat Pump

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

DAVE LENNOX SIGNATURE COLLECTION WITH SILENTCOMFORT TECHNOLOGY

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

S2HA, T2HA, T3HA, and

208/230/1/60 5/8 5/8 5/8 5/8 5/8 20 CLIMATUFF /230/1/

LRP14HP/LRP14DF/LRP14AC/LRP14GE/LRP16GE/LRP16HP SERIES UNITS

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

Nominal Circuit Capacities: 9,000 12,000 18,000 & 24,000 Btuh units.

13HPD MERIT SERIES R 22 H E A T P U M P O U T D O O R U N I T S

XC17 NOTICE WARNING. Service Literature XC17 (HFC 410A) SERIES UNITS. Accessories

Installation Instructions

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TGA WARNING CAUTION ROOFTOP UNITS. Service Literature. Table of Contents

R.A.S.E.R.S System. Installation Guide

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models)

4A6H5049E1000B 208/230/1/ /8 7/8 7/8 7/8 DURATION 208/230/1/ /230/1/ SPINE FIN 13 LBS., 10 OZ. YES

INSTALLATION INSTRUCTIONS

Air Conditioning Operation and Troubleshooting Matt Dunham

Transcription:

Service Literature Corp. 9619 L9 Revised 08 2004 HS27 SERIES UNITS HS27 The HS27 is a 14 SEER high efficiency residential split system condensing unit which features a scroll compressor. It operates much like a standard condensing unit, but the HS27 s scroll compressor is unique in the way that it compresses refrigerant. Several models are available in sizes ranging from 2 through 3.5 tons. The series is designed for use with an expansion valve in the indoor unit. This manual is divided into sections which discuss the major components, refrigerant system, charging procedure, maintenance and operation sequence. All specifications in this manual are subject to change. ELECTROSTATIC DISCHARGE (ESD) Precautions and Procedures CAUTION Electrostatic discharge can affect electronic components. Take precautions during unit installation and service to protect the unit s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface before performing any service procedure. WARNING Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly. Failure to follow this warning may result in personal injury or death. SPECIFICATIONS Model No. HS27-024 HS27-030 HS27-036 HS27-042 Net face area Outer coil 16.04 (1.49) 16.04 (1.49) 21.77 (2.02) 21.77 (2.02) sq. ft. (m 2 ) Inner coil 13.33 (1.24) 13.33 (1.24) 21.11 (1.96) 21.11 (1.96) Condenser Coil Tube diameter in. (mm) 5/16 (8) 5/16 (8) 5/16 (8) 5/16 (8) No. of rows 2 2 2 2 Fins per inch (m) 22 (866) 22 (866) 22 (866) 22 (866) Dia. in. (mm) no. of blades 24 (610) 3 24 (610) 3 24 (610) 3 24 (610) 3 Motor hp (W) 1/10 (75) 1/10 (75) 1/6 (124) 1/6 (124) Condenser Fan Cfm (L/s) 2500 (1180) 2500 (1180) 3000 (1415) 3000 (1415) Rpm 825 825 825 825 Watts 165 165 210 210 *Refrigerant HCFC-22 charge furnished 6 lbs. 10 oz. (3.0 kg) 6 lbs. 6 oz. (2.9 kg) 9 lbs. 15 oz. (4.5 kg) 9 lbs. 15 oz. (4.5 kg) Liquid line (o.d.) in. (mm) sweat 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) Suction line (o.d.) in. (mm) sweat 3/4 (19) 3/4 (19) 7/8 (22.2) 7/8 (22.2) Shipping weight lbs. (kg) 1 package 221 (100) 221 (100) 267 (121) 267 (121) *Refrigerant charge sufficient for 15 ft. (4.5 m) length of refrigerant lines. Page 1 1996 Lennox Industries Inc. Litho U.S.A.

ELECTRICAL DATA Model No. HS27-024 HS27-030 HS27-036 HS27-042 Line voltage data 60hz 208/230v 1ph 208/230v 1ph 208/230v 1ph 208/230v 1ph Rated load amps 10.3 12.2 13.5 16.5 Compressor Power factor.96.96.96.97 Locked rotor amps 56 61 73 95 Condenser Coil Fan Motor Full load amps 0.9 0.9 1.0 1.0 Locked rotor amps 1.6 1.6 2.5 2.5 Rec. max. fuse or circuit breaker size (amps) 20 25 30 35 *Minimum circuit ampacity 13.8 16.2 17.9 21.6 *Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. NOTE Extremes of operating range are plus 10% and minus 5% of line voltage. Page 2

DISCHARGE SCROLL COMPRESSOR NOTE During operation, the head of a scroll compressor may be hot since it is in constant contact with discharge gas. CROSS SECTION OF SCROLLS DISCHARGE PRESSURE STATIONARY SCROLL DISCHARGE FIGURE 1 I APPLICATION All major components (indoor blower/coil) must be matched according to Lennox recommendations for the compressor to be covered under warranty. Refer to the Engineering Handbook for approved system matchups. A misapplied system will cause erratic operation and can result in early compressor failure. II SCROLL COMPRESSOR The scroll compressor design is simple, efficient and requires few moving parts. A cutaway diagram of the scroll compressor is shown in figure 1. The scrolls are located in the top of the compressor can and the motor is located just below. The oil level is immediately below the motor. The scroll is a simple compression concept centered around the unique spiral shape of the scroll and its inherent properties. Figure 2 shows the basic scroll form. Two identical scrolls are mated together forming concentric spiral shapes (figure 3). One scroll remains stationary, while the other is allowed to orbit" (figure 4). Note that the orbiting scroll does not rotate or turn but merely orbits" the stationary scroll. SCROLL FORM FIGURE 2 TIPS SEALED BY ORBITING SCROLL DISCHARGE PRESSURE FIGURE 3 The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls (figure 4 1). The centrifugal action of the orbiting scroll seals off the flanks of the scrolls (figure 4 2). As the orbiting motion continues, the gas is forced toward the center of the scroll and the gas pocket becomes compressed (figure 4 3). When the compressed gas reaches the center, it is discharged vertically into a chamber and discharge port in the top of the compressor (figure 1). The discharge pressure forcing down on the top scroll helps seal off the upper and lower edges (tips) of the scrolls (figure 3). During a single orbit, several pockets of gas are compressed simultaneously providing smooth continuous compression. The scroll compressor is tolerant to the effects of liquid return. If liquid enters the scrolls, the orbiting scroll is allowed to separate from the stationary scroll. Continued slugging of liquid will cause damage to the scroll and replacement will be necessary.the liquid is worked toward the center of the scroll and is discharged. If the compressor is replaced, conventional Lennox clean up practices must be used. Due to its efficiency, the scroll compressor is capable of drawing a much deeper vacuum than reciprocating compressors. Deep vacuum operation can cause internal fusite arcing resulting in damaged internal parts and will result in compressor failure. Never use a scroll compressor for evacuating or pumping down" the system. This type of damage can be detected and will result in denial of warranty claims. Compressors on HS27 units feature a mechanical anti rotational device (AREST) which prevents backward rotation due to thermostat cycling or power interruption. The compressor is also equipped with a discharge thermostat limit and pressure relief valve, which opens at approximately 450 above suction pressure. All features are internal and are not field replaceable. Page 3

HOW A SCROLL WORKS MOVEMENT OF ORBIT INTERMEDIATE PRESSURE GAS POCKET STATIONARY SCROLL ORBITING SCROLL 1 2 FLANKS SEALED BY CENTRIFUGAL FORCE CRESCENT SHAPED GAS POCKET 3 4 HIGH PRESSURE GAS FIGURE 4 III UNIT COMPONENTS A Transformer The contactor coil and timed off control are all energized by 24VAC supplied by the indoor unit. All other controls in the outdoor unit are powered by line voltage. Refer to unit wiring diagram. The HS27 is not equipped with an internal line voltage to 24V trans former. B Contactor DANGER Electric Shock Hazard. May cause injury or death. Disconnect all remote electrical power supplies berore opening unit panel. Unit may have multiple power supplies. Some units are equipped with single pole contactors. When unit is equipped with a single pole contactor, line voltage is present at all components (even when unit is not in operation). DISCHARGE POCKET The compressor is energized by a contactor located in the control box. All HS27 1 units use DPST contactors. All HS27 2 and later units use single pole contactors. The contactor is energized by indoor thermostat terminal Y when thermostat demand is present. C TOC Timed Off Control Some HS27 units (see wiring digrams) are equipped with a TOC, timed off control. The TOC is located in the control box (figure 5). The time delay is electrically connected between thermostat terminal Y and the compressor contactor. Between cycles, the compressor contactor is delayed for 5 minutes + 2 minutes. At the end of the delay, the compressor is allowed to energize. When thermostat demand is satisfied, the time delay opens the circuit to the compressor contactor coil and the compressor is de energized. Without the time delay it would be possible to short cycle the compressor. A scroll compressor, when short cycled, can run backward if head pressure is still high. It does not harm a scroll compressor to run backward, but it could cause a nuisance tripout of safety limits.for this reason, if a TOC fails it must be replaced. NOTE: Do not attempt to repair the timed off control. Unsafe operation will result. If the TOC is found to be inoperative, simply replace it. Page 4

CONDENSER FAN (NOT SHOWN) TOP OF CABINET PARTS ARRANGEMENT FOR HS27 TIMED OFF CONTROL (Not all Units. See wiring diagrams) GROUND LUG DUAL CAPACITOR CONTACTOR TERMINAL BOX VALVE AND GAUGE PORT THERMOMETER WELL LIQUID LINE SERVICE VALVE AND GAUGE PORT COMPRESSOR LOW PRESSURE SWITCH HIGH PRESSURE SWITCH FIGURE 5 D Compressor Table 1 shows the specifications of compressors used in HS27 series units. TABLE 1 Unit Vac Phase LRA RLA Oil fl.oz. HS27 024 208/230 1 56 10.3 38 HS27 030 208/230 1 61 12.2 42 HS27 036 208/230 1 73 13.5 42 HS27 042 208/230 1 95 16.5 42 *Shipped with conventional white oil (Sontex 200LT). 3GS oil may be used if additional oil is required. E High Pressure Switch A manual-reset single-pole single-throw high pressure switch located in the liquid line of the compressor shuts off the compressor when liquid line pressure rises above the factory setting. The switch is normally closed and is permanently adjusted to trip (open) at 410 + 10 psi. See figure 5 for switch location. F Low Pressure Switch An auto-reset single-pole single-throw low pressure switch located in the suction line of the compressor shuts off the compressor when suction pressure drops below the factory setting. The switch is normally closed and is permanently adjusted to trip (open) at 25 + 5 psi. The switch automatically resets when suction line pressure rises above 55 + 5 psi. See figure 5 for switch location. COMPRESSOR TERMINAL BOX COMPRESSOR TERMINALS C R WARNING COMPRESSOR MUST BE GROUNDED. DO NOT OPERATE WITHOUT PROTECTIVE COV- ER OVER TERMINALS. DISCONNECT ALL POWER BEFORE REMOVING PROTECTIVE COVER. DISCHARGE CAPACITORS BEFORE SERVICING UNIT. COMPRESSOR WIRING DIA- GRAM IS FURNISHED INSIDE COMPRESSOR TERMINAL BOX COVER. FAILURE TO FOL- LOW THESE PRECAUTIONS COULD CAUSE ELECTRICAL SHOCK RESULTING IN INJURY OR DEATH. FIGURE 6 S Page 5

G Dual Capacitor The compressor and fan in HS27 single phase series units use permanent split capacitor motors. A single dual" capacitor is used for both the fan motor and the compressor (see unit wiring diagram). The fan side of the capacitor and the compressor side of the capacitor have different mfd ratings. The capacitor is located inside the unit control box (see figure 5). Table 2 shows the ratings of the dual capacitor. TABLE 2 HS27 DUAL CAPACITOR RATING UNITS FAN MFD HERM MFD VAC HS27 024 4 40 370 HS27 030 4 40 370 HS27 036 5 45 370 HS27 042 5 50 370 H Condenser Fan Motor All units use single phase PSC fan motors which require a run capacitor. The FAN" side of the dual capacitor is used for this purpose. The specifications table on page 1 of this manual shows the specifications of outdoor fans used in HS27s. In all units, the outdoor fan is controlled by the compressor contactor. See figure 7 if condenser fan motor replacement is necessary. Condenser fan and motor "A" SEE TABLE 3 FIGURE 7 TABLE 3 FAN GUARD Wiring Drip loop UNIT "A" DIM. TOLERANCE HS27 024, 030 1 1/16" + 1/8" HS27 036, 042 1 3/16" + 1/8" IV REFRIGERANT SYSTEM A Plumbing TABLE 4 REFRIGERANT LINE KITS HS27 UNIT 024 030 036 042 LIQUID LINE 3/8 in (10 mm) 3/8 in (10 mm) LINE 3/4 in. (19 mm) 7/8 in. (22 mm) L10 LINE SETS L10 41 20 ft. 50 ft. (6 m 15 m) L10 65 30 ft. 50 ft. (9 m 15 m) L15 LINE SETS L15 41 15 ft. 50 ft. (4.5 m 15 m) L15 65 15 ft. 50 ft. (4.5 m 15 m) Field refrigerant piping consists of liquid and suction lines from the outdoor unit (sweat connections). Use Lennox L10 or L15 series line sets as shown in table 4 or field fabricated refrigerant lines. Refer to the piping section of the Lennox Service Unit Information Manual (SUI 803 L9) for proper size, type and application of field fabricated lines. Separate discharge and suction service ports are provided at the compressor for connection of gauge manifold during charging procedure. B Service Valves The liquid line and suction line service valves and gauge ports are accessible by removing the compressor access cover. Full service liquid and suction line valves are used. See figures 8 and 9. The service ports are used for leak testing, evacuating, charging and checking charge. Service valves have a factory installed schrader valve. A service port cap is supplied to protect the schrader valve from contamination and assure a leak free seal. Valves are not rebuttable. If a valve has failed it must be replaced. To Access Schrader Port: 1 Remove service port cap with an adjustable wrench. 2 Connect gauge to the service port. 3 When testing is completed, replace service port cap. Tighten finger tight, then an additional 1/6 turn. To Open Liquid or Suction Line Service Valve: 1 Remove stem cap with an adjustable wrench. 2 Using service wrench and 5/16" hex head extension back the stem out counterclockwise until the valve stem just touches the retaining ring. 3 Replace stem cap and tighten finger tight, then tighten an additional 1/6 turn. DANGER Do not attempt to backseat this valve. Attempts to backseat this valve will cause snap ring to explode from valve body under pressure of refrigerant. Personal injury and unit damage will result. To Close Liquid or Suction Line Service Valve: 1 Remove stem cap with an adjustable wrench. 2 Using service wrench and 5/16" hex head extension, turn stem clockwise to seat the valve. Tighten firmly. 3 Replace stem cap. Tighten finger tight, then tighten an additional 1/6 turn. NOTE: Stem cap is the primary seal and must be replaced. Always keep stem cap clean. Page 6

LIQUID LINE SERVICE VALVE (VALVE OPEN) INSERT HEX WRENCH HERE STEM CAP LINE (BALL TYPE) SERVICE VALVE (VALVE OPEN) USE ADJUSTABLE WRENCH ROTATE STEM CLOCKWISE 90 TO CLOSE ROTATE STEM COUNTER-CLOCKWISE 90 TO OPEN SER- VICE PORT OUTLET (TO COMPRESSOR) OUTLET (TO COMPRESSOR) STEM CAP STEM SERVICE PORT CAP SCHRADE R VALVE SERVICE PORT SERVICE PORT CAP SCHRADER VALVE OPEN TO LINE SET WHEN VALVE IS CLOSED (FRONT SEATED) FIGURE 8 INLET (TO INDOOR COIL) LIQUID LINE SERVICE VALVE (VALVE CLOSED) RETAINING RING STEM CAP OUTLET (TO COMPRESSOR) INSERT HEX WRENCH HERE INLET (TO INDOOR COIL) (VALVE FRONT SEATED) SERVICE PORT CAP SCHRADE R VALVE SERVICE PORT BALL (SHOWN OPEN) INLET (FROM INDOOR COIL) FIGURE 9 V CHARGING The unit is factory charged with the amount of R-22 refrigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with a 15 foot (4.5m) line set. For varying lengths of line set, refer to table 5 for refrigerant charge adjustment. A blank space is provided on the unit rating plate to list actual field charge. IMPORTANT If line length is greater than 15 feet (4.5m), add the amount of refrigerant listed in table 4. If line length is less than 15 feet (4.5m), subtract this amount. Liquid Line Set Diameter TABLE 5 Ozs. per 5 ft. (g per 1.5m) adjust from 15 ft. (4.5m) line set* 3/8 in. (9.5mm) 3 ounces per 5 ft. (88.05g per 1.5m) *If line length is greater than 15 ft. (4.56 m), add this amount. If line length is less than 15 ft. (4.5 m), subtract this amount. Units are designed for line sets up to 50ft.(15.24m) Consult Lennox Refrigerant Piping Manual for line sets over 50 ft.(15.24m). Page 7

A Leak Testing 1 Attach gauge manifold and connect a drum of dry nitrogen to center port of gauge manifold. 2 Add a small amount of refrigerant to the lines and coil. Open high pressure valve on gauge manifold and pressurize line set and indoor coil to 150 (1034 kpa). WARNING Danger of Explosion. Can cause injury, death and equipment damage. When using dry nitrogen, use a pressure reducing regulator, set at 150 (1034 kpa) or less to prevent excessive pressure. 3 Check lines and connections for leaks. NOTE-If electronic leak detector is used, add a trace of refrigerant to nitrogen for detection by leak detector. 4 Release nitrogen pressure from the system, correct any leaks and recheck. B Evacuating the System Evacuating the system of non condensables is critical for proper operation of the unit. Non condensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non condensables such as water vapor, combine with refrigerant to produce substances that corrode copper piping and compressor parts. 1 Attach gauge manifold and connect vacuum pump (with vacuum gauge) to center port of gauge manifold. With both gauge manifold service valves open, start pump and evacuate evaporator and refrigerant lines. IMPORTANT A temperature vacuum gauge, mercury vacuum (U tube), or thermocouple gauge should be used. The usual Bourdon tube gauges are not accurate enough in the vacuum range. IMPORTANT The compressor should never be used to evacuate a refrigeration or air conditioning system. 2 3 4 5 6 7 CAUTION Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty. Evacuate the system to an absolute pressure of.92 inches (23 mm) of mercury, or 23,000 microns. After system has been evacuated to an absolute pressure of.92 inches (23 mm) of mercury, or 23,000 microns, close manifold valve to center port. Stop vacuum pump and disconnect from gauge manifold. Attach a drum of dry nitrogen to center port of gauge manifold, open drum valve slightly to purge line, then break vacuum in system to 3 (20.7 kpa) pressure by opening manifold high pressure valve to center port. Close nitrogen drum valve, disconnect drum from manifold center port and release nitrogen pressure from system. Reconnect vacuum pump to manifold center port hose. Evacuate the system to an absolute pressure less than.197 inches (5 mm) of mercury, or 500 microns, then turn off vacuum pump. If the absolute pressure rises above.197 inches (5 mm) of mercury, or 5000 microns within a 20 minute period after stopping vacuum pump, repeat step 6. If not, evacuation is complete. This evacuation procedure is adequate for a new installation with clean and dry lines. If excessive moisture is present, the evacuation process may be required more than once. After evacuation has been completed, close gauge manifold service valves. Disconnect vacuum pump from manifold center port and connect refrigerant drum. Pressurize system slightly with refrigerant to break vacuum. Page 8

C Charging If the system is completely void of refrigerant, the recommended and most accurate method of charging is to weigh the refrigerant into the unit according to the total amount shown on the unit nameplate. Also refer to the SPECIFI- CATIONS table on page 1. If weighing facilities are not available or if unit is just low on charge, the following procedure applies. The following procedures are intended as a general guide for use with expansion valve systems only. For best results, indoor temperature should be between 70 F and 80 F (21 C and 26 C). Outdoor temperature should be 60 F (15.5 C) or above. Slight variations in charging temperature and pressure should be expected. Large variations may indicate a need for further servicing. IMPORTANT Use table 8 as a general guide for performing maintenance checks. Table 8 is not a procedure for charging the system. Minor variations in these pressures may be expected due to differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system. Used prudently, table 8 could serve as a useful service guide. APPROACH METHOD (TXV SYSTEMS) (Ambient Temperature of 60 F [16 C] or Above) 1 Connect gauge manifold. Connect an upright HCFC-22 drum to center port of gauge manifold. IMPORTANT The following procedure requires accurate readings of ambient (outdoor) temperature, liquid temperature and liquid pressure for proper charging. Use a thermometer with accuracy of +2 F and a pressure gauge with accuracy of +5 PSIG. 2 Record outdoor air (ambient) temperature. 3 Operate indoor and outdoor units in cooling mode. Allow units to run until system pressures stabilize. 4 Make sure thermometer well is filled with mineral oil before checking liquid line temperature. 5 Place thermometer in well and read liquid line temperature. Liquid line temperature should be a few degrees warmer than the outdoor air temperature. Table 6 shows how many degrees warmer the liquid line temperature should be. Add refrigerant to make the liquid line cooler. Recover refrigerant to make the liquid line warmer. TABLE 6 APPROACH METHOD FOR TXV SYSTEMS APPROACH TEMPERATURE LIQUID LINE F ( C) OUTDOOR AMBIENT F ( C) HS27 024 HS27 030 HS27 036 HS27 042 5 + 1 (3 +.5) 5 + 1 (3 +.5) 6 + 1 (3.3 +.5) 7 + 1 (3.9 +.5) Note For best results, the same thermometer should be used to check both outdoor ambient and liquid temperatures. 6 When unit is properly charged, liquid line pressures should approximate those in table 8. The Subcooling Method (TXV SYSTEMS) (Ambient Temperature of 60 F [16 C] or Less ) Because the outdoor ambient temperature is below 60 F, airflow over the outdoor coil will need to be reduced to drive up the liquid line pressure to a range of 200 250. To do this block off the outdoor coil with cardboard or a plastic sheet. (Figure 10) BLOCKING OUTDOOR COIL OUTDOOR COIL SHOULD BE BLOCKED ONE SIDE AT A TIME WITH CARD BOARD OR PLASTIC SHEET UNTIL PROPER TESTING PRESSURES ARE REACHED. CARDBOARD OR PLASTIC SHEET FIGURE 10 1 Remove the cap from the liquid line service valve stem and turn the stem clockwise 1/4 to 1/2 turn. This will open the service port. 2 With the manifold gauge hose still on the liquid service port and the unit operating, read the liquid line pressure. 3 If the pressure is too low, block the airflow through the outdoor coil until the liquid line pressure stabilizes in a range of 200 to 250. At that time, record the liquid line temperature and the liquid line pressure reading. 4 Using a temperature/pressure chart for R22, determine the saturation temperature for the liquid line pressure reading. 5 Subtract the liquid line temperature from the saturation temperature (according to the chart) to determine Subcooling. (Liquid line temperature Saturation temperature = Subcooling) 6 Compare the Subcooling value with those in table 7. If Subcooling is greater than shown, refrigerant must be reclaimed. If Subcooling is less than shown, refrigerant must be added. Page 9

TABLE 7 SUBCOOLING METHOD LESS THAN 60 F MODEL SUBCOOLING TEMP. F + 2 (1.1 C) HS27 024 7 (3.8) HS27 030 8 (4.4) HS27 036 7 (3.8) HS27 042 8 (4.4) D Oil Charge Refer to Table 1 on Page 5. VI MAINTENANCE WARNING Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies. At the beginning of each heating or cooling season, the system should be cleaned as follows: A Outdoor Unit 1 Clean and inspect condenser coil. (Coil may be flushed with a water hose). 2 Visually inspect all connecting lines, joints and coils for evidence of oil leaks. IMPORTANT If insufficient heating or cooling occurs, the unit should be gauged and refrigerant charge checked. B Indoor Coil 1 Clean coil if necessary. 2 Check connecting lines and coil for oil leaks. 3 Check condensate line and clean if necessary. C Indoor Unit 1 Clean or change filters. 2 Adjust blower cooling speed. Check static pressure drop over coil to determine correct blower CFM. Refer to Lennox Engineering Handbook. 3 Belt Drive Blowers - Check condition/tension. 4 Check all wiring for loose connections. 5 Check for correct voltage at unit. 6 Check amp draw on blower motor. Unit nameplate Actual. OUT- DOOR TEMP. ( F) Liq. + 10 TABLE 8 NORMAL OPERATING PRESSURES HS27 024 HS27 030 HS27 036 HS27 042 Suct. + 5 Liq. + 10 Suct. + 5 Liq. + 10 Suct. + 5 Liq. + 10 Suct. + 5 65 143 76 139 72 138 70 141 74 75 168 77 163 73 164 71 166 75 85 196 78 191 74 192 72 186 76 95 226 79 223 76 223 73 227 78 105 260 80 255 77 256 75 261 79 Page 10

VII Unit Diagram Operation Sequence 1 Cooling demand energizes thermostat terminal Y. Voltage from terminal Y passes through low pressure switch and the timed off control (TOC), which energizes K1 compressor contactor coil (provided 5 minute delay is satisfied). 2 K1 1 and K1 2 contacts close, energizing compressor B1 and outdoor fan B4. 3 When cooling demand is satisfied, K1 1 and K1 2 open, compressor and outdoor fan are de energized. Time off control begins 5 minute off time. Page 11

Operation Sequence 1 Cooling demand energizes thermostat terminal Y. Voltage from terminal Y passes through low pressure switch and energizes K1 compressor contactor coil. 2 K1 1 and K1 2 contacts close, energizing compressor B1 and outdoor fan B4. 3 When cooling demand is satisfied, K1 1 and K1 2 open, compressor and outdoor fan are de energized. Page 12