Application of the 2012 North Carolina Energy Conservation Code

Similar documents
2009 IECC Commercial Mechanical Requirements

COMcheck Software Version Review Mechanical Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate

August 15, 2013 Page 1 of 19

COMcheck Software Version Mechanical Compliance Certificate

HVAC Mandatory Provisions Part II, Page 1

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

COMMERCIAL ENERGY EFFICIENCY

COMcheck Software Version Interior Lighting Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate

COMcheck Software Version Interior Lighting Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate

COMMERCIAL ENERGY EFFICIENCY

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

INDEX. ADDITIONS AND ALTERATIONS Defined Requirements ADMINISTRATION AND ENFORCEMENT... Chapter 1 AIR ECONOMIZERS

Mechanical Compliance Certificate

2006 Washington State Nonresidential Energy Code Compliance Form Washington State Nonresidential Energy Code Compliance Forms Revised July 2007

High Performance Building Guide 1

1 - This title will copy onto other forms Date

Inspection Phase Three. Mechanical, Electrical & Plumbing Section 503

SESSION Michigan Energy Code (MEC) Update (3 Technical) Per SMACNA Standard (TAB, Duct Design) and ASHRAE ( ) ASHRAE Detroit Members:

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

ASHRAE/IESNA Standard

COMcheck Software Version Mechanical Compliance Certificate

2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC

PRE-PRINT APPENDIX E GREEN MECHANICAL CODE SUPPLEMENT

2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below)

COMcheck Software Version Mechanical Compliance Certificate

Equipment Specifications and Required Information Quantity Rebate

COMcheck Software Version

Appendix 13. Categories of Cooling and Heating systems

ERRATA SHEET FOR ANSI/ASHRAE/IES STANDARD (I-P Edition) Energy Standard for Buildings Except Low-Rise Residential Buildings.

Address Account # Member # Equipment Specifications Quantity Rebate. ENERGY STAR Appliances

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Massachusetts Energy Code Compliance Support Commercial Energy Code Building Mechanical & Service Water Heating Provisions

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

AHRI Certification Program Scopes - COOLING

ONTARIO BUILDING CODE AND SUPPLEMENTARY STANDARD SB-10 PROJECT INFORMATION. Mechanical Designer Information*

Energy-Efficiency Measures List

Summary Comparison of Simulation Program Features

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

CHAPTER 4. HVAC DELIVERY SYSTEMS

ATTACHMENT D #1 - HVAC (OIL) - SINGLE FAMILY DWELLINGS Category C: OIL

COMMERCIAL HVAC PACKAGED EQUIPMENT. Split Systems

SECTION AIR-SOURCE UNITARY HEAT PUMPS

August 27, Section 3.2 Definitions. On page 11 delete the following definition:

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

Method to test HVAC equipment at part load conditions

Union County Vocational - Technical Schools Scotch Plains, New Jersey

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

IMC Significant Changes Summary Tier I

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

8 5.11: Finned-Tube Coils and Heat Exchangers : Humidifiers and Water Spray Systems : Access for Inspection, Cleaning, and Maintenance

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

COMMERCIAL ENERGY EFFICIENCY

Dehumidifying with Dedicated Outdoor Air

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC

Direct Install Program Eligible Measures Listing:

NAHB Green Home Building Guidelines. 3.1 Prerequisites. ResCheck. Energy Efficiency

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION

COMMERCIAL HVAC EQUIPMENT Indoor Self-Contained Units

City of Duluth Festival Center 04/25

AHRI Product Section and Subsection Scopes

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

Chiller Plant Design. Application Guide AG McQuay International. Elevation Difference. Column Height When Pump Is Off

2016 BUILDING ENERGY EFFICIENCY STANDARDS RESIDENTIAL HVAC ALTERATIONS

HVAC Controls Upgrades: Requirement Details ( )

Chapter 7: Heating and Cooling Systems

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

NET ENERGY WATER LOOPS A clear path to net zero energy buildings

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

Ventilation for New Low-Rise Residential Buildings July 20, 2015

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code. Table of Contents

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

ENGINEERING. Edition No. 13 October 2002

Snohomish County PUD #1 HEAT PUMP SYSTEM INSTALLATION STANDARDS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

SECTION/SUBSECTION (scroll down to view more listings; this list is arranged alphabetically) SCOPE. AHRI Section-Subsection Scopes

DIVISION 15 MECHANICAL

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

Performance Rating of Computer and Data Processing Room Air Conditioners

CONTENTS. B. System Design and Performance Requirements

wattsmart New Homes Contractor-Certified HVAC Quality Assurance (HVAC-QI)

Job Name Control Systems Description Date

Transcription:

Application of the 2012 North Carolina Energy Conservation Code Commercial Mechanical Presented By: NC Code Officials Qualification Board Office of State Fire Marshal NC Department of Insurance

2012

Modules Module 1 Administration Module 2 Residential building requirements Module 3 Commercial building requirements Module 4 Residential electric requirements Module 5 Commercial electric requirements Module 6 Residential mechanical requirements Module 7 Commercial mechanical requirements Module 8 Residential plumbing requirements Module 9 Commercial plumbing requirements

The first module, Module 1 Administrative Provisions, reviews the code requirements for administration, definitions, climate zones, materials, systems and equipment. This module should be reviewed before proceeding with this or other modules. Click the following link to view Module 1 now: www.module1.com, or advance to the next slide to continue with this module.

This module uses plan review and inspection checklists. The checklists should be printed and used as a reference during the module. Access the checklists via the Attachment button in the top right-hand corner of the screen.

The student will be able to: Learning Objectives Interpret plans for compliance with the 2012 North Carolina Energy Conservation Code. Recognize field conditions and construction documents that are in conflict with the North Carolina Energy Conservation Code. Defend and enforce basic energy conservation code concepts and principles. Identify and list common plan review and inspection items. Utilize checklists and other compliance tools to evaluate construction documents and field conditions for energy code compliance. This module will focus on the commercial mechanical requirements.

COMPLIANCE OPTIONS What are the choices for code compliance? Meet the mandatory and prescriptive requirements in Chapter 5 Include one of six additional prescriptive requirements as identified in Section 506 ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.) 90.1-2007 is referenced as a compliance path, but must include an additional 20% energy efficiency improvement North Carolina specific COMcheck Total Building Performance Section 507

Four components of Prescriptive building compliance in the NCECC, plus one additional requirement selected by the designer 502 - Building Envelope 503 - Building Mechanical Systems 504 - Service Water heating 505 - Electric Power and Lighting Systems 506 - Additional prescriptive compliance requirements Compliance with one of the following required Compliance option selected shall be indicated with submittal

506.2.1 - More efficient mechanical provisions 506.2.2 - Reduced lighting power density 506.2.3 - Energy recovery ventilation systems 506.2.4 - Higher efficiency service water heating equipment 506.2.5 - On-site supply of renewable energy 506.2.6 - Automatic daylighting control system

AIR LEAKAGE CONTROL Air leakage 502.4 (Mandatory)

Sealing of envelope 502.4.3 Seal penetrations in the building thermal envelope with caulking materials compatible with the construction materials and location Allow for expansion and contraction The following shall be air sealed: Openings at penetrations of utility services through roofs, walls, and floors, including but not limited to electrical, plumbing, mechanical, security, and communications and other openings in the thermal envelope

Appendix 2.1 Air Sealing Details

Appendix 2.1 Air Sealing Details

Stair and elevator vents 502.4.5 Shaft vents serving stairs and elevators Integral to the thermal envelope shall be equipped with a Class I motorized leakage rated damper Maximum leakage rate 4 cfm per square foot at 1 inch of water column when tested to AMCA 500D Exceptions Buildings without fire alarm systems Stairway vents open to the exterior

Motorized Damper

MECHANICAL PROVISIONS 503 1. Mechanical systems and equipment serving the building heating, cooling, or ventilating needs shall comply with 503.2 Mandatory (provisions) and 2. Either 503.3 (Simple systems) or 503.4 (Complex systems) Note: Does not apply to industrial or process equipment

DEFINE SIMPLE SYSTEM The code text in section 503.3 explains the parameters of a simple system Generally, unitary or packaged HVAC equipment, each serving one zone and controlled by a single thermostat Example of simple systems each shall serve a single zone by a single thermostat

Also applies to two pipe heating systems with no cooling This section does not apply to fan systems serving multiple zones, nonunitary or nonpackaged HVAC equipment and systems or hydronic or steam heating and hydronic cooling equipment and distribution systems that provide cooling or cooling and heating which are covered by Section 503.4. Everything else is COMPLEX

Calculation of heat and cooling loads 503.2.1 Calculations per ASHRAE / ACCA Standard 183 Adjustments for heat recovery systems ASHRAE HVAC Systems and Equipment Handbook

Equipment and system sizing 503.2.2 Heating and cooling equipment and systems capacity shall not exceed design loads calculated, within available equipment options System provides heating and cooling must satisfy provision for one function with the capacity for the other function as small as possible

Exceptions 1. Required standby equipment and systems provided with controls and devices that allow such systems or equipment to operate automatically only when the primary equipment is not operating. 2. Multiple units of the same equipment type with combined capacities exceeding the design load and provided with controls that have the capability to sequence the operation of each unit based on load. 3. When the equipment selected is the smallest size needed to meet the load within available

HVAC equipment performance requirements 503.2.3 HVAC equipment performance requirements Tables Minimum efficiency ratings and corresponding test procedure identified in Tables 503.2.3(1) / 503.2.3(2) / 503.2.3(3) / 503.2.3(4) / 503.2.3(5) / 503.2.3(6) / 503.2.3(7)

Equipment shall meet the minimum efficiencies in the Tables Tables list test procedures Verified through certification or supporting data Multiple requirements must comply with all New equipment NAECA National Appliance Energy Conservation Act Exception water cooled centrifugal water chilling packages Adjusted full load and NPLV applicable of specific ranges

Some types of equipment not on list can be used; no specific requirements for efficiency Absorption coolers, electric heaters, cooling towers Notes to Tables are critical

TABLE 503.2.3(1) UNITARY AIR CONDITIONERS AND CONDENSING UNITS, ELECTRICALLY OPERATED, MINIMUM EFFICIENCY REQUIREMENTS EQUIPMENT TYPE SIZE CATEGORYe SUBCATEGORY OR MINIMUM TEST PROCEDUREa RATING CONDITION EFFICIENCYb Air conditioners, < 65,000 Btu/hd (<w 5 Split system 13.0 SEER AHRI 210/240 Air cooled nominal tons) Single package 13 SEER > 65,000 Btu/h and Split system and 11.2 EERc < 135,000 Btu/h single package > 135,000 Btu/h and Split system and 11.0 EERc AHRI 340/360 < 240,000 Btu/h single package > 240,000 Btu/h and < 760,000 Btu/h Split system and single package 10.0 EERc 9.7 IPLVg > 760,000 Btu/h Split system and single package 9.7 EERc 9.4 IPLVc Through-the wall < 30,000 Btu/hd Split system 12.0 SEER AHRI 210/240 Air cooled Single package 12.0 SEER Air conditioners, Water and < 65,000 Btu/h Split system and 12.1 EER AHRI 210/240 evaporatively cooled single package > 65,000 Btu/h and Split system and 11.5 EERc < 135,000 Btu/h single package > 135,000 Btu/h Split system and 11.0 EERc AHRI 340/360 < 240,000 Btu/h single package > 240,000 Btu/h Split system and single package 11.5 EERc

TABLE 503.2.3(2) UNITARY AIR CONDITIONERS AND CONDENSING UNITS, ELECTRICALLY OPERATED, MINIMUM EFFICIENCY REQUIREMENTS EQUIPMENT TYPE SIZE CATEGORYe SUBCATEGORY OR MINIMUM TEST PROCEDUREa RATING CONDITION EFFICIENCYD Air cooled < 65,000 Btu/hd Split system 13.0 SEER AHRI 210/240 (Cooling mode) Single package 13.0 SEER > 65,000 Btu/h and Split system and 11.0 EERc < 135,000 Btu/h single package > 135,000 Btu/h and Split system and 10.6 EERc AHRI 340/360 < 240,000 Btu/h single package > 240,000 Btu/h Split system and 9.5 EERc Through-the wall (Air cooled, cooling mode) Water source (Cooling mode) Groundwater source (Cooling mode) Ground source (Cooling mode) Air cooled (Heating mode) single package 9.2 IPLVc < 30,000 Btu/hd Split system 12.0 SEER AHRI 210/240 Single package 12.0 SEER < 17,000 Btu/h 86ºF entering water 11.2 EER AHRI/ASHRAE-13256-1 > 17,000 Btu/h and 86ºF entering water 12.0 EER AHRI/ASHRAE-13256-1 < 135,000 Btu/h < 135,000 Btu/h 59ºF entering water 16.2 EER AHRI/ASHRAE-13256-1 < 135,000 Btu/h 77ºF entering water 13.4 EER AHRI/ASHRAE-13256-1 < 65,000 Btu/hd (Cooling capacity) > 65,000 Btu/h and < 135,000 Btu/h Split system 7.7 HSPF AHRI 210/240 Single package 7.7 HSPF 47ºF db/43ºf wb 3.3 COP outdoor air An air cooled unitary air conditioner, which is a split system and through the wall unit, with a capacity of < 30,000 Btu, has an efficiency of 12.0 SEER

TABLE 503.2.3(3) PACKAGED TERMINAL AIR CONDITIONERS AND PACKGED TERMINAL HEAT PUMPS EQUIPMENT TYPE PTAC (Cooling mode) New construction PTAC (Cooling mode) Replacements PTHP (Cooling mode) New construction PTHP (Cooling mode) Replacements PTHP (Heating mode) New construction PTHP (Heating mode Replacements SIZE CATEGORY (INPUT) SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCYb All capacities 95ºF db outdoor air 12.5 (0.213 - Cap/1000) EER All capacities 95ºF db outdoor air 10.9 (0.213 - Cap/1000) EER All capacities 95ºF db outdoor air 12.3 (0.213 - Cap/1000) EER All capacities 95ºF db outdoor air 10.8 (0.213 - Cap/1000) EER All capacities 3.2 (0.026 - Cap/1000) EER All capacities 2.9 (0.026 - Cap/1000) EER TEST PROCEDUREa ARI 310/380 A replacement PTHP, with a capacity of 6,000 Btu, has a minimum efficiency of. 9.309 Note b applies. Note b indicates 7,000 should be used - 10.8 - (0.213 x 7) = 9.309

TABLE 503.2.3(4) WARM AIR FURNACES AND COMBINATION WARM AIR FURNACES/AIR-CONDITIONING UNITS, WARM AIR DUCT FURNACES AND UNIT HEATERS, MINIMUM EFFICIENCY REQUIREMENTS EQUIPMENT TYPE Warm air furnaces, gas fired Warm air furnaces, oil fired Warm air duct furnaces, gas fired SIZE CATEGORY (INPUT)h SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCY d,e TEST PROCEDUREa < 225,000 Btu/h 78% AFUE DOE 10 CFR Part 430 or or ANSI Z21.47 80% Ere > 225,000 Btu/h Maximum capacityc 80% Erf ANSI Z21.47 < 225,000 Btu/h 78% AFUE DOE 10 CFR Part 430 or or UL 727 80% Er > 225,000 Btu/h Maximum capacityb 81% Erg UL 727 All capacities Maximum capacityb 80% Ec ANSI Z83.8 Warm air unit heaters, gas fired Warm air unit heaters, oil fired All capacities Maximum capacityb 80% Ec ANSI Z83.8 All capacities Maximum capacityb 80% Ec UL 731 The test standard for a warm air duct furnace, gas-fired is. ANSI Z83.8

TABLE 503.2.3(5) BOILERS, GAS- AND OIL FIRED, MINIMUM EFFICIENCY REQUIREMENTS EQUIPMENT TYPE SIZE CATEGORY SUBCATEGORY OR MINIMUM TEST PROCEDUREa (INPUT)h RATING CONDITION EFFICIENCY d,e Boilers, Gas fired < 300,000 Btu/h Hot water 80% AFUE DOE 10 CFR Steam 75% AFUE Part 430 > 300,000 Btu/h and < 2,500,000 Btu/h Minimum capacityb 75% Et and 80% Ec (See Note c, d) DOE 10 CFR Part 431 > 2,500,000 Btu/hf Hot water 80% Ec (See Note c, d) Steam 80% Ec (See Note c, d) Boilers, Oil fired < 300,000 Btu/h 80% AFUE DOE 10 CFR Part 430 Boilers, Oil fired (Residual) > 300,000 Btu/h and < 2,500,000 Btu/h Minimum capacityb 78% Et and 83% Ec (See Note c, d) > 2,500,000 Btu/hf Hot water 83% Ec (See Note c, d) Steam 83% Ec (See Note c, d) > 300,000 Btu/h and Minimum capacityb 78% Et and 83% Ec < 2,500,000 Btu/h (See Note c, d) > 2,500,000 Btu/hf Hot water 83% Ec (See Note c, d) Steam 83% Ec (See Note c, d) DOE 10 CFR Part 431 DOE 10 CFR Part 431 What is the required minimum AFUE for a 290,000 Btu/h oil-fired boiler? 80 %

What is the required test procedure for an electrically operated condensing unit with a size category greater than or equal to 135,000 Btu/hr? AHRI 365

EQUIPMENT TYPE Air-Cooled Chillers Air-Cooled without Condenser, Electrical Operated Water-Cooled Electrically Operated, Reciprocating Water Cooled Electrically Operated, Positive Displacement Water Cooled Electrically Operated, Centrifugal TABLE 503.2.3(7) WATER CHILLING PACKAGES, EFFICIENCY REQUIREMENTSa SIZE UNITS BEFORE 1/1/2010 AS OF 1/1/2010c TEST CATEGORY PATH A PATH B PROCEDURE FULL LOAD IPLV FULL LOAD IPLV FULL LOAD IPLV a <150 tons EER > 9,562 > 10,416 > 9,562 > 12,500 NAd NAd AHRI 550/590 >150 tons EER > 9,562 > 12,750 NAd NAd All Capacities EER > 10,586 > 11,782 Air-cooled chillers without condenses must be rated with matching condensers and comply with the air-cooled efficiency requirements All Capacities kw/ton < 0.837 < 0.696 Reciprocating units must comply with water cooled positive displacement efficiency requirements <75 tons kw/ton < 0.790 < 0.676 < 0.780 < 0.630 < 0.800 < 0.600 >75 tons and kw/ton < 0.775 < 0.615 < 0.790 < 0.586 <150 tons >150 tons and kw/ton < 0.717 < 0.627 < 0.680 < 0.580 < 0.718 < 0.540 <300 tons >300 tons kw/ton < 0.639 < 0.571 < 0.620 < 0.540 < 0.639 < 0.490 <150 tons kw/ton < 0.703 < 0.669 < 0.634 < 0.596 < 0.639 < 0.450 >150 tons and kw/ton < 0.634 < 0.596 <300 tons >300 tons and kw/ton < 0.576 < 0.549 < 576 < 0.549 < 0.600 < 0.400 <600 tons >600 tons kw/ton < 0.576 < 0.549 < 0.570 < 539 ARI 560 < 0.400

DEFINE Unitary equipment Self-contained, packaged equipment from a single manufacturer Split system heating and cooling with equipment in different locations Single zone One zone served by a single thermostat Multi-Zone Satisfy needs of multiple zones

ABBREVIATIONS PTAC Packaged terminal air conditioner PTHP Packaged terminal heat pumps AFUE Annual Fuel Utilization Equipment EER Energy efficiency ratio

ABBREVIATIONS (continued) SEER Seasonal energy efficiency ratio COP Coefficient of performance IPLV Integrated part-load value 1 ton cooling = 12,000 Btu/h

ABBREVIATIONS (continued) HSPF Heating seasonal performance factor Zone Space or group of spaces with similar load characteristics ERV Energy recovery ventilation

HVAC SYSTEM CONTROLS PER SECTION 503.2.4

All systems 503.2.4.1 / 503.2.4.2 / 503.2.4.3 / 503.2.4.4 Complex systems 503.4.1 / 503.4.2 / 503.4.3 / 503.4.4 Different demands, exposures or loads will require different zones, i.e., interior zones and perimeter zones

Thermostatic controls 503.2.4.1 Supply of heating and cooling energy controlled by an individual thermostat responding to conditions in the zone Dehumidification / humidification at least one control device for each humidity control system

Exception: Independent perimeter systems for perimeter heat losses or gains, or both serving one or more perimeter zones also served by an interior system provided: One thermostat control zone for exterior walls facing one orientation for each exposure of 50 or more contiguous feet, and the thermostat is located within the zones served by the system

Perimeter systems, thermostatic control zone when more than 50 contiguous feet

Heat Pump Supplementary Heat 503.2.4.1.1 Heat pumps require controls to prevent supplementary electric heat operation when the heat pump refrigeration circuit can supply load Except during defrost Section 503.2.4.1.1 Systems less than 65,000 Btu/h cooling capacity, heat strip lockout device if required Set no lower than 35 F or higher than 40 F

Set point overlap restriction 503.2.4.2 Single device controls both heating and cooling Dead band The temperature range at which no heating or cooling is used (the temperature range between heating and cooling set points) A minimum 5 F dead band is required with no or minimized heating and cooling Except manual changeover systems

Off-hour controls 503.2.4.3 Required in each zone Thermostatic setback controls that are controlled by either on automatic time clock or programmable control system Except Continuous operation Max load 6,800 Btu/h and accessible manual shutoff switch Motel guestrooms or other residential units complying with section 503.2.2 Packaged terminal air conditioners, packaged terminal heat pumps and room air conditioners

Thermostatic setback capabilities 503.2.4.3.1 Controls having the capability to setback or temporarily operate the system to maintain zone temperatures down to 55 F or up to 85 F Automatic setback and shutdown capabilities 503.2.4.3.2 Automatic time clock or programmable controls shall be capable of starting and stopping the system for seven different daily schedules per week and retaining programming and time setting during a loss of power for at least 10 hours. Additionally, the controls shall have a manual power override that allows temporary operation of the system for up to 2 hours, or a manually operated time capable to operate the system up to 2 hours, or an occupancy sensor.

Shutoff damper controls 503.2.4.4 Outdoor air supply and exhaust ducts, fans, or openings in the building thermal envelope shall be equipped with motorized dampers that will automatically shut when the system or spaces served are not in use Except gravity dampers allowed when: 1. Less than 3 stories OR 2. Outside air intake or exhaust 300 cfm or less

Snow melt systems 503.2.4.5 Supplied through the building energy system Automatic shut off when pavement above 50 F and no precipitation Automatic or manual control when outdoor temperature above 40 F

PROPERTIES On passing, 'Finish' button: On failing, 'Finish' button: Allow user to leave quiz: User may view slides after quiz: Goes to Next Slide Goes to Next Slide At any time At any time

Ventilation 503.2.5 Natural or mechanical, per the North Carolina Mechanical Code Chapter 4 When mechanical, the capability to reduce outside air to the minimum required by Chapter 4 of the NC Mechanical Code

Demand controlled ventilation 503.2.5.1 Demand control ventilation system required: 1. All buildings over 10,000 square feet 2. Building or spaces larger than 500 square feet with maximum occupant load of more than 40 occupants per 1,000 square feet (as established by Table 403.3 in the NC Mechanical Code) Monitor with a CO² monitoring system Reduce outdoor ventilation to at least 50% of design

Demand control ventilation system required (continued): Except 1. Energy recovery systems, which provide a change of enthalpy of outdoor air supply of 50% or more of difference between outdoor air and return air at design conditions 2. Primary ventilation needs for process loads, including laboratories and hospitals 3. Individual units with less than 65,000 Btu/h cooling capacity

Energy recovery ventilation systems 503.2.6 Define System that employs air-to-air heat exchangers to recover energy from exhaust air for the purpose of pre-heating, pre-cooling, humidifying or dehumidifying outdoor ventilation air prior to supplying air to the space, either directly or as part of an HVAC system These systems recover useful energy from exhaust air that would otherwise be released to the outdoor environment

Required in individual fan systems when: Fan design capacity of 5,000 cfm or greater and Minimum outside air supply of 70% or greater of the design supply air quantity Must provide a change in enthalpy of 50% or more of the difference between outdoor air and return air at design conditions Ability to bypass or control the energy recovery system to permit cooling with outdoor air where cooling with outdoor air is required

7 exceptions 1. When prohibited by the NC Mechanical Code 2. Lab fume hoods with at least one: 2.1 Variable air-volume exhaust and supply which reduce the system to 50% or less of the design values 2.2 Direct makeup air supply Equal to 75% or more of the exhaust, Heated to no more than 2 below setpoint, Cooled to no more than 3 above setpoint, No humidification, and No simultaneous heating and cooling used for dehumidification control

Additional ERVS Exceptions 3. Systems serving spaces that are not cooled and are heated to less than 60 F (15.5 C) 4. Where more than 60 percent of the outdoor heating energy is provided from site-recovered or site solar energy 5. Heating systems in climates with less than 3,600 HDD 6. Cooling systems in climates with a 1-percent cooling design wet-bulb temperature less than 64 F (18 C) 7. Systems requiring dehumidification that employ series-style energy recovery coils wrapped around the cooling coil

Duct and plenum insulation and sealing 503.2.7 All supply and return air ducts and plenums shall be insulated with a minimum of R-5 insulation when located in unconditioned spaces and a minimum of R-8 insulation when located outside the building. When located within a building envelope assembly, the duct or plenum shall be separated from the building exterior or unconditioned or exempt spaces by a minimum of R-8 insulation. Except When located within equipment or inside the thermal envelope When less than a 15 design temperature differential between the interior and exteriorof the duct or plenum

Insulation for energy code or for potential condensation?

Duct, air handlers and filter boxes Fastened and sealed per NCMC 603.9 Welds, gaskets, mastics, mastic plus embedded fabric, tapes

Duct Sealing Table UL 181 A Tapes and mastics ductwork UL 181 A-P Pressure sensitive UL 181 A-M Mastic UL 181 A-H Heat sensitive tape UL 181 B Tapes and mastics flexible air ducts and air connectors UL 181 B-FX Pressure sensitive tape UL 181 B-M Mastic UL 181 C Mechanical fasteners flexible nonmetallic air duct Unlisted tape (40 mile an hour tape) cannot be used No duct sealing when exposed within the space served by the duct for lowpressure duct systems

Duct Construction 503.2.7.1 Duct construction per the NC Mechanical Code Seams and connections Longitudinal, transverse, joints and seams Sealed Low pressure ducts supply and return 2 psi Welds, gaskets, mastics, tapes Installed per the manufacturer Medium pressure ducts and plenums > 2psi and < 3 psi Sealed per section 503.2.7 High pressure ducts > 3 psi Sealed per section 503.2.7 Leak tested Pressure indicated on construction documents

High pressure ducts are leak tested to SMACNA HVAC Air Duct Leakage Test Manual Rate of leakage less than 6.0 Air leakage = F x P 0.65 F = measured leakage rate in cfm per 100 ft 2 of duct surface P = static pressure of the test Test at least 25% of duct system Documentation of the required testing shall be furnished by the designer

Here are some duct insulation and sealing examples...

Vibration Duct Joint

Duct sealing

Piping insulation required per Table 503.2.8 TABLE 503.2.8 MINIMUM PIPE INSULATION (thickness in inches) Fluid NOMINAL PIPE DIAMETER 1.5 > 1.5 Steam 1 ½ 3 Hot water 1 ½ 2 Chilled water, brine or refrigerant 1 ½ 1 ½ Note: Section 503.2.8 requires all piping services as part of a heating and cooling system to be thermally insulated in accordance with Table 503.2.8

Piping insulation required per Table 503.2.8 Exceptions 1. Factory-installed piping within HVAC equipment tested and rated in accordance with a test procedure referenced by this code. 2. Factory-installed piping within room fan-coils and unit ventilators tested and rated according to AHRI 440 (except that the sampling and variation provisions of Section 6.5 shall not apply) and 840, respectively. 3. Piping that conveys fluids that have a design operating temperature range between 55 F (13 C) and 105 F (41 C). 4. Piping that conveys fluids that have not been heated or cooled through the use of fossil fuels or electric power. 5. Runout piping not exceeding 4 feet (1219 mm) in length and 1 inch (25 mm) in diameter between the control valve and HVAC coil. 6. Refrigerant suction piping located in conditioned space is not required to be insulated other than as may be necessary for preventing the formation of condensation.

503.2.9 HVAC System Completion: Prior to the issuance of a certificate of occupancy, the following shall be completed: 503.2.9.1 System balancing. All HVAC systems shall be balanced by contractor. 503.2.9.1.1 Air systems balancing. Each supply air outlet and zone terminal device shall be equipped with means for air balancing in accordance with the requirements of Chapter 6 of the North Carolina Mechanical Code. 503.2.9.1.2 Hydronic systems balancing. Individual hydronic heating and cooling coils shall be equipped with means for balancing and pressure test connections. Hydronic systems shall be balanced in a manner to first minimize throttling losses, then the pump impeller shall be trimmed or pump speed shall be adjusted to meet design flow conditions.

503.2.9.2 Manuals The manual shall include, at least, the following: 1. Equipment capacity (input and output) and required maintenance actions. 2. Equipment operation and maintenance manuals. 3. Name and address of at least one service. 4. HVAC system control maintenance and calibration information, including wiring diagrams, schematics, and control sequence descriptions. Desired or field-determined setpoints shall be permanently recorded on control drawings, at control devices or, for digital control systems, in programming comments. 5. A complete written narrative of how each system is intended to operate. 6. Name and addresses of designers of record, contractors, subcontractors and equipment suppliers.

Air system design and control 503.2.10 Total fan system motor nameplate horsepower exceeding 5 horsepower 503.2.10.1 and 5.3.2.10.2 must be met

503.2.10.1 Allowable fan horsepower. Each HVAC system at fan system design conditions shall not exceed the allowable fan system motor nameplate hp (Option 1) or fan system bhp (Option 2) as shown in Table 503.2.10.1(1). This includes supply fans, return/relief fans, and fan-powered terminal units associated with systems providing heating or cooling capability. Exceptions: 1. Hospital and laboratory systems that utilize flow control devices on exhaust or return to maintain space pressure relationships necessary for occupant health and safety or environmental control shall be permitted to use variable volume fan power limitation. 2. Individual exhaust fans with motor nameplate horsepower of 1 hp or less. 3. Fans exhausting air from fume hoods. (Note: If this exception is taken, no related exhaust side credits shall be taken from Table 503.2.10.1(2) and the Fume Exhaust Exception Deduction must be taken from Table 503.2.10.1(2).

Option 1: Fan system motor nameplate hp Hp = The maximum combined motor nameplate horsepower Calculation for allowable motor hp is as follows: Constant volume = hp CFMs * 0.0011 Variable volume = hp CFMs * 0.0015 CFMs = The maximum design supply airflow rate to conditioned spaces served by the system in cubic feet per minute

Option 2: Fan system bhp Calculation for allowable fan system bhp is as follows: Constant volume = bhp CFMs * 0.00094 + A Variable volume = bhp CFMs * 0.0013 + A CFM S = The maximum design supply airflow rate to conditioned spaces served by the system in cubic feet per minute A = Sum of (PD x CFM D / 4131) PD = Each applicable pressure drop adjustment from Table 503.2.10.1(2) in w.c. CFM D = Design airflow through each applicable device in Table 503.2.10.1(2) Bhp = The maximum combined fan bhp

Motor nameplate brake horsepower 503.2.10.2 (alternative to using 503.2.10.1) Limits size of motors for fans For each fan, the fan motor shall be no larger than the first available motor size greater than the brake horsepower (bhp) Bhp shall be indicated on the design documents For example, if a motor rated at 8 bhp is required and available sizes are 7, 9 and 10 then 9 can be used

Motor nameplate brake horsepower exceptions 1. For fans less than 6 bhp, where the first available motor larger than the brake horsepower has a nameplate rating within 50 percent of the bhp, selection of the next larger nameplate motor size is allowed. 2. For fans 6 bhp and larger, where the first available motor larger than the bhp has a nameplate rating within 30 percent of the bhp, selection of the next larger nameplate motor size is allowed. * The fan bhp shall be indicated on the design documents to allow for compliance verification by the code official

Heating outside a building 503.2.11 Outside heat shall be radiant Controlled by occupant sensors or timers De-energized when no one present

Simple HVAC systems and Equipment 503.3 (Prescriptive) Type of equipment Unitary or packaged equipment Tables 503.2.3(1) through 503.2.3(5) One zone / One thermostat / Two pipe heating systems with no cooling serving one or more zones Does not apply to certain complex systems

Unitary Heat Pump One or more factory-made assemblies that include an indoor conditioning coil, compressor(s) and outdoor coil or refrigerantto-water heat exchanger, including means to provide both heating and cooling functions. When heat pump equipment is provided in more than one assembly, the separate assemblies shall be designed to be used together.

Unitary Heating and Cooling Equipment One or more factory-made assemblies that include an evaporator or cooling coil, a compressor and condenser combination, and that shall be permitted to include a heating function as well. When heating and cooling equipment is provided in more than one assembly, the separate assemblies shall be designed to be used together.

Unitary Packaged Each package is a stand alone system which provides all of the heating and cooling requirements for the area of the building that it serves

Economizers 503.3.1

Cooling Systems Supply air economizers shall comply with Table 503.3.1(1) Capable of 100% outside air with additional cooling Relieve excess outdoor air without recirculating Except: Comply with Tables 503.2.3(1) or 503.2.3(2), and exceeding the minimum efficiencies in Table 503.3.1(2) Air or evaporated cooled condensers with open space refrigeration Air requiring extensive filtration (polluted air)

Table 503.3.1(1) Economizer Requirements CLIMATE ZONES ECONOMIZER REQUIREMENT 1A, 1B, 2A, 7, 8 No requirement 2B, 3A, 3B, 3C, 4A, 4B 4C, 5A, 5B, 5C, 6A, 6B Economizers on all cooling systems 65,000 BTU/h a Note a: The total capacity of all systems without economizers shall not exceed 480,000 Btu/hr, or 20% of its economizer capacity, whichever is greater

TABLE 503.3.1(2) EQUIPMENT EFFICIENCY PERFORMANCE EXCEPTION FOR ECONOMIZERS CLIMATE ZONES COOLING EQUIPMENT PERFORMANCE IMPROVEMENT (EER OR IPLV) 3B 15% Efficiency Improvement 4B 20% Efficiency Improvement

Hydronic system controls 503.3.2 Heat and chilled water to comfort conditioning systems At least 300,000 Btu/h design output Comply with complex system 503.4.3

COMPLEX HVAC SYSTEMS AND EQUIPMENT 503.4 (Prescriptive) Systems not simple as defined in Section 503.3 Typically multiple zones

Some types of equipment heating/cooling or both Gas - or oil-fired heaters storage greater than 140 gallons / Packaged VAV reheat / Built-up VAV reheat / Built-up single fan dual-duct VAV / Built-up or packaged dual-fan dual-duct VAV / Four pipe fan coil with central plant / Hydronic heat pump with central plant / Other multiple zone or package systems / Any combination of different simple systems such as hydronic heating and unitary packaged cooling

Economizers 503.4.1 Comply with Table 503.3.1(1) Cooling systems Capable of 100% outside air with additional cooling

Except: 1. Systems utilizing water economizers that are capable of cooling supply air by direct or indirect evaporation or both and providing 100 percent of the expected system cooling load at outside air temperatures of 50 F (10 C) dry bulb/45 F (7 C) wet bulb and below. Exceptions 2 and 3 do not apply to North Carolina since they reference Table 503.3.1(2) which lists zones that don t exist in North Carolina.

Water Economizer A system by which the supply air of a cooling system is cooled indirectly with water that is itself cooled by heat or mass transfer to the environment, without the use of mechanical cooling

Variable air volume (VAV) fan control 503.4.2 Individual fans with motors greater than 10 horsepower shall be: 1. Driven by a mechanical or electric variable speed drive Or 2. Fan motor shall have controls or devices that result in fan motor demand of No more than 30% of design wattage At 50% of air flow when static pressure setpoint equals 1/3 of total design static pressure Based on manufacturer s fan data Direct digital control

Hydronic system controls 503.4.3 Heating of fluids previously mechanically cooled and the cooling of fluids previously mechanically heated shall be limited in accordance with sections 503.4.3.1 through 503.4.3.3 Multiple packaged boilers require sequencing controls Hydronic heating systems comprised of a single boiler and greater than 500,000 Btu/h input design capacity shall include either a multistaged or modulating burner.

503.4.3.1 Three pipe systems prohibited Common return line for hot or chilled water 503.4.3.2 Two-pipe changeover system Common pipe for heated and chilled water Dead band of 15 F outside air temperature 4 hour operation before changeover Maximum 30 o F temperature difference at changeover

Hydronic (water loop) heat pump systems 503.4.3.3 Shall comply with sections: - 503.4.3.1: Temperature dead band - 503.4.3.2: Heat rejection - 503.4.3.3: Two position valve

Temperature dead band 503.4.3.3.1 - Hydronic heat pumps connected to a common heat pump water loop with central devices for - Heat rejection (cooling) and - Heat addition (heating) - Shall have controls capable of 20 o F dead band between initiation of heat rejection and heat addition by the central devices Except when loop temperature optimization controller is installed Heat rejection equipment 503.4.3.3.2 Must comply with 503.4.3.3.2.1 and 503.4.3.3.2.2 Exception: Where heat pump system will reject heat throughout the year

503.4.3.3.2.1 Climate zones 3 and 4 Closed circuit cooling tower used directly in the heat pump loop automatic bypass or low leakage damper shall be provided Open-circuit cooling tower used directly in the heat pump loop automatic valve bypassing all heat pump water around the tower shall be installed Open or closed circuit cooling tower used in conjunction with separate heat exchanger to isolate cooling tower from heat pump loop, then heat loss shall be controlled by shutting down the circulation pump on the cooling tower loop

503.4.3.3.2.2 Climate zones 5 through 8 If open or closed circuit cooling tower is used, then separate heat exchanger to isolate cooling tower from heat pump loop and heat loss controlled By shutting down the circulation pump on cooling tower loop to provide an automatic valve to stop the flow of fluid

Two position valve 503.4.3.3.3 Each hydronic heat pump on the hydronic system with total pump power exceeding 10 horsepower shall have a two-position valve

Part load controls 503.4.3.4 Hydronic heating systems 300,000 Btu/h output design capacity supplying heated or chilled water to comfort conditioning systems shall include controls capable of: 1. Automatically reset the supply hot water temperatures using zone-return water temperature, building-return water temperature, or outside air temperature as an indicator of building heating or cooling demand. The temperature shall be capable of being reset by at least 25 percent of the design supply-to-return water temperature difference; or 2. Reduce system pump flow by at least 50 percent of design flow rate utilizing adjustable speed drive(s) on pump(s), or multiple-staged pumps where at least one-half of the total pump horsepower is capable of being automatically turned off or control valves designed to modulate or step down, and close, as a function of load, or other approved means.

Pump isolation 503.4.3.5 Chilled water plants including more than one chiller shall have capability to reduce flow automatically through the chiller plant when a chiller is shut down Chillers piped in series for the purpose of increased temperature differential shall be considered as one chiller Boiler plants including more than one boiler shall have the capability to reduce flow automatically through the boiler plant when a boiler is shut down

Heat rejection equipment fan speed control 503.4.4 Each fan powered by a motor 7.5 horsepower or greater Shall be able to operate at 2/3 of full speed or less and shall have Controls to automatically change fan speed to control leaving water temperature or condensing temperature/pressure of the heat rejection device Exception: Factory-installed heat rejection devices within HVAC equipment tested and rated in accordance with Tables 503.2.3(6) and 503.2.3(7).

Requirements for complex mechanical equipment serving multiple zones 503.4.5 Multiple zones with supply air shall be VAV systems Shall include: 503.4.5.1 Single duct variable air volume (VAV) systems 503.4.5.2 Dual duct and mixing VAV systems 503.4.5.3 Single fan dual duct and mixing VAV systems

During periods of occupancy VAV systems shall be capable to reduce primary air supply to a zone to one of the following before reheating, recooling or mixing takes place 1. 30% of maximum air supply to each zone 2. 300 cfm or less where max rate is less than 10% of total fan system supply air flow 3. Minimum ventilation requirements of Chapter 4 of the NC Mechanical Code

6 exceptions to VAV control requirements 1. Zones where special pressurization relationships or cross-contamination requirements are such that VAV systems are impractical. 2. Zones or supply air systems where at least 75 percent of the energy for reheating or for providing warm air in mixing systems is provided from a site-recovered or site-solar energy source. 3. Zones where special humidity levels are required to satisfy process needs. 4. Zones with a peak supply air quantity of 300 cfm (142 L/s) or less and where the flow rate is less than 10 percent of the total fan system supply airflow rate. 5. Zones where the volume of air to be reheated, recooled or mixed is no greater than the volume of outside air required to meet the minimum ventilation requirements of Chapter 4 of the International Mechanical Code. 6. Zones or supply air systems with thermostatic and humidistatic controls capable of operating in sequence the supply of heating and cooling energy to the zone(s) and which are capable of preventing reheating, recooling, mixing or simultaneous supply of air that has been previously cooled, either mechanically or through the use of economizer systems, and air that has been previously mechanically heated.

Single duct variable air volume (VAV) systems 503.4.5.1 Shall use terminal device to reduce primary supply before reheating or recooling Dual duct and mixing VAV systems, terminal devices 503.4.5.2 Systems having one warm air duct and one cool air duct shall use terminal device able to reduce flow to a minimum before mixing

Single fan dual duct and mixing VAV system, economizers 503.4.5.3 Individual dual duct or mixing heating and cooling systems with single fan with total capacity greater than 90,000 Btu/h shall not be equipped with air economizers

Supply-air temperature reset controls 503.4.5.4 Multiple zone HVAC controls shall include controls that automatically reset the supply temperature in response to representative building loads, or to outside air temperature The controls shall be capable of resetting the supply-air temperature at least 25% of difference between the design supply air temperature and the design room temperature Except 1. Systems that prevent reheating, recooling or mixing of heated and cooled supply air. 2. Seventy five percent of the energy for reheating is from site-recovered or site solar energy sources. 3. Zones with peak supply air quantities of 300 cfm (142 L/s) or less.

Heat recovery for service water heating 503.4.6 Condenser heat recovery shall be installed for heating or reheating of service hot water given: Required when facility operates 24 hours a day and Water cooled systems exceed 6,000,000 Btu/hr of heat rejection and Water heating loads exceed 1,000,000 Btu/hr

The required heat recovery system shall have the capacity to provide the smaller of: 1. 60% of peak heat rejection at design conditions OR 2. The preheating required to raise the peak service hot water draw to 85 F Exceptions 1. Facilities that employ condenser heat recovery for space heating or reheat purposes with a heat recovery design exceeding 30 percent of the peak water-cooled condenser load at design conditions. 2. Facilities that provide 60 percent of their service water heating from site solar or site recovered energy or from other sources.

Hot gas by pass limitations 503.4.7 Cooling systems shall not use hot gas by pass or other evaporator pressure control systems unless the system is designed with multiple steps of unloading or continuous capacity modulations Maximum bypass capacities per Table 503.4.7 RATED CAPACITY Table 503.4.7 MAXIMUM HOT GAS BYPASS CAPACITY 20 nominal tons (240 kbtu/h) > 20 nominal tons (240 kbtu/h) MAXIMUM HOT GAS BYPASS CAPACITY (% of total capacity) 50% 25% Exception: Unitary packaged systems with nominal cooling capacities of 7.5 tons or less (approximately 90 kbtu/h or 26.4 kw)

504.7 Pools and Inground Permanently Installed Spas Readily accessible on-off switch outside of heater located in plain sight Gas fired, no constant burning pilot light

Time switches or other control method are required to be capable of turning off heaters and pumps Heaters, motors and pumps that have built in timers are considered in compliance Except 1) Public health requires 24-hour operation 2) Required to operate solar and waste heat recovery

Covers Required on heated pools and permanently installed inground spas Vapor-retardant cover Except More than 70% of energy for heating from solar or heat recovery equipment computed over an operating season

ADDITIONAL PRESCRIPTIVE COMPLIANCE REQUIREMENTS 506 Indicate the choice on the construction documents Comply with one of the following:

Comply with one of the following: a. 506.2.1 More efficient mechanical equipment b. 506.2.2 Reduced lighting power density c. 506.2.3 Energy recovery ventilation systems d. 506.2.4 Higher efficiency service water heating e. 506.2.5 On-site supply of renewable energy f. 506.2.6 Automatic daylighting control systems

506.2.1 More efficient mechanical equipment The mechanical equipment would have to comply with the higher efficiency rating in the Tables This is in addition to the requirements in section 503 Tables 506.2.1(1), 506.2.1(2), 506.2.1(3), 506.2.1(4), 506.2.1(5), 506.2.1(6) and 506.2.1(7) These table are used similar to the Table in section 503

506.2.3 Energy recovery ventilation systems Buildings using 500 cfm or more outdoor air shall have heat or energy recovery ventilation systems for at least 80 percent of ventilation air The recovery system shall provide a change in the enthalpy of the outdoor air supply of 50 percent or more of the difference between the outdoor air and return air at design conditions Provision shall be made to bypass or control the energy recovery system to permit cooling with outdoor air where cooling with outdoor air is required

506.2.5 On-site supply of renewable energy On-site renewable energy source for 3% or more of the total building energy load On-site power generation using a non-renewable source cannot be used to satisfy this requirement The jurisdiction shall be provided with an energy analysis as described in Section 506 that documents the renewable energy contribution to the building or a calculation demonstrating that the on-site supply of renewable energy: 1) is capable of providing at least 3% of the total energy load of the building, or 2) provides on-site renewable energy generation with a nominal (peak) rating of 175 BTU's or 0.50 watts per square foot of building.

TOTAL BUILDING PERFORMANCE SECTION 507 The Total Building Performance method is used to determine compliance The following shall be included: Heating systems, cooling systems, service water heating, fan systems, lighting power, receptacle loads, process loads Use of this method will require a registered design professional

Compliance with the following sections is mandatory 502.4 Air leakage 503.2 Provisions to all mechanical systems 504.2 Service water heating 504.3 Temperature controls 504.4 Heat traps 504.5 Pipe insulation 504.6 Hot water systems 504.7 Pools and permanent in-ground spas

Compliance with the following sections is mandatory (continued) 505.1 General 505.2 Lighting controls 505.3 Tandem wiring 505.4 Exit signs 505.5 Interior lighting power 505.6 Exterior lighting 505.7 Electrical energy consumption

Analysis procedure Determine annual energy costs for a proposed design as compared to a standard design; energy prices determined from an approved source, such as the US Department of Energy 8,760 hours per year in calculation Use local energy costs On-site non-depletable energy omitted from costs for proposed design

Documentation 507.4 Compliance report 507.4.1 Shows annual energy cost for proposed design is less than the standard reference design energy cost Include: - Address of building - Provide inspection checklist and details of component construction as listed in Table 507.5.1(1) - Name of person completing report - Name and version of software compliance tool - Annual energy cost for the proposed design and the standard reference design

Additional documentation 507.4.2 The Code Official shall be permitted to require the following documents: Building component characteristics Floor plans showing thermal zones for proposed and reference designs Input and output reports showing energy totals Explanation of error warning totals Explanation of error warning messages Certificate signed by the builder showing component characteristics of the proposed design Proposed design per Table 507.5.1(1)

507.5 Calculation procedure 507.5.1 Building specifications Show reference and proposed design - use the same method as specified by Table 507.5.1(1) 507.5.2 Thermal blocks Show reference design and proposed design -use the same thermal blocks as required in Section 507.5.1.1, 507.2.2 or 507.5.2.3. Tables 507.5.1(1), 507.5.1(2), 507.5.13), 507.5.1(4), 507.5.1(5) define the requirements for configuring and analyzing building models

HVAC zones designed 507.5.2.1 Each HVAC zone shall be modeled as a separate thermal block Exceptions: Different HVAC zones shall be combined to create a single thermal block provided: 1. Space use classification the same 2. Glazing facing the same orientation or within 45 degrees of each other 3. All zones served by the same HVAC system or same type of HVAC system

HVAC zones not designed 507.5.2.2 Thermal blocks defined on similar internal loads The following guidelines shall be used in the definition of the thermal blocks - Interior blocks more than 15 feet from exterior wall - Exterior blocks closer than 15 feet from exterior wall - Separate zone for each orientation - Separate blocks for ground floor or exposed to ambient conditions - Separate blocks with exterior ceilings or roofs from other floors

Multifamily residential buildings 507.5.2.3 One thermal block per unit unless similar orientation Corner units and units with roof or floor loads shall only be combined with units sharing these features

Calculation software tools 507.6 1. Computer generation of the standard reference design using only the input for the proposed design and not allow the user to directly modify the building component 2. Building operation for a full calendar year (8,760 hours) 3. Climate data for a full calendar year (8,760 hours) 4. Ten or more thermal zones 5. Thermal mass effects 6. Hourly variations in occupancy, illumination, receptacle loads, thermostat settings, mechanical ventilation, HVAC equipment availability, service hot water usage and any process loads 7. Part-load performance curves for mechanical equipment. 8. Capacity and efficiency correction curves for mechanical heating and cooling equipment 9. Printed code official inspection checklist listing each of the proposed design component characteristics from Table 507.5.1(1) determined by the analysis to provide compliance

507.6.1 Specific approval Performance analysis tools meeting the applicable sub-sections of Section 507 and tested according to ASHRAE Standard 140 shall be permitted to be approved.

507.6.2 Input Values Input values not specified from sections 502, 503, 504, and 505 shall be taken from an approved source

ASHRAE 90.1 2007 edition: Energy Standard for Buildings Except Low-rise Residential Buildings Designer choice Required by code: If more than 30% fenestrations Fenestration 30% or less above grade: designer choice Follow Appendix G Requires registered design professional

Provide additional energy conservation requirements Performance rating method Mandatory sections 5.4 Building Envelope 6.4 Heating, Ventilating, and Air Conditioning Systems 7.4 Service Water Heating 8.4 Voltage Drop 9.4 Lighting Systems 10.4 Electric Motors

Performance calculations Programs which can be used DOE-2, BLAST, EnergyPlus Create a proposed and baseline design Both use same weather data and energy rates Baseline calculations per Table G3.1

North Carolina COMcheck

North Carolina COMcheck

Mechanical Plan Review Objectives Method of Compliance HVAC Systems Ductwork Special Requirements Efficiency Ratings Documentation

Appendix B: 2012 Building Code Summary for All Commercial Projects

PROPERTIES On passing, 'Finish' button: On failing, 'Finish' button: Allow user to leave quiz: User may view slides after quiz: Goes to Next Slide Goes to Next Slide After user has completed quiz At any time

Questions This concludes Module 7: Commercial Mechanical All questions should be directed to the staff of the NC Department of Insurance, Engineering Division, Code Services Section. The primary contact for energy code questions is the Chief Energy Code Consultant: Mr. Dan Dittman, email: dan.dittman@ncdoi.gov