TRS21 IGNITION PROOF SERIES

Similar documents
TRS21 IGNITION PROOF SERIES

OWNER S MANUAL (English)

OWNER S MANUAL (English)

Oilless Refrigerant Recovery System. OWNER S MANUAL (English) TO BE OPERATED BY QUALIFIED PERSONNEL ONLY

OWNER S MANUAL (English)

Pro-Set TRA21 SERIES Mobile Multiple Refrigerant Recovery / Recycle System

Refrigerant Recovery Machine. Model No Operating Manual

RECOVERY EQUIPMENT RECOVER REFRIGERANTS QUICKLY & EFFICIENTLY

Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

R100 Oil-Less Refrigerant Recovery Unit

RecoverX-CAR Contaminated Automotive Refrigerant Recovery System Operation and Maintenance Manual

OPERATION & MAINTENANCE MANUAL TX600

PRO-SET AR2700 & AR2700M SERIES REFRIGERANT RECOVERY / RECYCLING SYSTEM

High Performance Oilless Residential Light Commercial. Product Leadership Training Service Reliability

OPERATION & MAINTENANCE MANUAL RHS680

OPERATING INSTRUCTIONS

Enspeco RMS. The Enspeco Refrigerant Management. The following instructions will INSTRUCTIONS

OPERATING INSTRUCTIONS

OPER LV Wheeler Way

OPERATION & MAINTENANCE MANUAL AC860

Caresaver Universal Refrigerant Recovery Unit

Additional users operating manual

Owner s Manual. Model AC375C Refrigerant Recovery, Recycle, and Recharge Unit

OPERATION & MAINTENANCE MANUAL TC670

Model K / K. Modelo K / K. Modèle K / K. Operating Manual

REFRIGERANT RECOVERY SYSTEMS

NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL

REFRIGERANT SYSTEM SERVICE WARNINGS

ENSPECO Recovery/ Recycle/ Evacuate/ Recharge

CONVERT-ABLE FA1234 REFRIGERANT RECOVER / RECYCLE / EVACUATION AND RECHARGE UNIT

OPERATING INSTRUCTIONS

Leak-Seeker I Refrigerant Leak Detector

OWNER S MANUAL (English)

User manual Flushing device VAS 6337/1a

OPERATION & MAINTENANCE MANUAL AC880

Refrigerant Recovery Unit, Model RRU134

Digital Refrigerant System Analyzer. MAXMIN Psi kpa Bar MPa C F R TIME P T UNITS

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC.

SERVICE PROCEDURE FOR RETROFITTED A/C SYSTEMS

14. The center port of the manifold is used for evacuation, charging and refrigerant recovery.

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

Operating Instructions

Operation Manual... 1 Manuel d utilisation Manual de Operación.. 60

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

DiscovR R134a Refrigerant Identifier

Operating Manual. Model 34700Z / 17700Z Recovery, Recycling, Recharging Unit

ariazone 601HD Refrigerant Recovery & Recycling Unit User's manual

Operating Manual, Model K/348012K Recovery/Recycling/Recharging Unit For R-12 and R-134a Refrigerants...1

99 Washington Street Melrose, MA Phone Toll Free Visit us at

RECOVERY/RECYCLE/RECHARGE

347002K/177002K/34900

OPERATING MANUAL. Model 34134Z. Refrigerant Unit Recover, Recycle, and Recharge

INDUSTRIAL - SOLVENT PARTS CLEANER CM200 (115V OR 230V PUMP)

RECOVERY/RECYCLE/RECHARGE

INSTALLATION INSTRUCTIONS

Original Instructions Instucciones originales Consignes originales. Model: AC R-1234yf A/C Recover, Recycle, Recharge Machine

USING R-134A REFRIGERANT

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

Ariazone 5001 HFO-1234yf

Operating Manual. Series 12134B Recovery/Recycling/Recharging Unit for R-12 and R-134a

Operating Manual Manual de Operación Manuel d utilisation

CC Series VACUUM PUMPS

Residential Piping and Long Line Guideline

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

Ariazone 601HD Refrigerant Recovery&Recycling unit

OPERATION MANUAL. FOR REFRIGERANT RECOVERY. DANGER Explosion Hazard. Do NOT use with hydrocarbons. See page 4.

HEATING AND AIR CONDITIONING

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

F-2000MLF(-C) F-2000MWF(-C) F-2000MRF(-C) F-2000MRF3(-C)

Model AC Original Instructions. Recover, Recycle, Recharge Machine for R1234yf A/C Systems

CMEP-OL. Oil less Explosion proof Recovery Pump. Operating Manual. Nanjing Wonfulay Precison Machinery Co.,Ltd

Model Operating Manual for. Recovery, Recycling, Recharging Unit P E R A T I N G A N U A L

Harold Ag & Mobile Products

MODEL A5-2 SOLVENT & WATER RECOVERY SYSTEMS (EXPLOSION PROOF UNITS)

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

S150 S300 CONSTRUCTION HEATERS. Rev: August 15, 2008 SERVICE AND MAINTENANCE MANUAL No PLEASE RETAIN FOR FUTURE REFERENCE PRODUCTS

YELLOW JACKET Recovery Machines for every refrigerant, every size system

RECOVERY/RECYCLE/RECHARGE

Refrigerant changeover guidelines

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!

MASS. MARITIME ACADEMY

Owner s Manual. FMI BRANDS INC Avenue Surrey, B.C. Canada V3Z 3V7 Toll Free Fax Model number FMPPC2F

AC 1 AIR CONDITIONING SYSTEM

Hoshizaki America, Inc.

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

ProVaxTM EUPOPEAN & AUSTRALIAN OPERATING MANUAL

Model Operating Manual for. Recovery, Recycling, Recharging Unit P E R A T I N G A N U A L

CBO-750 HYBRID-R OVEN Instructions Manual

OPERATING AND INSTALLATION MANUAL

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Setup and Operation Manual

Operating Manual for. Model Recovery, Recycling, Recharging Unit

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

Hybrid Conversion Kit Procedure Guide

Transcription:

TRS21 IGNITION PROOF SERIES 2 Cylinder Commercial Recovery Machine OWNER S MANUAL (English) Français, Español, Deutsch and latest updates: www.cpsproducts.com Series: TRS21, TRS21C, TRS21S Evaluated for performance in accordance with Sec. 608 of the Clean Air Act (Feb 29, 1996) using AHRI-740-98 test methods. TO BE OPERATED BY QUALIFIED PERSONNEL ONLY WARNING: THIS UNIT IS NOT RATED FOR USE IN EXPLOSIVE ENVIROMENTS. IT IS DESIGN TO RECOVER CLASS A1, A2 AND A3 REFRIGERANTS IN NORMAL OR STANDARD ENVIROMENTS. THIS EQUIPMENT HAS BEEN VERIFIED BY UNDERWRITERS LABORATORIES INC. TO MEET EPA S MINIMUM REQUIREMENTS FOR RECOVERY EQUIPMENT INTENDED FOR USE WITH ALL SYSTEMS CONTAINING REFRIGERANTS FROM ARI740-98 CATEGORIES III, IV, AND V. UL CONTROL NUMBER 2HA5.

Contents Key Features... 2 General Safety Instructions...2-3 Additional Safety Instructions... 3 Specifications... 4 Unit Layout... 4 KEY FEATURES Direct Vapor or Liquid Recovery...4-5 High Speed Direct Liquid Recovery... 6 Push - Pull Liquid Recovery... 7 Routine Maintenance... 8 Warranty... 8 Designed and tested to meet ANSI 12:12.01 Ignition Proof standards For use on refrigeration systems utilizing Class A1 (nontoxic, nonflammable), Class A2L (nontoxic, low flammability), Class A2 (nontoxic, flammable), and Class A3 (nontoxic, flammable) Maintenance free oil-less compressor Permanently lubricated and sealed main bearings Improved piston seal design for less leakage and deeper vacuums 550 Psig high pressure cutoff switch with LED indicator Cleanable 100 mesh inlet filter Fastest recovery rates in its class Ignition proof ON-OFF switch Sealed start relay Hard wired 9.8 ft. (3 m) power cord Other patents pending General Safety Instructions Please read, follow and understand the contents of this entire manual, with special attention given to Danger, Warning and Caution statements. FOR USE BY PROFESSIONALLY TRAINED AND CERTIFIED OPERATORS ONLY. Most states, countries, etc., may require user to be licensed. Please check with your local government agency. DANGER: DANGER: DANGER: The recovery tank used with this contains liquid refrigerant. Overfilling recovery tank may cause a violent rupture resulting in severe injury or even death. As a minimum, please use a scale to continuously monitor recovery tank weight. EXPLOSION RISK! This unit is not certified as explosion proof for explosive rated environments. It is only to be used in normal environments. ELECTRICAL SHOCK HAZARD: Always disconnect power source when servicing this equipment. WARNING: Do not use equipment in the vicinity of spilled or open containers of gasoline or other flammable substances. WARNING: All hoses may contain liquid refrigerant under pressure. Contact with refrigerant may cause frostbite or other related injuries. Wear proper personal protective equipment such as safety goggles and gloves. When disconnecting any hose, please use extreme caution. WARNING: TO REDUCE RISK OF FIRE: Avoid use of an extension cord because extension cord may overheat. If you must use an extension cord, use 10 awg minimum. WARNING: Avoid breathing refrigerant vapors and lubricant vapor or mist. Breathing high concentration levels may cause heart arrhythmia, loss of consciousness, or even cause suffocation. Exposure may irritate eyes, nose, throat and skin. Please read manufacturer s Material Safety Data Sheet for further safety information on refrigerants and lubricants. WARNING: Make certain all safety devices are functioning properly before operating equipment. CAUTION: To avoid cross contamination of refrigerant and potential leakage to the atmosphere, 2

General Safety Instructions CAUTION: CAUTION: proper hoses and fittings should be used and checked for damage. To avoid overfilling refrigerant tank, read and follow manufacturer s recommended filling instructions for refrigerant being recovered. This equipment is intended for use of one refrigerant at a time. Mixing of different refrigerants will cause your recovered supply of refrigerant to become contaminated. Note: It is very expensive to destroy mixed or damaged refrigerants. ADDITIONAL SAFETY INSTRUCTIONS FOR REFRIGERATION SYSTEMS CONTAINING CLASS A2, A2L & A3 REFRIGERANTS The following are additional safety recommendations when servicing refrigeration equipment that contain Class A2L, A2 or A3 refrigerants. These instructions do not replace existing occupational hazard procedures or other regulations that may be required by local,state or federal agencies. Technicians working on Class A2L, A2 and A3 systems should have detailed knowledge of and skills in handling flammable refrigerants, personal protective equipment, refrigerant leakage prevention,handling of cylinders, charging, leak detection and proper disposal. Additional knowledge of legislation, regulations and standards relating to flammable refrigerants may also be required. Special Certification or licensing may be required on Class A2L, A2, and A3 and refrigerant handling. Check your local occupational safety codes. The area of service should be marked as Temporary Flammable Zone. This will be 3 meter perimeter around the refrigeration equipment being serviced and should have no smoking and other hazardous signs posted. Local supervisor should be notified of the zone s existence. A flammable gas detector should be used to monitor air in the Temporary Flammable Zone. A dry powder or C02 fire extinguisher must be available at service location. A suitable ventilation fan should be used to maintain in the work space at a minimum of 5 air changeovers per hour. Ensure the refrigeration equipment s power has been discontinued. All potential ignition sources within Temporary Flammable Zone must be disabled. When connecting service equipment (such as vacuum pumps, scales, recovery units) to a power source, the connection must be made outside the Temporary Hazardous Zone. A ground strap must be used between the TRS21 motor frame and the recovery tank brass fitting. The ground strap must go on bare metal surface to ensure continuity and discharge of static electrical charges. Do not pull system into a vacuum. Stop recovery process at 0 PSIG. This is to prevent accidental ingestion of air into the recovery tank. Once recovery process of a Class A2L, A2 or A3 system is complete, system should be purged with 100% Nitrogen. Do not use Air. DANGER-EXPLOSION RISK: Do not mix Class A2L, A2 or A3 refrigerants with air. All precautions must be taken to eliminate mixing of air with flammable refrigerants,including monitoring Recovery Cylinder for air content. 3

Specifications Model # TRS21 TRS21C TRS21S Voltage (Hz) 115V 60Hz 230 V 50 Hz 1PH Motor Size 2/3 HP Motor Thermally Protected Yes Compressor Type 2 Cylinder Oilless Reciprocating Compressor Power Consumption 1000 W High Pressure Shut-Off 550 psig (Auto Reset) 450 psig (Auto Reset) 550 psig (Auto Reset) ARI740 CLASS III R-12, R-134A, R-401C, R-406A, R-500 ARI740 CLASS IV R-1234YF, R-22, R-401A/B, R-402B, R-407C/D/E/F, R-408A, R-409A, R-411A/B, R-412A, R-502, R-509A ARI 740 CLASS V R-32A, R-402A, R-404A, R-407A/B, R-410A/B, R-507A ASHRAE/ISO Class A2, A2L and A3 R-1234yf, R32, R290, R600, R601, R1276 Operating Temperature Range 32 F to 120 F (0 C -49 C) Power Cord Length 9.8 ft. (3 m) Dimensions 6" x 12" x 9" (15cm x 30cm x 23cm) Weight 24.3 lbs (11 kg) Approvals *UL, CSA Warranty (Years) 1 s *Verified UL Flow Rate @ 60Hz (Reduce 15% for all 50Hz models) Direct Vapor Direct Liquid Push - Pull Liquid High Temp Vapor Rate R410a.70 lb/min (0.32 kg/min) 11.94 lb/min (5.41 kg/min) 31.7 lb/min (14.3 kg/min) n/a R22.59 lb/min (0.27 kg/min) 8.86 lb/min (4.02 kg/min) 31.52 lb/min (14.3 kg/min) 0.39 lb/min (17 kg/min) R134a.49 lb/min (0.22 kg/min) 7.8 lb/min (3.54 kg/min) 25.66 lb/min (11.64 kg/min) n/a R407c.53 lb/min (0.24 kg/min) 9.50 lb/min (4.31 kg/min) 29.14 lb/min (13.22 kg/min) n/a *Evaluated for performance in accordance with Sec. 608 of the Clean Air Act (Feb 29, 1996) using AHRI-740-98 test methods. TRS21 SERIES Unit Layout Discharge port Hard Wired Power Cord Ignition Proof Switch Inlet port with filter Air Intake Louver Direct Vapor or Liquid Recovery IMPORTANT! If recovering Class A2, A2L, or A3 refrigerants, read ADDITIONAL SAFETY INSTRUCTIONS ON PAGE 3 OF THIS MANUAL. A. Use shortest length 1/4 (Inside Diameter) Refrigeration Hose on Suction Side of Recovery Unit. B. Use an evacuated DOT Tank (90lb or larger, and rated for 550 PSI/38 Bar). C. If refrigerant is clean, remove all suction side filters, screens, etc. D. Remove all Schrader type valve cores and any valve depressors from hoses and service valves. E. If Recovery Unit trips OFF on HIGH Pressure, change recovery cylinder. F. When recovering large amounts of R410A, or if Recovering under very high ambient temperatures, we suggest using the CPS MT69 (Molecular Transformator) which will increase the recovery speed. 4

Direct Vapor or Liquid Recovery CONNECT RECOVERY UNIT (See Diagram 1) Use a Manifold (with sight glass) and two spare hoses. Connect Ground Strap between Recovery Unit and Recovery Tank (to prevent static electricity build up). 1. Use a refrigerant manifold (with sight glass) and one spare hose. 2. Connect Manifold between A/C or Refrigeration Unit being serviced and Recovery Unit IN port. 3. Connect Hose from Recovery unit OUT port to evacuated DOT Recovery Tank VAPOR Valve. 4. OPEN VAPOR Valve on DOT Recovery Tank. 5. Keep Manifold Valves CLOSED at this time. 6. On Recovery Unit, set Main Power Switch to ON. 7. When Recovery Unit starts, OPEN both HIGH & LOW Manifold Valves to start refrigerant recovery flow. Note: Recovery Unit is designed to directly recover large amounts of liquid refrigerant. During Vapor Recovery, if compressor makes slugging or hammering noise, meter incoming liquid refrigerant by closing LOW Side Manifold Valve until noise subsides. 8. Recovery Unit will run continuously. When desired vacuum level is observed on LOW Side Manifold Gauge, close both LOW & HIGH Side Manifold Valves. CAUTION: For Class A2, A2L and A3 recovery, Recovery Unit must be turned off when 0 Psig to prevent possible ingestion of air during recovery process. 9. If Pressure on HIGH Side Manifold Gauge starts to rise, repeat steps 6-8. 10. If HIGH Side Manifold Gauge remains in a vacuum, close all tank, manifold and hose valves. 11. Remove discharge hose from Recovery Unit OUT Port. Recovery and Self-Clearing are now complete. Diagram 1 - Direct Vapor Or Liquid Recovery Manifold Set Optional Tank Overfill Sensor Cord VAPOR LIQUID TRS21 Recovery Recovery Unit Unit From From outlet OUT port Port of recovery To Tank Vapor unit to recovery Valve tank From A/C System Being being serviced Serviced IN To inlet IN Port port Onof Recovery recovery Unit unit OUT Ground Strap* Optional Tank tank Overfill overfill switch Switch DOT Recovery Tank * Must be bare metal to bare metal contact. High Capacity Charging Scale 5

High Speed Direct Liquid Recovery IMPORTANT! If recovering Class A2, A2L, or A3 refrigerants, read ADDITIONAL SAFETY INSTRUCTIONS ON PAGE 3 OF THIS MANUAL. TO MINIMIZE RECOVERY TIME: A. Use shortest length 1/4 (Inside Diameter) Refrigeration Hose on Suction Side of Recovery Unit. B. Use an evacuated DOT Tank (90lb or larger, and rated for 550 PSI/38 Bar). C. If refrigerant is clean, remove all suction side filters, screens, etc. D. Remove all Schrader type valve cores and any valve depressors from hoses and service valves. CONNECT RECOVERY UNIT (See Diagram 2) Use a Manifold (with sight glass) and two spare hoses. Connect Ground Strap between Recovery Unit and Recovery Tank (to prevent static electricity build up). 1. Connect Manifold between A/C or Refrigeration unit being serviced and Recovery Unit IN port. 2. Connect Hose from Recovery Unit OUT port to evacuated DOT Recovery Tank LIQUID Valve. 3. Connect another Hose from DOT Tank Vapor Port to Vapor Port of unit being serviced. 4. OPEN both Vapor and Liquid valves on DOT Recovery Tank. 5. Keep Manifold Valves CLOSED at this time. 6. On Recovery Unit, set Main Power Switch to ON. 7. Once Recovery Unit has started, OPEN LOW Side Manifold Valve to start liquid refrigerant flow to Recovery Unit. Monitor liquid refrigerant flow in Manifold Sight Glass. Note: Recovery Unit is designed to directly recover large amounts of liquid refrigerant. During Vapor Recovery, if compressor makes slugging or hammering noise, meter incoming liquid refrigerant by closing LOW Side Manifold Valve until noise subsides. 8. Once liquid refrigerant is no longer present in Manifold Sight Glass, CLOSE DOT Recovery Tank Vapor Valve. This will transition Recovery Unit into Direct Vapor Recovery. 9. Let Recovery Unit run continuously. When desired vacuum level is observed on Low Side Manifold Gauge, close both LOW & HIGH side Manifold Valves. CAUTION: For Class A2, A2L and A3 recovery, Recovery Unit must be turned OFF when 0 Psig to prevent possible ingestion of air during recovery process. 10. If pressure on LOW Side Manifold Gauge starts to rise, open LOW Side Manifold Valve and restart Recovery Unit. If LOW side manifold gauge remains in a vacuum, close all tank, manifold and hose valves. 11. Remove discharge hose from Recovery Unit OUT Port. Recovery and Self-Clearing are now complete. A/C System Being Serviced Diagram 2 - High Speed Direct Liquid Recovery Manifold Set Optional Tank Overfill Sensor Cord From OUT Port To Tank Liquid Valve VAPOR LIQUID A/C System being serviced IN IN OUT Recovery Unit Ground Strap* Optional Tank Overfill Switch DOT Recovery Tank 6 Hose From Dot Recovery Tank Vapor Port To A/C System Vapor Port * Must be bare metal to bare metal contact. High Capacity Charging Scale

Push-Pull Liquid Recovery IMPORTANT! If recovering Class A2, A2L, or A3 refrigerants, read ADDITIONAL SAFETY INSTRUCTIONS ON PAGE 3 OF THIS MANUAL. TO MINIMIZE RECOVERY TIME: A. Use shortest length 3/8 (Inside Diameter) Refrigeration Hose on Suction Side of Recovery Unit to Vapor Port on Tank. B. Use 3/8 (Inside Diameter) Hoses from system Liquid Service Valve to LIQUID Port on Recovery Tank. C. Use an evacuated DOT Tank (90lb or larger, and rated for 550 PSI/38 Bar). D. If refrigerant is clean, remove all suction side filters, screens, etc. E. Remove all Schrader type valve cores and any valve depressors from hoses and service valves. CONNECT RECOVERY UNIT (See Diagram 3) Use a Manifold (with sight glass) and two spare hoses. Connect Ground Strap between Recovery Unit and Recovery Tank (to prevent static electricity build up) 1. Connect Manifold between Liquid Port on A/C or Refrigeration Unit being serviced and DOT Recovery Tank LIQUID Valve. 2. Connect Hose from Recovery Unit IN port to evacuated DOT Recovery Tank VAPOR Valve. 3. Connect another Hose from Recovery Unit OUT Port to VAPOR Port of unit being serviced. 4. CLOSE Manifold LOW Side Valve. 5. OPEN Manifold HIGH Side Valve. 6. OPEN LIQUID Valve on DOT Recovery Tank. 7. On Recovery Unit, set Main Power Switch to ON. 8. OPEN VAPOR Valve on DOT Recovery Tank. A Push-Pull Flow is now enabled. 9. MONITOR Charging Scale for DOT Recovery Tank Capacity. 10. MONITOR Sight Glass in manifold for presence of liquid refrigerant. 11. When liquid refrigerant no longer being pushed out of Refrigeration System being recovered, CLOSE Vapor Valve on DOT Recovery Tank. 12. Let Recovery Unit run for 30 seconds, then turn Recovery unit OFF. 13. Note: Push-Pull recovery does completely recover all refrigerant. Proceed to Direct Vapor Recovery (Page 5) to complete the recovery process. Diagram 3 - Push-Pull Liquid Recovery A/C System Being Serviced Optional Tank Overfill Sensor Cord From Tank Vapor Valve To IN Port Ground Strap* VAPOR LIQUID IN OUT Manifold Set To Tank Liquid Valve * Must be bare metal to bare metal contact. Recovery Unit From Liquid Port To Manifold Optional Tank Overfill Switch DOT Recovery Tank High Capacity Charging Scale 7

Routine Maintenance Filter Maintenance: The TRS21 is equipped with a 100-mesh screen filter. This filter should be checked periodically. A partially clogged filter will slow recovery rate. Check filter cartridge as follows: 1. Use a 5/8" socket or boxed end wrench to remove IN port as shown in Figure 1. 2. Remove suction port-filter cartridge as shown in Figure 2. 3. Clean cartridge or replace with new cartridge. (CPS #CRXF3) 4. Inspect O-ring. Re-lubricate with compressor oil or equivalent. 5. Place filter cartridge back into suction port fitting. 6. Hand tighten this assembly back onto TRS21. 7. Use 5/8" socket or boxed end wrench to tighten 1/8 of a turn. Do not over tighten; O-ring damage may occur. 8. Check connection for leaks. Piston Seal Maintenance: In cases of virgin refrigerant recovery, it is recommended to add.25 ounce of refrigerant oil to inlet port before each use. Figure 1 Figure 2 WARRANTY CPS Products, Inc. guarantees that all products are free of manufacturing and material defects to the original owner for one year from date of purchase. If equipment should fail during guarantee period it will be repaired or replaced (at our option) at no charge. This guarantee does not apply to equipment that has been altered, misused or solely in need of field service maintenance. All repaired equipment will carry an independent 90 day warranty. This repair policy does not include equipment that is determined to be beyond economical repair. WARRANTY DISCLAIMER: Use this device to recover only HVAC/R refrigerants from sealed HVAC/R systems. WARRANTY VOIDED IF USED FOR ANY OTHER PURPOSE. LOCATIONS CPS Products, Inc. U.S.A. (Headquarters) 1010 East 31st Street, Hialeah, Florida 33013, USA Tel: 305-687-4121, 1-800-277-3808 Fax: 305-687-3743 E-mail: info@cpsproducts.com Website: www.cpsproducts.com CPS Products Canada Ltd. 1324 Blundell Road Mississauga, ON, L4Y 1M5 Tel: 905.615.8620 Fax: 905.615.9745 E-mail: info@cpsproducts.com Website: www.cpsproducts.com CPS PRODUCTS N.V Krijgsbaan 241, 2070 Zwijndrecht, Belgium Tel: (323) 281 30 40 E-mail: info@cpsproducts.be CPS AUSTRALIA PTY. LTD. 109 Welland Avenue, Welland, South Australia 5007 Tel: +61 8 8340 7055, E-mail: sales@cpsaustralia.com.au For latest update to this owner's manual, go to www.cpsproducts.com #73-115 Rev. C 8