Owner s Manual Refrigerated Compressed Air Dryer Model F-50

Similar documents
Owner s Manual Refrigerated Compressed Air Dryers Model F-100

Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350

Owner s Manual Refrigerated Compressed Air Dryers Models F-3528, F-3529, F-3530, F-3531 & F-3532

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

PROdry. High Inlet. Temperature. refrigerated. compressed air. dryers. Contents. For Sales & Service please contact:

Rev. A AUGUST 2012 RNP SERIES REFRIGERATED COMPRESSED AIR DRYERS OPERATOR MANUAL RNP25 RNP35 RNP50

Owners Manual Refrigerated Air Dryer MHT SERIES

OWNER/OPERATOR MANUAL COMPONENTS, INSTALLATION, OPERATION AND SERVICE INSTRUCTIONS

DRYMAX DRYMAX DRYMAX DRYMAX

NEWGATE TECHNOLOGIES, INC.

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Polar Air Dryer. Instructions Manual PDRCF PDRCF R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S

Owners Manual UA75 TO UA1200 SERIES Refrigerated Air Dryer

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual

GRF-SERIES REFRIGERATION TYPE NON CYCLING STANDARD

RNP SERIES 33 F 39 F 1 C 4 C OFF OPERATOR MANUAL

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

InstructIon Manual KrEs EQuIPMEnt stands

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

DHW Series INSTRUCTION MANUAL. Pressure Swing Desiccant Compressed Air Dryer Models 7 through 50 scfm

WILKERSON MODELS DE3, DE4 AND DE5 COMPACT HEATLESS AIR DRYERS

DRY-PAK INDUSTRIAL AIR DRYER Installation and Instruction Manual

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts

Rev. None AUGUST 2012 MDM SERIES MODULAR MEMBRANE AIR DRYERS OPERATOR MANUAL MDM1 MDM4 MDM9 MDM13 MDM24 MDM49 MDM66 MDM106 MDM138

MANUAL 8/12/05. Model BKP TM 100 INSTALLATION, OPERATION & MAINTENANCE. Commercial High Efficiency Heat Pipe Dehumidifier

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

REFRIGERATED DROP-INS (2-6)FT-DI Installation and Operating Manual

EBAC MODEL CD60 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100

EBAC MODEL NEPTUNE INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

MODEL MW200 MODEL MW600 AIR DRYER

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap. Operation & Maintenance Manual MDX MODELS 18 THRU 250

CHILLER. Model CH3000. Operator s & Installation Manual

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain. Operation & Maintenance Manual MODELS MDX

Air Cleaning Equipment, Inc. 303 N. Main St. Broadway, NC iers.com

EBAC MODEL BD-150 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

CH250 AND CH251 CHILLERS

SANI-VAC MODEL #750 WARNING! FOR YOUR SAFETY PLEASE READ INSTRUCTIONS BEFORE OPERATING TOOL. & WEAR EYE PROTECTION

Operating Instructions Manual. Condensate Separators. Models 4GNL3 thru 4GNL9 and 53RG84 thru 53RG95

Horizontal Bottle Cooler Installation and Operation Manual

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Refrigerated Air Dryers

3800 North Mill Road Vineland, NJ USA Tel: Fax: Web: Rev. A

VSA Series Air Dryer. User s Guide

OPERATING MANUAL MODEL AIR 1500TM AIR DRYER

CD30 / CD30E INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

INGERSOLLrAND AIR COMPRESSORS CAUTION: HMD SERIES AIR DRYERS MODELS 18 THROUGH 385 OPERATORS/ INSTRUCTION MANUAL REPLACEMENT PARTS

FAN-FORCED UTILITY HEATER

DR Series. Installation & Operations Manual. Model: DR-10 HIGH OUTPUT SHOCK TREATMENT OZONE GENERATOR

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

Power Pack Service Manual

Milk Coolers Installation and Operation Manual Please read this manual completely before attempting to install or operate this equipment!

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Power Pack Service Manual

WCPT-3 and WCPT-4. Effective Date: 2017 IMPORTANT INFORMATION READ BEFORE USE. Drop-in Display Cases

A910.8A Remote Water Chiller, 8 GPH A A / A A-220V TECHNICAL ASSISTANCE TOLL FREE TELEPHONE NUMBER:

CD30 / CD30E INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

KPHE24 SERIES WATER-TO-AIR HEAT EXCHANGER

Condensing Unit Installation and Operating Instructions

Blue Air. Commercial Refrigeration Inc. Installation & Operation Manual Ice Cream Freezers

CHILLER. Operator s & Installation Manual

Refrigerator Freezer Installation and Operation Manual

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

POWER PACK SERVICE MANUAL

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

Noncycling Refrigerated Air Dryers Range AD 10 to AD 4000

Power Pack Service Manual

Getz Equipment Innovators 450 lb Dual Portable Dry Chemical Fill System

ProAir CR43 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

Model 8780 INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS. Tempering Skid General Area Classification & Class I Division 2. No.

BLOCK ICE MAKERS BY DELTA ICE, AIR AND HEAT INC.

OWNER S MANUAL. Installation Operation Maintenance. Saturn Equipment

Superdryer Dehumidifiers

PDF Created with deskpdf PDF Writer - Trial ::

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model ABM - 700

OPERATING INSTRUCTIONS

WineZone Ceiling Mount Ductless Split 15

MIGHTY PRO 1/4 HP CHILLER

ProAir CR23 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

OWNER S MANUAL FINLEY FIREPLACE. Product code: UPC code: Date of purchase: / /

MDH Series Air Dryer. User s Guide

POWER PACK SERVICE MANUAL

T-Series Air Conditioner T15 Model

KPHE32 SERIES WATER-TO-AIR HEAT EXCHANGER

CAMAIR THE LEADER IN DRY AIR TECHNOLOGY

Portable Heated Black Glass Shelves

GL-DEH Series Portable Dehumidifier Operating Instructions

Model No. GB-PAC-08E4. 8,000 BTU Portable Air Conditioner Operating Instructions

Installation & Operation Manual Ice Cream Freezers

KNHE30 SERIES WATER-TO-AIR HEAT EXCHANGER

PORTABLE AIR CONDITIONER OWNER S MANUAL

PORTABLE AIR CONDITIONER OWNER S MANUAL

Refrigerator Freezer Installation and Operation Manual

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL

ProAir CR29 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

INSTALLATION AND OPERATING MANUAL

Transcription:

Owner s Manual Refrigerated Compressed Air Dryer Model F-50 Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage. Retain instructions for future reference. WARNING: Air treated by this equipment is not suitable for breathing without further purifi cation. Refer to O.S.H.A. standards for the requirements for breathing quality air. Figure 1 - F-50 ARROW DRYERS 745 CLARK AVE. BRISTOL, CT 06010 TOLL FREE: (877) 640-8300 Form F-0033A Revised 03/06

4 3 5 9 2 6 7 8 1 1) Separator 2) Compressor 3) Expansion/Control Valve 4) Refrigerant Filter 5) Fan Motor 6) Power On Light/Switch 7) Dew Point Indicator 8) Power Cord 9) Drain Line 1

Receiving and inspection Arrow Dryers are carefully prepared for shipment at the factory to protect them from damage in transit. Dryers are shipped F.O.B. factory. Immediately upon arrival, check the dryer for possible damage. If damage is found, report it to the carrier and file a damage claim. Check the suction pressure gauge. If the suction pressure gauge reads zero, it indicates a possible refrigerant leak. Notify your dealer immediately. Be sure you have the right dryer. Check the nameplate for voltage and amperage How the Air Dryer Works Compressed air enters the inlet and passes through the air-to-air heat exchanger where the air is partially cooled by the exiting cold air. Next, the air passes through a refrigerant-to-air heat exchanger where it is cooled to near the freezing point of water. As the air is cooled, it loses the capacity to hold water vapor. The water vapor condenses into water droplets and drains to the separator. Passing through the separator, air flow slows down and causes more water to condense and collect in the bottom of the separator bowl. The water is exhausted by the electronic timer drain. The compressed air, now at a pressure dew point of 35ºF, leaves the dryer through the air-to-air heat exchanger where it is heated by the incoming air. Typical Compressed Air Systems Location and Installation Locate the dryer indoors in a protected area where ambient temperature will range between 45ºF and 100ºF. Dryers are usually located near the compressor. Do not cycle the dryer with the compressor. If an aftercooler is used after the compressor, install the dryer downstream of the aftercooler and receiver (see figure 2). Install the dryer so that there is sufficient room around it to permit circulation of air through the refrigeration condensing unit. Allow for easy access into the dryer through the cover panel. Check the nameplate for voltage and amperage. The dryer is furnished with a 6 foot electrical cord for connection to a grounded outlet. The dryer can be mounted on a wall with the key hole slots provided or on a floor stand. Be sure that the compressor air passes through the dryer in the proper direction. Connect the compressed air lines to the inlet and outlet connection as marked on the cabinet. Connect the air lines with standard pipe fittings. The mechanical separator has a isolation valve and strainer to prevent debris from blocking the eletronic timer drain. The electronic timer drain is equipped with the dryer and should be mounted externally to the dryer in the 1/4 bulkhead fitting found on the lower left side of the dryer. It is recommended that a bypass line is piped around the dryer. Shutoff valves should be installed at both inlet and outlet, with another valve in the bypass line. This complies with O.S.H.A. lockout regulations and permits the dryer to be removed from the system or serviced without turning off the air supply. Figure 2 2

Dimensions F-50 Air Dryer 1/2 NPT INLET 1/2 NPT OUTLET Suction Pressure Gauge Lighted Rocker Switch ON OFF WATER DRAIN 16.00 2.00 1.00 22.25 F-50 Wiring Diagram 115/220V CSIR Specifications Model Power Capacity Dimensions Air Line Drain Net Max. Full L.R. No. Supply SCFM (Inches) Conn. Line H.P. Refrig Wt. Press. Load AMP @ 100 PSIG Length Height Width FPT Conn. Charge* Lbs. PSI AMP O.D. F-50-1 115/1/60 50 22 16.0 14 1 3/8 1/4 16 oz. 83 250 5.6 29.8 F-50-2 230/1/60 50 22 16.0 14 1 3/8 1/4 16 oz. 83 250 2.4 14.5 *CFC-Free R-134A NOTE: The air leaving the dryer is reheated to 25 F below the inlet air temperature 3

Design Conditions The Dryer must not be cycled with the air compressor. The dryer is non-cycle and is designed to run continuously (even under light loads). If the compressed air system remains pressurized and the air compressor cycles off and on to maintain line pressure, the dryer should remain in operation to keep the air lines dry. Air Flow SCFM: The rated air flow (SCFM) of the dryer is designed for 100 PSIG. Above the rated air flow, the dew point will rise and moist air may reappear downstream. The dryer may cycle off and on under excessive load and cause compressor damage. How to Make Minor Refrigerant Suction Pressure Adjustments 1) Keep the dryer running under no load and turn off or bypass the compressed air. 2) Remove the dryer cover and locate the control valve (See Figure 3). 3) Loosen the locknut and turn clockwise to increase or counterclockwise to decrease the suction pressure (1/4 turn will normally be enough). Tighten lockout securely and wait 3 to 4 minutes for the suction pressure to settle. Repeat if needed. Inlet Air Temperature: The dryer will function normally up to 100ºF. Above this temperature, the dryer capacity will fall off. Inlet air temperature should be controlled so that it does not exceed 100ºF. Line Pressure: The maximum design pressure is 250 PSIG. Ambient Air Temperature: Locate the dryer indoors in a protected area where the ambient temperature will range between 45ºF and 100ºF. Note: Above an ambient temperature of 100ºF the refrigerant will rise until the dryer shuts down. Several off and on cycles under these conditions will damage the compressor. Automatic Expansion Valve: The automatic expansion valve regulates the refrigerant suction pressure. The expansion valve is factory set between 33 and 36 PSIG. Start UP Always turn the dryer on 5 to 10 minutes before the air compressor. This will allow the dryer to reach operating temperature and will prevent moist air downstream of the dryer. After starting the dryer, the dew point indicator will slowly drop and hold within the green area of the gauge. A lighted on/off switch glows when the power is on. During normal operation, the light will be on and the gauge will read in the green area. If the gauge reads in lower red area, the cause is a low refrigerant charge or low expansion valve setting. If the gauge reads in the higher red area, the compressor could be off. Other causes of a high gauge reading: a dirty air cooled condenser, high ambient air temperature, high inlet air temperature or an air flow above the dryer s capacity. When the dryer is off, the gauge should read close to room temperature. Figure 3 Maintenance and Care Periodically or as part of a preventative maintenance program, check the following: Be sure that there is a free flow of water from the electronic timer drain. Check the drain mechanism and bronze element periodically and clean monthly. The drain can be activated by pressing the Test button located on the external timer mechanism. If the valve fails to open or operate correctly, replace the valve. To clean the drain assembly, close the ball valve located just below the separator bowl. Relieve the pressure on the drain assembly by pressing the test button located on the external timer drain. When the pressure is relieved, remove the strainer screen by turning the knurled retainer counterclockwise. Remove and clean the strainer and reassemble in the reverse order. Be sure that there is a free flow of air over the condenser coils. Check the condenser fins periodically to prevent a build up of dust deposit. If fins are coated with dust, blow compressed air through the fins to clean. Frosting on refrigerant lines is an indication of too much refrigeration capacity. This results in frozen air passages and prevents air flow through the dryer. It may be necessary to increase the refrigerant suction pressure. Model F-50 Figure 4 4

TROUBLESHOOTING CHART Symptom Possible Causes(s) Corrective Action Unit will not run. 1. No Power. 1. Correct power supply, fuses, circuit breaker. 2. Internal compressor overload. 2. Feel the temperature of the compressor and allow to cool off if hot. Observe the fan motor. Have the motor checked if it does not run. Clean the condenser. Dew Point Indicator Red (High) 1. Internal compressor overload. 1. Check for air overload. Check inlet air temperature. Check operation of fan motor. 2. High ambient temperature. 2. Check room temperature and hold between 45 F and 100 F. Dew Point Indicator Red (Low) 1. Low refrigerant charge. 1. Have qualifi ed refrigeration service technician check out dryer or call factory. 2. Low ambient temperature. 2. Relocate dryer to heated area between 45 F and 100 F 3. Low hot gas valve setting. 3. Re-adjust hot gas valve to green area on dew point indicator gauge (See minor pressure adjustment) High pressure drop 1. High air fl ow. 1. Air fl ow above rated fl ow of dryer. 2. Drain valve not discharging. 2. Manually blow down drain until water fl ow stops. Clean drain. 3. Freezing moisture in evaporator. 3. Re-adjust hot gas valve to green area on dew point indicator gauge (See minor pressure adjustment) 4. Plugged separator element or drain. 4. Clean or replace. Water downstream of dryer 1. Compressed air is fl owing through 1. Dryer must be operating 5-10 dryer before it is turned on. minutes before compressed air load. 2. Dirty separator element or drain. 2. Disassemble and clean. 3. Overload dryer above air fl ow 3. Reduce air load to dryer capacity. specifi cations.* 4. High suction pressure. 4. Inlet air temperature too hot. 5. Low outlet air pressure. 5. Freezing of water, adjust suction pressure.* 6. Low refrigerant charge. 6. Contact service technician to leak check. NOTE: Check or repairs of the refrigeration system must be done by a qualifi ed refrigeration service technician with the required gauges 5

If Trouble Starts If the dryer cycles off and on for any reason TURN OFF THE DRYER. Call the factory for instructions, Check or repairs of the refrigeration systems must be made by a qualified refrigeration service technician. Before calling the factory for instructions, have the following data to report. Model No. Serial No. Refrigeration Suction Pressure. REPLACEMENT PARTS Model F-50-1 F50-2 Voltage 115/1/60 220/1/60 Compressor Make TECUMSEH R-134A TECUMSEH R-134A Separator/ Drain Assembly PART NUMBER PART NUMBER Separator FK329-S1 FK329-S1 Bowl Separator 3110-S1-8 3110-S1-8 Repair Kit RFK329 RFK329 Element Kit EKF329 EKF329 Electronic Timer Drain 27901 27902 Refrigeration System Condensing Unit 94820 94821 Compressor 94917 98327 Condenser 93950 93950 Expansion Valve 91201 91201 Hot Gas Bypass Valve 91221 91221 Refrigerant Filter 91235 91235 Heat Exchanger 14142 14142 Electrical Fan Motor 94930 92933 Fan Blade 92940 92940 Overload 91441 91439 Power On Light/Switch 57300 57300 Gauges Suction Pressure 91303 91303 Cabinet Panels Base 14656 14656 Cover 14654 14654 End Panel Right Side Vented 14655 14655 End Panel Left Side Vented 14680 14680 6

ORDER REPLACEMENT PARTS BY CALLING (877) 640-8300 Please provide following information: Model Number Serial Number (if any) Part Description and Number Address parts correspondence to: ARROW DRYERS 745 Clark Ave. Bristol, CT 06010 WARRANTY POLICY When used under the conditions recommended by the manufacturer, Arrow Dryers, this model is warranted to be free from defects in material and workmanship for a period of twenty-four (24) months from date of receipt, not to exceed thirty (30) months from the factory ship date, provided Arrow is furnished the customer s name, address, and date of shipment information These units will utilize either a braze plate or modular type heat exchanger which will be warranted for five (5) years. This warranty is limited to the replacement of the heat exchangers, F.O.B. Factory, and subject to the same restrictions as outlined below concerning misuse, abuse or accident. The electronic timer drain carries a 90-day warranty. This warranty will apply to equipment installed, operated and maintained in accordance with the procedures and recommendations as outlined in the owner s manual published by Arrow Dryers. During the life of this warranty, Arrow Dryers will repair or replace (at Arrow Dryers option) any defective part or assembly, free of charge, F.O.B. its plant if such defect occurred in normal service and was not due to apparent misuse, abuse or accident. Any warranty service performed in the field must be authorized by Arrow Dryers, Unauthorized service voids the warranty and any resulting charge will not be paid by Arrow Dryers. Arrow Dryers makes no other warranties or guarantees, expressed or implied. The merchantability of the components is expressly excluded. The manufacturer assumes no liability for indirect or consequential damages. 7