Manual call points. Sinteso / Cerberus PRO FDM225, FDM226

Similar documents
Manual call point. Sinteso Cerberus PRO FDM223H, FDM224H. 'Heavy Duty' manual call point addressed (FDnet/C-NET)

Multi line separator module

Input module, input/output modules

FDCL221-M Multi line separator module

Input module, input/output module

FDCIO223 (ES 45) Transponder

Output module (230 V)

FDS229-R / FDS229-A Alarm sounder with supplementary optical indication

FDF Sinteso Cerberus PRO Cerberus FIT. Flame detector. Flame detector addressed or collective, ASAtechnology TM

DBS721, DBS729 Sounder interbase, Sounder beacon interbase

DM1131 / DM1133 / DM1134 Manual call points

Mimic display driver, LED ribbon cable

DM1101 / DM1103 / DM1104 DM1103-L / DM1103-S Manual call points Manual release button and emergency stop button

FDCL221-Ex Line adapter (Ex)

ASA linear smoke detector

13 tones to choose from, 2 programmable alarm levels Adjustable sound levels up to 93 dba

Interbases. Sinteso FDSB221, FDSB228, FDSB229

OH720, OP720, HI720, HI722

SWING radio fire detection system

FDOOT221, FDO221, FDT221

FDOOT241-9, FDOOT241-A, FDO241, FDT241

OOH740, OOHC740. Cerberus PRO. Automatic fire detectors

FDBZ290 Air sampling smoke detection kit

FDBZ290 Air sampling smoke detection kit

FDOOT241-A3, FDOOT241-A4, FDOOT241-A5, FDOOT241-A9, FDOOT241-8

OOH740, OOHC740 Automatic fire detectors

Radio fire detection system

DC1154 / DC1154-AA / DC1156-AA / DC1157-AA Input / Output modules

DC1192 Input /Output module

FDOOT241-A9-Ex Multisensor fire detector

DF1101-Ex Infrared flame detector

OOH740-A9-Ex Multisensor fire detector

DM1153H-Ex / DM1154H-Ex Manual call point 'Heavy Duty'-Ex

FDCW221 / DOW1171 / SMF121 SMF6120 (repair/replacement) Radio fire detection system

Fire control panels FC726 FC726-XA

OOH740-A9-Ex Multi-sensor fire detector

FC722 Fire control panel

FDCL221 Line separator

FC724 Fire control panel

FDCW241 Radio gateway Mounting

FC724 Fire control panel

FC722 Fire control panel

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation

FDM273 Radio manual call point Mounting

FC723 Fire control panel

Fire control panels FC360

FDCI221, FDCIO221 Input module, input/output module Technical Manual

Synova TM product catalog.

DC1136, DC1131-AA, DC1134-AA, DC1136-AA Input / Output modules

DT1101A / DT1102A / DO110xA Automatic fire detectors

DB110xA, DB1131A, SO620A, DB1151A Detector bases and accessories

FDM221, FDM223, FDM224, FDM223H, FDM224H Manual call points

FDL241-9 Linear smoke detector Mounting Commissioning

FDA241, FDA221 Siemens ASD

FC2020 Fire control panel

DOW1171 / DCW1151 Radio fire detection system

Fire control panel for modernization

Room thermostat with 24-hour time switch and large LCD

FT2080 Fire terminal (Touch) Mounting Installation

DF1151-Ex Infrared flame detector

FDBZ290 Air sampling smoke detection kit Technical Manual

FT2080 Fire terminal (Touch) Mounting Installation

XC10 Extinguishing control panels

Test units and accessories

Electronic timeswitch

FC2040. Fire control panel. Sinteso. FS20 series, MP6

FD20 Sinteso Detector system

SOL-LX-W, SOL-LX-C, RoLP-LX, RoLP Sounder, beacon, and sounderbeacon

FDA241, FDA221 Siemens ASD

Test units and accessories

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

Sinteso TM product catalog.

FDS229 Alarm sounder with supplementary optical indication Technical Manual

2015 NEW. Cerberus ECO. enjoy protecting. Product Brouchure. siemens.com/buildingtechnologies

FP120-Z1 Power supply kit A (70 W) Technical Manual

Test units and accessories

OH110, OP110, HI110 Automatic fire detectors

Cerberus FIT conventional system

Duct Temperature Sensors

FS20 Fire detection system

QXA2100. Condensation monitor QXA2101. Monitor to prevent damage caused by condensation on chilled ceilings and HVAC plants with AC/DC 24 V power.

Building Technologies. FDUL221 en Line tester operating instructions for electricians

OH720, OP720, HI720, HI722 Automatic fire detectors Technical Manual

Frost Units for air temperature monitoring

Semi flush-mount room thermostats

Room Temperature Controllers

FDA241, FDA221 Aspirating Smoke Detector Technical Manual

Flush-mounted room thermostat

Thermal Reset Limit Thermostats Electromechanical TW according to DIN EN 14597

Frost Protection Thermostat

XC10 combined fire detection and extinguishing control

Room thermostats with LCD RDD100..

Room Temperature Sensors

FDOOT241-A9-Ex Automatic fire detector Technical Manual

QFM41.. Duct sensors QFM41.. AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

FS720 Fire detection system (marine) Technical Manual

Room Temperature. for 2-pipe fan coil units for compressors in DX type equipment

Call stations and extensions

Room Temperature Controller

Transcription:

Sinteso / Cerberus PRO Manual call points FDM225, FDM226 Manual call points with direct activation for the FDnet/C-NET automatic addressable detector bus Manual call points for addressed Sinteso FS20 and Cerberus PRO FS720 fire detection systems Direct activation: type 'A' according to EN 54-11 Communication via the FDnet/C-NET detector line (addressed individually) FDM225 for surface and recessed mounting FDM226 for surface mounting with protection category IP66 Either glass insert or resettable plastic insert Special FDM225 housing designs available for the French market: FDM225-RG (F) with glass insert FDM225-RP (F) with plastic insert Two-wire installation for all cable types 2015-09-01 Control Products and Systems

Properties Features Integrated line separator: The defective part on the detector line is located by the fire control panel and isolated between two FDnet/C-NET devices. Built-in alarm indicator (LED) Address automatically issued during commissioning Protected electronics Connection terminal DBZ1190-AB (accessory) can be mounted if shielded cables are used Eco-friendly Environmentally friendly processing Reusable materials Electronic parts and synthetic materials can be easily separated Use Use For the immediate manual activation of a fire alarm Suitable for indoor and outdoor applications 2

Types of mounting The manual call points are suitable for surface and recessed mounting (FDM225-xx) or for surface mounting (FDM226-xx) in easily accessible locations. Device / Accessory Recessed mounting Surface mounting FDM225-RG with glass insert X X FDM225-RP with resettable plastic insert FDMH295-R back box X FDMH295-S back box with holes and grommets FDM226-RG X FDM226-RP X = device/accessory required for this type of mounting = not required for this type of mounting FDMH295-R FDMH295-S FDM225 FDM225 FDM226 FDM225-xx FDM225-xx with back box FDMH295-x FDM226-xx If you use back box FDMH295-R with the FDM225-xx, a hole with Ø 20 mm must be drilled in the back box for the surface-mounted cable entry. Use metal cable gland M20 x 1.5 with metal counter nut M20 x 1.5 (accessories). The manual call point FDM226-xx has two break-out openings on the top and two on the bottom of the housing for cable entry purposes. If protection category IP66 is to be achieved with the FDM226-xx, the lateral fastening tabs must be used to mount the back box. Cable entry must be effected using metal cable gland M20 x 1.5 and metal counter nut M20 x 1.5 (accessories). 3

Function of manual call points FDM225-RG and FDM226-RG Direct alarm activation by pushing in the glass insert Manual call point reset by replacing the glass insert Protective cover FDMC295 (accessory) protects the manual call point against the glass being broken and the alarm activated accidentally 2 1 Installing the protective cover FDMC295 1 Manual call point FDM225 2 Protective cover FDMC295 Function of manual call points FDM225-RP and FDM226-RP Direct alarm activation by pressing the plastic insert Manual call point reset with key FDMK295 Protective cover FDMC295 (accessory) protects the manual call point against the glass being broken and the alarm activated accidentally Using key FDMK295 to reset the manual call point (left) and open the housing (right) 4

Type Overview Type Designation Order no. Weight [kg] FDM225-RG Manual call point with glass element A5Q00013434 0,102 FDM225-RP Manual call point with plastic element A5Q00012020 0,100 FDM225-RG (F) Manual call point with glass element for 'France' FDM225-RP (F) FDM226-RG FDM226-RP Manual call point with plastic element for 'France' Manual call point with glass element including back box Manual call point with plastic element including back box A5Q00020274 0,102 A5Q00020273 0,100 A5Q00013435 0,196 A5Q00013436 0,208 FDMH295-R Back box A5Q00013437 0,061 FDMH295-S Back box with holes and grommets A5Q00013438 0,061 M20 x 1.5 metal cable gland A5Q00004478 0,036 M20 x 1.5 metal counter nut A5Q00004479 0,006 DBZ1190-AB 2.5 mm 2, 3-pin connection terminal BPZ:4942340001 0,001 Accessories FDMC295 Protective cover A5Q00013440 0,036 Replacement material FDMK295 Key A5Q00013448 0,001 FDMG295 Glass insert 'Neutral' A5Q00013442 0,012 FDMP295 Plastic insert 'Neutral' A5Q00013445 0,008 FDMG295-F Glass insert 'France' A5Q00013443 0,012 FDMP295-F Plastic insert 'France' A5Q00013446 0,008 Product documentation Document ID Title 008164 Equipment overview Sinteso Detector system FD20 A6V10225323 Equipment overview Cerberus PRO Detector system FD720 009757 Technical manual Manual call points FDM221, FDM225, FDM226 008331 List of compatibility (for 'Sinteso ' product line) A6V10229261 List of compatibility (for 'Cerberus PRO' product line) Related documents such as environmental declarations, CE declarations, etc., can be downloaded at the following Internet address: http://siemens.com/bt/download 5

Technical data FDnet/C-NET operating voltage Operating current (quiescent) DC 12 33 V 180 μa Operating temperature -25 +70 C Storage temperature -30 +75 C Air humidity Communication protocol 95 % rel. FDnet/C-NET Connection terminals 0.28 1.5 mm 2 Color Design according to EN 54-11 Environmental category according to EN 54-11: Color ~RAL 3000, flame red Direct activation 'type A' FDM225-xx: In buildings FDM226-xx: In buildings and outdoor areas ~RAL 3000, flame red Protection category (IEC 60529): FDM225-xx: IP44 FDM226-xx: IP66 Approvals: FDM225-RP FDM225-RP (F) FDM225-RG FDM225-RG (F) FDM226-RP FDM226-RG VdS G207092 G207092 G209194 G209194 LPCB System compatibility: 126ap/01 126ap/10 126ap/02 126ap/11 FDnet: FS20, AlgoRex, SIGMASYS C-NET: FS720 126ap/03 126ap/04 6

Dimensional drawings Manual call point FDM225-xx (recessed mounting) 35.5 20 Manual call point FDM225-xx with back box FDMH295-x (surface mounting) 53 20 Manual call point FDM226-xx 113 57 When mounting protective cover FDMC295 on manual call points, the depth dimension increases by 7 mm accordingly. 7

Issued by Siemens Switzerland Ltd Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 www.siemens.com/buildingtechnologies Siemens Switzerland Ltd, 2014 Technical specifications and availability subject to change without notice. 8 Document ID Edition 2015-09-01 Register 4